Method Statement For Testing & Commissioning of Central Battery System
Method Statement For Testing & Commissioning of Central Battery System
Method Statement For Testing & Commissioning of Central Battery System
1. PRE-COMMISSIONING
1.1 The following to be completed before starting the Testing & Commissioning
Insulation resistance measurement of cables.
All Emergency & Exit luminaires to be installed.
Central battery control panel & Battery cabinet to be installed.
All outgoing circuit cables to be marked & terminated at panel.
Batteries interconnection & termination.
Main’s power supply to the panels.
2.5. ATTACHMENTS:
REPORTS.
RISK ASSESSMENT
PANEL TYPE
OBSERVATION REMARKS
VISUAL CHECK
Check control panel installation for interior/ exterior damage
Check mains power supply & battery cable termination
Check outgoing circuits cable identification and termination
Check batteries installation for interior/exterior damage if any
PROJECT
PANEL LOCATION
PANEL TYPE
ACTIVITY EXPECTED RESULT OBSERVATION REMARKS
Check mains present LED
indication during mains power Mains present LED ON
present condition
Check mains present LED
indication during mains power Mains present LED OFF
failure condition
Check battery operation LED
Mains present LED OFF &
indication (switch off mains power
Battery operation LED ON
supply)
Check battery fault LED
Battery over voltage, Battery fault
indication (Disconnect battery
and Internal fault LED ON
fuse)
Check battery under voltage LED
indication (Switch off mains Battery under voltage LED ON,
power supply for few minutes and Recharge LED blinks
switch on again)
Internal fault LED indication Battery over voltage, Battery fault
(Disconnect the battery fuse) and Internal fault LED ON
External fault LED indication
( Remove one Emergency /Exit External fault LED ON after the
light from the one of the circuit test
and make manual luminaire test)
Check mains power to Battery Panel operates in battery mode
mode operation (Switch off mains also all emergency & Exit lights
power ) are ON
Check battery to mains power Panel operates in normal mode,
mode operation (Switch on mains also all Emergency lights are OFF
power ) and all Exit lights are ON
Check light fault (Remove one External fault LED ON &
Emergency / Exit light from one Respective luminaire address led
of the circuit and make manual is blinking in the panel control
luminaire test ) module
Check Emergency light operation
Respective area Emergency lights
during normal lighting DB mains
will switch on automatically
power failure condition
Remarks:
End time
Battery Voltage
O Mins
60 Mins
120 Mins
180 Mins
Remarks: