DATA SHEET FOR PREMIUM / PERTAMAX/SOLAR STORAGE TANK 5000 KL

No. Dokumen BJM-EC-20-DS-009-A4


Rev. 00 Tanggal 07-03-2019 1 of 5

JASA KONSULTASI PENYUSUNAN FEED


UNTUK PENGEMBANGAN TERMINAL BBM BANJARMASIN
KALIMANTAN SELATAN

PT. PERTAMINA (PERSERO)


2018

0 Issued For Approval 07 Mar 19 AGG NDP NDP


DISETUJUI
Rev. DESKRIPSI TANGGAL DIBUAT DIPERIKSA DISETUJUI
PERUSAHAAN
DATA SHEET FOR PREMIUM / PERTAMAX/SOLAR STORAGE TANK 5000 KL

No. Dokumen BJM-EC-20-DS-009-A4


Rev. 00 Tanggal 07-03-2019 2 of 5

LEMBAR REVISI

No Rev. Tanggal Diskripsi

00 07/03/19 Issued For Approval


DATA SHEET FOR PREMIUM / PERTAMAX/SOLAR STORAGE TANK 5000 KL

No. Dokumen BJM-EC-20-DS-009-A4


Rev. 00 Tanggal 07-03-2019 3 of 5

SUPPLIER’S
NO. DESCRIPTION UNIT REQUIREMENT
RESPONSE
DATA SHEET FOR
PREMIUM / PERTAMAX / SOLAR
1 1
STORAGE TANK

NOTES:
1.
2. .
DOCUMENT NO.:
DATASHEET FOR
PREMIUM/PERTAMAX/SOLAR TANK BJM-EC-20-DS-009-A4

PAGE : 4 of 5

PROJECT NAME : JOB NO.

JASA KONSULTASI PENYUSUNAN FEED UNTUK TBA


PENGEMBANGAN TERMINAL BBM
0 7-Mar-19 AGG ISSUED FOR APPROVAL DATE REVISION
BANJARMASIN
REV. DATE BY DESCRIPTION 07-Mar-19 0
TAG NO. : 20-T-21 CONTRACTOR COMPANY
SERVICE : Premium/Pertamax/Solar Storage Tank ORIGINATOR: CHECKED: APPROVED: APPROVED:
AGG NDP NDP
1 Applicable to : Proposal Purchase As Built
2 Quantity : 2 set
3 Manufacturer : TBA
4 DESIGN DATA MATERIAL
5 Service Premium/Pertamax/Solar Storage Tank Part Material Spec (Note 8.)
o
6 Liquid Flash Point C 130 Shell ASTM A283 Gr.C
7 Code API 650 12th Ed. 2015 Bottom ASTM A283 Gr.C
8 Temperature Design °C 60 Roof ASTM A283 Gr.C
9 Operating °C Ambient Annular ASTM A283 Gr.C
10 Min. Design Metal Temp. °C -10 Reinforcing pads ASTM A283 Gr.C
11 Pressure Flange ASTM A105
12 Design kg/cm2 Full of Water Nozzle pipes ASTM A106 Gr. B
13 Operating kg/cm2 Atmosphere Earthing lugs 316 SS
14 Hydrotest Pressure kg/cm2 Full of Water Platform, ladder, pipe clip ASTM A36 (HDG)
15 MAWP kg/cm2 as per Spec and Code Structure - tower ASTM A36
16 Capacity Support beam ASTM A36
17 Nominal m3 6133 Platform grating Note 6.
18 Working m3 5000 Handrail Pipe (HDG)
19 Tank Type Cylindrical Saddle N/A
20 Tank Dimension Inlet Baffle N/A
21 Diameter mm 20000 Internal Pipe ASTM A106 Gr. B
22 Height / Length mm 19800 Internal Ladder N/A
23 Corrosion Allowance Stiffening Ring Yes
24 Roof/Shell/Bottom/Annular mm 1,2,2,2
25 Base Ring / Plate ASTM A36
26 Wall Thickness External Attachment
27 Shell (minimum) mm 8 (*) Stilling Well 316 SS
28 Bottom (minimum) mm 10 (*) Support beam ASTM A36
29 Roof (minimum) mm 8 (*) Grating Note 6.
30 Weld Joint Efficiency Ladder ASTM A36
31 Shell 0.85 Nameplate 316 SS
32 Bottom 0.85 Nameplate Bracket ASTM A36
33 Roof 0,85 External
34 Non Destructive Test SHELL BOTTOM ROOF Bolts SA 193 Gr. B7 Flouro Carbon
35 Radiography Spot Spot Spot Nuts SA 194 Gr. 2H Flouro Carbon
36 Ultrasonic Note 5 Note 5 Note 5 Gasket Spiral Wound 316 SS Graphite Filler
37 Magnetic Particle Note 5 Note 5 Note 5 Internal
38 Dye Penetrant Note 5 Note 5 Note 5 Bolts N/A
39 PWHT N/A Nuts N/A
40 Insulation mm N/A Material impact test required No
41 Fire Proofing mm N/A Certified low temp. test req. No
42 Painting Note 11. CONSTRUCTION
43 External Yes Type of Bottom Fall at center, Slope 1:120
44 Internal Yes Type of Roof Fixed Cone Roof
45 Seismic Design as per SNI 1726 - 2012 Type of Support N/A
46 Seismic Zone G 0,3 Internal Floating Roof No
47 Wind Code ASCE Latest Ed. Platform, ladder, pipe clip Circular Ladder
48 Wind Speed km/hr 140 Insulation ring clip No
49 ESTIMATED WEIGHT Manhole Yes
50 Empty (incl. attached piping) ton 158,15 Earthing lugs Yes
51 Shipping Approx. ton 158,15 Lifting Lugs - eyes No
52 Operating Approx. ton 5.433,36 Splash Plate Yes
53 Shop Test Approx. ton 6.292,11 Dripping Ring Yes
54 Nameplate Yes
55 Foundation Concrete
56 Roof handrail Yes
57 Setting bolts SA193 Gr.B7 Hot Dipped Galvanized
58 Code stamp No
59
60
DOCUMENT NO.:
DATASHEET FOR
PREMIUM/PERTAMAX/SOLAR TANK BJM-EC-20-DS-009-A4

PAGE : 5 of 5

PROJECT NAME : JOB NO.

TBA
JASA KONSULTASI PENYUSUNAN FEED UNTUK
PENGEMBANGAN TERMINAL BBM BANJARMASIN 0 07-Mar-19 AGG ISSUED FOR APPROVAL DATE REVISION
REV. DATE BY DESCRIPTION 07-Mar-19 0
TAG NO. : 20-T-21 CONTRACTOR COMPANY
SERVICE : Premium/Pertamax/Solar Storage Tank ORIGINATOR: CHECKED: APPROVED: APPROVED:
AGG NDP NDP
1 CONSTRUCTION DETAILS (CONTINUED)
2
3 SCHEDULE OF APPURTENANCES
4
5 SIZE ANSI FLANGE
MARK DESCRIPTION QTY. REMARKS
6 (in) CLASS TYPE
7 N1 Inlet Nozzle 1 8 #150 RFWN c/w diffuser
8 N2 Outlet Nozzle 1 10 #150 RFWN c/w Fortex Breaker
9 N3 Spare 1 2 #150 RFWN c/w Blind Flange
10 N4A/B Level Switch Low Low 2 2 #150 RFWN
11 N5A/B Level Switch High High 2 2 #150 RFWN
12 N6A Water Drain 1 4 #150 RFWN to Open Ditch, c/w Internal Pipe
13 N6B Drain 1 4 #150 RFWN to Tank Drainage, c/w Internal Pipa
14 N7 Level Indicator Transmitter (ATG) 1 6x8 #150 RFWN c/w Stilling Well
15 N8 Temperature Indicator 1 2 #150 RFWN
16 N9 Slot Dipping Device 1 4 #150 RFWN c/w Gauge Hatch and Stilling Well
17 N10 Roof Spare 1 4 #150 RFWN c/w Blind Flange
18 N11 Inlet 1 4 #150 RFWN
19 N12 Nozzle Foam Chamber 1 10 #150 RFWN c/w Platform for Maintenance
20 M1A/B Manhole 2 24 #150 RFWN c/w Blind Flange
21 M2A/B Roof Manhole 2 24 #150 RFWN c/w Davit
22 V Vent 1 4 #150 RFWN c/w Flame Arrestor
23 Sketch :
24
25 V
26
N9 N10
27 M2
N8
N7 A/B
28
29
30
31 N5B
32
N5A
33
N12
34
35 N3
36
37 N4B

38
N11 N4A
39 N1 N2
M1A/B
40
N6B N6A
41
42
43 slope 1 : 120
44
45 Notes :
46 1. Specification for this tank should be refer to BJM-EC-20-SP-001-A4 Spesifikasi Umum Tangki Timbun Bahan Bakar
47 2. All materials used in construction, fabrication and assembly shall conform to all applicable ANSI and ASTM listed publications.
48 3. All weld joints must conform to the applicable listed AWS publications & API 650 12 th ed. 2013
49 4. All tank connections shall conform to ANSI B16.5
50 5. Refer to API 650 12 th ed. 2013
51 6. Grating should be hot dip galvanized
52 7. Tank fabricator / manufacturer should determined details engineering stage before construction phase
53 8. Refer to ASTM materials standard
54 9. BJM-EC-10-DG-010-A3 P & ID Diagram Premium Storage Tank
55 10. VTA/(*) = Vendor To Advice
56 11. Painting:
57 External : LS 11
58 Internal : Epoxy Resin 250 Micron
59 Underside Tank : Coal Tare Epoxy 1000 Micron