Manual Yokogawa Awx

This document provides guidance on setting up PID control loops for Rockwell Automation's PowerFlex 523 and 525 AC drives. It explains that these drives have PID functionality for proportional, integral, and derivative control. It outlines the key parameter settings needed to enable the PID loop, select the PID reference and feedback, set the desired setpoint, and configure the drive for exclusive PID control. It recommends referring to the user manual for more details on setting up and tuning PID loops on these drives.

Uploaded by

alexiel1806
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
259 views2 pages

Manual Yokogawa Awx

This document provides guidance on setting up PID control loops for Rockwell Automation's PowerFlex 523 and 525 AC drives. It explains that these drives have PID functionality for proportional, integral, and derivative control. It outlines the key parameter settings needed to enable the PID loop, select the PID reference and feedback, set the desired setpoint, and configure the drive for exclusive PID control. It recommends referring to the user manual for more details on setting up and tuning PID loops on these drives.

Uploaded by

alexiel1806
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TECH TOPICS Q&As: PID Setup for

PowerFlex 523 and 525

This Tech Topic provides guidance for PID


setup for Rockwell Automation’s PowerFlex
523 Series and 525.

POWERFLEX 520 SERIES:


PID SETUP AND FUNCTIONALITY

Questions:

• Do PowerFlex 520 Series AC drives


have PID functionality?
• How do I set up PID loop with a PowerFlex
520 series drive?

Answer:

Both the PowerFlex 525 (2 PID inputs) and the


PowerFlex 523 (1 PID input) AC Drives have
the PID functionality (proportional, integral,
derivative) control loops. The PID loop is used
to maintain a process feedback (such as
pressure, flow or tension) at a desired set point. Setup
The PID loop works by subtracting the PID
feedback from a reference and generating an To enable the PID loop, Parameters P047, P049,
error value. The PID loop reacts to the error, or P051 [Speed Referencex] must be set to 11
based on the PID Gains, and outputs a “PID1 Output” or 12 “PID2 Output,” and the
frequency to try to reduce the error value to 0. corresponding speed reference activated.

hesconet.com 1
• Set Parameter A459 [PID 1 Ref Sel] and In Exclusive Control, the Speed Reference
A471 [PID 2 Ref Sel] to PID reference. becomes 0, and the PID Output becomes the
entire Freq Command. Exclusive Control is used
• Set Parameter A460 [PID 1 Fdback Sel] and when Parameter A458 [PID 1 Trim Sel] or
A472 [PID 2 Fdback Sel] to PID feedback. Parameter A470 [PID 2 Trim Sel] is set to option
0. This configuration does not require a master
• Set Parameter A464 [PID 1 Setpoint] and reference, only a desired set point, such as a
A476 [PID 2 Setpoint] to the proper setpoint flow rate for a pump.
if PID x Ref Sel is set to 0.
Parameter Settings
• Set Parameter A467 [PID 1 Invert Err] and
A479 [PID 2 Invert Err] to a 1 if your analog • Set Parameter P047 [Speed Reference1],
input has an inverted relationship with Parameter P049 [Speed Reference2], or
your reference. Parameter P051 [Speed Reference 3] to
Option 11 “PID1 Output” or 12 “PID2 Output.”
Note: If your start source is set to 3-wire control,
the PID only runs the motor in one direction no • Set Parameter A459 [PID 1 Ref Sel] or
matter what. If you have a digital input Parameter A471 [PID 2 Ref Sel] to option 0
programmed for 3-wire direction, the drive will run “PID Setpoint.”
in both directions even if in 3-wire control. If your
start source is set to 2-wire control or keypad, it • Set Parameter A460 [PID 1 Fdback Sel] or
will change motor direction based of the setpoint Parameter A472 [PID 2 Fdback Sel] to the
and feedback (the drive will run in the reverse analog input where the transducer is
direction if the feedback is higher than the set- connected (4-20 mA or 0-10 V).
point). If the drive never should run in the reverse
direction, set Parameter A544 [Reverse Disable] to • Set Parameter A464 [PID 1 Setpoint] or
a value of 1 for Reverse Disable. Parameter A476 [PID 2 Setpoint] to the desired
setpoint level that the drive will try to maintain.
Reference:
Make sure Parameter A458 [PID 1 Trim Sel] or
Refer to TechNote 627551 - PowerFlex 525 send Parameter A470 [PID 2 Trim Sel] is set to option 0.
PID setpoint and feedback through Ethernet/IP.
Reference:
POWERFLEX 525 PID SETUP For additional information on setting up and
tuning a PID loop on a PowerFlex 520 drive,
Question: refer to appendix F of the PowerFlex 520-Series
How do you set up a PowerFlex 525 for PID Adjustable Frequency AC Drive User Manual.
control on a fan or pump application?
Learn More:
Answer:
Application such as fans and pumps are best For more information, contact HESCO at
suited for a “Exclusive Control” PID set up. [email protected], (860) 236-6363.

hesconet.com 2