1 Zaragoza Sample Lectrical Computation (SAMPLE)
1 Zaragoza Sample Lectrical Computation (SAMPLE)
LOCATION : Block 4 Lot 7b Agoho st., Town and Country North, Abangan Norte,
Marilao, Bulacan
OWNER : Mr. & Mrs. Armando Mendoza
DESIGN ANALYSIS
SHORT CIRCUIT CURRENT, VOLTAGE DROP
AND LOAD CALCULATION
SHORT CIRCUIT CURRET CALCULATIONS
(Line to Line Fault at load side of 150AT Breaker of 240 volts)
Given: 50KVA, 240 Volts secondary, 1.5% Z (worst condition)
MERALCO max supply transformer 50 KVA for residential load
Main Feeder: 2-150mm. sq. THW, 1-38mm sq. THW grounding
5. Is.c. Line to line = short circuit fault at load side of 150AT breaker of 240 volts
= 6,337.098 amperes + ISC Motor Distribution
=6,753.2 amperes
Main Feeder:
Use: 2#38mm. sq. THW, 1#22mm.sq. THW Grounding 150AT, 2p, 240Volts, 22
KAIC
Line to Line Fault at load side of 150AT Main Breaker
38mm sq. Cable Constant =7,293
F= 2 x length x I S.C. SYS.RMS/cable Constant x 240 volts
F=2 x 20 feet x 6,337.098 amps/7293 x 240 volts
=0.144
M=1/1+F=1/1.144=0.89
I sc. Motor RMS=6,337.98 x 0.89=5,639 amperes
I sc Motor Distribution=418 amperes
Line to Line Fault at the Load Side of 20 AT breaker for Outlet per Circuit
Line to Line Fault at the Load Side of 30 AT breaker for Outlet per Circuit
Load Calculation
M= 1 = 0.6896
1+0.45