RSLogix 5000 Emulate Software - SIM Module Configuration
RSLogix 5000 Emulate Software - SIM Module Configuration
Question
How does the manual recommend setting the 1789-SIM module?
How to configure the Emulate 5000 I/O in the RSLogix 5000/Studio 5000 software?
How do I configure 1789-SIM module in RSLogix 5000/Studio 5000 software?
Environment
RSLogix Emulate 5000
RSLogix 5000
Studio 5000 Logix Designer
Answer
You will need to add SIM module to RSLogix Emulate 5000 Chassis Monitor and configure generic 1756-Module
in I/O configuration of RSLogix 5000/Studio 5000 software.
Note: Starting with version 13 of RSLogix 5000 software the 1789 Sim module is no longer available. Use 1756-
Module instead.
1. Right click on any empty slot in the RSLogix Emulate 5000 Chassis Monitor and select Create
2. Select 1789-SIM 32 Point Input/Output Simulator. Accept defaults
3. 1789-SIM module should appear in the RSLogix Emulate 5000 Chassis Monitor
4. Open RSLogix 5000/Studio 5000 project file (create new if necessary), Right click on I/O Configuration,
and select New Module
5. Select 1756-MODULE
6. Select the Slot number where the module was inserted into the chassis and configure it
Input: Assembly Instance: 1, Size: 2
Output: Assembly Instance: 2, Size: 1
Configuration: Assembly Instance 16, Size 0
Comm Format Data - DINT
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/732965/page/1 1/3
9/2/2019 732965 - RSLogix 5000 Emulate software - SIM module configuration
Note: The input data will appear in the second DINT tag, for example: Local:1:I.Data[1].0 (module in slot 1, first bit
of data).
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/732965/page/1 2/3
9/2/2019 732965 - RSLogix 5000 Emulate software - SIM module configuration
Attachments
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular subject or
subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this web site is not
intended to constitute application, design, software or other professional engineering advice or services. Before
making any decision or taking any action, which might affect your equipment, you should consult a qualified
professional advisor.