SINAMICS G110
Warnings, Cautions and Notes Issue 11/04
The Compact version of the Operating Instructions will cover the majority of
typical applications. It is valid for inverters firmware versions 1.0 and 1.1. For
full details please refer to the Operating Instructions and the Parameter List.
WARNING
! ¾ This equipment contains dangerous voltages and controls potentially
dangerous rotating mechanical parts. Non-compliance with Warnings or failure
to follow the instructions contained in this manual can result in loss of life,
severe personal injury or serious damage to property.
¾ Only suitable qualified personnel should work on this equipment, and only after
becoming familiar with all safety notices, installation, operation and
maintenance procedures contained in this manual. The successful and safe
operation of this equipment is dependent upon its proper handling, installation,
operation and maintenance.
¾ The DC link of all SINAMICS G110 modules remains at a hazardous voltage
level for 5 minutes after all voltages have been disconnected. Therefore always
wait for 5 minutes after disconnecting the inverter from the power supply before
carrying out work on any modules. The drive unit discharges itself during this
time.
¾ The mains input, DC and motor terminals carry dangerous voltages even if the
inverter is inoperative, wait 5 minutes to allow the unit to discharge after
switching off before carrying out any installation work.
¾ During the parameter download with the STARTER commissioning tool or
from the BOP to the inverter, the digital output may produce a spurious signal.
Prior to performing a download to the inverter appropriate counter-measures
must be taken to ensure that any suspended load is secured, for example, by
the use of external brakes or the load being lowered to ground level and
secured.
SINAMICS G110
2 Operating Instructions (Compact)
Issue 11/04 Warnings, Cautions and Notes
NOTES
¾ This equipment is capable of providing internal motor overload protection in
accordance with UL508C section 42 (refer to P0610 and P0335). I2t monitoring
is ON by default.
Motor overload protection can also be provided using an external PTC via a
digital input.
¾ This equipment is suitable for use in a circuit capable of delivering not more
than 10,000 symmetrical amperes (rms), for a maximum voltage of 230 V
when protected by an H or K type fuse, a circuit breaker or self-protected
combination motor controller.
¾ Use Class 1 75 °C copper wire only with the cross-sections as specified in
Section 2.1
¾ The maximum permissible ambient temperature is, depending on the
equipment, 40 °C or 50 °C (refer to Section 2.1).
¾ Before installing and commissioning, please read these safety instructions and
warnings carefully and all the warning labels attached to the equipment.
¾ Make sure that the warning labels are kept in a legible condition and replace
missing or damaged labels.
SINAMICS G110
4 Operating Instructions (Compact)
Issue 11/04 Contents
Contents
1 Installation ............................................................................................................... 6
1.1 Clearance distances for mounting ............................................................................ 6
1.2 Mounting dimensions ................................................................................................ 6
2 Electrical Installation.............................................................................................. 7
2.1 Technical specifications............................................................................................ 7
2.2 Power terminals ........................................................................................................ 7
2.3 Control terminals....................................................................................................... 7
2.4 Block diagram ........................................................................................................... 8
4 Communications................................................................................................... 11
4.1 Establishing communications SINAMICS G110 ⇔ STARTER .............................. 11
6 Commissioning ..................................................................................................... 15
6.1 Quick commissioning .............................................................................................. 15
6.2 Commissioning the application ............................................................................... 17
6.2.1 Serial interface (USS) ............................................................................................. 17
6.2.2 Selection of command source ................................................................................ 18
6.2.3 Digital inputs (DIN).................................................................................................. 18
6.2.4 Digital output (DOUT) ............................................................................................. 19
6.2.5 Selection of frequency setpoint............................................................................... 19
6.2.6 Analog input (ADC) ................................................................................................. 20
6.2.7 Motor potentiometer (MOP) .................................................................................... 20
6.2.8 Fixed frequency (FF)............................................................................................... 21
6.2.9 JOG......................................................................................................................... 21
6.2.10 Ramp-function generator (HLG) ............................................................................. 22
6.2.11 Reference / limit frequencies .................................................................................. 22
6.2.12 Motor control ........................................................................................................... 22
6.2.13 Inverter/motor protection......................................................................................... 24
6.2.14 Inverter-specific functions ....................................................................................... 24
6.3 Series commissioning ............................................................................................. 27
6.4 Parameter reset to factory setting........................................................................... 27
SINAMICS G110
Operating Instructions (Compact) 5
1 Installation Issue 11/04
1 Installation
1.1 Clearance distances for mounting
The inverters can be mounted adjacent to each other. If they are mounted on top of
each other, however, a clearance of 100 mm has to be observed.
SIDE OF CABINET ENCLOSURE
15 mm >0 mm 30 mm 15 mm
SINAMICS G110
6 Operating Instructions (Compact)
Issue 11/04 2 Electrical Installation
2 Electrical Installation
2.1 Technical specifications
1 AC 200 - 240 V ± 10 %, 47 - 63 Hz
0AB 11-2xy0* 12-5xy0* 13xy0* 15xy0* 17xy0* 21-1xy0* 21-5xy0* 22-2xy0* 23-0xy0*
Order No. 6SL3211-
0KB 11-2xy0* 12-5xy0* 13xy0* 15xy0* 17xy0* - - - -
Frame Size A B C
Inverter Output kW 0,12 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3,0
Rating hp 0,16 0,33 0,5 0,75 1,0 1,5 2,0 3,0 4,0
Output Current 0.9 1.7 2.3 3.2 3.9 6.0 7.8 11.0 13.6
A (50 °C) (50 °C) (50 °C) (50 °C) (40 ºC) (50 °C) (40 ºC) (50 °C) (40 ºC)
(perm. ambient temp.)
Input Current
A 2.3 4.5 6.2 7.7 10.0 14.7 19.7 27.2 32.0
(230 V)
Recommended A 10 10 10 10 16 20 25 35 50
Fuse 3NA 3803 3803 3803 3803 3805 3807 3810 3814 3820
mm2 1,0 - 2,5 1,0 - 2,5 1,0 - 2,5 1,0 - 2,5 1,5 - 2,5 2,5 - 6,0 2,5 - 6,0 4,0 - 10 6,0 - 10
Input Cable
AWG 16 - 12 16 - 12 16 - 12 16 - 12 14 - 12 12 - 10 12 - 10 11 - 8 10 - 8
mm2 1,0 - 2,5 1,0 - 2,5 1,0 - 2,5 1,0 - 2,5 1,0 - 2,5 1,5 - 6,0 1,5 - 6,0 2,5 - 10 2,5 - 10
Output Cable
AWG 16 - 12 16 - 12 16 - 12 16 - 12 16 - 12 14 - 10 14 - 10 12 - 8 12 - 8
Tightening
Nm
Torque of power 0.96 (8.50) 1.50 (13.30) 2.25 (19.91)
(lbf.in)
terminals
*→ the last digit of the Order No. depends x = A/B → with integrated filter y = A → analog version
on hardware and software changes x = U → without filter y = B → USS version
SINAMICS G110
Operating Instructions (Compact) 7
2 Electrical Installation Issue 11/04
SINAMICS G110
8 Operating Instructions (Compact)
Issue 11/04 3 Factory setting
3 Factory setting
The SINAMICS G110 frequency inverter has already been programmed at the
factory (motor parameters P0304, P0305, P0307, P0310), for standard V/f
applications on Siemens 4-pole asynchronous motors 1LA that have the same
power rating as the inverters
Further factory setting
Command sources P0700 see Section 3.1/3.2
Setpoint source P1000 see Section 3.1/3.2
Motor cooling P0335 = 0 (self-cooled)
Motor current limit P0640 = 150%
Min. frequency P1080 = 0 Hz
Max. frequency P1082 = 50 Hz
Ramp-up time P1120 = 10 s
Ramp-down time P1121 = 10 s
Control mode V/f P1300 = 0 (V/f with linear characteristic)
SINAMICS G110
Operating Instructions (Compact) 9
3 Factory setting Issue 11/04
Bus termination
SIMATIC S7-200
G110 G110 G110
max. 31 SINAMICS
Fig. 3-4 Motor Base Frequency DIP Switch and Bus Termination
SINAMICS G110
10 Operating Instructions (Compact)
Issue 11/04 4 Communications
4 Communications
4.1 Establishing communications SINAMICS G110 ⇔
STARTER
The following optional components are additionally required in order to establish
communications between STARTER and SINAMICS G110:
¾ PC <-> frequency inverter connecting kit (order no 6SL3255-0AA00-2AA0)
¾ BOP, as far as the USS standard settings already kept in the Sinamics G110
shall be changed (order no 6SL3255-0AA00-4BA0)
PC <-> SINAMICS G110 connecting Kit SINAMICS G110
USS settings, refer to Section 6.2.1, Page 17.
STARTER
Menu, Options --> Set PG/PC interface -->
Select "PC COM-Port (USS)" --> Properties
--> Interface "COM1", select a baud rate
NOTE
The USS parameter settings in the SINAMICS
G110 frequency inverter and the settings in
STARTER must match!
SINAMICS G110
Operating Instructions (Compact) 11
5 BOP (Option) Issue 11/04
5 BOP (Option)
5.1 Buttons and their Functions
Panel/ Function Effects
Button
Indicates
The LCD displays the settings currently used by the converter.
Status
Start Pressing the button starts the converter. This button is disabled by default.
converter Activate the button: P0700 = 1 or P0719 = 10 ... 15
OFF1 Pressing the button causes the motor to come to a standstill at the
selected ramp down rate. This button is disabled by default.
Stop Activate the button: P0700 = 1 or P0719 = 10 ... 15
converter OFF2 Pressing the button twice (or once long) causes the motor to coast
to a standstill.
This function is always enabled.
Change Press this button to change the direction of rotation of the motor. Reverse is
direction indicated by a minus (-) sign or a flashing decimal point. Disabled by default.
Activate the button: P0700 = 1 or P0719 = 10 ... 15.
In the " Power-on/Ready" state, when this key is pressed, the motor starts
Jog motor and rotates with the pre-set jog frequency. The motor stops when the button
is released. Pressing this button when the motor is running has no effect.
This button can be used to view additional information.
It works by pressing and holding the button. It shows the following, starting
from any parameter during operation:
1. DC link voltage (indicated by d – units V)
2. output frequency (Hz)
3. output voltage (indicated by o – units V).
4. The value selected in P0005 (If P0005 is set to show any of the above
(1 - 3) then this will not be shown again).
Functions Additional presses will toggle around the above displays.
Jump Function
From any parameter (rxxxx or Pxxxx) a short press of the Fn button will
immediately jump to r0000, you can then change another parameter, if
required. Upon returning to r0000, pressing the Fn button will return you to
your starting point.
Acknowledgement
If alarm and fault messages are present, then these can be acknowledged by
pressing key Fn.
Access Pressing this button allows access to the parameters.
parameters
Increase Pressing this button increases the displayed value.
value
Decrease Pressing this button decreases the displayed value.
value
SINAMICS G110
12 Operating Instructions (Compact)
Issue 11/04 5 BOP (Option)
6 Now access level 3 is set and all level 1 to level 3 parameters are visible to the user.
SINAMICS G110
Operating Instructions (Compact) 13
5 BOP (Option) Issue 11/04
SINAMICS G110
14 Operating Instructions (Compact)
Issue 11/04 6 Commissioning
6 Commissioning
6.1 Quick commissioning
The quick commissioning function will adapt the inverter to the motor and will set
important technological parameters. The quick commissioning can be omitted if a
4-pole 1LA Siemens motor will be used, which matches the rating data of the
frequency inverter.
In order to have access to all motor parameters it is recommended to set the user
access level P0003=3 (see 5.2)
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
START
Factory setting
Commissioning parameter * 0
P0010 = 1
0 Ready
1 Quick commissioning
30 Factory setting
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
Europe/ North America 0
P0100 =...
(enters the default motor base frequency and power
settings hp/kW)
P0100 = 1 0 Europe [kW], frequency default 50 Hz
1 North America [hp], frequency default 60 Hz
2 North America [kW], frequency default 60 Hz
P0100 = 0, 2 NOTE
For P0100 = 0 or 1, the setting of the DIP switch
must be in line with the value of P0100 (refer to the
parameter list).
NOTICE
Motor parameters must be accurately
configured for motor overload protection
to operate correctly above 5 Hz.
230 V
P0304 =... P0304 =... Rated motor voltage P0310 P0304
(Nominal motor voltage [V] from rating
plate)
The rated motor voltage on the rating
plate must be checked, regarding the
star/delta circuit configuration to ensure
that it matches with the circuit
connection configured at the motor
terminal board P0307 P0305
P0308 P0311
FU-spec.
P0305 =... P0305 =... Rated motor current
(Nominal motor current [A] from rating plate)
FU-spec.
P0307 =... P0307 =... Rated motor power
(Nominal motor power [kW/hp] from rating plate)
If P0100 = 0 or 2, value will be in kW. If P0100 = 1, value will be in in hp.
SINAMICS G110
Operating Instructions (Compact) 15
6 Commissioning Issue 11/04
0
P0308 =... P0308 =... Rated motor cosPhi
(Nominal motor power factor (cos ϕ) from rating plate)
If the setting is 0, the value is automatically calculated
P0100 = 1: P0308 no significance, no entry required.
0
P0309 =... P0309 =... Rated motor efficiency
(Nominal motor efficiency in [%] from rating plate)
Setting 0 causes internal calculation of value.
P0100 = 0, 2: P0309 no significance, no entry required.
Rated motor frequency 50.00 Hz
P0310 =...
(Nominal motor frequency in [Hz] from rating plate)
Pole pair number recalculated automatically if parameter is changed.
Rated motor speed FU-spec.
P0311 =...
(Nominal motor speed in [rpm] from rating plate)
Setting 0 causes internal calculation of value.
NOTE
For slip compensation, the input is absolutely necessary.
Motor cooling 0
P0335 =...
(Selects motor cooling system used)
0 Self-cooled: Using shaft mounted fan attached to motor
1 Force-cooled: Using separately powered cooling fan
Motor overload factor 150 %
P0640 =...
(Motor overload factor in [%] relative to P0305)
This defines the limit of the maximum output current as a % of the rated motor
current (P0305).
Selection of command source 2/5
P0700 =...
(see Section 6.2.2 "Selection of command source")
0 Factory default setting
1 BOP (keypad)
2 Terminal
5 USS
Selection of frequency setpoint 2/5
P1000 =...
(see Section 6.2.5 "Selection of frequency setpoint")
1 MOP setpoint
2 Analog setpoint
3 Fixed frequency
5 USS
Min. frequency 0.00 Hz
P1080 =...
(enters the minimum motor frequency in Hz)
Sets minimum motor frequency at which motor will run irrespective of frequency
setpoint. The value set here is valid for both clockwise and anticlockwise rotation.
Max. frequency 50.00 Hz
P1082 =...
(enters the maximum motor frequency in Hz)
Sets maximum motor frequency at which motor will run irrespective of the
frequency setpoint. The value set here is valid for both clockwise and
anticlockwise rotation.
Ramp-up time 10.00 s
P1120 =...
(enters the ramp-up time in s)
Time taken for motor to accelerate from standstill up to maximum motor frequency
(P1082) when no rounding is used.
Ramp-down time 10.00 s
P1121 =...
(enters the deceleration time in s)
Time taken for motor to decelerate from maximum motor frequency (P1082) down
to standstill when no rounding is used
OFF3 ramp-down time 5.00 s
P1135 =...
(enters the fast stop ramp-down time in s)
Defines ramp-down time from maximum frequency to standstill for OFF3
command.
SINAMICS G110
16 Operating Instructions (Compact)
Issue 11/04 6 Commissioning
Control mode 0
P1300 =...
(enters the required control mode)
0 V/f with linear characteristic
2 V/f with quadratic characteristic
3 V/f with programmable characteristic
End of quick commissioning 0
P3900 = 1
(means: the start of the motor calculation)
0 No quick commissioning (no motor calculations)
1 End quick commissioning, with factory reset of all other settings
2 End quick commissioning, with factory reset of I/O settings
3 End quick commissioning, without reset of all other settings
NOTE
For P3900 = 1,2,3 → P0340 is internally set to 1 and the appropriate data
calculated (refer to the parameter list P0340).
P3900=3 is useful in case of motor change
END
End of quick commissioning/ drive setting
If additional functions must be implemented at the drive inverter, use the following
Section "Commissioning the application". We recommend this procedure for
drives with a high dynamic response.
Factory setting
User access level * 1
P0003 = 3
1 Standard (Allows access into most frequently used parameters)
2 Extended (Allows extended access e.g. to inverter I/O functions)
3 Expert (for expert use only)
SINAMICS G110
Operating Instructions (Compact) 17
6 Commissioning Issue 11/04
DIN channel
Kl.6 P24 Function of digital input 0
Debounce time for digital inputs 0 ... 29
0 ... 3 P0701 (1)
Kl.7 0 V P0724 (3)
24 V T 0 0
Function
&
...
29
0V
r0722
r0722
CO/BO: Binary input values
SINAMICS G110
18 Operating Instructions (Compact)
Issue 11/04 6 Commissioning
DOUT channel
Function of digital output 0
0 ... 22
Invert digital outputs
P0731 (5)
0 ... 1
P0748 (0) CO/BO: State of digital outputs
r0747
0 r0747.0
Functions
0
...
1
-1
2
23 DOUT+
24 V DC 50 mA
1
DOUT-
SINAMICS G110
Operating Instructions (Compact) 19
6 Commissioning Issue 11/04
ADC channel
P0757
P0758
P0759
P0760
r0754
KL8 P0753 P0761
+10 V
P1000 = 2
KL9 ADC
A ADC
KL10 scaling dead Setpoint
D zone
r0752
P0704 = x
1
1.7 V
Function
0
3.9 V r0722
r0722.3
SINAMICS G110
20 Operating Instructions (Compact)
Issue 11/04 6 Commissioning
6.2.9 JOG
JOG frequency 5.00 Hz
P1058 =...
Frequency in Hz when the motor is being JOG
jogged in the selected direction of rotation.
f
JOG ramp-up/down time 10.00 s P1082
P1060 =... (f max )
Ramp-up/down time. The JOG ramp-up is
limited by P1058. P1058
t
P1060 P1060
SINAMICS G110
Operating Instructions (Compact) 21
6 Commissioning Issue 11/04
2 Hz
fin
P1091
SINAMICS G110
22 Operating Instructions (Compact)
Issue 11/04 6 Commissioning
V
Linear V/f
Boost voltage
Vmax
Validity range
Vn e
ag ON
(P0304) olt
u tv OFF t
tp
Ou ⏐f⏐
actual VBoost
VConBoost,100 f
V/ )
al = 0 t
m
or 0 P1310 active
N 130
VConBoost,50 (P 1
0 t
f
0 fBoost,end fn f max
(P1316) (P0310) (P1082)
SINAMICS G110
Operating Instructions (Compact) 23
6 Commissioning Issue 11/04
⎛ r0027 ⎞
2 Motor F0011
⎜ ⎟ i2t
⎝ P0305 ⎠ r0034
temp. I_max reduction
t
( i2 t ) reaction
r0021 A0511
P0610
P0310
P0335
P0614
Warning threshold
Flying start 0
P1200 =...
Starts inverter onto a spinning motor by rapidly changing the output frequency of the
inverter until the actual motor speed has been found.
0 Flying start disabled
1 Flying start is always active, start in direction of setpoint
2 Flying start is active if power on, fault, OFF2, start in direction of setpoint
3 Flying start is active if fault, OFF2, start in direction of setpoint
4 Flying start is always active, only in direction of setpoint
5 Flying start is active if power on, fault, OFF2, only in direction of setpoint
6 Flying start is active if fault, OFF2, only in direction of setpoint
Motor-current: Flying start (entered in %) 100 %
P1202 =...
Defines search current used for flying start.relative to rated motor current (P0305)
Search rate: Flying start (entered in %) 100 %
P1203 =...
Sets factor by which the output frequency changes during flying start to synchronize with
turning motor.
SINAMICS G110
24 Operating Instructions (Compact)
Issue 11/04 6 Commissioning
Automatic restart 1
P1210 =...
Configures automatic restart function.
0 Disabled
1 Trip reset after power on
2 Restart after mains blackout
3 Restart after mains brownout or fault
4 Restart after mains brownout
5 Restart after mains blackout and fault
6 Restart after mains brown/blackout or fault
SINAMICS G110
Operating Instructions (Compact) 25
6 Commissioning Issue 11/04
SINAMICS G110
26 Operating Instructions (Compact)
Issue 11/04 7 Displays and messages
Commissioning parameter 0
P0010=30
30 Factory setting
Factory reset 0
P0970 = 1
0 disabled
1 Parameter reset
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically exits the reset menu and sets:
P0970 = 0 : disabled
END
P0010 = 0 : ready
SINAMICS G110
Operating Instructions (Compact) 27
SINAMICS G110 Operating Instructions (Compact)
Regional Contacts
Please get in touch with your contact for Technical Support in your Region for
questions about services, prices and conditions of Technical Support.
Siemens AG
Automation & Drives © Siemens AG 2004
Standard Drives Subject to change without prior notice
Postfach 3269, D – 91050 Erlangen Issue 11/04
Germany
www.siemens.com