Kabelindo Nyy
Kabelindo Nyy
Kabelindo Nyy
Specification :
SNI IEC 60502-1 : 2009
Constructions:
Conductor Applications:
Annealed plain copper round solid or round circular stranded Indoor and outdoor induct installation or of laying in the ground where
according to SNI IEC 60228 not sustain mechanical damage.
sales@kabelindo.co.id 7
Copper Conductor PVC Insulated and PVC Sheathed non Armoured Control Cable
Specification :
SNI IEC 60502-1 : 2009
Constructions:
Insulation Applications:
Extruded layer of Polyvinyl Chloride (PVC) complied with SNI IEC Indoor and outdoor induct installation or of laying in the ground where
60502-1 not sustain mechanical damage.
No. of Cores Nominal Thickness Overall Weight Current Carrying Short Circuit
Min. Insulation Capacity at 30°C Current Standard
and Coss Diameter of Cable DC. Resistance Delivery
Section Area Outer Capacity at
Insulation (approx) (approx) at 20°C 1.0 second Length
Sheath In Ground In Air
12 www.kabelindo.co.id
Copper Conductor PVC Insulated and PVC Sheathed non Armoured Power Cable
Specification :
SNI IEC 60502-1 : 2009
Constructions:
Insulation Applications:
Extruded layer of Polyvinyl Chloride (PVC) complied with Indoor and outdoor induct installation or of laying in the ground where not
SNI IEC 60502-1Colour sustain mechanical damage.
8 www.kabelindo.co.id
Copper Conductor PVC Insulated and PVC Sheathed non Armoured Control Cable
Specification :
SNI IEC 60502-1 : 2009
Constructions:
Insulation Applications:
Extruded layer of Polyvinyl Chloride (PVC) complied with SNI IEC Indoor and outdoor induct installation or of laying in the ground where
60502-1 not sustain mechanical damage.
No. of Cores Nominal Thickness Overall Weight Current Carrying Short Circuit
Min. Insulation Standard
and Cross Diameter of Cable Capacity at 30°C Current
DC. Resistance Delivery
Section Area Outer Capacity at
Insulation (approx) (approx) at 20°C In Ground In Air Length
Sheath 1.0 second
sq.mm mm mm mm kg/km M.Ohm.km A A kA m
7 x 2.5 re 0.8 1.8 15.8 421 50 26 21 0.29 1000/D
7 x 2.5 rm 0.8 1.8 16.5 450 50 26 21 0.29 1000/D
8 x 2.5 re 0.8 1.8 16.9 471 50 23 18 0.29 1000/D
8 x 2.5 rm 0.8 1.8 17.7 505 50 23 18 0.29 1000/D
10 x 2.5 re 0.8 1.8 19.1 570 50 21 17 0.29 1000/D
10 x 2.5 rm 0.8 1.8 20.1 611 50 21 17 0.29 1000/D
12 x 2.5 re 0.8 1.8 19.7 637 50 20 16 0.29 1000/D
12 x 2.5 rm 0.8 1.8 20.7 682 50 20 16 0.29 1000/D
14 x 2.5 re 0.8 1.8 20.5 724 50 18 15 0.29 1000/D
14 x 2.5 rm 0.8 1.8 21.6 777 50 18 15 0.29 1000/D
16 x 2.5 re 0.8 1.8 21.5 804 50 17 14 0.29 1000/D
16 x 2.5rm 0.8 1.8 22.6 863 50 17 14 0.29 1000/D
19 x 2.5 re 0.8 1.8 22.5 907 50 17 13 0.29 1000/D
19 x 2.5 rm 0.8 1.8 23.6 974 50 17 13 0.29 1000/D
21 x 2.5 re 0.8 1.8 23.6 989 50 16 12 0.29 1000/D
21 x 2.5 rm 0.8 1.8 24.9 1062 50 16 12 0.29 1000/D
24 x 2.5 re 0.8 1.8 25.9 1118 50 15 11 0.29 1000/D
24 x 2.5 rm 0.8 1.8 27.3 1200 50 15 11 0.29 1000/D
30 x 2.5 re 0.8 1.8 27.3 1335 50 14 11 0.29 1000/D
30 x 2.5 rm 0.8 1.8 28.8 1433 50 14 11 0.29 1000/D
40 x 2.5 re 0.8 1.9 30.5 1718 50 14 11 0.29 1000/D
40 x 2.5 rm 0.8 1.9 32.3 1846 50 14 11 0.29 1000/D
52 x 2.5 re 0.8 2.0 35.8 2220 50 14 11 0.29 1000/D
52 x 2.5 rm 0.8 2.0 37.9 2384 50 14 11 0.29 1000/D
61 x 2.5 re 0.8 2.1 37 2552 50 14 11 0.29 1000/D
61 x 2.5 rm 0.8 2.1 39.1 2741 50 14 11 0.29 1000/D
sales@kabelindo.co.id 13
Copper Conductor PVC Insulated and PVC Sheathed non Armoured Power Cable
Specification :
SNI IEC 60502-1 : 2009
Constructions:
Insulation Applications:
Extruded layer of Polyvinyl Chloride (PVC) complied with Indoor and outdoor induct installation or of laying in the ground where not
SNI IEC 60502-1 sustain mechanical damage.
sales@kabelindo.co.id 9
Copper Conductor PVC Insulated and PVC Sheathed non Armoured Power Cable
Specification :
SNI IEC 60502-1 : 2009
Constructions:
Insulation Applications:
Extruded layer of Polyvinyl Chloride (PVC) complied with Indoor and outdoor induct installation or of laying in the ground where
SNI IEC 60502-1 not sustain mechanical damage.
10 www.kabelindo.co.id
Copper Conductor PVC Insulated and PVC Sheathed non Armoured Power Cable
Specification :
SNI IEC 60502-1 : 2009
Constructions:
Insulation Applications:
Extruded layer of Polyvinyl Chloride (PVC) complied with SNI IEC Indoor and outdoor induct installation or of laying in the ground where
60502-1 not sustain mechanical damage.
Current Carrying
No. of Cores Nominal Thickness Overall Weight Short Circuit
Min. Insulation Capacity at 30°C Standard
and Cross Diameter of Cable DC. Resistance Current Delivery
Section Area Insulation Outer at 20°C In Ground In Air Capacity at Length
Sheath (approx) (approx) 1.0 second
sq.mm mm mm mm kg/km M.Ohm.km A A kA m
5 x 1.5 re 0.8 1.8 12.8 255 50 24 18 0.17 1000/D
5 x 1.5 rm 0.8 1.8 13.3 268 50 24 18 0.17 1000/D
5 x 2.5 re 0.8 1.8 14 329 50 32 25 0.29 1000/D
5 x 2.5 rm 0.8 1.8 14.6 352 50 32 25 0.29 1000/D
5 x 4 re 1.0 1.8 16.3 470 50 41 34 0.46 1000/D
5 x 4 rm 1.0 1.8 17.1 505 50 41 34 0.46 1000/D
5 x 6 re 1.0 1.8 17.7 602 50 52 44 0.69 1000/D
5 x 6 rm 1.0 1.8 18.6 650 50 52 44 0.69 1000/D
5 x 10 rm 1.0 1.8 20.4 893 50 69 60 1.15 1000/D
5 x 10 rm 1.0 1.8 21.1 912 50 69 60 1.15 1000/D
5 x 16 rm 1.0 1.8 23.8 1279 40 89 80 1.84 1000/D
5 x 25 rm 1.2 1.8 28.3 1914 40 116 105 2.88 1000/D
5 x 35 rm 1.2 1.9 31.5 2505 40 138 130 4.03 1000/D
5 x 50 rm 1.4 2.0 36.4 3273 30 165 160 5.75 1000/D
sales@kabelindo.co.id 11