The Consequences of Compressor Operation in Overload: by James M. Sorokes
The Consequences of Compressor Operation in Overload: by James M. Sorokes
The Consequences of Compressor Operation in Overload: by James M. Sorokes
by
James M. Sorokes
Manager of Development Engineering
Harry F. Miller
Product Manager - Marketing of Turbo Products
and
Jay M. Koch
Manager of Aero/Thermo Design Engineering
Dresser-Rand Company
Olean, New York
cause the impellers or stages to operate at successively higher compressor had operated in overload for long periods. In this case,
capacity relative to design until the latter stages are operating at or the dynamic forces because of incidence caused a portion of the
near choke. impeller blade’s leading edge to fracture and separate from the
impeller. The loss of material produced an unbalance on the rotor
Undersized Compressor/Alternate and the compressor had to be taken offline for repairs.
Operating Conditions/Unexpected Changes
At times, compressors are purposely or inadvertently undersized
in the selection process. For example, an end user may anticipate a
sizeable reduction in flow rate during the life of the compressor.
This user may choose, in the beginning, to operate the compressor
at the high-flow end of its map, knowing that in coming years the
flow rate will be reduced and the compressor will operate nearer
the center of its map.
Occasionally, end users purchase equipment before finalizing
their operating requirements. When the compressors are put into
operation, they discover that the inlet conditions and/or gas
mixtures are not as expected or that their production requirements
exceed those originally projected. These changes can cause the
compressor to operate at flow rates that are much higher than
anticipated. In short, the compressor operates in the overload
region of its performance map.
Finally, process conditions may also change during the life of a
compressor, causing the flow rate through the machine to increase.
The end user may lack sufficient funding to revamp or upgrade the Figure 4. Schematic of Blade Leading Edge Fracture
compressor, choosing instead to operate existing equipment in
overload despite the low performance. While the mechanisms that ultimately led to the impeller
fractures were different (more on this in the discussion to follow),
generally speaking, the root cause for the fractures was the same—
POTENTIAL CONSEQUENCES operation in overload.
OF OVERLOAD OPERATION
Two examples are presented to illustrate the potential DESCRIPTION OF FORCES
consequences of overload operation. In both cases, the compressors Although the forces resulting from operation in overload have a
were known to have operated for extended periods in the overload similar root cause to those found in surge or stall, the true nature of
region. Note: Before proceeding further, it must be noted that end those forces is radically different. The violent forces associated
users and OEMs are often very reluctant to provide details on with surge are typically very low frequency (6 Hz or less) and
difficulties resulting from off-design operation. End users do not result from the flow reversal through the compressor when the
want details of their operating practices made public and OEMs impeller or impellers can no longer overcome the downstream
typically do not want any suggestion that their products are static pressure. When in surge, the inability of the compressor to
anything but perfect. For that reason, limited details will be overcome such pressure is directly related to the increase in
provided on the two sample cases. incidence or other losses in the compressor components, i.e.,
The first example is taken from a high-pressure gas reinjection impellers, diffusers, return channels, etc. That is, as the flow rate in
compressor. The compressor experienced repeated impeller a compressor is reduced from design toward surge, the angle at
fractures. The welded impeller was a low flow coefficient design, which the flow impinges on the bladed or vaned components
having a very short blade height relative to the impeller diameter increases, thus increasing the incidence (or delta angle between the
(low b/r). Essentially, the impeller disk was fracturing at or around flow angle and the blade/vane angle) (Figure 5). At some point, the
the leading edge region of the impeller. In the worst case, the inner incidence angles lead to flow separation or other anomalies that
portion of the impeller disk separated from the outer portion. cause very high losses within all of the compressor components,
Following an investigation by the OEM and end user, it was making it impossible for the compressor to overcome the
reported that the impeller had been run extensively in the overload downstream pressure. Because flow moves from the region of
region of its performance map when a parallel train was taken higher pressure to a region of lower pressure, the flow reverses
offline. Dynamic forces caused by the combination of high direction and goes backward through the compressor. The resulting
impeller leading edge incidence, and a nonuniform pressure forces on the compressor internals can be destructive.
distribution caused by the downstream discharge volute, were
sufficient to initiate cracks in the impeller, leading to the fractures.
The compressor had to be taken out of service for several days to
allow installation of the spare rotor.
It should be noted that the forces that led to the fractures were
significantly lower at the design flow condition. That is, at design
flow, the dynamic forces due to incidence and the volute pressure field
were not sufficient to initiate the cracking. Further details on this case
can be found in Borer, et al. (1997), and Sorokes, et al. (1998).
The second example is from a compressor processing heavy
hydrocarbons. The subject impeller was a high-flow coefficient
design, implying that the leading edge was quite tall (high b/r).
Blade fractures occurred near the impeller’s leading edge. In a few
of the blades, a portion of the blade broke away as indicated by the
crosshatched area in Figure 4. Again, based on an analysis
conducted by the end user and the OEM, it was found that the Figure 5. Impeller Incidence.
Table of Contents
THE CONSEQUENCES OF COMPRESSOR OPERATION IN OVERLOAD 67
CFD can also be used to develop pressure loads or net impeller blade
forces that can be applied when conducting finite element analyses to
assess the structural integrity of designs. CFD can also be used to
determine how said forces vary with flow rate. Historically, CFD was
limited to providing steady-state (or time averaged) pressure
distributions that could be applied as pressure loads in FEA studies.
However, in the past decade, advances in CFD have made it possible to
generate unsteady or transient pressure distributions. These unsteady
pressures can be translated into a force at a frequency and imposed as a
boundary condition in an impeller natural frequency analysis. This
offers designers the opportunity to assess possible excitation and
determine if changes are needed to avoid a resonance problem.
High-flow coefficient impellers that may be subjected to overload
gas going to shore. Because of the declining pressure nature of the “overload” has many connotations, so it is important that all parties
field, the compressors were designed with both the present and adopt a common definition. Because one person’s “overload”
several future conditions in mind to allow for change-out of internal might well be another’s normal operation, a more rigorous
parts over the life of the field to accommodate the changing definition must be applied when specifying compressor flow range
operating conditions. Because the application required very high requirements or discussing how the compressor is being operated
horsepower drivers (>40 MW), and because the early years of in production. It might also be possible to adopt an industrywide
operation had the highest inlet pressures, only a few stages standard that defines “overload” as operating a compressor at
(impellers) were required to meet the specified discharge pressure. flow rates that exceed the maximum flow rates shown on the
This resulted in a fairly high horsepower per stage relative to the performance map provided by the OEM. This would put the onus
end user’s and OEM’s experience for this particular size unit. In on both the OEM to provide an accurate prediction of overload
contrast, operation in future years at much lower inlet pressures capability and the end user to properly assess their need to operate
would require more stages (impellers) to meet the same desired at such high flow rates.
discharge pressure. Therefore, in the later years of operation, the As seen herein, in some reported cases, prolonged operation in
horsepower per stage would drop into more a comfortable range. overload can lead to impeller fractures. Overload operation can
The end user also desired that if one unit had to be taken out of also exacerbate structural natural frequency interference issues that
service, the remaining units would need to accept more inlet flow; may exist within a compressor flow path. Forces and/or pressure
that is, operated in overload, a flow rate 30 percent to 50 percent nonuniformities tend to be greater when operating at flow rates
higher than the design flow rate. Because the stage power was high much higher than design. Such increases are caused in large part by
at the normal design point, the OEM was concerned about the the increased incidence levels on impeller blades or adjacent
prospect of even higher powers being absorbed in an off-design stationary vanes (i.e., vaned diffusers).
mode. When the end user consulted the OEM about the potential Advanced analytical tools such as computational fluid dynamics
operation at higher flows, the OEM responded with an engineering or finite element analysis help quantify the magnitude of the forces
study to determine the magnitude of the dynamic stress. The study associated with overload operation. Such analyses can also be used
included an innovative combination of transient CFD and FEA. to mitigate risk. Designs can be modified to reduce the potential for
The resulting analyses indicated that the original impeller geometry harmful interferences, or operating limits can be derived so as to
was acceptable but with relatively low safety margins. The OEM avoid risky portions of the performance map. However, the most
then determined that the calculated stresses could be significantly sophisticated analyses and most advanced manufacturing methods
reduced with very minor changes to the geometry of the impeller, cannot eliminate the risk of component failures due to overload
notably in the blade to shroud fillet weld. This substantially operation. Common sense dictates that the most effective way to
increased the factor of safety, and providing confidence that the eliminate such risk is to avoid high risk operating conditions.
impeller integrity would not be at risk due to overload operation. Simply put, if there is increased risk of mechanical failure by
If the end user had not consulted the OEM, it is uncertain running at a portion of the performance envelope, the risks must be
whether or not a problem would have occurred. However, by weighed against the potential gains and the cost of maintenance or
having an open dialog, and by being proactive in performing an replacement of the equipment.
analysis, the risk of a problem was much more remote. In conclusion, though not receiving as much attention as surge,
Of course, it may not be possible to eliminate all of the risks prolonged operation in overload can have very detrimental effects on
associated with overload operation. Even the most advanced a centrifugal compressor. End users and OEMs alike need to be
analyses are but approximations of the real world. Therefore, one cognizant of the potential risks associated with operating in this
cannot be assured that such analyses will capture all of the portion of the performance map. End users accept the risks associated
potentially damaging phenomena within the compressor flow path. with surge and, despite the extra horsepower consumed, often run
Further, even the most robust designs will fail if subjected to the their compressors on recycle so as to avoid surging the units. As
right excitation mechanism, i.e., one that aligns with the natural noted, the forces associated with surge and overload are similar, yet
frequency of the impellers. Even a solid ring would fail if subjected the industry has not taken steps to protect equipment from overload
to the right excitation. At some point, common sense must prevail. operation. Failure to recognize the risks associated with overload
The end user and OEM must face the reality that the safest operation can have a devastating impact on compression equipment,
approach is to avoid operating in the overload region of the production, profitability, and engineering careers.
performance map. If the compressor might break if you run there,
do not run thereóor be prepared to undergo regular overhauls to NOMENCLATURE
check for internal damage.
End users can employ overload control systems to ensure that a ACFM = Actual cubic feet per minute
compressor does not operate beyond some agreed upon maximum A0 = Sonic velocity of gas at impeller inlet
capacity. These are implemented by incorporating algorithms in b = Impeller blade height
the control system that limit driver operation (speed, load, etc.) or Cm = Impeller meridional velocity
restrict the movement of control valves to keep the compressor in D2 = Impeller exit diameter
a safe region on its performance map. Some argue that such IGV = Inlet guide vane
overload controls limit production and decrease profitability. LSD = Low solidity vaned diffuser
However, when this reduction is weighed against the costs and lost N = Rotational speed in rpm
production associated with equipment failure, limiting overload Q = Inlet volumetric flow in ACFM
operation does not seem to be a bad choice. r = Impeller radius
U1 = Impeller inlet peripheral velocity
CONCLUSIONS U2 = Impeller exit peripheral velocity
U2/A0 = Machine Mach number
The most important conclusion to be derived from this work is V = Gas velocity
that, contrary to many commonly held beliefs, operation in W1 = Impeller
. inlet relative velocity
φ
overload can subject a centrifugal compressor to adverse forces. In
700Q
Ν D23
fact, in some circumstances, overload operation can be just as =
ρ
detrimental to component structural integrity as surge.
Of course, it is critical that the end user and OEM come to an = Gas density
understanding on the meaning of overload operation. The term
Table of Contents
THE CONSEQUENCES OF COMPRESSOR OPERATION IN OVERLOAD 71