Introduction To Power System Protection
Introduction To Power System Protection
Economy
Simplicity
Speed
Reliability
Sensitivity
Selectivity
Design Criteria/Characteristics
• Reliability
– Operate dependably and in healthy operating
condition when fault conditions occur, even after
remaining idle for months or years.
• Selectivity
– Clearly discriminate between normal and
abnormal system condition to avoid unnecessary,
false trips.
• Sensitivity
– Ability to distinguish the fault condition,
although the different between fault and normal
condition is small.
small
Design Criteria/Characteristics
• Speed
– Fault at any point in the system must be
detected and isolated rapidly to minimize fault
duration and equipment damage. Any intentional
time delays should be precise.
• Economy
– Provide maximum protection at minimum cost
• Simplicity
– Minimize protection equipment and circuitry
Economic Factor
• Total cost should take account of :
– Relays, schemes and associated panels and panel wiring
– Setting studies
– Commissioning
– CTs and VTs
– Maintenance and repairs to relays
– Damage repair if protection fails to operate
– Lost revenue if protection operates unnecessarily
Economic Factor
• The cost of protection is equivalent to an insurance
policy against damage to plant, and loss of supply
and customer goodwill.
• Acceptable
p cost is based on a balance of economics
and technical factors. Cost of protection should be
balanced against
g the cost of p
potential hazards.
• There is an economic limit on what can be spent.
• MINIMUM COST :Must ensure that all faulty
equipment is isolated by protection.
System Protection Components
• Transducer / Instrument Transformer
• Relay
R l
• Circuit Breaker
System Protection Components
Function:
• Transducers/Instrument Transformers (PT/VT & CT)
– Provide low current and voltage, standardized levels
y operation.
suitable for the relays p
• Relays
– Discriminate between normal operating and fault
conditions.
– When current exceed a specified value, relay will be
operated and cause the trip coil of CB to be
energized/open their contact.
• Circuit Breakers
– Open the line, isolate the fault portion from the rest of the
y
system
System Protection Components
System Protection Components
System Protection Flow
l
voltage or current rise from normal condition
activate
ti t circuit
i it bbreaker
k
circuit isolation
I’I’
Operating
O i coil
il causes the
h NO
contacts to close
CB open
Zones off Protection
• For fault anyway within the zone, the
protection system
p y responsible
p to
isolate everything within the zone from
y
the rest of the system.
• Isolation done by CB
• Must isolate only the faulty equipment
or section
Zones off Protection
• Zones are defined for:
– Generators
– Transformers
– Buses
– Transmission and distribution lines
– Motors
Zones off Protection
Zones off Protection
• 3 main characteristics:
– Zones are overlapped.
– Circuit breakers are located in the overlap
regions.
g
– For a fault anywhere in a zone, all circuit
breakers in that zone open to isolate the
fault.
Overlapped
l d off Protection
• No blind spot:
– Neighboring zones are overlapped to avoid
the possibility of unprotected areas
• Use overlapping CBs:
– Isolation done by CB. Thus, it must be
inserted
se ted in eac
each ove
overlap
lap region
eg o to identify
de t y
the boundary of protective zones.
Primary & Back-up
k Protection
• Primary protection is the protection
provided byy each zone to its elements.
p
• However, some component of a zone
protection scheme fail to operate.
operate
• Back-up protection is provided which
take over only in the event of primary
protection failure.
Example
l
a) Consider the power system shown below, with the
generating source beyond buses 1, 3 and 4. What
are the zones of protection in which the system
should be divided? Which circuit breakers will open
for faults at P1 and P2?
1 3
A P1 2 C P2
B
4
Fault at P1 = A, B, C
Fault at P2 = A,, B,, C,D,
, ,E
Example
l
a) If three circuits breakers are added at the tap
point 2, how would the zones of protection be
modified? Which circuit breakers will operate for
fault at P1 and P2 under these conditions?
1 3
A P1 2 C P2
B
4
Fault at P1 = A, F
Fault at P2 = C,D,E,G
Example
l
Voltage/Potential
Transformer
(
(VT/PT))
Voltage
l Transformers
f
Voltage
l Transformers
f
Voltage
l Transformers
f
HV and EHV
• Capacitor-coupled
p p VT ((CVT))
– C1 & C2 are adjusted, so that a few kVs of
voltage
g is obtains across C2
– Then, stepped down by T
• VTs must be fused or protected by MCB.
Voltage
l Transformers
f
Voltage
l Transformers
f
• VT ratios:
– ratio of the high voltage/secondary
voltage
1:1 2:1 2.5:1 4:1
5:1 20:1 40:1 60:1
80:1 100:1 200:1 300:1
400:1 600:1 800:1 1000:1
2000:1 3000:1 4500:1
Current Transformers
f
• CT is an instrument transformer that is used
to supply a reduced value of current to
meters, protective relays, and other
instruments.
• The
Th primary
i winding
i di consist
i off a single
i l turn
which is the power conductor itself.
• CT secondary
d iis connected
t d tto a current-
t
sensing device with zero impedance.
Function
Isolate
Isolate the high primary voltage of the system (main
the high primary voltage of the system (main
system) from the protection and measuring
equipment
Transform the high primary current of the circuit to a
small secondary current in the 1 – 5 Amp range
Example of CT ratio: 100/1, 200/1 100/5, 200/5, etc
If the primary current changes the secondary
current output will change accordingly For
current output will change accordingly. For
example, if 150 amps flow through the 300 amp
rated primary (300:5), the secondary current
p y( ), y
output will be 2.5 amps.
Advantages:
Safety
provide electrical isolation from power system so that
personnel working with relays will work in a safer
environment
currents of 10 to 20 times (or greater) normal rating
often occur in CT windings for a few cycles during short
circuit
Economy
lower input for relays ( smaller, simpler and less
expensive)
• Accuracy
– reading from measurement will be more
accurate since the range has been scaled
down.
– Because of their high degree of accuracy,
these
h CTs
CT are typically
i ll usedd b by utility
ili
companies for measuring usage for billing
purposes
Two main types
Protection CT
Monitor operation of power grid
not as accurate as Measuring CTs
for supplying current to protective relays.
The wider range of current allows the protective relay
to operate at different fault levels.
Measuring
M i CT ((metering)
t i )
are used where a high degree of accuracy is required
from low-load values up to full-load of a system.
An example
e ample : utilized
tili ed b
by utility
tilit companies for large
capacity revenue billing.
Current Transformers
f
• CTs ratio(secondary current rating is 5A)
50:5 100:5 150:5 200:5
250:5 300:5 400:5 450:5
500:5 600:5 800:5 900:5
1000:5 1200:5
• CTs also available with the secondary rating
of 1A
Current transformers used in metering equipment for 3 phase 400 ampere electricity supply
On
On the other hand, a protection CT has to be
the other hand a protection CT has to be
accurate for currents well in excess of the
rated current i.e. at least 10 times the rated
current.
To
To provide the required accuracy, the CT
provide the required accuracy the CT’ss
have to operate in the linear portion of the
magnetizing curve as shown in figure below;
CT Errors
•This
hi error is
i due
d to burden
b d whichhi h is
i parallel
ll l with
i h excitation
i i
impedance.
•A small value of input
p current is used to excite the core,, thus,,
current flows to the burden is reduced.
Ip’ = Io’ + Is Ip = Io + Is’
Ip’ = Primary current referred secondary Ip = primary current
Io’ = excitation current referred to secondary
Io excitation current referred to secondary Io = excitation current
Io excitation current
Is = secondary current Is’ = secondary current referred to primary.
Current ratio error ((refer to sec))
Is I p
100% Where,
Ip Kn – rated transformer ratio
Ip Ip ‐ actual primary current
Is
Kn Is ‐ actual secondary current
100%
Ip when Ip is flowing
Kn
2.91 V
0 25 A
0.25 A
(b) I S 8 A, Z B 0.8
ZTotal 0.082 0.8
0.882
0 882
ES I S ZTotal
8 0.882
7.06V
From the curve, I o ' 0.4 A
I P ' 0.4 8
8.4 A
100
I P 8.4
5
168A
Is IP '
current ratio error 100%
IP '
8 8.4
84
100%
8.4
4.8%
C) IS = 15A , ZS = 1.5Ω
ZTOTAL = 0.082 + 1.5
0 082 + 1 5
= 1.582Ω
ES = IS X ZTOTAL
=15 X 1.582
15 X 1 582
= 23.73V
From the curve, IO’=20A
Conclusion:
IP’ = 20 + 15 = 35A
High CT saturation causes a
IP = 35 X 100/5
large CT error as in case( C ).
= 700A
700A
S d d practice
Standard i isi to select
l a
•Current ratio error =
CT ratio to give a little less
15 35 than 5A secondaryy current
100% 57.1%
35 (IS< 5A) at max normal load.
However, case (a) is still
suitable for a max primary load
current of about 100A
Example
p
• An over current relay set to operate at 8A is
connected to a 100/5A CT with Is = 8A. Will
the relay detect a 200A primary fault
current if the burden ZB
(a) 0.8 Ω
(b) 3.0 Ω
• Use excitation current curve and secondary
Use excitation current curve and secondary
resistance table for multi‐ratio CT
Solution
• IS = 8A (overcurrent relay setting)
8A ( t l tti )
• IP = 200A (fault current), 100/5A CT , ZEQ’ = 0.082
Is 8A
Z total Z eq ' Z b 0 . 082 0 . 8 0 . 882
E s I s Z total 8 0 . 882 7 . 06 V
from the curve , I o ' 0 . 4 A
I p ' I s I o ' 8 0 .4 8 .4 A
100 IP = 168A produces IS = 8A
I p I p ' K n 8 . 4 168 A
5 – relayy will operate
p
So, if IP = 200A (>168A)
– relay will operate
Reclosers
l and
d Fuses
• Automatic reclosers are commonly used for
distribution circuit protection.
• Recloser: self-controlled device for automatically
interrupting and reclosing an AC circuit with preset
sequence of openings and reclosures
• Have
Ha e bbuilt-in
ilt in control to clear temporary
temporar fa
faults
lts and
restores service with momentary outages.
• Disadvantages:
– increase hazard when circuit is physically contacted by
people.
– Recloser should be locked out during live-line maintenance.
Reclosers
l and
d Fuses
1. An upstream fuse/relay
has detected a fault
2. Downstream system
isolated by fuse or
b k
breaker
3. Automatic re-closing
after
ft ddelay
l successfulf l if
fault not permanent
Relays
l
• Discriminate between normal operating
and fault conditions.
• Type of Relays
– Magnitude Relay
– Directional Relay
– Distance/Ratio Relay
– Differential Relay
– Pilot Relay
Magnitude
d Relays
l
• Also called as Overcurrent Relay
• Response to the magnitude of input
quantities ie.ie current
current.
• Energize CB trip coil when the fault current
magnitude exceeds a predetermined value or
trips
i when h a current rises
i above
b a set point
i
(pick-up current).
• If it is less than the set point value, the relay
remains open, blocking the trip coil.
• Time-delay Overcurrent Relay also have the
same operating method but with an
intentional time-delay.
Directionall Relays
l
• R
Respondsd to
t ffault
lt only
l iin one di
direction,
ti
either to the left or to the right of its
location
• Operation depends upon the direction (lead
or lag) of the fault current with respect to a
reference voltage.
• The directional element of these relays
checks the phase angle between the current
and voltage of one phase, and allows the
overcurrent unit to operate
p if this p
phase
angle indicates current in the reverse
direction.
Ratio Relays
l
• Operate for
f certain relations
l between
b the
h
magnitudes of voltage, current and the
phase angle between them.
them
• Measures the distance between the relay
location and the point of fault,
fault in term of
impedance, reactance and admittance.
• Respond to the ratio of two phasor
quantities as example Voltage and Current (Z
= V/R))
• Also called impedance or distance relay
Differential
ff l Relays
l
• Respond to the vector difference between two
currents within the zone protection determined by
the location of CTs.
CTs
• Not suitable for transmission-line protection
because the terminals of a line are separated
p byy too
great a distance to interconnect the CT secondaries.
• For the protection of generators, transformers,
buses,
buses
• Most differential-relay applications are of the
‘current-differential’ type.
yp
Differential
ff l Relays
l
Relay
• Fault occur at X
• Suppose that current flows through the primary
circuit either to a load or to a short circuit located
at X.
• If the two current transformers have the same ratio,
and are properly connected, their secondary
currents will merely circulate between the two CTs
as sho
shown
nb by the arro
arrows,
s and no ccurrent
rrent will
ill flo
flow
through the differential relay.
Differential
ff l Relays
l
R l
Relay
ZA
ZB