SCC Calc

The document contains calculations to determine short circuit fault currents at different points in an electrical system for a printing press. It first calculates the short circuit current from the transformer primary to be 39,550 amps. It then calculates the fault current from the transformer to a downstream point to be 34,357 amps, taking into account cable impedance factors. Finally, it calculates the fault current from that point to another point further downstream to be 20,991 amps, and notes a motor adds an additional 3,464 amps of current.

Uploaded by

Syed S Al-Ameen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
361 views1 page

SCC Calc

The document contains calculations to determine short circuit fault currents at different points in an electrical system for a printing press. It first calculates the short circuit current from the transformer primary to be 39,550 amps. It then calculates the fault current from the transformer to a downstream point to be 34,357 amps, taking into account cable impedance factors. Finally, it calculates the fault current from that point to another point further downstream to be 20,991 amps, and notes a motor adds an additional 3,464 amps of current.

Uploaded by

Syed S Al-Ameen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Short Circuit Current Calculation : Kilo-10, Printing Press

3-phase Transformer Fault Current

Primary Fault (Isca(P)) in kA *if unknown = "x" x


Primary Voltage (V) 13800
Trans. Size (kVA) 1500
Impedance (%Z) 6.00
Secondary Voltage (V) 400.00
I = kVA x 1000 = Trans. FLA IS (Current) (A) 2,165
V x 1.732
Isca(s) = trans. FLA x 100 Isca(s) (A) 39,550
transformer Z
*Isca = ampere short-circuit current RMS symmetrical kA

Fault Current from Transformer to Point


Primary Fault (Isca(P)) in kA *if unknown = "x" x
Primary Voltage (kV) 13800
Trans. Size (kVA) 1500
Impedance (%Z) 6
Secondary Voltage (V) 400
Fault Transformer Isca (A) 36,085
Sizing Standard Metric
Voltage (V) 400 Single or Multi-Wire ? 3 Conductor Cable
Phase Conductor Wire Size # Conductors per
300 mm2 8
(mm2 or AWG/kcmil) phase (n)
Length - L (ft or m) 80 Conductor Type Copper
Cable Voltage Rating (V) 600 Conduit Type Non-Magnetic
C Value (Metric) 9296
M = 1 / (1 + f) C Value (AWG) N/A
3 phase faults f = 1.73 x L x IL-L-L f Factor 0.1681
VL-L x C x n M Factor 0.8561
1 phase faults f = 2 x L x IL-L
VL-L x C x n Isca x M = fault current L-L = 34,357

Calculation does not include motor contribution

Fault Current from Point-to-Point

Isca at Fault #1 (A) 34,357 Sizing Standard Metric


Fault #1
Voltage (V) 400 Single or Multi-Wire ? 3 Conductor Cable
Phase Conductor Wire Size # Conductors per
300 mm2 1
(mm2 or AWG/kcmil) phase (n)
Length - L (ft or m) 60 Conductor Type Copper
Cable Voltage Rating (V) 600 Conduit Type Non-Magnetic
C Value (Metric) 9296
Fault #2 C Value (AWG) N/A
f Factor 0.9602
M Factor 0.5101
Branch Circuit Panel

Isca x M = fault current L-L = Isca at Fault #2 (A) 20,991

Calculation does not include motor contribution

Fault Current Contribution from Motor


Total Motor HP 600
Motor Voltage (V) 400
Motor Contribution Isca (A) 3464