3-Phase Short-Circuit Current (Isc) at Any Point Within A LV Installation
3-Phase Short-Circuit Current (Isc) at Any Point Within A LV Installation
Contents
1- Method of calculating ZT
2- Determination of the impedance of each component
2.1- Network upstream of the MV/LV transformer
2.2- Transformers
2.3- Busbars
2.4- Circuit conductors
2.5- Motors
2.6- Fault-arc resistance
2.7- Recapitulation table
2.8- Example of short-circuit calculations
3- Notes
where
Method of calculating ZT
Each component of an installation (MV network, transformer, cable, busbar,
and so on...) is characterized by its impedance Z, comprising an element of
resistance (R) and an inductive reactance (X). It may be noted that
capacitive reactances are not important in short-circuit current
calculations.
The parameters R, X and Z are expressed in ohms, and are related by the sides
of a right angled triangle, as shown in the impedance diagram of Figure G35.
Where sections are connected in series in the network, all the resistive
elements in the section are added arithmetically; likewise for the
reactances, to give RT and XT.
The impedance (ZT) for the combined sections concerned is then calculated
from
Any two sections of the network which are connected in parallel, can, if
predominantly both resistive (or both inductive) be combined to give a single
equivalent resistance (or reactance) as follows:
or for reactances
Fig. G36: The impedance of the MV network referred to the LV side of the MV/LV transformer
A formula which makes this deduction and at the same time converts the
impedance to an equivalent value at LV is given, as follows:
where
Za = impedance of the MV voltage network, expressed in milli-ohms
U20 = phase-to-phase no-load LV voltage, expressed in volts
Psc = MV 3-phase short-circuit fault level, expressed in kVA
Figure G36 gives values for Ra and Xa corresponding to the most common MV[2]
short-circuit levels in utility power-supply networks, namely, 250 MVA and
500 MVA.
Transformers
in milli-ohms
where:
The transformer windings resistance Rtr can be derived from the total load-
losses as follows:
so that in milli-ohms
where
Oil-immersed Cast-resin
Rated Power
kVA) Usc Rtr Xtr Ztr Usc Rtr Xtr Ztr
(%) (mΩ) (mΩ) (mΩ) (%) (mΩ) (mΩ) (mΩ)
100 4 37.9 59.5 70.6 6 37.0 99.1 105.8
160 4 16.2 41.0 44.1 6 18.6 63.5 66.2
200 4 11.9 33.2 35.3 6 14.1 51.0 52.9
250 4 9.2 26.7 28.2 6 10.7 41.0 42.3
315 4 6.2 21.5 22.4 6 8.0 32.6 33.6
400 4 5.1 16.9 17.6 6 6.1 25.8 26.5
500 4 3.8 13.6 14.1 6 4.6 20.7 21.2
630 4 2.9 10.8 11.2 6 3.5 16.4 16.8
800 6 2.9 12.9 13.2 6 2.6 13.0 13.2
1,000 6 2.3 10.3 10.6 6 1.9 10.4 10.6
1,250 6 1.8 8.3 8.5 6 1.5 8.3 8.5
1,600 6 1.4 6.5 6.6 6 1.1 6.5 6.6
2,000 6 1.1 5.2 5.3 6 0.9 5.2 5.3
Fig. G37: Resistance, reactance and impedance values for typical distribution 400 V transformers (no-load voltage = 420 V) with
MV windings ≤ 20 kV
Busbars
Circuit conductors
ρ has to be considered:
at cold state (20°C) to determine maximum short-circuit current,
at steady state (normal operating temperature) to determine minimum short-circuit current.
PR/XLPE PVC 70
20 °C
90 °C °C
Copper 18.51 23.69 22.21
Alu 29.41 37.65 35.29
Fig. G38: Values of ρ as a function of the temperature, cable insulation and cable core material, according to IEC60909-0 and
Cenelec TR 50480 (in mΩ mm2/m).
Cable reactance values can be obtained from the manufacturers. For c.s.a. of
less than 50 mm2 reactance may be ignored. In the absence of other
information, a value of 0.08 mΩ/metre may be used (for 50 Hz systems) or
0.096 mΩ/metre (for 60 Hz systems). For busways (busbar trunking systems) and
similar pre-wired ducting systems, the manufacturer should be consulted.
Motors
Iscm = 3.5 In from each motor i.e. 3.5m In for m similar motors operating
concurrently.
Fault-arc resistance
Short-circuit faults generally form an arc which has the properties of a
resistance. The resistance is not stable and its average value is low, but at
low voltage this resistance is sufficient to reduce the fault-current to some
extent. Experience has shown that a reduction of the order of 20% may be
expected. This phenomenon will effectively ease the current-breaking duty of
a CB, but affords no relief for its fault-current making duty.
Recapitulation table
Parts of power-
R (mΩ) X (mΩ)
supply system
Xa = 0.995 Za
Supply network
Figure G34
where
Transformer with
Figure G35
Rtr is often negligible compared to Xtr
for transformers > 100 kVA
Fig. G39: Recapitulation table of impedances for different parts of a power-supply system
Example of short-circuit calculations
RT XT
LV installation R (mΩ) X (mΩ)
(mΩ) (mΩ)
MV network
0.035 0.351
Psc = 500 MVA
Transformer 20
kV / 420 V
Pn = 1000 kVA
2.35 8.5
Usc = 5%
Pcu = 13.3 x
103 watts
Single-core
cables Xc = 0.08
5 m copper x 5 = 2.48 9.25 Isc1 = 25 kA
4 x 240 0.40
mm2/phase
Main circuit-
Not considered in practice
breaker
Busbars 10 m Not considered in practice
Three-core
Xc = 100
cable
x 0.08 = 22 17.3 Isc3 = 8.7 kA
100 m
8
95 mm2 copper
Three-core
cable Xc = 20 x
20 m 0.08 = 59 18.9 Isc4 = 3.9 kA
10 mm2 copper 1.6
final circuits
RT : Total resistance. XT: Total reactance. Isc : 3-phase maximum short-circuit current
Calculations made as described in figure G36
Fig. G40: Example of maximum short-circuit current calculations for a LV installation supplied at 400 V (nominal) from a 1000
kVA MV/LV transformer
Notes
1. ^ Short-circuit MVA: EL Isc where:
EL = phase-to-phase nominal system voltage expressed in kV (r.m.s.)
Isc = 3-phase short-circuit current expressed in kA (r.m.s.)
2. ^ up to 36 kV
3. ^ For 50 Hz systems, but 0.18 mΩ/m length at 60 Hz
Retrieved from "http://www.electrical-installation.org/enw/index.php?title=3-
phase_short-
circuit_current_(Isc)_at_any_point_within_a_LV_installation&oldid=24148"
Category: Chapter - Sizing and protection of conductors