DZR Fixed Orifice Commissioning Valve (FODRV) - ISO 228 Parallel Thread, With Regulation, Isolation and Flow Measurement Functions

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7
At a glance
Powered by AI
The document describes DZR Fixed Commissioning Valves and provides specifications and installation guidelines.

DZR Fixed orifice commissioning valves (FODRV) with ISO 228 parallel thread that have regulation, isolation and flow measurement functions.

The Fixed Commissioning Valve has regulation, isolation and flow measurement functions.

DZR Fixed orifice commissioning valve (FODRV).

ISO 228 parallel thread, with regulation,


isolation and flow measurement functions.
1260 Fixed Commissioning Valve Size Pattern No. Pack 1 Qty Pack 2 Qty Code Barcode Price (£) ex VAT

1/2" 1260MF 1 0 126043 50222050435286 £66.18

1/2" 1260LF 1 0 126022 5022050217295 £66.18

1/2" 1260ULF 1 0 126039 5022050434746 £66.18

1/2" 1260SF 1 0 126023 5022050217325 £66.18

3/4" 1260SF 1 0 126024 5022050217356 £94.42

1" 1260SF 1 0 126025 5022050217370 £107.73

1.1/4" 1260SF 1 0 126026 5022050217400 £135.00

1.1/2" 1260SF 1 0 126027 5022050217431 £172.98

2" 1260SF 1 0 126028 5022050217455 £204.51

1260 Fixed Commissioning Valve Code Description A B Kg

126043 1/2" 1260MF

126022 1/2" 1260LF 79 106 0.54

126039 1/2" 1260ULF

126023 1/2" 1260SF 79 106 0.53

126024 3/4" 1260SF 86 106 0.59

126025 1" 1260SF 103 113 0.90

126026 1.1/4" 1260SF 121 120 1.29

126027 1.1/2" 1260SF 127 123 1.68

126028 2" 1260SF 157 138 2.97

Pegler Yorkshire reserve the right to change specifications

Size Pattern No. Code Kv m3/h Kvs m3/h

1/2" 1260MF 126043

1/2" 1260LF 126022 0.40 0.41

1/2" 1260ULF 126039

1/2" 1260SF 126023 1.86 2.15

3/4" 1260SF 126024 2.27 4.78

1" 1260SF 126025 6.11 8.11

1.1/4" 1260SF 126026 12.65 15.41

1.1/2" 1260SF 126027 19.00 22.23

2" 1260SF 126028 28.42 48.21

Pegler Yorkshire reserve the right to change specifications

Valves and Fittings

Pegler Yorkshire Customcare 5 Year Guarantee - Terms and Conditions

Products are subject to a 5 year guarantee that is between Pegler Yorkshire and the final purchaser of the
product.

The guarantee is subject to proof of purchase being supplied.

This guarantee does not affect any statutory rights the consumer may have in law.

The guarantee covers manufacturing or material defects and does not cover parts subject to normal wear
and tear.

This product range has been designed for the use of homeowners, domestic and commercial applications
and therefore the guarantee is subject to the product being properly selected for their intended service
conditions.
The guarantee is not applicable where the product is fitted contrary to the conditions in the fitting
instructions.

This is reinforced where valves are covered by the European Pressure Equipment Directive (PED97/23/EC)
where Installation, Operating and Maintenance Instructions are supplied with each product and/or carton.

Provided it is installed correctly and receives adequate preventative maintenance it should give years of
trouble –free service. 

Abusive behaviour and accidental damage to the product are not covered by this guarantee.

The extent of this liability is limited to the cost of the replacement of the defective item and not to fitting or
consequential damages.

Component Material

Body GDCBr, BSEN 1982, CC 752S

Bonnet EBB, BSEN 12164, CW 617N

Spindle EBB, BSEN 12164, CW 617N

Disc EBB, BSEN 12164, CW 617N

Gland Packing Piece EBB, BSEN 12164, CW 617N

'O' rings EPTO

Orifice plate EBB, BSEN 12164, CW 617N

Circlip Carbon spring steel

Adjustment screw EBB, BSEN 12164, CW 617N

Test points DZR Brass

Seals EPTO

Handle 30% Glass filled nylon 66

Set screw Brass

Steam Water Oil Air Gas Inert Gas Combustible† Gas Corrosive†† Gas Oxygen

no yes no no no no no no

Pegler Yorkshire reserve the right to change specifications

Gas application guide


Class 1. INERT Air, argon, carbon dioxide, helium, nitrogen
Class 2. COMBUSTIBLE Hydrogen, methane, natural gas, town gas
Class 3. CORROSIVE Chlorine, sulphur dioxide Class 4. OXYGEN
Class 1. INERT Air, argon, carbon dioxide, helium, nitrogen
† Valves are suitable for British Gas Applications Family Gases 1, 2 and 3.
†† Suitable in applications where moisture is completely absent.

Pegler Yorkshire Group Ltd, St Catherine's Ave, Doncaster, S Yorkshire, DN4 8DF
Telephone: Phone +44 (0) 844 243 4400 Fax: +44 (0) 844 243 9870 Website: www.pegleryorkshire.co.uk
Registered office : Pegler Yorkshire Group Ltd, St Catherine's Ave, Doncaster, S Yorkshire, DN4 8DF Company no : 00401507
Installation, Operating and Maintenance Instructions –
1200 DRV and 1260 FODRV Double Regulating and Commissioning valves

The Pressure Equipment Directive environment, corrosive or erosive service, or for


97/23/EC and CE Marking carrying fluids containing abrasive solids. There is
no allowance for corrosion in the design of these
The Pressure Equipment Regulations 1999 valves. Designs for this valve do not allow for
(SI 1999/2001) have now been introduced into decomposition of unstable fluids and must not be
United Kingdom law. used where this could occur.
Valves with a maximum allowable pressure greater Pegler valves are not designed to withstand the
than 0.5 bar are covered by these new Regulations. effects of fire, wind, earthquakes and traffic.
Vales are categorised according to their maximum
working pressure, size and rising level of hazard. When Pegler valves are fitted with pressure
The level of hazard varies according to the fluid equipment or assemblies, suitable protective
being carried. Fluids are classified as Group1, devices may be required.
dangerous fluids or Group 2, all other fluids
including steam. The Categories designated are Pegler 1200 DRV and 1260 FODRV are suitable for:
SEP (sound engineering practice). Valves up to Gas
and including 25mm (1") are designated SEP Steam Water Oil Air Inert Combustible Corrosive Oxygen
regardless of the fluid group. Those identified as        
having increased hazard are Categorised as I, II,
III or IV. All valves designated as SEP do not bear Operational Limits
the CE mark nor require a Declaration of
Conformity. Categories I, II, III or IV carries the Pressure and temperature limitations for PN rated valves
CE mark and require a Declaration of Conformity.
Valves classified from the piping chart would not Non-shock pressure at Non-shock pressure
be included in Category IV. PN Connection temperature range at Max temperature
16 Compression 16bar, 2°C - 30°C 5bar at 120°C
Valve selection 16 XPress Press-fit 16bar, -10°C - 110°C 5bar at 120°C
20 Female thread 20bar, -10°C - 100°C 17.2bar at 120°C
It is important that the valve selected is suitable
for the required service conditions. Provided it is
installed correctly and receives adequate Pegler 1200 DRV and 1260 FODRV PED categorisation
preventative maintenance it should give years of ⁄2"
1 3
⁄4" 1" 11⁄4" 11⁄2" 2"
trouble-free service. S.E.P. S.E.P. S.E.P. S.E.P. S.E.P. S.E.P.
Pegler valves are not suitable for fatigue loading,
creep conditions, fire testing, fire hazard CE marking is not required.
Pressure/Temperature rating Use suitable hangers close to both ends of the valve
in order to remove stresses transmitted by the pipe.
Valves rated at PN16 and PN20 must be installed in a
piping system whose normal pressure and temperature Confirm that the pipe threading length is correct to
do not exceed the indicated ratings. The maximum avoid excessive penetration of the pipe into the valve
allowable pressure in valves as specified in the that would otherwise cause damage.
standards is for non-shock conditions. Water Hammer Thread depths for 1200DRV and 1260FODRV Double
and impact should also be avoided. regulating and Commissioning valves
If system testing will subject the valve to pressure in ⁄"
12
⁄"
34
1" 11⁄4" 11⁄2" 2"
excess of the working pressure rating, this should be DN15 DN20 DN25 DN32 DN40 DN50
within the “shell test pressure for the body” to a
16.5mm 17.6mm 20.0mm 21.5mm 21.3mm 26.1mm
maximum of 1.5 times the PN rating and conducted
with the valve fully opened. Care should be taken to apply jointing compound to
It may be hazardous to use these valves outside of the pipe only and not in the valve threads. Surplus
their specified pressure and temperature limitations compound will then be forced outwards and will not
and also when not used for the correct application. enter the valve. Overuse of compound can lead to
valve failure on the body ends.
Valve location and end-of-line service Threads should be engaged correctly when tightening
the valve onto the pipe. The wrench should always be
To ensure ease of operation, adjustment, maintenance
fitted on the body end adjacent to the joint being
and repair, valve siting should be decided during the
made. Severe damage can occur to stems, valves and
system design phase. To prevent straining on the
seats by the use of hand wheels or levers larger than
valve seat, pipe work and valves must be adequately
those originally supplied by the manufacturer, and by
supported.
wheel keys.
These valves are not suitable for end of line service. Valve options include pre-assembled with adaptors for
Compression, Press fitting and Push fittings.
Installation
Compression joints should be made with Kuterlite
Unpack the valve and check that the flow paths and joints that are suitable for Copper, stainless steel tube
valve threads are clean and free from debris. and carbon steel tube (15mm to 28mm). Joints
Check the body markings and nameplate, where fitted, should be made to hand tight and then further
to ensure that the correct valve has been selected for tightened as follows:
installation. 360° turn for 6mm - 12mm and 270° turn for
15mm - 54mm. A few drops of light oil on the
Before valve installation the pipe work to which the
threads will assist, on sizes 35mm and above.
valve is to be connected should be inspected for
cleanliness and freedom from debris. All tightening should be carried out using a close
fitting spanner. The larger size fittings may require a
The valve is marked with a directional flow arrow on
drop of light oil to aid joint tightening.
the body. The valve will function correctly providing
it is fitted so that the fluid transported follows the Press fit valves include the Xpress connectors and these
indicated flow direction. are bronze and are suitable for copper tube, stainless
steel and carbon steel tube. The Joints are of the leak
Pegler Valves are manufactured to exacting standards
before press type and utilise the M press profile.
and, therefore, should not be subjected to misuse.
The following should be avoided: Push fit valves utilise the Tectite connectors that also
incorporate a special grab ring to allow connection to
I Careless handling of the valve – (valves should not
copper, carbon steel and stainless steel tube.
be lifted using the hand wheel or the stem).
The Pegler 1200 DRV can be used with a 1250 metering
I Dirt and debris entering the valve through the end
station but the design does not allow for close coupling.
ports.
It is important that when they are used in conjunction
I Excessive force during assembly and hand wheel the metering station test points are positioned to allow
operation. for the easy use of manometer probes.
When commissioning an upstream straight length of of the selected valve. Such a program would need to
tube should be a minimum of 5 pipe diameters to include a risk assessment and a planned procedure of
allow for lamina flow and more accurate measurement how the maintenance will be carried out. The
of the valve signal. possibility of operational limits being exceeded and
Straight pipe lengths are not necessary downstream of the potential hazards ensuing must be considered as
the 1200DRV. part of this assessment.
Installation of the 1260 FODRV Commissioning valve This should be implemented to include visual checks
should take account of the position of the test points on the valve’s condition and any development of
to allow for easy connection of the Manometer probes. unforeseen conditions, which could lead to failure.
When fitting a Pegler 1260 FODRV commissioning The valve should be at zero pressure and ambient
valve an upstream straight length of tube should be a temperature before any valve maintenance is carried
minimum of 5 pipe diameters to allow for lamina flow out.
and more accurate measurement of the valve signal. The correct fitting tools and equipment should be
Adequate space should be allowed for easy adjustment used for valve maintenance work.
of the valve control handle, giving easy operability, Separate means of draining the pipe work must be
regulation and position setting for the double provided when carrying out any maintenance to the
regulating mechanism. valves.

Operation – 1200DRV and 1260FODRV Where there may be any system debris this should be
collected and / or filtered by installation of the
Valve operation by hand wheel appropriate protective device.
Regulation – an anti-clockwise rotation of the hand
Before starting work, de-pressurise the system, turn
wheel will open the valve. When it will go no further,
off any circulating pumps.
return the hand wheel clockwise 1/2 turn.
Prior to any inspection all valves should be at zero
When using the Pegler 1200 or 1260 in water
pressure and at ambient temperature.
distribution balancing mode the valve should always
be in a fully open position prior to system flushing or
Product life span
commissioning.
When a valve is properly selected for its service
The Pegler 1200 and 1260 valves have a visible
conditions it should give years of trouble-free service
position indicator set into the valve hand wheel. This
provided it is installed correctly and receives adequate
allows for double regulation at positions from 00 to
preventative maintenance. By not considering the
79, with a securing mechanism in the handle that
compatibility of the system design and the pressure
locks the set position. When the valve is closed in its
and temperature requirements the life expectancy of
isolating position the valve can be reopened to the
the valves can be adversely affected and valve failure
previous set point to avoid further costly
may occur. The nature of the fluid being carried
commissioning.
through the valve could also affect the valve
To close the valve – a clockwise rotation of the hand performance as this could lead to premature valve
wheel will close the valve. Closure will be confirmed failure. There may also be interactions between
when the handle can be turned no further. metals in the pipe system and the valve which need
Caution: Suitable hand protection should be worn to be considered. Appropriate flushing and cleaning
when operating valves used in extreme temperature of the pipe work installation should take place when
applications. commissioning the system as they would help extend
the valve life.
Maintenance Stress corrosion cracking (SCC) is a phenomenon that
Under normal working conditions Pegler 1200 and occurs occasionally with brass compression fittings. It
1260 valves do not normally require any maintenance; is almost always introduced during installation, either
however, in the event of maintenance being from over-tightening of fittings
necessary, the following procedure should be followed: or contamination from a corrosive substance. The
A regular maintenance program is the most efficient usual corrosive substance involved in SCC is ammonia
method of ensuring longer-term operational efficiency or ammoniacal compounds, which can be found in
cleaning fluids, refrigeration gases, sewage waste
products, building materials, insulating materials
(especially foams) and flame and smoke retarding
treatments. An essential ingredient in the SCC
process is moisture. Moisture on the fitting or
pipework allows the corrosive substance to collect
and become more concentrated. This is a particular
problem in chilled water installations, where
insulating materials allow the condensed moisture to
be retained and kept in close contact with the UK sales
fitting surface. Free Phone: 0800 156 0010
Pegler Yorkshire does not recommend the use of Free Fax: 0808 156 1011
brass components in chilled water applications. Email: uk.sales@pegleryorkshire.co.uk
Instead, we recommend fittings made from SCC
resistant or immune materials, such as copper or
gunmetal. Fittings from our XPress, Tectite, Yorkshire Export
or Endex ranges are the preferred products for chilled Tel: +44 (0) 1302 855 656
water applications. If compression fittings are used Fax: +44 (0) 1302 730 513
then they should be assembled exactly in accordance Email: export@pegleryorkshire.co.uk
with our published instructions and securely bound
by a moisture barrier such as Densotape® to prevent
moisture build up on the fitting. The following Technical Help
installation practices should be adhered to when Free Phone: 0800 156 0050
installing compression fittings in order to avoid SCC: Free Fax: 0808 156 1012
1. Do not overtighten brass components. Email: tech.help@pegleryorkshire.co.uk
2. Use correctly fitting spanners.
3. Use a drop or two of light oil on the threads of Brochure Hotline
fittings of sizes 35mm and above. Free Phone: 0800 156 0020
Free Fax: 0808 156 1011
4. Avoid contaminating the threads or nuts with
jointing compounds. Email: info@pegleryorkshire.co.uk

5. Use parallel threaded adaptors to avoid stressing


the female threaded ends.
www.pegleryorkshire.co.uk
Minimise the risk of contamination from a potential
corrosive substance. Wrapping susceptible fittings in
a vapour barrier or applying impermeable paints can
be helpful in preventing contact with a corrosive
substance.
Reference Material: Pegler Commercial Valves
Package Brochure, Pegler Yorkshire Group Limited Pegler Yorkshire Group Limited
St. Catherine’s Avenue, Doncaster,
website.
South Yorkshire, DN4 8DF, England.
A technical file is held at Doncaster as part of the Tel: 0844 243 4400 Fax: 0844 243 9870
requirements for compliance to the European Registered in England Company No. 00401507
Pressure Equipment Directive (PED 97/23 EC). Registered Office: Haigh Park Road, Stourton, Leeds,
West Yorkshire, LS10 1RT, England.

All brand names and logo styles are registered trademarks.


Maintaining a policy of continual product development,
Pegler Yorkshire reserves the right to change specifications,
design and materials of products listed in this publication
without prior notice.

REF: 1200-1260IOM150609