1 Zaragoza Sample Lectrical Computation (SAMPLE)

This document provides an analysis of the proposed electrical design for a two-storey residence located in Bulacan, Philippines. It includes calculations of short circuit current, voltage drop, and load for the system. Short circuit current calculations are provided for the main feeder and branch circuits. Load calculation determines the full load current to be 120.7 amps. Voltage drop and short circuit current are within acceptable limits by code standards.

Uploaded by

Emarlito Buna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
530 views7 pages

1 Zaragoza Sample Lectrical Computation (SAMPLE)

This document provides an analysis of the proposed electrical design for a two-storey residence located in Bulacan, Philippines. It includes calculations of short circuit current, voltage drop, and load for the system. Short circuit current calculations are provided for the main feeder and branch circuits. Load calculation determines the full load current to be 120.7 amps. Voltage drop and short circuit current are within acceptable limits by code standards.

Uploaded by

Emarlito Buna
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 7

PROJECT : Proposed Two Storey Residence

LOCATION : Block 4 Lot 7b Agoho st., Town and Country North, Abangan Norte,
Marilao, Bulacan
OWNER : Mr. & Mrs. Armando Mendoza

DESIGN ANALYSIS
SHORT CIRCUIT CURRENT, VOLTAGE DROP
AND LOAD CALCULATION
SHORT CIRCUIT CURRET CALCULATIONS
(Line to Line Fault at load side of 150AT Breaker of 240 volts)
Given: 50KVA, 240 Volts secondary, 1.5% Z (worst condition)
MERALCO max supply transformer 50 KVA for residential load
Main Feeder: 2-150mm. sq. THW, 1-38mm sq. THW grounding

1. Short Circuit at the terminal of 50 KVA Transformer


I f.I. = 50x1000/240 volts=208 amperes
Multiplier=100/1.5=666.667
I S.C. = 208 x 66.667=13,866.736

2. I S.C. MPTOR CONTRIBUTION =4 X ASSUME 50% 0F 208 AMPS=418 AMPS


3. Cable short circuit current RMS Symmetrical
F = 2 x L x L S.C.SYS.RMS / C x n V LL
F= Factor (impedance of cable where the fault is calculated)
L= length of conductor relative to the immediate upstream fault
point
C= conductor factor and the values given in the table of IEEE
Std. 241-1990 (Gray Book)
N=Number of parallel conductor
VLL=line to line voltage
F=2x25 feet x 13,866.73/12,844x 240 volts = 0.225
4. Multiplier factor (Multiplier to be used against the value of fault current in the immediate
fault point.
Multiplier=1/1/+F=1/1/0.225 = 2.39
I S.C. SYS RMS =13,866.73 x .457 = 3,120.01 amperes

5. Is.c. Line to line = short circuit fault at load side of 150AT breaker of 240 volts
= 6,337.098 amperes + ISC Motor Distribution
=6,753.2 amperes

Main Feeder:
Use: 2#38mm. sq. THW, 1#22mm.sq. THW Grounding 150AT, 2p, 240Volts, 22
KAIC
Line to Line Fault at load side of 150AT Main Breaker
38mm sq. Cable Constant =7,293
F= 2 x length x I S.C. SYS.RMS/cable Constant x 240 volts
F=2 x 20 feet x 6,337.098 amps/7293 x 240 volts
=0.144
M=1/1+F=1/1.144=0.89
I sc. Motor RMS=6,337.98 x 0.89=5,639 amperes
I sc Motor Distribution=418 amperes

Fault at Load Side of 150AT Breaker = 6059 amperes

Use: 2-#38mm sq. THW, 1#22mm sq. THW grounding


150 AT, 2P 240 Volts, 10KVAIC

Line to Line Fault at the Load Side of 20 AT breaker for Outlet per Circuit

#2.0mm sq. Cable Constant =389


F= 2 x length x I S.C. SYS.RMS/cable Constant x 240 volts
F=2 x 20 feet x 3,776.8 amps/389 x 240 volts
=1.618
M=1/1+F=1/1+1.618=0.381
I sc. Motor RMS=3,776 x .381=1,438 amperes
I sc Motor Distribution=418 amperes

Fault at Load Side of 20AT Breaker = 1856 amperes

Use: 2-#2.0mm sq. THW, 1#2.0mm sq. THW grounding


20 AT, 2P 240 Volts, 5KVAIC

Line to Line Fault at the Load Side of 30 AT breaker for Outlet per Circuit

#3.5 mm sq. Cable Constant =617


F= 2 x length x I S.C. SYS.RMS/cable Constant x 240 volts
F=2 x 20 feet x 3,776.8 amps/617 x 240 volts
=1.020
M=1/1+F=1/1+1.020=0.495

I sc. Motor RMS=3,776 x .495=1,869 amperes


I sc Motor Distribution=418 amperes

Fault at Load Side of 20AT Breaker = 2287 amperes

Use: 2-#3.5mm sq. THW, 1#2.0mm sq. THW grounding


30 AT, 2P 240 Volts, 10KVAIC
USE: 22 KAIC FOR MAIN LP
10 KAIC FOR BRANCHES:

Voltage drop between 50 KVA Transformer and ^AT main Breaker

Assumption: 25 feet distance between transformer and breaker


2# 150mm. sq. THW, 22mm. sq. THW grounding

Philippine Electrical Code:


Voltage Drop = (2 x L x R x I)/1000
L=25 feet
R=0.45 ohms/1000 ft in steel conduit
I=23 amperes
Voltage Drop= 2 x 25 x .45 x 23 / 1000 = 0.518 volts

% Voltage Drop= (0.518/240) 100%=0.22%

BASED ON on IEEE Std 241-1990

Voltage Drop = (((L x Ix volt loss x (1/#/phase)/1,000,000) x 1/240 volts) 100%


L x I x Volt loss=25 x 23 x 860 = 494,500
1/#/phase=1/1
=(((494,500 a 1/1)/1,000,000) x 240) x 100%

% Voltage Drop= 0.21% based on IEEE Std.

Load Calculation

(Computed based on NEC 220)

General and small appliances


General Lightings & Small Appliances Load:
Lighting Load for 130 sq.m @ 24w/sq m = 3,120 W
Small appliance load 3ckt @ 1,500W/ckt = 4,500 W
TOTAL = 7,620 W

APPLICATION OF DEMAND FACTOR


First 3,000 W @ 100% D.F =3,000 W
Next 4,620 W @ 35 % D.F = 1,617 W
1-.75H ACU @ 125% D.F. (8.00 ×1.25) x 230V = 2,300 W
4-1H ACU @ 100% D.F. (8.00 × 4.00) x 230V = 9,200 W
1-800 W Ref = 800 W
1- Range/Range hood = 3,000 W
1- Washing Machine = 1,150 W
1- Dryer = 1,800 W
1- Water Pump = 1,900 W
1- WAter Heater = 3,000 W

TOTAL DEMAND LOAD = 27,767 W

Full load Current = 27,767 W


230V
Full Load Current = 120.70 Amps

Assuming 80% Demand Factor


Use 2#38mm sq. THW, 1#22mm. sq. THW Grounding
150AT 2P, 240 volts 22KAIC

*VOLT LOSS COMPUTATION


Distance from Service Entrance
To LP 10M x 3.28 ft per meter = 32.8 FT
Demand Load = 120.70 A
Size of wire: 50mm2 Copper conductor in
non-metallic conduit for single phase, 60hz
@80 Demand Factor = 538

Volt Loss = 32.8 FT x120.70 A x538 = 2.13 Volts


1,000,000.00

SHORT CIRCUIT CURRENT CALCULATION:

Assume 20 KVa, 240v, Single Phase


Transformer % = 1.4
Distance from service Entrance ENT to LP = 32.8 ft
(10M x 3.28 ft per meter)
Wire Size: 50mm2 copper in PVC =3826
Demand Factor = 120.70 A

I of Transformer = 20x1000 = 83.33A


240V

Multifier = 100 = 71.43 A


1.4
Isc ( Transformer) 83.33 x 71.43 = 6.309 Amperes

F= 2x32.8 x 6.309 = 0.45


3826

M= 1 = 0.6896
1+0.45

Isc = 6309x0.6896 = 4350 Amps


Isc Motors = 120.70 = 120.70 Amps

TOTAL Isc = = 8,964.00 Amps