1. INTRODUCTION
Sensing Input External Volts Adjustment
Voltage 95 ~ 132 VAC or 190 ~ 264 VAC ±7% with 1K ohm 1 watt trimmer
1 phase, jumper selectable
Frequency 50 / 60 Hz, selectable Unit Power Dissipation
Max. 10 watt
Output
Voltage Max. 90 VDC @ 207 VAC Under Frequency Protection
Current Continuous 4A Set point 95% Hz
Intermittent 10A for 10 sec. ( UFRO )
Resistance Min. 15 ohm Slope 170% down to 30 Hz
Voltage Regulation Soft Start Ramp Time
< ± 1.5% ( with 4% engine governing ) 2 sec.
Voltage Build-up Dimensions
Residual voltage at AVR terminal > 5 VAC 135mm L * 100mm W * 49mm H
Thermal Drift Weight
0.05% per °C change in AVR ambient 243g ± 2%
1. The connection and examination procedures 6. Connect a 300VAC meter across line to neutral
must be executed by the profession engineers. of generator.
2. Place the EA460 inside of the generator, 7. Start and run the generator at no load and rated
especially the moisture-proof and anticorrosive speed. The generator output voltage should build
space. up to a minimum level if the voltage does not
build up, It may cause by low residual voltage of
generator. Refer to field flashing section in
3.2 Startup procedure generator manual.
1. The surface temperature pf the EA460 will be 8. Slowly adjust voltage potentiometer until the
over 60 °C. generator voltage reach the proper value.
______________________________________________________________________________________
2 NEWAGE SX460 AVR
9. Turn the stability potentiometer clockwise until 1. With the Prime-mover at rest and the regulator s
instability is shown, and then turn it anticlockwise field output wires disconnected, apply a DC
slightly still both meter mention in (5) and (6) source ( NOT grounded ) of not more than 3~12
shown stable. Vdc with Positive to F+ and Negative to F-, in
series with a current-limiting resistor of 3~5 ohms
10.Interrupt regulator power for a short time
20 watt. (The set battery is a suitable source.)
(approximately 1 to 2 second). If the voltage still
stable, the adjustment is now completed. 2. Allow approximately 3 seconds before removing
Otherwise increase the stability slightly, repeat the DC source.
procedure (10) until stability is reached.
3. With the voltage regulator disconnected ( wires 3
and 4 ), start the prime mover and measure the
4. ADJUSTMENTS residual voltage available at the auxiliary
winding. If this voltage is greater than 5 Vac,
4.1 Frequency roll-off adjustment reconnect voltage regulator, and voltage build-up
● As using 50Hz, please connect a jumper between should be successful. If less than 5 Vac is
Com and 50Hz. As 60Hz, between Com and 60 Hz. measured, repeat field flashing procedure.
● To reset the frequency roll-off, proceed as follow: 4. If repeating steps a. and b. does not result in
generator voltage build-up, and residual is
1. Startup engine and build voltage. greater than 5 Vac, replace voltage regulator.
5. FIELD FLASHING
When the regulator is operated with the generator for
the first time, the polarity of residual magnetism may
be reversed or too small to achieve the necessary
build-up voltage for the regulator. If reversing the field
connections does not induce build-up, and the residual
voltage is less than the specified value of 5 Vac, shut
down the Prime-mover and proceed with the following
steps :
______________________________________________________________________________________
NEWAGE SX460 AVR 3
Outline Drawing
Figure 1
120 120
GENERATOR OUTPUT VOLTAGE
100 100
( % OF MONINAL)
( % OF MONINAL)
80 80
50HZ
60HZ
60 60
40 40
20 20
0 10 20 30 40 50 60 0
1 2
FREQUENCY (HZ) SOFT START (V/Sec)
Frequency Compensation Curves Soft Start Curve
Figure 2 Figure 3
______________________________________________________________________________________
4 NEWAGE SX460 AVR
Wiring and adjustment
Figure 4
Note :
1. When there is no connection to VR, 1 and 2 must be joined.
2. When LED lamp is light on, it means the frequency isn t enough ,The output voltage will decrease to
prevent over load exciting current to damage the exciter field winding.
6. TROUBLE SHOOTING
SYMPTOM CAUSE CORRECTION
Voltage does not Residual voltage below 5VAC Flash generator field with proper method
build up Incorrect wiring Check wiring diagram for proper connection
Power/sensing or field wires not Connect the wires properly
connected
Generator not up to speed Increase generator speed
Out voltage low Poor adjustment is made Read start procedure carefully and adjust again
Frequency roll-off Increase generator speed
Incorrect voltage selection Read user s manual to select correct voltage
Out voltage high Poor adjustment is made Read start procedure carefully and adjust again
Incorrect voltage selection Read user s manual to select correct voltage
Out voltage instable Poor adjustment is made Read start procedure carefully and adjust again
Field voltage requirement lower Inquire our distributor to solve
the rang of regulator
______________________________________________________________________________________
NEWAGE SX460 AVR 5