100% found this document useful (2 votes)
1K views27 pages

Chapter 4 Differential Protection

Differential protection compares currents on each side of a transformer or transmission line. It operates when there is a difference, indicating an internal fault. Basic differential relies solely on differential current. Bias/restrained differential uses both differential and average currents to compensate for CT errors and inrush. CTs on the Δ side of a Δ-Y transformer are connected in Y to avoid operation during external faults. Examples show calculating currents for different transformer and generator connections to determine relay operation.

Uploaded by

James
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
1K views27 pages

Chapter 4 Differential Protection

Differential protection compares currents on each side of a transformer or transmission line. It operates when there is a difference, indicating an internal fault. Basic differential relies solely on differential current. Bias/restrained differential uses both differential and average currents to compensate for CT errors and inrush. CTs on the Δ side of a Δ-Y transformer are connected in Y to avoid operation during external faults. Examples show calculating currents for different transformer and generator connections to determine relay operation.

Uploaded by

James
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 27

CHAPTER 4

CHAPTER 4
DIFFERENTIAL PROTECTION
Differential protection principle is used in the
following g applications.
pp
1. Protection of generator, protection of generator
transformer unit.
2 Protection of transformer
2.
3. Protection of feeder (transmission line) by pilot
wire differential protection.
4. Protection
P i off transmission
i i li
line b
by phase
h
comparison carrier current protection.
55. Protection of large
g motor.
6. Bus‐zone protection.
Intro.

 Differential protection is a unit scheme that 
compares the current on the primary side of a 
transformer with that on the secondary side.
y
 Where a difference exists, it is assumed that the 
transformer has developed a fault and the plant 
i  
is automatically disconnected by tripping the 
i ll  di d b   i i   h  
relevant circuit breakers.
 The principle of operation is made based of the 
fact that large transformers are very efficient 
and hence under normal operation power‐in 
equals power‐out.
Cont….
 This scheme is used for tx ≥ 5MVA
 Normally used on generators & transformers. Also 
used to protect lines & busbars.
d     li  & b b
 2 CTs used to monitor protection zone
 Signals from both ends of the CTs are compared by 
differential relay
 CB will trip if the quantity that has been compared is 
p q y p
different from setting value; meaning that a fault 
has occurred within protection zone (internal fault)
 External fault should not affect the CB (CB not trip)
 2 schemes of differential protection system:
 Basic differential protection system
p y
 Bias/restrain differential protection system
Basic differential protection system
 Moderate scheme
 Currents from both ends in protection zone are compared by a 
relay for each phase 
 Relay will operate , if differential current , iR > relay current 
setting, 
 Consider differential protection on transformer (single infeed):

• healthy / external fault condition > >


the CTs are identical:
•the CTs are identical: I
Ip Is
i1 = i2, iR = 0 and iR < iset
Relay not operate
>
<
iR

<
• the CTs are not identical: i
i1 i2
i1≠ i2
>

iR < iset  relay not operate i1
>
iR > iset  relay operate i2

Cause tripping Lead to bias differential scheme
Zone of protection
• internal fault (single infeed) : 
i2 =0, i1 > i2, iR = i1 >
Ip
 iR flows in relay , relay operate >

<
i1 i1

>
i1
internal fault (double infeed) : 
Zone of 
iR =  i1+i2
  i i protection

>
>
Ip Is

> <
iR
<
i1 i2
>

i1
i2

Zone of protection
Problem with basic differential relay

1. CT ratio mismatch
 The two CT must be perfectly matched
 For feeder or generator – the CTs must have same ratio
 For transformer ;
 The CT ratios must be carefully chosen to minimize the 
normal differential c rrent
normal differential current

Ideal Case
= 11%  unbalance
 3  2.67 
  100
00%  11% 
 3 
CT ratio mismatch
2. The magnetic inrush current which flow 
when the tx is switced ON

 When a transformer is initially connected to a 
Wh     f  i  i i i ll   d     
source of AC voltage, there may be a 
substantial surge of current through the 
primary winding called inrush current. 
 Thus, CT can be substantial @ significant 
Th  CT   b   b t ti l @  i ifi t 
errors when magnetic inrush currents exist
BIAS DIFFERENTIAL PROTECTION
SYSTEM

 2 set of coils 
 Operating coil
 Uses differential current to operate the relay
 Restraining coil
 2 halves of a bias coil
 Uses average fault current to restrain the relay from 
operating
Currents flowing in the 2 coils
produce opposing magnetic field

The magnetic
g fields produce
p
opposing torques on an induction
disc

When the torque produced by the


operating coil’s magnetic field
exceeds that of the restraining coil
& the spring, the relay will operate
y  mxc
I o  p I r  I set
I o  operating current  I1  I 2
I r  average restrainin g current


1
I1  I 2 
2
Io
p  bias setting 
Ir
I set  relay setting current

EG 3
2 conditions for relay’s operation:
d f l
 Io> Iset
 Io  p
IR
Connection of CTs
Connection of CTs

 3 phase transformer connection = 
3 phase transformer connection   YY, ∆ ∆ , 
Y  ∆ ∆   Y ∆ 
, ∆ Y
 CTs on Y side of transformer is connected in ∆     
 CTs on ∆ side of transformer is connected in Y
 This arrangement is required to:
 Compensate 30 degree phase shift across transformer 
Y ∆ or ∆Y
 Avoid relay operation when an external earth fault 
A id  l   ti   h     t l  th f lt 
occurred on the ground Y side. This external earth fault 
causes zero sequence currents on the Y side not 
b l
balanced by zero sequence on the ∆ side.
d b         h  ∆  id
i p  i1 & i s  i 2

For ∆ :
For ∆ :
I line  3 I load
i1  3 i p
During full load :  i1 = i2
Example 1
CT1 Y      Δ CT2
Solution
Ip 
5MVA
 262.43 A Δ 5MVA Y
3 11kV 500/5 11/33kV ?/5
5
ip   262.43  2.62 A
500
i1  3  i p  3  2.62  4.55 A
During full load , i1  i2  4.55 A
is  i2
5MVA
Is   87.48 A
3  33kV
I s 87.488
  19.27
is 4.55
CT ratio  19.27  5  96.13
 nearest CT  100 / 5
Example 2
Solution
Primary CT1 Y      Δ CT2

10 MVA
Ip   524.86 A
3  11kV
Δ 10MVA Y
i1  5 A ?/5 11/66kV ?/5
i1 5
ip    2.89 A
3 3 S
Secondary
d
I p 524.86
  181.82 During full load , i1  i2  4.55 A
ip 2.89
is  i2
CT ratio  181.82  5  909 10 MVA
Is   87.48 A
 the nearest CT ratio  1000 / 5 3  66kV
f CT ratio
for i 1000 / 5, I s 87.48
  19.25
is 4.55
i p  524.86  5  2.62 A
1000 CT ratio  19.25  5  96.23
i1  3  i p  3  2.62  4.55 A  nearest CT  100 / 5
EXAMPLE 3
Figure 1 show a simple differential protection on generator
Figure 1 show a simple differential protection on generator.
CT1 and CT2 rated at 1000/1. Relay setting current, Is=0.2A,
i1=9.8A, i2=10.2A, No=1 and percentage bias setting is set 
to 20%.For fault 10kA at F1, determine
i. Operating current, Io
ii
ii. Average bias current IR
Average bias current, I
iii. Comment the relay operation
iv. Repeat step above if I2=0 for fault at F2

Figure 1
solution
(i ) I o  i1  i2  0.4 A

(ii ) I R  9.8  10.2   10


1
2
I 0.4
(iii ) o   0.04  p, p  0.2  relay not operate
I R 10
(iv) I o  9.8  0  9.8 A

I R  9.8  0   4.9 A
1
2
I o 9.8
  2  p & I o  I s  relay operate
I R 4.9

recall
Example 4
Solution
CT1 Δ Y CT2

Y 30MVA Δ
500/5 33/11kV 2000/5

Secondary
Primary
30 MVA
Is 
30 MVA
 524.86 A Is   1574.6 A
3  33kV 3 11kV
I s ( fault )  2  524.86 A  1.05kA I s ( fault )  2 1574.6 A  3.15kA
5 5
is ( fault )  1.05k  10.5 A f l ) 
is ( fault  3.15k  7.87 A
500 2000
i1( fault )  10.5 A i2 ( fault )  3  7.87  13.64 A

I o  10.5  13.64  3.14 A  relay setting current , I s


Example 5
solution
CT1 Y      Δ CT2

3phase fault
Δ 30MVA Y
250/5 132/33kV 600/5
X=0.09p.u

MVAbase 30 MVA ii ) io  50.49  48.58  1.91A


i ) MVA fault    333.3MVA
X p.u 0.09
333.3MVA A
ir 
1
50.49  48.58  49.54 A
I f  Is   5.83kA 2
3  33kV
33 iii ) is  c  0
I p  5.83k   1.46kA
132 p  m  0.2
5 relay bias characteristics  y  0.2 x or io  0.2ir
i p  1.46kA   29.15 A
250 io 1.91
  0.04  p  relay not operate
i1  29.15  3  50.49 A ir 49.54
5
is  5.83kA   48.58  i2
600
90

80 y = 0.2x 

70

60

50
erating current

40 Series1
Linear (Series1)
Ope

30

20

10

0 F (49.54, 1.91)
0 550 100 150
5 200 250
5 3300 350
35 400
4 450
45

‐10
restrain current
Example 6 
(
(Assignment 3)
g 3)

You might also like