Renewable and Sustainable Energy Reviews: Sachit A. Gopalan, Victor Sreeram, Herbert H.C. Iu
Renewable and Sustainable Energy Reviews: Sachit A. Gopalan, Victor Sreeram, Herbert H.C. Iu
art ic l e i nf o a b s t r a c t
Article history: Distributed generation (DG) using renewable energy resources, is intended to reduce the impact of
Received 3 September 2013 power generation from fossil fuels on climate change. Microgrids (MGs) represent a method of
Received in revised form interconnecting several low voltage (LV) renewable energy sources and loads to the distribution system.
19 November 2013
Multi-microgrids (MMGs) integrate distributed generators (DGs) and MGs with medium voltage (MV)
Accepted 4 January 2014
Available online 31 January 2014
distribution systems. Protection system design for MGs pose significant challenges due to bi-directional
flow from DGs as well as lower fault current levels due to the inverter connected DG sources in islanded
Keywords: MGs. This paper reviews the coordination strategies and protection schemes that have been proposed
Microgrids for MGs to address these challenges. The protection coordination strategies based on communication
Multi-microgrids
and time grading including their relative performance are described. The advantages and limitations
Coordination strategies
of existing MG protection schemes are discussed. As most of these protection schemes apply to relatively
Protection schemes
small MGs, they may need to be extended for larger MG configurations in practical power systems. Some
future directions for research in the protection system design for both MGs and MMGs are also outlined
in this paper.
& 2014 Elsevier Ltd. All rights reserved.
Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
2. Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
2.1. Microgrids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
2.2. Multi-microgrids . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
3. Microgrid protection schemes and coordination strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
3.1. Protection coordination strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
3.1.1. Time grading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
3.1.2. Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
3.1.3. Other coordination strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
3.2. Protection schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
3.2.1. Voltage-based protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
3.2.2. Admittance relaying. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
3.2.3. Adaptive techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
3.2.4. Differential zone protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
4. Discussion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
5. Conclusion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
1. Introduction
1364-0321/$ - see front matter & 2014 Elsevier Ltd. All rights reserved.
http://dx.doi.org/10.1016/j.rser.2014.01.037
S.A. Gopalan et al. / Renewable and Sustainable Energy Reviews 32 (2014) 222–228 223
MGs interconnect microsources, storage devices, and loads at MMGs consist of DGs and MGs that are connected to the MV
LV level. They can either be DC or AC grids. Examples of micro- distribution system. The large load pockets of an MMG can be
sources include renewable energy sources of wind, PV, and hydro divided into smaller load units served by individual MGs. The
as well as combined heat and power (CHP) plants. Storage devices MMG can operate either connected to a HV transmission grid or in
employ technologies such as flywheels, batteries, and super- islanded mode [6,7].
224 S.A. Gopalan et al. / Renewable and Sustainable Energy Reviews 32 (2014) 222–228
Fault detection cleared. Adding a communication network can improve the speed
module of the protection system operation, though it may become vulner-
Zone Zone Zone able to communication failures. No experimental results have been
C1 C2 C3 provided for this scheme.
A protection strategy based on microprocessor relays for both
the grid-connected and islanded modes was proposed in [9]. Each
microprocessor relay contains modules for tripping, interface,
Utility grid Zone Zone Zone
B1 B2 B3 negative-sequence directional function, three-phase protection,
and also phases a, b, and c. Each phase module protects the
corresponding phase of its secondary mains feeders. The three-
phase protection module provides redundant protection based on
Zone Zone Zone zero/negative sequence detection. The protection of the MG is
A1 A2 A3 coordinated with a time grading technique containing directional
Fig. 3. MG with multiple protection zones and fault detection modules. elements for identifying forward and reverse faults. If the primary
protection relay fails with this technique, downstream relays will
respond one-by-one after different time delays until the fault is
A hierarchical frequency control scheme for MMGs proposed in cleared. This scheme does not use communication or adaptive
[6,7] is shown in Fig. 2. The DGs and MGs are treated as individual protection devices, but adapts to different fault current levels and
controllers. The remote telemetry units (RTUs) control the opera- fault types. However, it experiences relatively long fault clearing
tion of the HV/MV substations. A Central Autonomous Manage- times due to the time grading technique for protection
ment Controller (CAMC) is interfaced with a DMS similar to the coordination.
one described in Section 2.1. The CAMC performs the following
tasks: acquiring active and reactive power measurements from the
MGCCs, DGs, and RTUs; receiving commands from the DMS for 3.1.2. Communication
balancing generation and load; and scheduling the operation of In communication-based protection schemes, a central control
the MGCCs, DGs and RTUs. The operation of this scheme is similar unit is interconnected with the measurement devices and circuit
to that of Automatic Generation Control (AGC). breakers via communication networks. The central control unit
MMGs provide improved reliability due to the presence of analyses the measured voltages and currents to determine the
several MGs. Their distributed control structure ensures greater fault location. Trip signals are then sent to nearby circuit breakers.
stability and controllability [6,7]. Sortomme et al. [10] proposed a protection scheme for phase-
A-to-ground faults using digital relays and a communication
system. The primary protection based on the differential scheme
3. Microgrid protection schemes and coordination strategies for each feeder segment trips the switching device on both ends of
a faulted feeder. If the switching device fails to operate, a backup
Protection systems for islanded MGs need to consider the following trip signal is sent to the adjacent relay on the same bus after a time
factors: protecting the MV side of the MG; microsource protection; delay. But if either the backup protection relay or communication
protection of distribution transformers; and neutral grounding con- link fails, the relays use comparative voltage protection until the
siderations. This section reviews protection schemes and coordination system recovers. When the MG is islanded, this scheme also
strategies for both grid-connected and islanded MGs. Section 3.1 detects high impedance faults (HIFs) from the measured differ-
describes the protection coordination strategies and Section 3.2 the ential current. It has high reliability because of its looped config-
various protection schemes. uration and can cope with communication failures. However, the
placement of relays and switching devices at each end of the
3.1. Protection coordination strategies feeders is expensive. The errors and mismatches of the current
transformers (CTs) has not been considered in this protection
Strategies are needed to coordinate the operations of primary scheme. It also assumes technical features such as faster tripping
and backup protection schemes. Primary protection acts as the times that are not available in state-of-the-art equipment.
first line of defence against the damaging consequences of faults, A scheme proposed in [11] for radial grid-connected MG
whereas backup protection acts only when the primary protection configurations uses an integrated protection and control (IPC)
fails. The strategies for protection coordination based on time unit. An IPC is interconnected by an optical Ethernet communica-
grading, communications and other techniques are reviewed in tion network to the measurement devices, circuit breakers, and
the following subsections. control units at each bus. The currents, voltages, and other
electrical quantities are used by the IPC to make protection and
3.1.1. Time grading control decisions to be sent to the circuit breakers and control
When the primary protection fails, time grading strategies units respectively. A pilot instantaneous overcurrent protection
enable the backup relays to operate after varying time delays. Loix scheme for the local feeder and remote busbar is implemented.
et al. [8] developed a strategy to detect and clear faults within This protection scheme provides faster fault clearing times. How-
radial MGs containing a large number of inverter-coupled energy ever, communication failures and lack of available communication
sources. Fig. 3 shows a MG consisting of multiple protection zones channels are not considered.
that are each covered by fault detection modules. Traditional Nthontho et al. [12] proposed a wide-area differential protection
overcurrent protection is used within a given time delay to detect scheme using communication links to protect a MG containing
a fault in the grid-connected MG. If the fault is not detected within household PV systems against three-phase faults. Intelligent electro-
the time delay, the MG is islanded from the grid and the fault is nic devices (IEDs) and circuit breakers at each bus are connected to
detected using voltage measurements. The direction for each fault the control centre via wireless mobile broadband. The embedded
type is determined by the voltage and current measurements from sensors in the IEDs monitor the real-time current measurements and
the fault detection module. When the fault direction is known, communicate this information to the control centre. The control
time delays are selectively applied to each module until the fault is centre executes advanced differential protection for each feeder to
S.A. Gopalan et al. / Renewable and Sustainable Energy Reviews 32 (2014) 222–228 225
determine the faulted section, send trip signals to the circuit breakers
at the faulted location, and apply auto-reclosing. If this primary
protection fails, backup protection uses the current sensor measure-
ments and time-stamped Global Positioning System (GPS) coordi- R K
nates to locate and isolate the fault. This scheme is simple, effective,
and adaptable to the dynamic behaviour of MGs. However, it has only
been tested for small grid-connected PV systems. Communication
failures and the optimisation of the networking technologies have
not been considered in this scheme.
Li et al. [13] investigated the differential and voltage protection Fig. 4. Feeder segment showing the measured admittance Ym between points R
methods for islanded MGs using communication networks. The and K and total admittance Yt.
differential scheme was implemented at every connection point in
the MG. This scheme works for both internal and external faults, fault. If the primary protection for the feeder fails, then the circuit
operates accurately, and adapts to changes in MG configuration. breakers near the converter and battery must be opened. Fuses on
However, it does not detect HIFs or provide backup protection for the AC side provide backup protection to the converter. Low
neighbouring feeders. It is also expensive to implement due to the impedance ground faults are easily detected and cleared. The
placement of relays at every connection point. In the voltage based converter is effectively protected by using both the converter
scheme, the control centre determines the fault type and location current derivative and DC link undervoltage protection. However,
using the indicator voltage waveforms at each connection point HIF detection within the MG is difficult due to the low ground
and sends trip signals. This method accurately determines the fault currents. The protection methods are not systematically
faulted zone for large MGs that have sufficient gradient voltage dip coordinated.
along the feeders. However, it cannot cope with shorter feeder
distances since the gradient voltage dip would be low. The
3.2. Protection schemes
calculation complexity for this method is high.
A communication-assisted protection strategy for MV MGs
In each protection scheme, relays compare the measured data
using microprocessors was proposed in [14]. Each microprocessor
such as voltages and currents against pre-determined thresholds.
relay consists of directional, grid-connected, islanded, interface,
Trip signals are sent to the circuit breakers when these thresholds
and tripping modules. The proposed protection strategy intercon-
are exceeded. The protection schemes vary based on the measure-
nects a MG protection commander (MGPC) and the individual
ments used such as voltages, currents, power, and frequency as
relays at each MG subsection via a communication network. The
well as the operating characteristics defining the trip thresholds.
MGPC determines the faulted MG subsection using the fault
The various schemes proposed are grouped under voltage-based
detection and directional signals from each relay. The primary
protection, admittance relaying, adaptive techniques, and differ-
protection trip signals are sent to the circuit breakers near the
ential zone protection in the following subsections.
faulted MG subsection. If the primary protection fails, backup trip
signals are sent to the neighbouring circuit breakers after a time
delay. Time grading is applied to all the circuit breakers in the 3.2.1. Voltage-based protection
faulted MG subsection if either the backup protection or commu- Al-Nasseri et al. [17,18] developed voltage-based schemes to
nication link fails. This protection strategy can cope with different protect islanded MGs containing inverter-interfaced microsources
fault current levels, fault types, MG operating modes, as well as for all the fault types. The measured utility voltages undergo a
deal with different types, sizes, and locations of DGs. The fault series of conversions before they are used to identify the fault type
clearing time for this strategy is faster than the scheme in [9]. and zone. In [17], the faulted zone is tripped if the disturbance
Looped configurations of MGs are not considered in this scheme. voltage exceeds the threshold corresponding to the fault type. In
[18], the measured voltage is transmitted via communication links
between any two relays within the MG, and compared with the
3.1.3. Other coordination strategies mean average value of the two relays to identify the faulted zone
Primary and backup protection strategies for MGs in both grid- within the network. This scheme protects against both internal
connected and islanded modes were proposed by Nikkhajoei and and external faults relative to any protective zone. However, it
Lasseter [15] without communication links or time-grading. The ignores HIFs and symmetrical faults and also does not enable
primary protection scheme for the single-line-to-ground fault uses single phase tripping.
differential current detection for zones upstream of the fault
and zero-sequence detection for downstream zones. Negative
3.2.2. Admittance relaying
sequence current detection is used for line-to-line faults. The main
The admittance relays proposed in [19] protect feeder seg-
backup protection for both single-line-to-ground and line-to-line
ments of a radial MG connected to the utility network via back-to-
faults is I2t. Undervoltage backup protection is also employed for
back converters against the three-phase-to-ground fault. The
the islanded MG. Three-phase faults are not considered in this
feeder segment in Fig. 4 shows the measured admittance Y m
protection scheme and it lacks systematic coordination. It also
between the relay and an arbitrary point on the feeder K as well as
does not enable single phase tripping.
the total admittance value Y t . The normalised admittance Y r is
Salomonsson et al. [16] proposed a protection system for a
calculated in the following equation:
radial LV direct current (DC) MG that uses primary protection
schemes for the converter, battery, and feeder against pole-to-pole Y m
Y r ¼ ð1Þ
and pole-to-ground faults. The converter is protected by compar- Yt
ing the measured current derivative with a minimum threshold.
The inverse time characteristic is used to find the tripping time
Undervoltage protection is used for the DC link capacitor and
corresponding to Yr in the following equation:
overcurrent protection for the battery. For feeder protection, the
measured ground currents of the converter and battery are A
tp ¼ þk ð2Þ
compared against their predetermined ranges to detect the ground Yrρ 1
226 S.A. Gopalan et al. / Renewable and Sustainable Energy Reviews 32 (2014) 222–228
Table 1
Advantages and disadvantages of various coordination strategies.
Time grading [8] Reliable scheme as it does not use communication. Absence of communication could slow down the speed of
operation. No study results have been reported to test the proposed
scheme.
Microprocessor-based Accommodates different fault levels. Does not use adaptive Does not use communication devices. Slower fault clearing times.
strategy for LV MGs [9] protection devices.
Communication-assisted Increased reliability as it accommodates looped configuration and Placement of relays and switching devices on each end of the feeder
digital relays [10] communication failures. is expensive. CT errors and mismatches were not considered within
the protection scheme. Assumes technical features not present in
state-of-the-art equipment.
Integrated protection and Faster fault clearing times. Possibility of failure or lack of availability of communication
control scheme [11] network was not considered.
Wide-area differential Can adapt to dynamic behaviour of MGs. Simple and effective. Only tested for small grid-connected PV systems within MG. Does
protection [12] not consider the optimisation of the communication technologies or
communication failures.
Communication-based Differential protection works for internal and external faults, Differential protection does not detect HIFs, cannot provide backup
protection schemes [13] operates accurately, and adapts to changes in MG configuration. protection to neighbouring feeders, and expensive to implement.
Voltage measurement method is able to accurately determine the Voltage measurement method cannot cope with reduced feeder
faulted location provided that the MG is large and there is sufficient distances due to insufficient gradient voltage dip. Voltage
gradient voltage dip along the faulted feeders. measurement method has high calculation complexity.
Communication-assisted Accommodates different fault current levels, MG operating modes, Does not consider the looped configuration of MG.
microprocessor-based and type, size, and location of DG units. Faster fault clearing times.
strategy for MV MGs
[14]
MG protection coordination Covers both primary and backup protection strategies. Three-phase faults are not considered in the protection scheme.
strategy [15] A systematic coordination technique was also missing from this
scheme. Does not enable single phase tripping.
LV DC MG protection [16] Low impedance ground fault are easily detected and cleared. Low ground currents make HIFs difficult to detect. No systematic
Combination of dc link voltage and converter current derivative coordination between the protection methods.
protects the converter more effectively.
Table 2
Advantages and disadvantages of voltage, admittance, adaptive, and differential zone protection schemes.
Voltage-based [17,18] Able to protect against faults that are internal and Does not consider symmetrical faults, single phase tripping, and HIFs.
external to any protection zone.
Admittance relaying [19] Each upstream relay protects their downstream relay. Only considers a smaller MG system.
Relay0 s inverse time characteristic does not use safety
margins.
Novel adaptive Adapts to a variety of MG configurations. Off-line analysis data may consume large amounts of computational
protection scheme Communication improves the speed of operation. memory. Does not consider HIFs. Connections of new loads and DGs are not
[20] considered in this scheme.
Adaptive protection for High speed communication enables the scheme Does not consider the possibility of communication network failure.
future MGs [21] to have fast, selective, and reliable operation. Does not consider new deployments of plug-and-play DGs.
Centralised protection Works well for the MG component models based Does not work for complex systems with changing relay connections. Does not
scheme based on IEC on IEC 61850 and IEC 61850-7-420. consider the dynamic behaviour of the communication network.
61850-7-420 [22]
Differential zone [23] Effective and less expensive. No test results have been performed for the proposed scheme.
[2] Planas E, Gil-de-Muro A, Andreu J, Kortabarria I, Martinez de Alegria I. General [13] Li X, Dysko A, BurtGM. Application of communication based distribution
aspects, hierarchical controls and droop methods in microgrids: a review. protection schemes in islanded systems. In: Proceedings of the 14th Interna-
Renew Sustain Energy Rev 2013;17:147–59. tional Universities Power Engineering Conference (UPEC). Cardiff; 2010. p. 1–6.
[3] Jiayi H, Chuanwen J, Rong X. A review on distributed energy resources and [14] Zamani MA, Yazdani A, Sidhu TS. A communication-assisted protection
MicroGrid. Renew Sustain Energy Rev 2008;12:2472–83. strategy for inverter-based medium-voltage microgrids. IEEE Trans Smart Grid
[4] Justo JJ, Mwasilu F, Lee J, Jung JW. AC-microgrids versus DC-microgrids with 2012;3:2088–99.
distributed energy resources: a review. Renew Sustain Energy Rev [15] Nikkhajoei H, Lasseter RH. Microgrid protection. In: Proceedings of the IEEE
2013;24:387–405. Power and Energy Society General Meeting. Tampa; 2007. p. 1–6.
[5] Ustun TS, Ozansoy C, Zayegh A. Recent developments in microgrids and [16] Salomonsson D, Soder L, Sannino A. Protection of low-voltage DC microgrids.
example cases around the world – a review. Renew Sustain Energy Rev IEEE Trans Power Deliv 2009;24:1045–53.
2011;15:4030–41. [17] Al-Nasseri H, Redfern MA, O0 Gorman R. Protecting micro-grid systems con-
[6] Pecas Lopes JA. Algorithms for state estimation for MV multi-microgrids. taining solid-state converter generation. In: Proceedings of the International
Advanced architectures and control concepts for more microgrids.
Conference on Future Power Systems. Amsterdam; 2005. p. 1–5.
[7] Pecas Lopes JA. Coordinated voltage support. Advanced architectures and
[18] Al-Nasseri H, Redfern MA, Li F. A voltage based protection for micro-grids
control concepts for more microgrids. 2007.
containing power electronic converters. In: Proceedings of the IEEE Power and
[8] Loix T, Wijnhoven T, Deconinck G. Protection of microgrids with a high
Energy Society General Meeting. Montreal; 2006. p. 1–7.
penetration of inverter-coupled energy sources. In: Proceedings of the IEEE
[19] Majumder R, Dewadasa M, Ghosh A, Ledwich G, Zare F. Control and protection
Power and Energy Society/CIGRE Joint Symposium. Calgary; 2009. p. 1–6.
[9] Zamani MA, Sidhu TS, Yazdani A. A protection strategy and microprocessor- of a microgrid connected to utility through back-to-back converters. Electr
based relay for low-voltage microgrids. IEEE Trans Power Deliv Power Syst Res 2011;81:1424–35.
2011;26:1873–83. [20] Oudalov A. Novel protection systems for microgrids. Advanced architectures
[10] Sortomme E, Venkata SS, Mitra J. Microgrid protection using communication- and control concepts for more microgrids. 2009.
assisted digital relays. IEEE Trans Power Deliv 2009;25:2789–96. [21] Laaksonen HJ. Protection principles for future microgrids. IEEE Trans Power
[11] Li B, Li Y, Bo Z, Klimek A. Design of protection and control scheme for Electron 2010;25:2910–8.
microgrid systems. In: Proceedings of the 44th International Universities [22] Ustun TS, Ozansoy C, Zayegh A. Modeling of a centralized microgrid protection
Power Engineering Conference (UPEC). Glasgow; 2009, p. 1–5. system and distributed energy resources according to IEC 61850-70420. IEEE
[12] Nthontho MP, Chowdhury SP, Winberg S , Chowdhury S. Protection of Trans Power Syst 2012;27:1560–7.
domestic solar photovoltaic based microgrid. In: Proceedings of the 11th [23] Sortomme E, Ren J, Venkata SS. A differential zone protection scheme for
International Conference On Developments in Power Systems Protection. microgrids. In: Proceedings of the IEEE Power and Energy Society General
Birmingham; 2012. p. 1–6. Meeting. Vancouver; 2013. p. 1–5.