0% found this document useful (0 votes)
51 views2 pages

Power Plant Data Query Regarding Protection Setting Review

The document requests power plant data for protection setting review, including: 1. A single line diagram showing connection points, layout, and equipment ratings. 2. Pre-calculation notes and a list of proposed protection setting values. 3. Generator characteristics curves and limits. 4. Generator parameter data like reactances, time constants, and saturation levels. 5. Transformer data including ratings, impedances, taps, and losses.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views2 pages

Power Plant Data Query Regarding Protection Setting Review

The document requests power plant data for protection setting review, including: 1. A single line diagram showing connection points, layout, and equipment ratings. 2. Pre-calculation notes and a list of proposed protection setting values. 3. Generator characteristics curves and limits. 4. Generator parameter data like reactances, time constants, and saturation levels. 5. Transformer data including ratings, impedances, taps, and losses.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ENJINIRING PROTEKSI P3BS

POWER PLANT DATA QUERY

REGARDING PROTECTION SETTING REVIEW

1. Single line diagram of power plants that describe:


1.1 Connection point to PLN power grid.
1.2 Power plant swicthyard/swicthgear layout.
1.3 The essential information of every EHV, HV, and LV apparatus (i.e. breakers, disconnectors,
power cables, transmission conductors, busbar conductors, etc.)
- Rated continous current for every equipment
- Short time short-circuit current rating for every equipment
- Breaking capacity for breakers
1.4 CTs and PTs class type, ratio, and connection to the related protection, energy meter, and
control devices. The related ANSI code should also be described (i.e. 21, 51, 51N, 87G, 25,
27, 79, etc).
2. Pre-calculation note of protection setting document.
3. List of protection setting value proposal.
4. Generator characteristics :
- Generator capability curve
- Short circuit characteristics
- Overfluxing characteristics (V/Hz vs time)
- Generator turbine permissible frequency (Hz) vs time (sec) curve
- Permissibe negative sequence current curve (I2 vs time)
- Generator voltage and frequency limits for continous operation ( V vs Hz)
5. Generator data parameter :

No. Parameter Unit Value


1 Nominal Apparent Power MVA
2 Terminal Voltage kV
3 Power Factor (p.f.)
4 Stator rated current A
5 Short circuit ratio
6 Winding Connection (YN/Y/D)
7 Generator grounding resistance/reactance ohm
8 Inertia time constant (H) sec
9 Direct axis synchronous reactance (xd) p.u.
10 Quad axis synchronous reactance (xq) p.u.
11 Direct axis transient synchronous reactance (xd') p.u.
12 Quad axis transient synchronous reactance (xq') p.u.
13 Direct axis subtransient synchronous reactance (xd") p.u.
14 Quad axis subtransient synchronous reactance (xq") p.u.
15 Direct axis saturated synch. Reactance (xdsat) p.u.
16 Direct axis subtransient saturated synch. Reactance (xd"sat) p.u.
17 Zero sequence reactance (x0) p.u.
18 Zero sequence resistance (r0) p.u.
19 Negative sequence reactance (x2) p.u.
ENJINIRING PROTEKSI P3BS

20 Negative sequence resistance (r2) p.u.


21 Stator resistance (rstr) p.u.
22 Stator leakage reactance (xl) p.u.
23 Rotor type (Salient/Round Rotor)
24 Direct axis short circuit transient time constant (Td') sec
25 Quad axis short circuit transient time constant (Tq') sec
26 Direct axis open loop transient time constant (Td0') sec
27 Quad axis open loop transient time constant (Tq0') sec
28 Direct axis short circuit subtransient time constant (Td") sec
29 Quad axis short circuit subtransient time constant (Tq") sec
30 Direct axis open loop subtransient time constant (Td0") sec
31 Quad axis open loop subtransient time constant (Tq0") sec
32 Machine saturation at 1.0 pu voltage (SG1.0) p.u.
33 Machine saturation at 1.0 pu voltage (SG1.2) p.u.

6. Generator transformer, Auxiliary transformer, Start/stand by transformer data:

No. Parameter Unit Value


1 Rated Power MVA
2 HV side rated voltage kV
3 LV side rated voltage kV
4 HV side rated current A
5 LV side rated current
6 Impedance short ciruit % p.u
7 Zero sequence impedance % p.u
8 Vector group
9 Minimum tap voltage
10 Maximum tap voltage
11 Additional voltage per tap %
12 Minimum tap position
13 Neutral tap position
14 Maximum tap position
15 No load current %
16 No load losses kW
17 Transformer neutral grounding resistor/reactor ohm

You might also like