DZR Fixed Orifice Commissioning Valve (FODRV) - ISO 228 Parallel Thread, With Regulation, Isolation and Flow Measurement Functions
DZR Fixed Orifice Commissioning Valve (FODRV) - ISO 228 Parallel Thread, With Regulation, Isolation and Flow Measurement Functions
DZR Fixed Orifice Commissioning Valve (FODRV) - ISO 228 Parallel Thread, With Regulation, Isolation and Flow Measurement Functions
Products are subject to a 5 year guarantee that is between Pegler Yorkshire and the final purchaser of the
product.
This guarantee does not affect any statutory rights the consumer may have in law.
The guarantee covers manufacturing or material defects and does not cover parts subject to normal wear
and tear.
This product range has been designed for the use of homeowners, domestic and commercial applications
and therefore the guarantee is subject to the product being properly selected for their intended service
conditions.
The guarantee is not applicable where the product is fitted contrary to the conditions in the fitting
instructions.
This is reinforced where valves are covered by the European Pressure Equipment Directive (PED97/23/EC)
where Installation, Operating and Maintenance Instructions are supplied with each product and/or carton.
Provided it is installed correctly and receives adequate preventative maintenance it should give years of
trouble –free service.
Abusive behaviour and accidental damage to the product are not covered by this guarantee.
The extent of this liability is limited to the cost of the replacement of the defective item and not to fitting or
consequential damages.
Component Material
Seals EPTO
Steam Water Oil Air Gas Inert Gas Combustible† Gas Corrosive†† Gas Oxygen
no yes no no no no no no
Pegler Yorkshire Group Ltd, St Catherine's Ave, Doncaster, S Yorkshire, DN4 8DF
Telephone: Phone +44 (0) 844 243 4400 Fax: +44 (0) 844 243 9870 Website: www.pegleryorkshire.co.uk
Registered office : Pegler Yorkshire Group Ltd, St Catherine's Ave, Doncaster, S Yorkshire, DN4 8DF Company no : 00401507
Installation, Operating and Maintenance Instructions –
1200 DRV and 1260 FODRV Double Regulating and Commissioning valves
Operation – 1200DRV and 1260FODRV Where there may be any system debris this should be
collected and / or filtered by installation of the
Valve operation by hand wheel appropriate protective device.
Regulation – an anti-clockwise rotation of the hand
Before starting work, de-pressurise the system, turn
wheel will open the valve. When it will go no further,
off any circulating pumps.
return the hand wheel clockwise 1/2 turn.
Prior to any inspection all valves should be at zero
When using the Pegler 1200 or 1260 in water
pressure and at ambient temperature.
distribution balancing mode the valve should always
be in a fully open position prior to system flushing or
Product life span
commissioning.
When a valve is properly selected for its service
The Pegler 1200 and 1260 valves have a visible
conditions it should give years of trouble-free service
position indicator set into the valve hand wheel. This
provided it is installed correctly and receives adequate
allows for double regulation at positions from 00 to
preventative maintenance. By not considering the
79, with a securing mechanism in the handle that
compatibility of the system design and the pressure
locks the set position. When the valve is closed in its
and temperature requirements the life expectancy of
isolating position the valve can be reopened to the
the valves can be adversely affected and valve failure
previous set point to avoid further costly
may occur. The nature of the fluid being carried
commissioning.
through the valve could also affect the valve
To close the valve – a clockwise rotation of the hand performance as this could lead to premature valve
wheel will close the valve. Closure will be confirmed failure. There may also be interactions between
when the handle can be turned no further. metals in the pipe system and the valve which need
Caution: Suitable hand protection should be worn to be considered. Appropriate flushing and cleaning
when operating valves used in extreme temperature of the pipe work installation should take place when
applications. commissioning the system as they would help extend
the valve life.
Maintenance Stress corrosion cracking (SCC) is a phenomenon that
Under normal working conditions Pegler 1200 and occurs occasionally with brass compression fittings. It
1260 valves do not normally require any maintenance; is almost always introduced during installation, either
however, in the event of maintenance being from over-tightening of fittings
necessary, the following procedure should be followed: or contamination from a corrosive substance. The
A regular maintenance program is the most efficient usual corrosive substance involved in SCC is ammonia
method of ensuring longer-term operational efficiency or ammoniacal compounds, which can be found in
cleaning fluids, refrigeration gases, sewage waste
products, building materials, insulating materials
(especially foams) and flame and smoke retarding
treatments. An essential ingredient in the SCC
process is moisture. Moisture on the fitting or
pipework allows the corrosive substance to collect
and become more concentrated. This is a particular
problem in chilled water installations, where
insulating materials allow the condensed moisture to
be retained and kept in close contact with the UK sales
fitting surface. Free Phone: 0800 156 0010
Pegler Yorkshire does not recommend the use of Free Fax: 0808 156 1011
brass components in chilled water applications. Email: uk.sales@pegleryorkshire.co.uk
Instead, we recommend fittings made from SCC
resistant or immune materials, such as copper or
gunmetal. Fittings from our XPress, Tectite, Yorkshire Export
or Endex ranges are the preferred products for chilled Tel: +44 (0) 1302 855 656
water applications. If compression fittings are used Fax: +44 (0) 1302 730 513
then they should be assembled exactly in accordance Email: export@pegleryorkshire.co.uk
with our published instructions and securely bound
by a moisture barrier such as Densotape® to prevent
moisture build up on the fitting. The following Technical Help
installation practices should be adhered to when Free Phone: 0800 156 0050
installing compression fittings in order to avoid SCC: Free Fax: 0808 156 1012
1. Do not overtighten brass components. Email: tech.help@pegleryorkshire.co.uk
2. Use correctly fitting spanners.
3. Use a drop or two of light oil on the threads of Brochure Hotline
fittings of sizes 35mm and above. Free Phone: 0800 156 0020
Free Fax: 0808 156 1011
4. Avoid contaminating the threads or nuts with
jointing compounds. Email: info@pegleryorkshire.co.uk
REF: 1200-1260IOM150609