DSE5510 AUTO START CONTROL MODULE (ELECTRONIC engine ENABLED) SPECIFICATION DC SUPPLY 8V to 35V continuous CRANKING DROPOUTS Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V.

Uploaded by

Mas_Dani_9771
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views4 pages

Sharing With Simplicity.: Power

DSE5510 AUTO START CONTROL MODULE (ELECTRONIC engine ENABLED) SPECIFICATION DC SUPPLY 8V to 35V continuous CRANKING DROPOUTS Able to survive 0V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V.

Uploaded by

Mas_Dani_9771
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DSEPOWER

® ®

SHARING
WITH
SIMPLICITY.
DSE5510 SPECIFICATION
AUTO START CONTROL MODULE (ELECTRONIC ENGINE ENABLED)

DC SUPPLY
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries

MAXIMUM OPERATING CURRENT


460mA at 12V. 245mA at 24V
ELECTRONIC ENGINE CAPABILITY
MAXIMUM STANDBY CURRENT
375mA at 12V. 200mA at 24V

ALTERNATOR INPUT RANGE


15V(L-N) to 333V AC (L-N) absolute maximum

ALTERNATOR INPUT FREQUENCY


50Hz - 60Hz at rated engine speed (Minimum:
15V AC L-N)

MAGNETIC PICK-UP VOLTAGE RANGE


+/- 0.5V to 70V Peak

MAGNETIC INPUT FREQUENCY


10,000 Hz (max)

START RELAY OUTPUT


16A DC at supply voltage
The DSE5510 is an Automatic reverse power, generator phase LOAD SHARE FEATURES
Engine Control Module, designed rotation error, earth fault protection, • ROCOF & vector shift FUEL RELAY OUTPUT
to provide advanced load share loss of speed signal, fail to open, • Automatic starting & stopping of 16A DC at supply voltage
functionality for diesel and gas fail to close, out of sync, MPU generator on load demand
AUXILIARY RELAY OUTPUTS
generating sets that include non- open circuit failure, negative phase • Automatic hours run balancing of
Three outputs 5A DC at supply voltage
electronic and electronic engines. sequence and loss of excitation. generator sets Two outputs volt free 8A at 250V AC
The module also provides • Dead bus sensing
• Module has the ability to interface DIMENSIONS
excellent engine monitoring and FEATURES 240mm x 172mm x 57mm
with existing load share lines
protection features. • Electronic engine capability 9.4” x 6.8” x 2.2”
• Direct communication from the
• RS232 and RS485 remote
module to the governor and AVR PANEL CUTOUT
The modules load share functions communications
• Link up to 16 generators 220mm x 160mm
include, automatic synchronising • Modbus RTU 8.7” x 6.3”
• Volts & frequency matching
with built in synchroscope and • Pin number protected front panel
• KW and Kvar load sharing with CHARGE FAIL/EXCITATION RANGE
closing onto dead bus. Direct and programming
multiple generators 0V to 35V
flexible outputs from the module • Engine exercise timer
• Back-lit LCD 4-line text display BUILT IN GOVERNOR CONTROL
are provided to allow connection BENEFITS
• Multiple display languages Fully Isolated
to the most commonly used speed • Sends SMS messages to Minimum Load Impedence:
• Voltage measurement
governors and automatic voltage engineers to notify specific 1000Ω
• Configurable inputs (9)
regulators (AVR’s). engine problems (GSM Modem Gain Volts 0V - 10V DC
• Configurable outputs (5) Offset Volts + / - 10V DC
and SIM card required)
• Automatic start
The module has been designed to • On-site and remote module BUILT IN AVR CONTROL
• Manual start
combine a maximum of 16 configuration Fully Isolated
• Audible alarm
• In-built engine diagnostics Minimum Load Impedence:
generators and 16 mains (utility) • LED indicators 1000Ω
removes the requirement for
supplies up to a maximum of 20 in • Built-in governor and AVR control Gain Volts 0V - 10V DC
service equipment Offset Volts + / - 10V DC
one system, e.g. 16 generators and • Engine history event log
• Full engine protection &
4 mains (utility) supplies (DSE5560 • Engine protection
instrumentation without the need ENCLOSURE PROTECTION
required to synchronise with the • Fault condition notification to a (front of module)
for additional senders (Electronic
mains). designated PC IP55 (with optional gasket)
engines only) IP42 (without gasket)
• Front panel mounting
• Remote monitoring of the module
The module has the ability to • PC configuration
using comprehensive DSE PC
• Mains (utility) failure detection
monitor under/over generator software
• Configurable alarm timers
volts, over current, under/over • License free PC software
• Configurable start & stop timers
generator frequency, under speed, • Automatic load transfer
over speed, charge fail, emergency • SMS alert messaging
stop, low oil pressure, high engine • Multi set communications
temperature, fail to start, low/high • Front panel mounting
DC battery volts, fail to stop, • Remote monitoring
generator short circuit protection, • Magnetic pick-up
OPERATION TELEMETRY
ENVIRONMENTAL TESTING The module is operated using the front STOP/RESET, MANUAL, AUTO and The module gives the user full
STANDARDS START push buttons. Three of these push buttons include an LED indicator. telemetry facilities when using the
Additional push buttons provide LCD display scroll, lamp test, mute optional communications software.
ELECTRO MAGNETIC COMPATIBILITY (EMC) functionality and breaker control. The module can be connected to a
BS EN 50081-2 EMC Emission PC using the DSE810 PC interface
Standard for the Industrial Environment TIMERS & INPUT FUNCTIONS or by using a suitable modem.
ELECTRICAL SAFETY The module has been designed to include the following timers and input functions:
BS EN 60950 Low Voltage Directive/Safety of The PC software is Microsoft
Information Technology Equipment, including • Start delay timer Windows based. All access into
Electrical Business Equipment • Stop delay timer the module can be configured to
TEMPERATURE • Crank timer become password protected to
COLD • Crank rest timer prevent unauthorised entry. The PC
o
BS EN 60068-2-1 to -30 C • Engage attempt & manual crank limit timers software allows the module to be
HOT • Safety on delay timer
o controlled from a remote location.
BS EN 60068-2-2 to 70 C
• Warm up timer
BS EN 50082-2 EMC IMMUNITY • Cooling timer COMMUNICATIONS
Standard for the Industrial Environment • Energise to stop hold timer The DSE5510 has a number of
• Pre-heat timer different communication capabilities.
VIBRATION
BS EN 60068-2-6 Ten sweeps (up and back • Pre-heat bypass timer
down) at 1 octave/minute in each of the three • Smoke limiting control timer SMS Messaging
major axes • Fail to stop timer When the module detects an alarm
5Hz to 8Hz @ +/-7.5mm constant displacement • Over speed over shoot timer condition, it has the ability to send
8Hz to 500Hz @2gn constant acceleration
• Breaker pulse control timers an SMS message to a dedicated
HUMIDITY • DC battery alarm delay timers mobile number, notifying an engineer
o
BS EN 2011 part 2.1 93% RH @ 40 C for 48 • Sync/fail to sync timer of the problem. (GSM Modem and
hours
SIM Card required).
SHOCK BUILT-IN FUNCTIONS
BS EN 60068-2-27 Three half sine shocks in • Alternator under/over volts Remote Communications
each of the three major axes 15gn amplitude • Alternator under/over frequency When the module detects an
11mS duration • Warning or shutdown on engine temperature, over/under speed, oil alarm condition, it dials out to a PC
pressure notifying the user of the exact alarm
• Warning, shutdown or electrical trip on battery volts or over current condition.
• Shutdown or electrical trip on reverse power, phase rotation or short
TYPICAL LOAD SHARE
circuit fault Building Management
APPLICATION
• Earth fault shutdown The module has been designed to
• Adjustable crank cycle/attempts be integrated into new and existing
• Full remote control and telemetry building management systems.
• 9 configurable digital inputs
G1
• 5 configurable and 2 fixed relay outputs PC Software
• System lock input The module has the ability to be
• Load switching control push-button inputs configured and monitored from a
• ROCOF/vector shift (mains/utility decoupling) remote PC, using the DSE810
G2 • Negative phase sequence interface.
• Loss of excitation
EVENT LOG
INSTRUMENTATION AND ALARMS The module includes a
G3 LOAD The DSE5510 module provides advanced metering and alarm functionality comprehensive event log that
via the LCD display. The information can be accessed using the display scroll shows the 25 most recent alarm
push buttons. The table below shows the instrumentation and alarm features conditions and the date and time
the module provides. that they occurred.
This function assists the user when
Generator Volts L1-N, L2-N, L3-N fault finding and maintaining the
Generator Volts L1-L2, L2-L3, L3-L1 generating set.
Generator Amps L1, L2, L3
Generator Frequency Hz EXPANSION MODULES
Generator kVA L1, L2, L3, Total DSE123 Load Share Lines Interface
Generator kW L1, L2, L3, Total Module
Generator pf L1, L2, L3, Average DSE157 Relay Input Expansion
Generator kVAr L1, L2, L3, Total Module
Generator KWh DSE545 & DSE548 Remote
Generator KVAh Annunciation Expansion Module
Generator KVArh DSE130 Input Expansion Module
Generator Phase Sequence
Synchroscope Display ELECTRONIC ENGINE
Engine Speed RPM COMPATIBILITY
Engine Oil Pressure • Cummins
Engine Temperature • Deutz
Plant Battery Volts • John Deere
Engine Hours Run • MTU
Number of Start Attempts • Perkins
Maintenance Display • Scania
Engine ECU diagnostics information via industry standard CAN interface • Volvo
Enhanced metering via CAN when connected to an electronic engine • Generic
• Plus additional manufacturers
®

DSE5510

AUTOMATIC MCCB
AUTOMATIC ACB
or CONTACTOR
CTs MUST BE 5 AMP 3 or 4 POLE
SECONDARY

P1 P2
L1 L1
S1 S2

L2 L2

FROM
GENERATOR L3 L3 TO LOAD

N N

2 AMP 2 AMP
FUSES

SCREEN EARTHED AT
SCREEN EARTHED AT

FUSES

SCREEN TO ENGINE
SCREEN TO ENGINE
TO MAG PICK UP IF

DO NOT CONNECT
DO NOT CONNECT
TO GEN SWITCHING

TO ENGINE ECU

THIS END ONLY


DEVICE CIRCUITRY

THIS END ONLY


USED

49 50 51 53 52 45 46 47 48 39 40 20 21 22 37 38 54 55 56 29 30 31 23 24 25 41 42 43 44

CT1 CT2 CT3 CT4 COM L1 L2 L3 N SCR SCR B A SCR B L L1 L2 L3 N


UNUSED

L151 L251 L351 N52 MPU RS485 J1939


BUS VOLTS
GEN VOLTS CLOSE OUTPUT
GEN CURRENT GEN 5
OUTPUT
4
P810 TO OTHER 5510 AND 5560
SCR 26 MSC CONNECTIONS
MAX 250 METERS
RS232

MODULE 5510 MSC H 27


120 OHM SCREEN CABLE
COMMON GROUND

L 28
CRANK
FUEL

OIL PRESSURE

WATER TEMP

CHARGE ALT

157

UNUSED
BATTERY 3 OUTPUTS THE FIRST AND LAST UNITS
PLANT +VE
GOVERNOR AVR
MSC MUST BE FITTED WITH A
FUEL

9 INPUTS
O/P O/P
+VE

-VE

B A B A 120 OHM RESISTOR ACROSS


2 1 3 4 5 57 58 59 60 9 10 11 12 13 14 15 16 17 18 6 7 8 19 32 33 34 35 36 H(27) AND L(28)
TO CRANK SOLENOID MAX 16AMP
TO FUEL SOLENOID MAX 16AMP

CHARGE ALTERNATOR
FOR REMOTE EM STOP
REMOVE LINK FOR

USER CONFIGURATION INPUT 1

USER CONFIGURATION INPUT 2

USER CONFIGURATION INPUT 3

USER CONFIGURATION INPUT 4

USER CONFIGURATION INPUT 5

USER CONFIGURATION INPUT 6

USER CONFIGURATION INPUT 7

USER CONFIGURATION INPUT 8

USER CONFIGURATION INPUT 9

USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT


FUEL TEMP
HIGH COOLANT TEMP
LOW OIL PRESSURE

TO TO
GOVERNOR AVR
CONECT SCREEN AT

CONECT SCREEN AT
GENERATOR ONLY

GENERATOR ONLY

SCREEN EARTHED
TO ENGINE EARTH

AT THIS END ONLY


ANTI-SURGE FUSE

UPTO32 AMPS
MAX 20 AMP
MIN 2 AMPS

FUSE

BATTERY +VE
(12 OR 24 VDC ) BATTERY -VE

ALL BATTERY NEGATIVES MUST BE CONNECTED TOGETHER

RELATED MATERIALS
TITLE PART NO’S
DSE5560 Data Sheet 055-041
DSE5510 Manual 057-015
DSE5560 Manual 057-017
DSE123 Data Sheet 055-044
Load Share Design & Commissioning 057-047
Guide to Synchronising and 057-045/6
Load Sharing
55xx Software manual 057-007
CAN & DSE wiring guide 057-004
DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL ®
Highfield House +44 (0)1723 890099 [email protected]
Hunmanby Industrial Estate
Hunmanby, North Yorkshire FACSIMILE WEBSITE
YO14 0PH England +44 (0)1723 893303 www.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL


THAILAND +66 (0) 2678 3028 [email protected]
TPI Tower, Lobby 3
Floor 27, 26-56 Chan New Road FACSIMILE WEBSITE
Tungmahamek, Sathom +66 (0) 2670 6228 www.deepseaplc.com
Bangkok 10120, Thailand

DEEP SEA ELECTRONICS INC TELEPHONE EMAIL


USA +1 (815) 316 8706 [email protected]
3230 Williams Avenue
Rockford FACSIMILE WEBSITE
IL 61101-2668 USA +1 (815) 316 8708 www.deepseausa.com

YOUR LOCAL DISTRIBUTOR.

DEEP SEA ELECTRONICS PLC maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-039/05/07 (1)