KP310 Operation Manual
KP310 Operation Manual
KP310 Operation Manual
0 Controller
Operation Manual
Model KP310V1.0
V A
RUN
www.kipor.com
Version No.:KP310.1.1.0
July 20th, 2011
KP310V1.0 Controller Operation Manual
Index
1. Brief Introduction................................................................................................................. - 1 -
2. Model Nomenclature Explained .......................................................................................... - 1 -
3. Performance and Features .................................................................................................... - 1 -
4. Specifications ....................................................................................................................... - 2 -
5. Operation.............................................................................................................................. - 3 -
5.1 Function of keys............................................................................................................. - 3 -
5.2 Controller Layout........................................................................................................... - 5 -
5.2.1 Main Display....................................................................................................... - 6 -
5.2.2 “Parameters Set” menu ....................................................................................... - 9 -
5.3 Manual Operation ........................................................................................................ - 10 -
5.4 Remote Operation ........................................................................................................ - 11 -
6. Protection ........................................................................................................................... - 11 -
6.1 Alarm............................................................................................................................ - 12 -
6.2 Time delayed stop alarms............................................................................................. - 12 -
6.3 Emergency stop alarms ................................................................................................ - 13 -
7. Wiring ................................................................................................................................ - 14 -
8. Parameter Set ..................................................................................................................... - 15 -
8.1 Parameters Set list........................................................................................................ - 16 -
8.2 Programmable output list ............................................................................................. - 21 -
8.2.1 Remote set......................................................................................................... - 21 -
8.2.2 Set Input ............................................................................................................ - 22 -
8.3 Programmable output list ............................................................................................. - 23 -
9. Commission ....................................................................................................................... - 24 -
10. Applications ............................................................................................................... - 24 -
11. Installations ................................................................................................................ - 25 -
12. Trouble shooting ........................................................................................................ - 26 -
13. Serial Communication................................................................................................ - 26 -
13.1 Physical Layer of Communication Protocol .............................................................. - 27 -
13.2 Enquiry/ Response Period .......................................................................................... - 27 -
13.3 Comm RTU ................................................................................................................ - 28 -
13.3.1 Address field ................................................................................................... - 28 -
13.3.2 Function field .................................................................................................. - 28 -
13.3.3 Data field......................................................................................................... - 28 -
13.3.4 Data CRC field................................................................................................ - 28 -
Appendix 1 CRC16-CCITT Sheet ............................................................................................. - 29 -
Appendix 2 CRC16-CCITT ....................................................................................................... - 30 -
Appendix 3 Wiring Diagram...................................................................................................... - 31 -
1) 3-Phase 4-Line ........................................................................................................... - 31 -
2) 3-Phase 3-Line ........................................................................................................... - 32 -
3) 1-Phase 2-Line ........................................................................................................... - 33 -
4) 2-Phase 3-Line ........................................................................................................... - 34 -
I
KP310V1.0 Controller Operation Manual
1. Brief Introduction
The KP310V1.0 controller has the function of manual/remote start and stop genset, data
measurement, alarm and protection. The KP310V1.0 can display detailed genset running and
alarming data through LED digit display in five numbers. RS232 interface with the host computer,
can start, stop genset and display real-time running data through the host computer. The host
computer software has the Chinese and English interface, featured by simple & reliable operation.
RS485 interface is also available for remote monitor and control genset.
KP310V1.0
KP310V1.0 KIPOR
KP310V1.0 Controller Model
KP310V1.0 Version No.
Main features:
☞Microprocessor controller, higher hardware integration, higher reliable;
☞ Display through LED display in five digital numbers; convenient to test genset by touch
buttons;
☞ Manual/remote start and stop genset;
☞ RS232 interface with PC to run and monitor genset; RS485 interface to remote monitor genset;
☞ Applied to 3-phase 4-line, 3-phase 3-line, 1-phase 2-line, double-voltage power sources;
☞ Monitor and display three-phase voltage, three-phase current, frequency, revolutions and
battery voltage;
☞ Fault alarms, including over-voltage, under-voltage, over-frequency, under-frequency and
charging fault;
☞ Protection against high water temperature and low oil voltage;
☞ All output interface are relay output;
☞ “Parameters Set” menu: parameters can be set by users through controllers or PC. All
parameter are stored in internal flash memory so they won’t lose even the power turns off;
☞ Working voltage: 8-16VDC, adaptable to different batteries;
☞ Maintenance remind function (fuel filter, air filter, oil filter) ;
☞ Digital control, more reliable;
☞ Fault alarms are recorded until manual delete;
☞ Copy system configuration and restore system configuration, assure system can be restored due
to wrong action;
-1-
KP310V1.0 Controller Operation Manual
4. Specifications
Working Voltage 12VDC (8~16VDC)
Voltage measurement AC Input Voltage:
Phase voltage 10~290VAC RMS
Precision level:2.0
Three-phase four-line
Three-phase three-line
Single-phase two-line
Double-voltage output simultaneously
Double-voltage output alternative
Current measurement Primary current:
1A -900A (Parameters Set)
Secondary current:
5mA
Precision level:
2.0
Frequency measurement Frequency range:
20~70HZ(voltage>15V)
Precision level:
0.5
Revolution measurement Voltage range:
5-50V
Max. frequency:
10000Hz
Flywheel tooth:
1-500
Output Fuel output relay:
15A/12VDC
Start output relay:
15A/12VDC
Preheat output relay:
5A/12VDC
Configuration output relay Ⅰ:
5A/12VDC
Configuration output relay Ⅱ:
5A/12VDC
Ambient temperature -20~70℃
-2-
KP310V1.0 Controller Operation Manual
5. Operation
Note:
1 when the generator is stopped and in “Manual” Mode, press and for 5 seconds at
the same time, it displays password “Test” mode . If user doesn’t input the right
password in 60 seconds, the system will automatically exit password menu and enters System
Operation menu.
2 In “Parameters Set” menu, press , and for 5 seconds in the same time to
backup current system set, and the digital tube displays “Backup” for 2 seconds.
3 When genset is stopped, and in “Manual” Mode, press , and for 5secs to
restore system set, and the digital tube displays “Reset” for 2 seconds.
4 In the “Oil Filter Running Time” mode, press for 5 seconds, it will clear alarm of oil filter
-3-
KP310V1.0 Controller Operation Manual
5 In the “Fuel Filter Running Time” mode, press for 5 seconds, it will clear alarm of fuel
filter maintenance, and reset it.
6 In the “Air Filter Running Time” mode, press for 5 seconds, it will clear alarm of air filter
maintenance, and reset it.
7 In the “Running Time” mode, press for 5 seconds, it will clear running time, and reset it.
8 Press and for 5 seconds until the signal twinkles, which shows that system has
blocked some protection functions (over/under frequency, over/under voltage); then press
and for 5 seconds until the signal stop flickering, which shows that system has restored the
protection functions (over/under frequency, over/under voltage).
-4-
KP310V1.0 Controller Operation Manual
Model KP310V1.0
V A
RUN
-5-
KP310V1.0 Controller Operation Manual
Press , it will display voltage, current, frequency, revolution, battery voltage, run time and
maintenance time.
Note:
Battery charging voltage, switch value input/output state and system delay state is also available
with RS232 Port.
If genset switches to the following status, the digital tube will display genset status:
Preheat:
Start:
Starting idle:
Stopping idle:
Stopping delay:
-6-
KP310V1.0 Controller Operation Manual
Three-phase three-line
Single-phase two-line
Two-phase three-line
-7-
KP310V1.0 Controller Operation Manual
Three-phase three-line
Single-phase two-line
Two-phase three-line
Revolution
✪Note: If the “Revolution low” is set as zero, then the speed won’t be displayed..
Battery voltage
Running time
Maintenance Time
Oil filter
Fuel filter
-8-
KP310V1.0 Controller Operation Manual
Air filter
-9-
KP310V1.0 Controller Operation Manual
For example:
When genset is stopped, and is in “Manual” Mode, press and for 5 seconds at the
same time, it displays password test mode
After inputting the right password, press to enter the “Parameters Set” menu. Take the
settings of flywheel tooth for example, after enter the flywheel tooth menu, press to set the
number, the default value is 100. While the value twinkles, press or to increase or
decrease the value. After inputting the value, press to confirm and save the value. Press
- 10 -
KP310V1.0 Controller Operation Manual
outputting.
After starting genset, the security delay countdown timer works. During the security delay range,
low oil voltage, high temperature, under speed, under voltage, under frequency and battery
charging fault are allowed. When the configuring output is set as “4-Genset Idle”, and starting idle
time isn’t 0, the related configuring output relay outputs, the start idle timer counting down, and
generator is in idle mode.
After the starting idle status, the configuring output relay stop working and genset start to work in
rated status.
When the KP310V1.0 controller is working, it is initialized to the “Manual” Mode. Press
to login into the remote mode.
Start steps:
Preheat relay output, meanwhile the preheating timer start counting down. If the preheating time is
set as zero, the relay won’t output.
After preheating, the preheating relay stop working, the fuel relay and starting relay begin to
output. The maximum starting timer begins to count down. If genset can start successfully during
the countdown, the starting relay stops outputting. If failed, the fuel relay and starting relay stop
outputting.
After starting genset, the security delay countdown timer works. During the security delay range,
low oil voltage, high temperature, under speed, under voltage, under frequency and battery
charging fault are allowed. When the configuring output is set as “4-Generator Idle”, and starting
idle time isn’t 0, the related configuring output relay outputs, the idle time start counting down,
and generator is in idle mode.
Press remote stop key to stop genset.
6. Protection
KP310V1.0 controller has a lot of protection functions. When genset has some problems, relevant
fault LED alarms. The fault alarm includes three types: warning, delay shutdown, immediately
shutdown.
- 11 -
KP310V1.0 Controller Operation Manual
6.1 Alarm
In the following alarms, relevant LED twinkles, but genset keeps running.
No. Type Description
When oil filter is overtime than the maintenance value, there will
1 Oil filter overtime
be an oil filter overtime alarm, maintenance LED twinkles.
2 Fuel filter overtime will be a fuel filter overtime alarm, maintenance LED
twinkles.
When air filter is overtime than the maintenance value, there will
3 Air filter overtime
be a air filter overtime alarm, maintenance LED twinkles.
Over battery When the battery voltage is larger than the set value, battery
4
voltage LED twinkles.
Under battery When the battery voltage is lower than the set value, battery
5
voltage LED twinkles.
When the charging voltage is lower than the set value, battery
6 Charging faults
LED twinkles.
After detecting the time delayed stop alarms, relevant LED twinkles, and genset will be stopped
after a delayed time.
No. Type Description
If genset current is larger than Over Current 1, over current LED
- 12 -
KP310V1.0 Controller Operation Manual
After detecting the emergency stop alarms, relevant LED twinkles, and genset will be stopped
instantly. Buzzer will give alarms.
No. Type Description
If genset frequency is larger than the set value, over frequency LED
Over
1 twinkles, genset will be stopped instantly.
Frequency
Customers can set values to disable the protection.
If genset frequency is lower than the set value, under frequency LED
Under
2 twinkles, genset will be stopped instantly.
Frequency
Customers can set values to disable the protection.
If genset voltage is larger than the set value, over voltage LED
Over
3
Voltage twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
If genset voltage is lower than the set value, under voltage LED
Under
4
Voltage twinkles, genset will be stopped instantly.
Customers can set values to disable the protection.
Over If genset frequency is larger than the set value, over frequency LED
5
Frequency twinkles, genset will be stopped instantly.
Under If genset frequency is lower than the set value, under frequency LED
6
Frequency twinkles, genset will be stopped instantly.
Low Oil If oil pressure is lower than the set value, low oil pressure LED
7
Pressure twinkles, genset will be stopped instantly.
High Water If water temperature is higher than the set value, high water temperature
8
Temperature LED twinkles, genset will be stopped instantly.
If genset failed to start in the set time, start failure LED twinkles,
9 Start failure
genset will be stopped instantly.
Emergency While press the emergency stop button, emergency stop LED
10
Stop twinkles, genset will be stopped instantly.
Note:
1、“Over frequency” protection can be disabled if “over frequency alarm delay time” is set as 0.
2、“Under frequency” protection can be disabled if “under frequency alarm delay time” is set as 0.
- 13 -
KP310V1.0 Controller Operation Manual
7. Wiring
The back panel of KP310V1.0 controller is as follows:
31 30 29 28 27 26 25 24 23 22 21 20 19
Current
Genset Voltage (Rated 5mA)
Comm_GND
Comm_VCC
A B C N ICOM IA IB IC
RXD
TXD
DIR
31 30 29 28 27 26 25 24 23 22 21 20 19
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
High Temp
Fuel
Crank
Bat Charge
-
B+
120/240 Select
Aux_Out2
Aux_Out1
+
B-
Oil Press
Start sw
Aux_In2
Preheat
Remote
Aux_In1
EM Stop
+
MPU
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
- 14 -
KP310V1.0 Controller Operation Manual
8. Parameter Set
After login into the Parameter Set menu, remote mode lighter twinkles, parameters will be
displayed on the controller.
- 15 -
KP310V1.0 Controller Operation Manual
If there is no operation for more than 60s, system will automatically exit Parameter Set menu, and
enter the System Operation menu.
Model KP310V1.0
V A
Parameter Code
Data
RUN
- 16 -
KP310V1.0 Controller Operation Manual
- 17 -
KP310V1.0 Controller Operation Manual
Communication
Communication Communication address with the
33 ●○○○○● 0-32 1 1
Address PC
Maintenance
Fuel filter Engine Fuel filter replace
34 maintenance ●○○○●○ 0-65535 0.1Hr 5000 countdown
time
Air filter Engine Air filter replace
35 maintenance ●○○○●● 0-65535 0.1Hr 5000 countdown
time
Oil filter Engine Oil filter replace
36 maintenance ●○○●○○ 0-65535 0.1Hr 5000 countdown
time
Programmable Input Set
0-Remote Start Normally Open
1-Remote Start Normally Closed
2-Remote Stop Normally Open
3-Remote Stop Normally Closed
37 Remote set ●○○●○● 0-5 1 4
4-Remote Start & Stop Normally
Open
5-Remote Start & Stop Normally
Closed
Remote start In remote mode, timing from give
38 ●○○●●○ 0-65535 0.1s 50
delay start signal to successfully start.
Remote Stop In remote mode, timing from give
39 ●○○●●● 0-65535 0.1s 50
Delay Stop signal to successfully stop.
Remote start In remote mode, start times in the
40 ●○●○○○ 1-10 1 3
Times normal range
0-Warning Normally Open
1-Warning Normally Closed
41 Input 1 Type ●○●○○● 0-3 1 0
2-Stop Normally Open
3-Stop Normally Closed
Input 1 Fault Set input 1 Fault Delay timing
42 ●○●○●○ 0-65535 0.1s 0
Delay
0-Warning Normally Open
1-Warning Normally Closed
43 Input 2Type ●○●○●● 0-3 1s 0
2-Stop Normally Open
3-Stop Normally Closed
Input 2 Fault Set input 2 Fault Delay timing
44 ●○●●○○ 0-65535 0.1s 0
Delay
Programmable Output Set
0-Reserved
45 Set Output 1 ●○●●○● 0-16 1 0 1-Genset Stop
2-Genset Preheat
- 18 -
KP310V1.0 Controller Operation Manual
3-Genset Start
4-Genset Idle
5-Genset Running
6-Genset Electric Parameters
Normal
7-System Warning Alarm
8-System Delay Stop Alarm
9-System Stop Alarm
10-System Alarm
11-Manual Mode
12-Remote Mode
13-Oil Filter Overtime
14-Fuel Filter Overtime
15-Air Filter Overtime
16-Start Failure
0-Reserved
1-Genset Stop
2-Genset Preheat
3-Genset Start
4-Genset Idle
5-Genset Running
6-Genset Electric Parameters
Normal
7-System Warning Alarm
46 Set Output 2 ●○●●●○ 0-16 1 0
8-System Delay Stop Alarm
9-System Stop Alarm
10-System Alarm
11-Manual Mode
12-Remote Mode
13-Oil Filter Overtime
14-Fuel Filter Overtime
15-Air Filter Overtime
16-Start Failure
Idle
Timing from start idle running to
47 Start idle Time ●○●●●● 0-65535 0.1s 0
rated RPM
Timing from stop idle running to
48 Stop idle Time ●●○○○○ 0-65535 0.1s 0
successfully stop.
Password
49 Password ●●○○○● 0-65535 1 0310 Set Password
Generator Parameter
Regulate the Gain to display the
L1 Phase
50 ●●○○●○ 0-2047 1 1024 same L1 phase voltage on the
Voltage Gain
controller with the actual voltage.
- 19 -
KP310V1.0 Controller Operation Manual
- 20 -
KP310V1.0 Controller Operation Manual
Terminal “8” has “Remote” function; the function is only valid in “Remote mode”.
No. Contents Note
1 0—Remote start normally Normally Open : in the default state, input signal
open open ( high potential);
1—Remote start normally input signal close ( low potential) is valid;
2
closed Normally Closed : in the default state, input
2—Remote Stop normally signal close ( low potential);
3
open input signal open ( high potential) is valid;
3—Remote Stop normally
4
closed
4—Remote start & stop
5
normally open
5—Remote start & stop
6
normally closed
In the “Remote mode ”, after Terminal “8” is closed ( low potential), genset start after Remote
start delay(parameters can be setup).Terminal “8” open ( high potential), genset won’t stop.
In the “Remote mode ”,after Terminal “8” is open ( high potential),genset start after remote start
delay(parameters can be setup).Terminal “8” close ( low potential), genset won’t stop.
In the “Remote mode ”,After Terminal “8” is closed( low potential), genset won’t start.Terminal
“8” open ( high potential),genset stop after Remote Stop Delay(parameters can be setup).
In the “Remote mode ”,After Terminal “8” is open ( high potential), genset won’t start.Terminal
“8” close ( low potential),genset stop after Remote Stop Delay(parameters can be setup).
- 21 -
KP310V1.0 Controller Operation Manual
In the “Remote mode ”,After Terminal “8” is closed ( low potential),genset start after remote
start delay(parameters can be setup).Terminal “8” open ( high potential),genset stop after
Remote Stop Delay(parameters can be setup).
In the “Remote mode ”,After Terminal “8” is open ( high potential),genset start after remote
start delay(parameters can be setup).Terminal “8” close ( low potential),genset stop after
Remote Stop Delay(parameters can be setup).
Terminal “13” and Terminal “14” has “self-definition selective input” function ;
KP310_1.00 controller has the following set input function.
No. Contents Note
0-Warning Normally Normally Open : in the default state, input signal
1
Open open ( high potential);
1-Warning Normally input signal close ( low potential) is valid;
2
Closed Normally Closed : in the default state, input
3 2-Stop normally open signal close ( low potential);
4 3-Stop normally closed input signal open ( high potential) is valid;
After Terminal is closed ( low potential), Warning alarm. Relevant set input faults LED light up.
After Terminal is open ( high potential), the Set Input faults is eliminated.
After Terminal is open ( high potential), Warning alarm. Relevant set input faults LED light up.
After Terminal is closed ( low potential), the Set Input faults is eliminated.
After Terminal is closed ( low potential),confirmed by Set Input Fault Delay, stop the alarm
immediately, relevant set input faults LED light up.
- 22 -
KP310V1.0 Controller Operation Manual
After Terminal is open ( high potential),confirmed by Set Input Fault Delay, stop the alarm
immediately. Relevant set input faults LED light up.
- 23 -
KP310V1.0 Controller Operation Manual
9. Commission
Before commission, please check as follows:
1、Check all connections and wires;
2、Right connection with batteries;
3、Right connection of Emergency Stop button with battery;
4、Take proper measures to prevent engine from starting such as dismantle fuel valve connections,
then connect with battery, select manual mode.
5、Press (start )button, genset will start ; start failure alarms, press (Stop )to recover
the controller;
6、Recover Engine to start(such as recover fuel valve connections), press (start )button ,
genset will start , if everything is OK, genset will be in the idle state for a while(if idle running is
available)then genset will run normally. In this period, check if everything is OK, for example
voltage, frequency. If there are some abnormal situations, stop genset, check the connection refer
to the Manual;
7、Please contact with us if you need help..
10. Applications
QF
A U
B V
C W
N N
Comm_GND
Comm_VCC
ICOM IA IB IC
RXD
TXD
DIR
A B C N
31 30 29 28 27 26 25 24 23 22 21 20 19
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
120/240 Select
High Temp
Fuel
Oil Press
Start sw
Crank
Bat Charge
Remote
-
B+
EM Stop
Aux_In2
Aux_Out2
Preheat
Aux_In1
Aux_Out1
+
B-
+ MPU
- 24 -
KP310V1.0 Controller Operation Manual
31 30 29 28 27 26 25 24 23 22 21 20 19
Current
Genset Voltage (Rated 5mA)
Comm_GND
Comm_VCC
A B C N ICOM IA IB IC
RXD
TXD
DIR
KP310V1.0 controller is panel mounting. Dimensions are as follows:
31 30 29 28 27 26 25 24 23 22 21 20 19
KP310V1.0 GENSET CONTROLLER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
High Temp
Fuel
Crank
Bat Charge
-
120/240 Select
B+
Aux_Out2
Aux_Out1
+
B-
Oil Press
Start sw
Aux_In2
Preheat
Remote
Aux_In1
EM Stop
+
MPU
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
- 25 -
11. Installations
KP310V1.0 Controller Operation Manual
- 26 -
KP310V1.0 Controller Operation Manual
Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7 Bit8 Bit9 Bit10
Start D0 D1 D2 D3 D4 D5 D6 D7 Stop
The host starts enquiring actively, and the slave responds passively as following:
Host inquiry
Address Address
Slave response
- 27 -
KP310V1.0 Controller Operation Manual
This communication protocol uses RTU (remote terminals communication unit ) mode, namely
binary.
Function code is the Host operation code and reply code from Host..
Data check uses CRC16-CCITT as standard to check all data in MODBUS except data in check
field. Low byte stands after high byte.
The host machine sends messages to MODBUS and the slave produces CRC16 code to respond;
the host and slave have to calculate CRC16 code according to CRC16 multinomial.
- 28 -
KP310V1.0 Controller Operation Manual
- 29 -
KP310V1.0 Controller Operation Manual
Appendix 2 CRC16-CCITT
/*******************************************************************
Function: generate CRC16CCITT code
Input: p = mouse cursor points to first byte
DataLen =data length
Output: CRC16CCITT
*******************************************************************/
Unsigned int CRC16CCITT (unsigned char *p, unsigned int DataLen)
{
Unsigned int crc16=0;
Unsigned int i;
Unsigned char b;
for (i=0;i<DataLen;i++)
{
b=(unsigned char)(crc16>>8);
crc16<<=8;
crc16^= CRC16CCITT [b^*p];
p++;
}
return crc16;
}
- 30 -
KP310V1.0 Controller Operation Manual
1) 3-Phase 4-Line
QF
A U
B V
Generator Load
C W
N N
Comm_GND
Comm_VCC
ICOM IA IB IC
31 30 29 28 27 26 25 24 23 22 21 20 19
KP310V1.0 GENSET CONTROLLER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Crank 120/240 Start
SelectswRemote + - High Temp
B- B+ EM StopFuel Oil PressAux_In1Aux_In2Bat Charge Aux_Out2
Preheat Aux_Out1
+ MPU
- 31 -
KP310V1.0 Controller Operation Manual
2) 3-Phase 3-Line
QF
A U
B V
Load
C W
Generator
Comm_GND
Comm_VCC
ICOM IA IB IC
RXD
TXD
DIR
A B C N
31 30 29 28 27 26 25 24 23 22 21 20 19
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
120/240 Select
High Temp
Fuel
Oil Press
Start sw
Crank
Remote
Bat Charge
-
B+
EM Stop
Aux_In2
Aux_Out2
Preheat
Aux_In1
Aux_Out1
+
B-
+
MPU
- 32 -
KP310V1.0 Controller Operation Manual
3) 1-Phase 2-Line
QF
A U
N N
Load
Generator
Comm_GND
Comm_VCC
ICOM IA
RXD
TXD
DIR
A N
31 30 29 28 27 26 25 24 23 22 21 20 19
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
120/240 Select
High Temp
Fuel
Oil Press
Start sw
Crank
Bat Charge
Remote
-
B+
EM Stop
Aux_In2
Aux_Out2
Preheat
Aux_In1
Aux_Out1
+
B-
+
MPU
- 33 -
KP310V1.0 Controller Operation Manual
4) 2-Phase 3-Line
QF
A U
Generator B V Load
N W
Comm_GND
Comm_VCC
ICOM IA IB
RXD
TXD
DIR
A B N
31 30 29 28 27 26 25 24 23 22 21 20 19
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
120/240 Select
High Temp
Fuel
Oil Press
Start sw
Crank
Bat Charge
Remote
-
B+
EM Stop
Aux_In2
Aux_Out2
Preheat
Aux_In1
Aux_Out1
+
B-
+
MPU
- 34 -