Route
Route
0 NOP
M6020 M6020
<UF0080:0:O.Data.4> <UF0080:0:O.Data.4> TON
1 / Timer On Delay EN
Timer Lube_Module_Fail_TON
M6020_FB M6020_FB
Preset 1000 DN
<UF0090:I.Data[0].12> <UF0090:I.Data[0].12>
Accum 0
/
FL_Lube_Module_Fail
Lube_Module_Fail_TON.DN <HMI_FSLO[3].4> PGM_Lube.Activate_Backup_System
L
PS6010
Lube_Mode.Engine_Turning_Post_Lube <UF0080:I.Data[1].0> TON
/ Timer On Delay
Timer Pre_Post_Pump_Fa
PGM_Sequence.Test_Crank Preset
Accum
RSLogix 5000
_400_Pmp_Ctrl_Eng_Main_FS_212 - Ladder Diagram Page 2
PD3H422_MG10N85:Turbomachinery_Task:Lube_B008_261 6/16/2019 2:09:01 PM
Total number of rungs in routine: 14 C:\Documents and Settings\Administrator\Desktop\DCS BACKUP\Allen Bradley\Module 70 - GTG\GTG-A\PLC\PD3H422_MG10N85.ACD
FN_M6010_Fail
<HMI_FSNL[1].19> PGM_Lube.AuxPumpLoss
L
Pre_Post_Pump_Fail_TON.DN
EN
Pre_Post_Pump_Fail_TON
1000 DN
0
FN_M6020_Fail
Backup_Pump_Run Pump_Lag_Delay_Backup_TOF.DN LES <HMI_FSNL[1].20>
3 / Less Than (A<B) L
Source A Lube_Oil_Header_Press.Val
0.048076924
Source B KF_Backup_Pump_Min_Check.Val
8.0
Pre_Post_Pump_Required PGM_Start.Starter_Dropout_Speed
/
Pre_Post_Pump_Required PGM_Sequence.Start_Run
/
FL_PT6060_Fail
<HMI_FSLO[3].7>
RSLogix 5000
_400_Pmp_Ctrl_Eng_Main_FS_212 - Ladder Diagram Page 3
PD3H422_MG10N85:Turbomachinery_Task:Lube_B008_261 6/16/2019 2:09:01 PM
Total number of rungs in routine: 14 C:\Documents and Settings\Administrator\Desktop\DCS BACKUP\Allen Bradley\Module 70 - GTG\GTG-A\PLC\PD3H422_MG10N85.ACD
FN_M6010_Fail
Lube_Mode.Pump_Check Backup_Pump_Press_Decay_Passed_PP_On <HMI_FSNL[1].19> Pre_Post_Pump_Run
5 /
FN_M6020_Fail
Pre_Post_Pump_Required
<HMI_FSNL[1].20>
ST_Pre_Post_Lube_Pump_Command
<HMI_STATUS[4].20>
PS6010 ST_Pre_Post_Lube_Pump_Press
<UF0080:I.Data[1].0> <HMI_STATUS[4].21>
6
Lube_Mode.Engine_Turning_Post_Lube Backup_Pump_On_Due_To_Lo_Press_AL
Backup_Pump_Test
Restart_BU_Pump_Check
PS6010 AL_PT6060_L
<UF0080:I.Data[1].0> Pre_Post_Pump_Run <HMI_ALARM[7].9>
/
ST_Backup_Lube_Pump_Command
Backup_Pump_Run <HMI_STATUS[4].8> PGM_Lube.Backup_Lube_Oil_Pump_On
RSLogix 5000
_400_Pmp_Ctrl_Eng_Main_FS_212 - Ladder Diagram Page 4
PD3H422_MG10N85:Turbomachinery_Task:Lube_B008_261 6/16/2019 2:09:01 PM
Total number of rungs in routine: 14 C:\Documents and Settings\Administrator\Desktop\DCS BACKUP\Allen Bradley\Module 70 - GTG\GTG-A\PLC\PD3H422_MG10N85.ACD
PS6020 ST_Backup_Lube_Pump_Press
<UF0080:I.Data[1].2> <HMI_STATUS[4].9>
8
MUL MUL
9 Multiply Multiply
Source A KF_Pump_Lag_Delay_Pre_Post.Val Source A KF_Pump_Lag_Delay_Backup.Val
60.0 30.0
Source B 1000 Source B 1000
M6020
Backup_Pump_Run <UF0080:0:O.Data.4>
12 /
M6010
Pre_Post_Pump_Run <UF0090:O.Data[1].6>
13 /
(End)
RSLogix 5000