0% found this document useful (0 votes)
106 views37 pages

Genset Controller, GC-1F Option B3, Automatic Mains Failure (AMF) and Automatic Transfer Switch Control (ATS)

This document describes the functionality of Option B3 for the GC-1F genset controller. Option B3 allows the controller to operate as an automatic mains failure and automatic transfer switch system. It provides monitoring and control of mains power sources and the generator, transferring load between sources as needed.

Uploaded by

luis machuca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views37 pages

Genset Controller, GC-1F Option B3, Automatic Mains Failure (AMF) and Automatic Transfer Switch Control (ATS)

This document describes the functionality of Option B3 for the GC-1F genset controller. Option B3 allows the controller to operate as an automatic mains failure and automatic transfer switch system. It provides monitoring and control of mains power sources and the generator, transferring load between sources as needed.

Uploaded by

luis machuca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 37

80

DESCRIPTION OF OPTIONS

Genset Controller, GC-1F


Option B3, Automatic Mains Failure (AMF)
and Automatic Transfer Switch control (ATS)

 Description of option
 Functional description
 Parameter list

Document no.: 4189340473H


GC-1F Option B3, AMF and ATS

This description includes the following versions:

GC-1F SW version 1.2x.x


GC-1F/2 SW version 2.0x.x or later

DEIF A/S Page 2 of 37


GC-1F Option B3, AMF and ATS

Table of contents

1. WARNINGS, LEGAL INFORMATION AND SAFETY ........................................................... 4


LEGAL INFORMATION AND DISCLAIMER ........................................................................................... 4
ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 4
SAFETY ISSUES ............................................................................................................................ 4
FACTORY SETTINGS ...................................................................................................................... 4
DEFINITIONS ................................................................................................................................ 4
2. DESCRIPTION OF OPTION B3............................................................................................. 5
ANSI NUMBERS ............................................................................................................................ 5
AUTOMATIC MAINS FAILURE (AMF) ............................................................................................... 5
AUTOMATIC TRANSFER SWITCH (ATS) .......................................................................................... 5
LOAD TAKE OVER (LTO) .............................................................................................................. 6
3. HARDWARE........................................................................................................................... 7
TERMINALS .................................................................................................................................. 7
W IRING 3-PHASE .......................................................................................................................... 8
W IRING 1-PHASE .......................................................................................................................... 9
W IRING SPLIT-PHASE .................................................................................................................. 10
W IRING 3-PHASE 3-POSITION ATS .............................................................................................. 11
PUSH-BUTTONS AND LEDS ......................................................................................................... 12
4. FUNCTIONAL DESCRIPTIONS .......................................................................................... 13
AMF/ATS FAILURE LOGIC ........................................................................................................... 14
ATS TIMING SEQUENCES ............................................................................................................ 17
ATS CONFIGURATIONS ............................................................................................................... 24
CONFIGURATION......................................................................................................................... 28
INPUT FUNCTIONS (B3) ............................................................................................................... 28
OUTPUT FUNCTIONS (B3) ........................................................................................................... 30
ATS - SOURCE – SOURCE .......................................................................................................... 35
5. PARAMETER LIST .............................................................................................................. 37

DEIF A/S Page 3 of 37


GC-1F Option B3, AMF and ATS

1. Warnings, legal information and safety

Legal information and disclaimer


DEIF takes no responsibility for installation or operation of the genset. If there is any doubt about
how to install or operate the engine/generator controlled by the unit, the company responsible for
the installation or the operation of the set must be contacted.

The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.

Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.

The English version of this document always contains the most recent and up-to-date infor-
mation about the product. DEIF does not take responsibility for the accuracy of translations, and
translations might not be updated at the same time as the English document. If there is a
discrepancy, the English version prevails.

Electrostatic discharge awareness


Sufficient care must be taken to protect the terminals against static discharges during the
installation. Once the unit is installed and connected, these precautions are no longer necessary.

Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.

Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.

Factory settings
The unit is delivered with certain factory settings. Given the fact that these settings are based on
average values, they are not necessarily the correct settings for matching the individual
engine/generator. Thus precautions must be taken to check the settings before running the
engine.

Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.

Notes
The notes provide general information, which will be helpful for the reader to
bear in mind.

Warnings

The warnings indicate a potentially dangerous situation, which could result in


death, personal injury or damaged equipment, if certain guidelines are not
followed.

DEIF A/S Page 4 of 37


GC-1F Option B3, AMF and ATS

2. Description of option B3

This document describes the functionality of AC voltage measurement and functions contained
in option B3.

ANSI numbers

Function ANSI no.


3-phase AC voltage measurement, 50 to 480 V AC, 50/60 Hz -
3-phase over- and under-voltage failure 27/59
3-phase over- and under-frequency failure 81
3-phase voltage unbalance 60
3-phase – phase rotation sequence 47

Automatic Mains Failure (AMF)


Option B3 is a software and hardware option, which means that the front foil will have to be
changed. The basic GC-1F genset controller unit can be equipped with option B3. With option
B3, the GC-1F will function as a real emergency power system controller. The mains (busbar) is
supervised, and if a fault (voltage/frequency/unbalanced) is detected, a disconnection signal will
be sent to the mains breaker. At the same time the start sequence for the generator is initiated.
When the generator voltage is within the limits, a signal will be transmitted to close the generator
breaker. When the mains returns and the mains OK timer has expired, the generator breaker
will open and the mains breaker is closed.

Automatic Transfer Switch (ATS)


The basic GC-1F genset controller unit can be equipped with option B3. With option B3, the GC-
1F will be able to operate several different ATS mechanisms with AMF logic. There are two
different ATS types:

 Generator – Mains
 Mains Source 1 – Mains Source 2 or Normal Source – Emergency Source.
In this document, it will be called “Source – Source”

Generator – Mains
This ATS type will be able to operate the mechanism of an ATS with control signals, defined by
the input/output settings. The ATS will use AMF logic for the operation. The ATS controller will
be able to control and protect the genset like in normal mains failure situations.

It will also be possible just to give a start signal, “Start genset”, to a genset. In this mode, the
control and protection of the genset is done by the genset controller, with the GC-1F/2 ATS
controller operating the ATS.

Source – Source
This type of ATS control will operate the mechanism of an ATS with control signals as defined by
the input/output settings. The AMF handling is available between two mains or utility sources.
Similar parameters as Generator – Mains are used, but with parameter names better suited to fit
the Source – Source application. The GC-1F/2 ATS controller will not be able to control a genset
directly, for example managing the start sequence with prepare and crank, but it will be able to
give a start signal, “Start genset”, for both sources. Priority selection of the sources will be
possible by settings or done by M-Logic.

DEIF A/S Page 5 of 37


GC-1F Option B3, AMF and ATS

Load Take Over (LTO)

The purpose of the LTO mode is to allow the controller to transfer the load to the genset
regardless of the mains status. This could be used with command timer functions. There are two
LTO modes, mode shift with normal LTO and LTO with AMF.

Mode shift OFF (normal LTO)


If a mains failure event occurs, the controller will not automatically shift mode from LTO to AMF,
thus the genset will not start. In this mode, the GC-1F will only start and take over the load when
the unit is started in auto mode via digital input: “Auto start/stop”, regardless of the mains status.
If a mains failure event occurs when a stop signal is given, the genset will continue to stop and
open GB. The MB will remain open until the mains voltage is normal again, then it will close the
MB. If a mains failure event occurs while the genset is not running in this mode, the genset will
not react to the mains failure.

Mode shift ON (LTO with AMF mode)


If a mains failure occurs when a stop genset signal is active, the genset will shift mode to AMF
and run the AMF sequence. This will keep the genset running and GB closed until the mains
voltage is normal again. When mains is normal, it will shift mode back to LTO. If a mains failure
occurs while the genset is stopped (not running), the genset will react to the mains failure and
start up like in a normal mains failure situation. The genset will stop again when the mains has
been restored.

Start/stop of the genset in auto mode requires configuration of “auto start/stop”


digital input.

DEIF A/S Page 6 of 37


GC-1F Option B3, AMF and ATS

3. Hardware

Terminals
The AC voltage inputs are placed on terminals 28-32. The mains breaker control relay output is
placed on terminals 47 and 48.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27
+ 0 com 1 2 3 com 1 2 3 4 5 6 com Input
R24 R26
R21 R22 R23
B(- 49
Power Status Multi Binary Emergen- RS485
sup- tional modbus
stop Option GND 50
A(+ 51
52
Can H 53
Can 1
GND 54
Option
Can L 55
56
Can H 57
Can
GND 58
Option H8/X4
Can L 59
Mains voltage Gen Voltage Gen
L1 N L2 NA L3 L1 N NA L2 NA L3 L1 L2 L3
28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 47

Unit rear view

AMF control
28 Mains L1 voltage
29 Mains neutral voltage
30 Mains L2 voltage Voltage range 50 to 480 V AC Ph-Ph value
31 Do not connect
32 Mains L3 voltage
47-48 Mains breaker control relay Function NC (normally closed). Configurable

DEIF A/S Page 7 of 37


GC-1F Option B3, AMF and ATS

Wiring 3-phase

MAINS GC-1F AMF


N L1 L2 L3
28 U L1
29 Neutral
Mains
30 U L2 voltages

32 U L3

15 MB OFF feedback
Supply

47
MB ON command
48
45
MB GB ON command
46

Consumers 14 GB OFF feedback

GB

33 U L1
36 U L2
Generator
34 Neutral voltage

38 U L3

S2
40 L1 s2
S1
39 L1 s1
S2
42 L2 s2 Generator
current
S1
41 L2 s1
S2
44 L3 s2
S1
43 L3 s1

N L1 L2 L3

Generator

DEIF A/S Page 8 of 37


GC-1F Option B3, AMF and ATS

Wiring 1-phase

MAINS
GC-1F AMF
N L1

28 U L1
Mains
voltages
29 Neutral

15 MB OFF feedback
Supply

47
MB ON command
48
45
MB GB ON command
46

Consumers 14 GB OFF feedback

GB

33 U L1 Generator
34 Neutral voltages

S2
40 L1 s2
Generator
S1
39 L1 s1 current

N L1

Generator

DEIF A/S Page 9 of 37


GC-1F Option B3, AMF and ATS

Wiring split-phase

MAINS GC-1F AMF


N L1 L2
28 U L1
31 Neutral
Mains
30 U L2 voltages

15 MB OFF feedback
Supply

47
MB ON command
48
45
MB GB ON command
46

Consumers 14 GB OFF feedback

GB

33 U L1
36 U L2
Generator
34 Neutral voltage

S2
40 L1 s2
S1
39 L1 s1
S2
42 L2 s2 Generator
current
S1
41 L2 s1

N L1 L2

Generator

DEIF A/S Page 10 of 37


GC-1F Option B3, AMF and ATS

Wiring 3-phase 3-position ATS

DEIF A/S Page 11 of 37


GC-1F Option B3, AMF and ATS

Push-buttons and LEDs


The display for option B3 includes two extra push-buttons and one LED.

For general information about the display push-buttons and LEDs, see the
Installation Instructions and Reference Handbook.

DEIF A/S Page 12 of 37


GC-1F Option B3, AMF and ATS

4. Functional descriptions

The following sequences will be shown in two conditions:

Mains fail timing sequence

Start engine + Open MB

DEIF A/S Page 13 of 37


GC-1F Option B3, AMF and ATS

Start engine

Mains OK

MB On
tMBC
GB On
tGBC
Gen start seq
tFD
Gen stop seq
tFOD
Gen running

Gen f/U OK
tFU
Mains failure Mains OK
detected

AMF/ATS failure logic


The following describes the normal failure situations handled by the GC-1F during a mains
failure/OK sequence (refer to “Mains fail timing sequence” for details).

AMF/ATS logic will only activate in AUTO mode.

Mains failure, open MB


When a mains failure occurs, the MB is opened when either mains failure is detected (7065
Start eng. + open MB) or when GB is ready to take load (7065 Start eng.). If the MB cannot be
opened, the GC-1F signals an MB open failure. The genset is kept running to have it ready when
the MB failure has been fixed.

The fail class for MB open failure (2200):


1. Warning
a. Alarm is activated
b. GB is not closed, since MB cannot be opened
c. Genset stays running
2. Trip of GB
a. Alarm is activated
b. Genset stays running
3. Trip and stop
a. Alarm is activated
b. Genset is stopped including cooldown
4. Shutdown
a. Alarm is activated
b. Genset is stopped without cooldown
5. Trip of MB
a. Alarm is activated
b. Genset stays running
6. Shutdown and manual mode
a. Alarm is activated
b. Genset is stopped without cooldown
c. Controller changes running mode to MANUAL

DEIF A/S Page 14 of 37


GC-1F Option B3, AMF and ATS

Mains failure, closing GB


When the genset has been started and the MB is opened (no MB open failure), the GB must be
closed. If this results in a GB close failure, the GB relay/pulse will be opened/given again and a
GB close failure will be signalled. It is possible to change the fail class of the GB close failure to
either “Trip and stop” or “Shutdown” to have the genset stopped when the GB cannot be closed.

The fail class for GB close failure (2170):


1. Warning
a. Alarm is activated
b. GB is tripped
c. Genset stays running
2. Trip of GB
a. Alarm is activated
b. GB is tripped
c. Genset stays running
3. Trip and stop
a. Alarm is activated
b. GB is tripped
c. Genset is stopped including cooldown
4. Shutdown
a. Alarm is activated
b. GB is tripped
c. Genset is stopped without cooldown
5. Trip of MB
a. Alarm is activated
b. GB is tripped
c. MB trips (if closed) and load is dropped
d. Genset stays running
6. Shutdown and manual mode
a. Alarm is activated
b. GB is tripped
c. Genset is stopped without cooldown
d. Controller changes running mode to MANUAL

Mains OK, Open GB


When mains returns, the GB must be opened and the MB can be closed. If the GB cannot be
opened, a GB open failure is signalled and the GB relay/pulse is closed/given again.

The fail class for GB open failure (2160):


1. Warning
a. Alarm is activated
b. Genset stays running
2. Trip of GB
a. Alarm is activated
b. Genset stays running
3. Trip and stop
a. Alarm is activated
b. Genset is stopped including cooldown
4. Shutdown
a. Alarm is activated
b. Genset is stopped without cooldown
5. Trip of MB
a. Alarm is activated
b. Genset stays running
6. Shutdown and manual mode
a. Alarm is activated

DEIF A/S Page 15 of 37


GC-1F Option B3, AMF and ATS

b. Genset is stopped without cooldown


c. Controller changes running mode to MANUAL

Mains OK, Close MB


When the GB has been opened, the genset starts its cooldown sequence and the MB is closed.
If this results in an MB close failure, an MB close failure is signalled, and the MB relay/pulse is
opened/given again. Furthermore, the GB is closed again, sourcing the load.

The fail class for MB close failure (2210):


1. Warning
a. Alarm is activated
b. If Gen V/Hz is OK, GB is closed
c. Genset stays running
2. Trip of GB
a. Alarm is activated
b. GB trips. Load is dropped
3. Trip and stop
a. Alarm is activated
b. GB is tripped and the genset is stopped including cooldown
4. Shutdown
a. Alarm is activated
b. GB is tripped and the genset is stopped without cooldown
5. Trip of MB
a. Alarm is activated
b. MB trips and load is dropped
c. If Gen V/Hz is OK, GB is closed. Genset stays running
6. Shutdown and manual mode
a. Alarm is activated
b. GB is tripped and the genset is stopped without cooldown
c. Controller changes running mode to MANUAL

External trip of GB/CB1 or MB/CB2


If parameter 2240 (GB/CB1) or 2250 (MB/CB2) is activated, the GC-1F will monitor the breaker
activity and act according to the configured fail class.

For example, if one of the breakers, CB1, is tripped by external events, the unit will report “CB1
Ext. tripped Unacknowledged” and the alarm LED will be turned ON.

The function requires configuration of breaker feedbacks.

DEIF A/S Page 16 of 37


GC-1F Option B3, AMF and ATS

ATS timing sequences

2 standard, fast operating, stored energy circuit breakers (2CBFO)

Open mains breaker and start engine

Start engine and open mains breaker

Mains OK

MB ON (pulse)

MB OFF (pulse)

GB ON (pulse)
tGBC
GB OFF (pulse)
tFOD tMBC
Gen start seq
tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen cooldown

Mains failure
Mains OK
detected

DEIF A/S Page 17 of 37


GC-1F Option B3, AMF and ATS

2 position electrically held, solenoid style ATS or 2 contactors electrically held, (2COEH)

Open mains breaker and start engine

Mains OK
tFOD
MB (cont)
tMBC
GB (cont)
tGBC
Gen start seq
tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen cooldown

Mains failure
Mains OK
detected

Start engine and open mains breaker

Mains OK
tFOD
MB (cont)
tMBC
GB (cont)
tGBC
Gen start seq
tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen running

Mains failure
Mains OK
detected

DEIF A/S Page 18 of 37


GC-1F Option B3, AMF and ATS

2 position mechanically held solenoid style ATS or 2 contactors, mechanically held


(2COMH)

Open mains breaker and start engine

Mains OK

MB ON (pulse)

GB ON (pulse)
tGBC tFOD tMBC
Gen start seq
tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen cooldown

Mains failure
Mains OK
detected

Start engine and open mains breaker

DEIF A/S Page 19 of 37


GC-1F Option B3, AMF and ATS

3 position electrically held solenoid style ATS or contactors (3COEH) – 2 outputs

Open mains breaker and start engine

Start engine and open mains breaker

DEIF A/S Page 20 of 37


GC-1F Option B3, AMF and ATS

3 position electrically held solenoid style ATS or contactors (3COEH) – 3 outputs

Open mains breaker and start engine

Start engine and open mains breaker

DEIF A/S Page 21 of 37


GC-1F Option B3, AMF and ATS

3 position mechanically held solenoid style ATS or contactors (3COMH) – 2 outputs

Open mains breaker and start engine

Mains OK

MB ON (pulse)
tMBC
GB ON (pulse)
tGBC tFOD
Neutral pos ON

Gen start seq


tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen cooldown

Mains failure
Mains OK
detected

Start engine and open mains breaker

Mains OK

MB ON (pulse)
tMBC
GB ON (pulse)
tGBC tFOD
Neutral pos ON

Gen start seq


tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen cooldown

Mains failure
Mains OK
detected

DEIF A/S Page 22 of 37


GC-1F Option B3, AMF and ATS

3 position mechanically held solenoid style ATS or contactors (3COMH) – 3 outputs

Open mains breaker and start engine

Mains OK

MB ON (pulse)
tMBC
Neutral ON (pulse)
tFOD
GB ON (pulse)
tGBC
Gen start seq
tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen cooldown

Mains failure
Mains OK
detected

Start engine and open mains breaker

Mains OK

MB ON (pulse)
tMBC
Neutral ON (pulse)
tFOD
GB ON (pulse)
tGBC
Gen start seq
tFD
Gen stop seq

Gen running

Gen Hz/V OK
tFU
Gen cooldown

Mains failure
Mains OK
detected

DEIF A/S Page 23 of 37


GC-1F Option B3, AMF and ATS

ATS configurations

2 × standard fast operating stored energy circuit breakers (2CBFO)


2CBFO needs one trip and one close contact for each breaker. Often they are mechanically
and/or electrically interlocked so they cannot both be closed at the same time. Thus the
controller will not send a close signal to the GB until an open signal from the MB has been
received (when feedback signals are assigned).

Settings Gen-Mains Source-Source


Relay GB ON (pulse) CB1 ON (pulse)
Relay GB OFF (pulse) CB1 OFF (pulse)
MB feedback
GB feedback

Relay MB ON (pulse) CB2 ON (pulse)


MB OFF
GB OFF

MB ON
GB ON

Relay MB OFF (pulse) CB2 OFF (pulse)

2 position electrically held solenoid style ATS (2COEH)


2COEH needs one continuous signal for each ATS position. When GB is closed (and MB is
opened), it electrically holds the ATS in the Gen position. When MB is closed (and GB is
opened), it electrically holds the ATS in the Mains position.

Settings Gen-Mains Source-Source


Relay GB (cont) CB1 (cont)
Relay MB (cont) CB2 (cont)
MB feedback
GB feedback

MB OFF
GB OFF

MB ON
GB ON

2 position mechanically held solenoid style ATS (2COMH)


2COMH operates like a 2COEH, but with pulse signals instead of continuously held signals.
There is no open signal, only close signals. Closing the ATS in Gen position will mechanically
open mains and vice versa. The closing signals are pulses with a variable pulse length
(adjustable in USW), or until a close feedback is detected.

Settings Gen-Mains Source-Source


Relay GB ON (pulse) CB1 ON (pulse)
Relay MB ON (pulse) CB2 ON (pulse)

DEIF A/S Page 24 of 37


GC-1F Option B3, AMF and ATS

Motorised rotary switch (MRS)


An MRS is controlled by only one signal input, controlling a motor that runs to change the ATS
position. The motor only runs in one direction, and therefore feedback signals are needed to tell
when the ATS is in the correct position. The GB ON and the MB ON pulse outputs must be
connected in parallel to operate the motor run signal. When feedback signals are detected, the
pulse outputs are opened and the motor is stopped in the position.

Settings Gen-Mains Source-Source


Relay GB ON (pulse) CB1 ON (pulse)
Relay MB ON (pulse) CB2 ON (pulse)
Input GB position ON CB1 position ON
Input MB position ON CB2 position ON

3 position mechanically held solenoid style ATS or contactors (3COMH)


3COMH can be operated with either two or three pulse outputs. For both setups, the ATS must
go through neutral when moving from either Gen to Mains or from Mains to Gen (Gen -> Neutral
-> Mains, Mains -> Neutral -> Gen).

Settings Gen-Mains Source-Source


Relay GB ON (pulse) CB1 ON (pulse)
Relay MB ON (pulse) CB2 ON (pulse)
Input Neutral position ON Neutral position ON

For the setup with two outputs, a neutral feedback must be configured as well. When the
3COMH must go from Mains to Gens, it will first send a GB ON pulse to go to neutral, and when
neutral feedback is detected, a second GB ON pulse will be given to go to Gens.
When the 3COMH must go from Gen to Mains, it will first send an MB ON pulse to go to neutral,
and when neutral feedback is detected, a second MB ON pulse will be given to go to mains.

Settings Gen-Mains Source-Source


Relay GB ON (pulse) CB1 ON (pulse)
Relay Neutral ON (pulse) Neutral ON (pulse)
Relay MB ON (pulse) CB2 ON (pulse)

For a setup with three outputs, the neutral ON pulse will be given to move the ATS to neutral,
GB ON pulse will be given to go to Gen, and an MB ON pulse will be given to go to mains.

DEIF A/S Page 25 of 37


GC-1F Option B3, AMF and ATS

3 position electrically held solenoid style ATS or contactors (3COEH)


The 3COEH is operated like the 3COMH, but with continuous signals. Operation with either two
or three outputs is supported. For both setups, the ATS must go through neutral when moving
from either Gen to Mains or from Mains to Gen (Gen -> Neutral -> Mains, Mains -> Neutral ->
Gen).

Settings Gen-Mains Source-Source


Relay GB (cont) CB1 (cont)
Relay MB (cont) CB2 (cont)
MB feedback
GB feedback

Input Neutral position ON Neutral position ON


MB OFF
GB OFF

MB ON
GB ON

For the setup with two outputs, a neutral feedback must be configured as well. When the
3COEH must go from Mains to Gens, it will first open both GB and MB to go to neutral, and
when neutral feedback is detected, the GB relay is closed to go to Gens.
When the 3COEH must go from Gen to Mains, it will first open both MB and GB to go to neutral,
and when neutral feedback is detected, the MB relay is closed to go to mains.

Settings Gen-Mains Source-Source


Relay GB (cont) CB1 (cont)
Relay Neutral (cont) Neutral (cont)
MB feedback
GB feedback

Relay MB (cont) CB2 (cont)


MB OFF
GB OFF

MB ON
GB ON

For a setup with three outputs, the neutral relay will be closed to move the ATS to neutral, GB
relay will be closed to go to Gen and an MB relay will be closed to go to mains (only one relay
closed at a time).

DEIF A/S Page 26 of 37


GC-1F Option B3, AMF and ATS

Timer explanation

Timer Description
tFD Mains failure delay
See 7063 and 7073
tFU Frequency/voltage OK
See 6220
tFOD Mains failure OK delay
See 7062 and 7072
tGBC GB ON delay
See 6231
tMBC MB ON delay
See 7082

ON and OFF sequences

The condition(s) must be met before the operation can take place
Operation Condition
GB ON, direct closing Running feedback
Generator OK (ATS) input, direct closing Generator frequency/voltage OK
MB open
MB ON, direct closing Mains frequency/voltage OK
Mains OK (ATS) GB open
GB OFF, direct opening Shutdown
Trip GB alarms
MB OFF, direct opening Mains failure

Mains failure control (7065) set Start engine + open MB.


If the generator fails to start or the generator breaker fails to close and the
mains is OK, the mains “ok u” and mains “ok f” timer must expire, before the
mains breaker is closed.

Mains failure control (7065) set Start engine.


If the generator fails to start or the generator breaker fails to close, the mains
breaker is closed.

DEIF A/S Page 27 of 37


GC-1F Option B3, AMF and ATS

Configuration

Genset mode

ATS type: Source – Source can only be selected by display, and it will only be
possible when “ATS” is selected as Genset mode (parameter 6070).

Input functions (B3)

Input function Comment


MB Pos on Configurable
MB Pos off Configurable
Neutral Pos on Configurable
Remote MB open Configurable
Remote MB close Configurable
Remote neutral pos Configurable
LTO mode Configurable
AMF mode Configurable
ATS mode Configurable
Generator Ok (ATS) Configurable
Mains OK (ATS) Configurable
Bypass to generator (ATS) Configurable
Bypass to mains (ATS) Configurable
MB close inhibit Configurable

Input function description

1. MB Pos on
When this input is activated, the GC-1F sees the generator breaker as closed. If the MB
on/off feedbacks is high/high simultaneously, an MB position failure is displayed.

2. MB Pos off
When this input is activated, the GC-1F sees the generator breaker as open. If the MB on/off
feedback is high/high simultaneously, an MB position failure is displayed.

DEIF A/S Page 28 of 37


GC-1F Option B3, AMF and ATS

3. Neutral Pos on
When this input is activated, the GC-1F sees the generator and mains breaker as open. If this
input is used, no GB/MB off breaker signals can be used.

4. Remote MB open
This input will open the mains breaker, but will only work in Man mode

5. Remote MB close
This input will close the mains breaker, but will only work in Man mode

6. Remote neutral pos


This input will force the ATS in neutral position, but will only work in Man mode

7. LTO mode
This input will change mode to load take over (LTO)

8. AMF mode
This input will change mode to AMF

9. ATS mode
This input will change mode to ATS

10. Generator Ok (ATS)


This input will skip the generator AC measurement and start the Ok timer right away.

11. Mains OK (ATS)


This input will skip the mains AC measurement and start the Ok timer right away.

12. Bypass to generator (ATS)


This input will bypass the Hz/V OK timer and close the generator breaker.

13. Bypass to Mains (ATS)


This input will bypass the mains OK Hz/V timer and close the mains breaker.

14. MB close inhibit


This input will make an inhibit of closing the mains breaker.

DEIF A/S Page 29 of 37


GC-1F Option B3, AMF and ATS

Output functions (B3)

Output function Factory setting


MB (continuous) Relay 47
Neutral (continuous)
MB ON (pulse)
MB OFF (pulse)
Neutral ON (pulse)
Genset start (ATS)
MB status
Neutral status
Mains OK
Mains fail

Relays 21/22/23 cannot be configured as MB.

Relay 47 is closed when de-energised, but works as all other relays when the
GC-1F is powered up.

Output function description

1. MB (continuous)
MB relay contact will close continuously.

2. Neutral (continuous)
Neutral relay contact will close continuously.

3. MB ON (pulse)
MB relay contact will give an ON pulse signal (adjustable in 7084).

4. MB OFF (pulse)
MB relay contact will give an OFF pulse signal (adjustable in 7084).

5. Neutral ON (pulse)
Neutral relay contact will give an ON pulse signal (adjustable in 2310).

6. Genset start (ATS)


This function is used to give remote start/stop signal in cascade ATS applications.

7. MB status
This output contact will close when the MB is closed.

8. Neutral status
This output contact will close when the ATS is in neutral position.

9. Mains OK
Output contact will close when no mains failure is present or the mains Ok timer is running.

10. Mains fail


Output contact will close when mains failure is present.

DEIF A/S Page 30 of 37


GC-1F Option B3, AMF and ATS

The example below shows the menu for setting the mains failure low voltage:

The example below shows the menu for setting the mains failure high voltage:

The timer for both low and high voltage set point is set in the menu for low
voltage. The same principle is used for the setting of low and high frequency.

DEIF A/S Page 31 of 37


GC-1F Option B3, AMF and ATS

The example below shows the MB close delay timer. The delay set is the time between the
transmission of the GB open signal to the transmission of the MB close signal.

“MB pulse ON time” defines the MB relay out’s pulse time.

“MB pulse ON time” will be interrupted if “MB ON” feedback is present or MB


OFF signal is given in manual.

DEIF A/S Page 32 of 37


GC-1F Option B3, AMF and ATS

The example below shows the MB open failure timer. If the timer expires before the MB is open,
the alarm will be activated. If no sign signals are used, the GC-1F will automatically assume that
the breaker is opening.

The same principle is used for the GB.

The example below shows the MB close failure timer. If the timer expires before the MB is
closed, the alarm will be activated. If no sign signals are used, the GC-1F will automatically
assume that the breaker is closing.

The same principle is used for the GB.

DEIF A/S Page 33 of 37


GC-1F Option B3, AMF and ATS

MB position failure:

If “MB ON” and “MB OFF” inputs give the same feedback signals (High/High), an MB position
failure will be present.

Neutral pulse ON time:

“Neut. pulse ON time” will be interrupted if “Neut. ON” feedback is present or


“Open breaker” signal is given in manual.

DEIF A/S Page 34 of 37


GC-1F Option B3, AMF and ATS

Neutral failure:

This alarm is used for 3 pos. ATS switches where a neutral is used.

Auto-mode shift:

“Auto-mode shift” is used for alarms with fail class “Shutdown + man-mode” and the controller
running in auto-mode. When alarms are acknowledged either by display or by “auto-
acknowledge” setting, the mode will automatically switch to auto-mode.

“Auto-mode shift” parameter and the alarms with “auto-acknowledge” enabled


will ensure the load of a source in case of periodic failures or unstable systems
causing this shutdown.

DEIF A/S Page 35 of 37


GC-1F Option B3, AMF and ATS

ATS - Source – Source


This variant is normally used to switch the load between two mains sources. One of the mains is
working as emergency source for the other mains. In case of mains failure on the “first priority”
mains, the second priority mains will take the load.

ATS type
Change of ATS type from, for example, “Gen – Mains” to “Source – Source” can only be done
via display, when the genset mode 6070 = “Automatic Transfer Switch”.

Change of ATS type resets the unit and default parameters will be present.

Source priority

Parameter overview
The Source – Source ATS type uses the same parameters as Gen – Mains, but parameters for
engine protection and control have been removed. In addition to this, the generator (Gen) and
Mains (BB) parameters have changed names. The parameter numbers are kept the same, so it
is easy to navigate.

Two new groups of protections; “Source 1”, “Source 2” and one new group called ATS logic.
ATS logic has the same functionality and operates as the known AMF logic. “Priority 1” will
always be operated as the “mains” like in normal emergency applications. “Source priority”
makes it possible to choose first priority between Source 1 and Source 2.

Detailed information about standard functionality refers to “Installation Instruc-


tions and Reference Handbook”.

DEIF A/S Page 36 of 37


GC-1F Option B3, AMF and ATS

5. Parameter list

Related to this option are parameters 1620, 2160-2170, 2200-2210, 2240-2250, 6050-6070,
6104, 7060-7082 and 7110.

See the “Installation Instructions and Reference Handbook”, document number 4189340472.

DEIF A/S reserves the right to change any of the above.

DEIF A/S Page 37 of 37

You might also like