Route

This ladder logic diagram controls lubrication pumps for turbomachinery. It contains 14 rungs of logic to monitor pump operation, trigger backup pumps if needed, and display status values to the HMI. Key logic includes checking lube oil pressure, timing pump runs, and activating backup systems if primary pumps fail or pressure decays too much.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views4 pages

Route

This ladder logic diagram controls lubrication pumps for turbomachinery. It contains 14 rungs of logic to monitor pump operation, trigger backup pumps if needed, and display status values to the HMI. Key logic includes checking lube oil pressure, timing pump runs, and activating backup systems if primary pumps fail or pressure decays too much.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

_400_Pmp_Ctrl_Eng_Main_FS_212 - Ladder Diagram Page 1

PD3H422_MG10N85:Turbomachinery_Task:Lube_B008_261 6/16/2019 2:08:58 PM


Total number of rungs in routine: 14 C:\Documents and Settings\Administrator\Desktop\DCS BACKUP\Allen Bradley\Module 70 - GTG\GTG-A\PLC\PD3H422_MG10N85.ACD

0 NOP

M6020 M6020
<UF0080:0:O.Data.4> <UF0080:0:O.Data.4> TON
1 / Timer On Delay EN
Timer Lube_Module_Fail_TON
M6020_FB M6020_FB
Preset 1000 DN
<UF0090:I.Data[0].12> <UF0090:I.Data[0].12>
Accum 0
/

FL_Lube_Module_Fail
Lube_Module_Fail_TON.DN <HMI_FSLO[3].4> PGM_Lube.Activate_Backup_System
L

Pre_Post_Pump_Run Pump_Lag_Delay_Pre_Post_TOF.DN LES


2 / Less Than (A<B)
Source A Lube_Oil_Header_Press.Val
0.048076924
Source B KF_Lube_Oil_Pre_Post_Pump_Check_Limit.Val
8.0

PS6010
Lube_Mode.Engine_Turning_Post_Lube <UF0080:I.Data[1].0> TON
/ Timer On Delay
Timer Pre_Post_Pump_Fa
PGM_Sequence.Test_Crank Preset
Accum

RSLogix 5000
_400_Pmp_Ctrl_Eng_Main_FS_212 - Ladder Diagram Page 2
PD3H422_MG10N85:Turbomachinery_Task:Lube_B008_261 6/16/2019 2:09:01 PM
Total number of rungs in routine: 14 C:\Documents and Settings\Administrator\Desktop\DCS BACKUP\Allen Bradley\Module 70 - GTG\GTG-A\PLC\PD3H422_MG10N85.ACD

FN_M6010_Fail
<HMI_FSNL[1].19> PGM_Lube.AuxPumpLoss
L

Pre_Post_Pump_Fail_TON.DN
EN
Pre_Post_Pump_Fail_TON
1000 DN
0

FN_M6020_Fail
Backup_Pump_Run Pump_Lag_Delay_Backup_TOF.DN LES <HMI_FSNL[1].20>
3 / Less Than (A<B) L
Source A Lube_Oil_Header_Press.Val
0.048076924
Source B KF_Backup_Pump_Min_Check.Val
8.0

Lube_Oil_Required LES Pre_Post_Pump_Required


4 Less Than (A<B)
Source A Lube_Oil_Header_Press.Val
0.048076924
Source B KF_Pre_Post_Pump_On_Limit.Val
25.0

Pre_Post_Pump_Required PGM_Start.Starter_Dropout_Speed
/

Pre_Post_Pump_Required PGM_Sequence.Start_Run
/
FL_PT6060_Fail
<HMI_FSLO[3].7>

RSLogix 5000
_400_Pmp_Ctrl_Eng_Main_FS_212 - Ladder Diagram Page 3
PD3H422_MG10N85:Turbomachinery_Task:Lube_B008_261 6/16/2019 2:09:01 PM
Total number of rungs in routine: 14 C:\Documents and Settings\Administrator\Desktop\DCS BACKUP\Allen Bradley\Module 70 - GTG\GTG-A\PLC\PD3H422_MG10N85.ACD

FN_M6010_Fail
Lube_Mode.Pump_Check Backup_Pump_Press_Decay_Passed_PP_On <HMI_FSNL[1].19> Pre_Post_Pump_Run
5 /
FN_M6020_Fail
Pre_Post_Pump_Required
<HMI_FSNL[1].20>

ST_Pre_Post_Lube_Pump_Command
<HMI_STATUS[4].20>

PS6010 ST_Pre_Post_Lube_Pump_Press
<UF0080:I.Data[1].0> <HMI_STATUS[4].21>
6

Lube_Mode.Pump_Check Lube_Press_Decay_Passed_BU_On Backup_Pump_Check_Passed_BU_Off


7 /

Lube_Mode.Engine_Turning_Post_Lube Backup_Pump_On_Due_To_Lo_Press_AL

Backup_Pump_Test

Restart_BU_Pump_Check

Pre_Post_Pump_Required Post_Lube_BU_Cycle_Off_TON.TT Pump_Lag_Delay_Backup_TOF.DN Backup_Pump_Run


/
FN_M6010_Fail
<HMI_FSNL[1].19>

PS6010 AL_PT6060_L
<UF0080:I.Data[1].0> Pre_Post_Pump_Run <HMI_ALARM[7].9>
/

ST_Backup_Lube_Pump_Command
Backup_Pump_Run <HMI_STATUS[4].8> PGM_Lube.Backup_Lube_Oil_Pump_On

RSLogix 5000
_400_Pmp_Ctrl_Eng_Main_FS_212 - Ladder Diagram Page 4
PD3H422_MG10N85:Turbomachinery_Task:Lube_B008_261 6/16/2019 2:09:01 PM
Total number of rungs in routine: 14 C:\Documents and Settings\Administrator\Desktop\DCS BACKUP\Allen Bradley\Module 70 - GTG\GTG-A\PLC\PD3H422_MG10N85.ACD

PS6020 ST_Backup_Lube_Pump_Press
<UF0080:I.Data[1].2> <HMI_STATUS[4].9>
8

MUL MUL
9 Multiply Multiply
Source A KF_Pump_Lag_Delay_Pre_Post.Val Source A KF_Pump_Lag_Delay_Backup.Val
60.0 30.0
Source B 1000 Source B 1000

Dest Pump_Lag_Delay_Pre_Post_TOF.PRE Dest Pump_Lag_Delay_Backup_TOF.PRE


60000 30000

Pre_Post_Pump_Run Pre_Post_Pump_On_ONS TOF


10 ONS Timer Off Delay EN
Timer Pump_Lag_Delay_Pre_Post_TOF
Pre_Post_Pump_Run Pre_Post_Pump_Off_ONS Preset 60000 DN
/ ONS Accum 60009

Backup_Pump_Run Backup_Pump_On_ONS TOF


11 ONS Timer Off Delay EN
Timer Pump_Lag_Delay_Backup_TOF
Backup_Pump_Run Backup_Pump_Off_ONS Preset 30000 DN
/ ONS Accum 30015

M6020
Backup_Pump_Run <UF0080:0:O.Data.4>
12 /

M6010
Pre_Post_Pump_Run <UF0090:O.Data[1].6>
13 /

(End)