18 Chapter 6 PDF
18 Chapter 6 PDF
CHAPTER 6
RESULTS AND DISCUSSION
_____________________________________________________________________
Two modes of tests were conducted; one for calorimeter test for air conditioning purpose and
other test for vapour compressor cycle performance analysis purpose under steady state
conditions. The Data acquisition system (DAQ) scanned all the given input test conditions and
once the steady state achieved, the corresponding scanned data were retrieved and DAQ was to
process the raw data and the make the all necessary system performance parameters calculation.
For calculation of the refrigerant properties for wide range of ambient temperatures which has
(NIST), which provides thermodynamic and transport properties of pure refrigerant and
refrigerant mixtures and also provide the thermodynamic properties of plots and tables.
The results obtained from the both simulated and experimental are compared by fixing the set
values in the calorimeter by choosing the various ambient test conditions. The operating
conditions in the evaporator have been analyses by constant condenser temperature. All the
system components were studied has been balanced for proper mass flow rate through the
capillary tube and through the compressor. For analysis parameters like temperature, pressure,
density, quality, enthalpy, entropy and specific heats of selected refrigerant analyzed and
compared [31&70]. If any two properties are known other required properties can be evaluated
and analyzed for performance comparison both for pure refrigerants and mixture refrigerants.
142
The ultimate effect of the refrigeration load is to influence the parameters are suction and
discharge pressures, return gas temperatures, current drawn power consumed and motor winding
temperature.
The both evaporator (Low Pressure side) and condenser (High Pressure side) pressures should be
positive i.e. above atmospheric pressure and it should be as near to the atmospheric pressure
possible to avoid leakages. Fig. 6.1 the variation of pressures with respect to temperatures, the
trend of pressures and temperatures profiles are nearly same for the refrigerant R32 and R410A.
It is observed that for the evaporator temperature of -10˚C the suction pressure for the R22 is 355
kPa, R410A is 574 kPa and R32 is 583kPa.Too high evaporator and condenser pressures would
4000
3500
3000
2500 R22
2000 R410A
1500 R32
1000
500
0
-10 0 10 20 30 40 50 60
Temperature ˚C
Fig. 6.2 to 6.5 Shows, the Critical properties of selected refrigerants, the Critical temperature of
high pressure. It should be above the condensing temperature of the application. If the critical
temperature of a refrigerant is too near the desired condensing temperature, the excessive power
consumption results.
pressure is the extreme pressure at which a refrigerant can be condensed. The boiling
The high boiling temperatures reduce the capacity of the compressor. Freezing point of the
refrigerant should be well below the operating evaporator temperature. The refrigerant with high
78˚C
80 72˚C
60
40 Critical Temperature˚C
20
0
R22 R410A R32
Refrigerant
5000
Critical Pressure in kPa
4000
3000
1000
0
R22 R410A R32
Refrigerant
Freezing Point ˚C
Boiling Point ˚C
Refrigerant
R22 R410A R32
0
-50
-41˚C
-52.7˚C -51.75˚C
Temperature in˚ C
-100
-150
-160˚C -155˚C
-200
-213˚C
-250
600
Critical Density kg/m3
500
400
300
200
100
0
R22 R410A R32
Refrigerant
capacity, compressor power consumption per ton of refrigeration. The most two important
parameters for the refrigerant compressors the evaporator (suction) pressure and temperature and
condenser pressure and temperature the effect of two parameters on refrigerating capacity are
Fig. 6.6 shows the relation between temperature and density, it is observed that for all the
refrigerants the density decreases with increase in temperature. If the evaporator temperature is
maintained at -10˚C the density of R32 is 1020 kg/ m3, R410A is 1130 kg/ m3 and for R22 is
1247 kg/ m3, the density of R22 is highest among all the refrigerants and lowest for R32.Low
density indicates higher specific volume hence the quantity of refrigerant required in the system
will be more.
146
Fig. 6.7 shows the variation of density as pressure drop takes place in a throttling process, as the
pressure decreases from condenser pressure to evaporator pressure, the liquid density increase.
Hence it enhances the mass flow rate of refrigerant, it is observed from the plot the trend of
density is decreasing as the pressure increases, for evaporator pressure of 500 kPa the refrigerant
R22 can be seen as 1303 kg/ m3, for R410A is 1246 kg/ m3 and for R32 is 1122 kg/m3
1500
1300
Density in kg/m3
1200 R22
1100 R410A
R32
1000
900
800
-10 -5 0 5 10
Evaporator Temperature ˚C
1500
Variation of density for evaporator pressure of 500kPa
1400
Density in kg/m3
1300
1200
R22
1100
R410A
1000
R32
900
800
100 200 300 400 500 600 700 800 900 1000
Pressure in kPa
Low specific heat of liquid refrigerant and high specific heat of vapour refrigerant are desirable
both tend to increase the refrigerant effect per kg of refrigerant, low specific heat of liquid
refrigerant helps in increase sub-cooling of liquid and high specific heat of vapour helps in
increasing the superheating of vapour. Fig. 6.8, shows the various specific heats, it is observed
that the liquid specific heat is moderately same for the R32 and R410A and Vapour specific heat
is very high for the refrigerant 410A.At very high condensing temperature the vapour specific
4
Variation of specific heat with temperature
3.5
3
Specific Heat in kJ/kg-K
2.5
2
R-22
1.5 R-410A
1 R-32
0.5
0
-10 0 10 20 30 40 50 60
Temperature˚C
The specific volume of refrigerant vapour at evaporator temperature indicates the displacement
of compressor. Low volume of refrigerants are being used for reciprocating compressor where as
rotary compressor are used for high specific volume refrigerants. Fig. 6.9 & 6.10 shows the
variation of specific volume at different evaporator and condenser temperatures; from the Fig.
6.9 the trend of specific volume is increases as the evaporator temperature is increases. From the
Fig. 6.10 shows, specific volume decreases as the condensing temperature increases. For
evaporator temperature of +10˚C the specific volume for the refrigerant R22 is 0.0008 m3/ kg,
R32 is 0.00098 kg/m3and for R410A is 0.00088 kg/m3. It is observed that at condenser
temperature of 40˚c the specific volumes for R22, R410a and R32 are 0.0136 kg/m3, 0.015 kg/m3
0.00095
Specific Volume m3/ kg
0.0009
R22
0.00085 R410A
R32
0.0008
0.00075
0.0007
-10 -5 0 5 10
Evaporator temperature ˚C
0.02
Variation of vapour specific volume with condenser temperature
0.018
0.016
Vapour specific Volume in m3 /kg
0.014
0.012
0.01
R22
0.008
R410A
0.006
R32
0.004
0.002
0
35 40 45 50 55 60
Condenser temperature ˚C
The thermodynamic concept involves vapour pressure and latent heat which is called enthalpy of
evaporation. It is the indication of specific internal energy and specific flow work. Fig. 6.11
show the variation of enthalpy with pressure, the enthalpy is very high for the R32 and very low
for R22 refrigerants, for the operating pressure of 800 kPa the enthalpy for R32 is 382 kJ/kg, for
R410A is 280 kJ/kg and for R22 is 255 kJ/kg. With compare to R22 and R410A the R32
enthalpy is 33% and 27% more, this may be a advantage to R32 refrigerant.
150
380
360
340
Enthalpy in kJ/kg
320
R22
300
R410A
280
R32
260
240
220
200
100 200 300 400 500 600 700 800
Pressure in kPa
Entropy, like enthalpy, is thermodynamic property. Fig. 6.12 shows the variation of entropy with
temperature, the entropy decreases for all the refrigerants, however the entropy values for
refrigerant R32 is more with compare to other two refrigerants. It can be seen from the plot, for
the condenser temperature of 35˚c the entropy value 1.29 kJ/kg-K, for R 410A is 0.9656 kJ/kg-K
1.4
Variation of entropy with condensing temperature
1.3
1.2
Entropy kJ/kg-K
1.1 R22
R410A
1 R32
0.9
0.8
35 40 45 50 55 60
Condenser temperature˚C
The selection of compressor depends on the pressure ratio; a good compressor has a volumetric
efficiency of 70 to 80 percent. The advantages of lower pressure ratio refrigerants are lower
lubricating oil temperature, greater capacity. Too high pressure ratios require stronger
refrigerating equipment. The pressure ratio increases when either the evaporator pressure
decreases or the condenser pressure increases. Hence, the mass flow rate through the compressor
decreases with increase in condenser pressure and with decrease in evaporator pressure [75].
Fig. 6.13 shows the variation of pressure ratios for different condenser and evaporator
temperatures for the fixed condenser temperature of 65˚C and for the evaporator temperature
of -5˚C the pressure ratio obtained was 6.29.In all the cases the pressure ratio decreases for fixed
152
condenser temperature and for the evaporator temperature of -5˚C to +5˚C. The pressure should
6.53
Variation of pressure ratio (Pr)
6.03 for fixed condenser temperature
5.53
Pressure ratio
35˚ C
5.03
4.53 40˚ C
4.03 45˚ C
3.53 50˚ C
3.03 55˚ C
2.53 60˚ C
2.03 65˚ C
-6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6
Evaporator Temperature ˚C
The variation Pressure ratio it is the ratio of absolute discharge pressure to the absolute suction
pressure, the absolute discharge pressure is always more than the absolute suction pressure, and
hence the pressure ratio is always more than unity. It is observed from the Fig. 6.14 that; for
evaporator temperature of -10˚C and condenser temperature of 35˚C the pressure ratios for R22,
R410A and R32 are 3.81, 3.72 and 3.75. It observer that both simulated and experimental results
5
Pressure ratio
4 R-410a
R-32
3
R-22
2
0
-10 -5 0 5˚ C 10
Evaporator temperature º C
The performance of the refrigerant depends upon the net refrigerating effect of the system the
typical variation of refrigeration is shown in Fig. 6.15, as the condenser temperature increases
the refrigeration effect is decreasing. If the condenser temperature is at 55˚C, the enthalpy values
for R32 is 204 kJ / kg, R22 is 138kJ/kg and for R410A is122 kJ/kg, the value of R32 is 32.35%
higher than the R22 A refrigerant should have a high latent heat of vaporization at evaporator
temperature. The latent heat results in high refrigerating effect per kg of refrigerant circulated
300
Net refrigeration effect with variation of condenser temperature
Refrigeration effect in kJ/kg
250
200
R-22
150 R-410A
R-32
100
50
35˚ C 40˚ C 45˚ C 50˚ C 55˚ C 60˚ C
Condenser Temperature ˚C
The Fig. 6.16 shows, the latent heats of selected refrigerants operating between the Evaporator
temperature -15˚C and condenser temperature at +30˚C, the refrigerant effect is more for R-32
refrigerant410A, hence refrigerant effect produced for R-32 is high with compare to R-410A,
R-32
Refrigerants
Refrigeration
R-410A Effect(kJ/kg)
Latent
heat(kJ/kg)
R-22
The mass flow rate of refrigerant is depends on the latent heat of refrigerant, i.e. high latent heat
results in high refrigerating effect per kg of refrigerant circulated which reduces they the mass of
refrigerant to be circulated per ton of refrigeration. Fig. 6.17 shows the variation of mass flow
rate for fixed condenser temperature and for the evaporator temperature of -10˚C to +10˚C, for
the condenser temperature of 65˚C and evaporator temperature of 0.0466 kg/s which was very
high. It observed that; if the condenser temperature is high the mass flow required also high.
0.044
35˚ C
0.042
0.04 40˚ C
0.038
45˚ C
0.036
50˚ C
0.034
0.032 55˚ C
0.03 60˚ C
-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10
Evaporator temperature ˚C 65˚ C
The following Fig. 6.18 shows the variation of mass flow rate with different evaporator
temperatures (Suction Pressure), the trend of mass flow rate for all three cases increases as the
evaporator temperature increases, at the same evaporator temperature the mass flow rate is less
for R32 and R410A refrigerants [104]. Mass flow rate required for Refrigerant 22 is high, if the
156
condenser temperature is 54.5˚C and for different evaporator temperature from -10˚C to +10˚C,
the mass flow rate required for R32 is 0.0307 kg/s, for R410A is 0.0408 kg/s and for R22 is
0.0422 kg/s. Hence, the refrigerant which is having lower mass flow rate the system coefficient
0.04
Mass flow rate in kg/ s
0.035
0.03
R22
0.025
R410A
0.02
R32
0.015
0.01
-10 -5 0 5 10
Evaporator temperature in ˚C
0.03
Variation of Mass flow with sub-cooling
0.025
Mass flow in kg/s
0.02
0.015 R-22
R-410A
0.01
R-32
0.005
0
1˚C 2˚C 3˚C 4˚C 5˚C
Degree of Sub-Cool
The following Fig. 6.19, shows the variation of mass flow with sub-cooling; Sub-cooling of
refrigerant is always good [16, 52 & 90]. It is observed that for the condenser temperature with
5˚C sub-cooling the mass flow rate for R32 is very less i.e. 0.0153 kg/s for R410A 0.0217 kg/s
and for R22 are0.0241kg/s. When compare to R22 and R410A refrigerants the R32 mass flow
rate required by 36.5% and 29% less. The sub cooling increases the refrigeration effect; hence
Fig. 6.20 shows, the effect of degree of super heat, superheating of suction vapour is always
good because the degree of super heat serves as means of actuating and modulating capacity of
the expansion valve also dry compression possible. In all the three cases the trend of mass flow
rate decreasing with degree of superheat, for R32 the if the degree of superheat is 5˚C the amount
of mass flow rate required for R32 is 0.0146 kg/s, R22 is0.0225 kg/s and for R410A is
0.0201kg/s, the mass flow rate required for R32 low compare to the other two refrigerants.
0.023
Mass flow in kg/s
R-22
0.021
R-410A
0.019
R-32
0.017
0.015
0.013
1 2 3 4 5
Degree of superheat in ˚C
The discharge temperatures must be moderate to avoid the overheating the coil. Too high
discharge temperatures sometimes not good for superheating the refrigerants because it may
Fig. 6.21 shows the variation of compress discharge temperature; R32 has a significantly higher
discharge temperature than the other investigated refrigerants. Many of the problems associated
with very high maintenance costs were due to high refrigerant temperatures at compressor outlet.
The compressor discharge temperature for R32 is 106˚C, and R410A is 99.24˚C and for R22 is
92˚C .The high discharge temperatures of the compressor may cause the decomposition of the
130
Compressor dischrge Temperature ˚C
Compressor Discharge Temperature ˚C
110
90
R22
70
R410A
R32
50
30
10
-10 0 10
Evaporator temperature˚C
The performance index of any device is the ratio of useful desired output to the amount of work
input; the useful desired output is the refrigeration capacity and work input is the compressor
work [9].For an ideal refrigerant, COP should approach Carnot COP and power consumption
should be minimum. The Fig.6.22 shows the trends of COP variation for range of evaporator
temperature from -5˚C to +5˚C for fixed condenser temperature. Fig. 6.23 shows the variation of
COP, for the constant evaporator and condenser temperatures Te=10˚C & Tc =55˚C) the COP of
the refrigerant R32 is 3.367 and R22 is 2.55 and R410A 2.91. It is observed that for the same
condenser and evaporator temperatures the R32 COP is 24.26 % and 13.57% more with compare
to R22 and R410A.It is also observed that the trend of COP is decreases with decrease in
evaporator temperature.
3.05 35˚ C
40˚ C
3 45˚ C
50˚ C
COP
2.95
55˚ C
2.9 60˚ C
65˚ C
2.85
2.8
-6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6
Evaporator Temperature ˚C
Fig. 6.22 Variation of COP with different evaporator and condenser temperature
160
Fig. 6.24 show the effect of compressor work and the coefficient of performance, the COP of the
system is decreasing as the as the compressor power is increases. It is observed that for 1 TR
capacity the COP of the system for R22, R410A and R32 is 3.12, 3 and 3.3. For the higher
ambient conditions the compressor consumes more power hence the COP of the system
drastically decreases.
2
R410A
1.5
1 R32
0.5
0
-10 0 10
Evaporator temperature˚C
3.5
Variation of COP with Compressor Power
3
2.5 R22
COP
2 R410
1.5 R32
0.5
1 1.5 2 2.5
Power in kW
The refrigeration capacity of a refrigeration system is its cooling capacity or the heat transfer rate
that it can provide for cooling. Compressor capacity decreases with the decrease in evaporator
temperature. Lower the evaporator temperature, the lower is the vaporizing pressure and density
hence the mass of refrigerant circulated per unit time decreases. From the Fig. 6.25 it is observed
that evaporator temperature of -10˚c and condenser temperature of 54.5˚C the cooling capacities
are 3.887kW, 3.538kW and 2.461kW for the refrigerants of R32, R410Aand R22.
7
6
Capacity in kW
R-22
5
R-410A
4
R-32
3
2
1
0
-10 -5 0 5 10
Evaporator Temperature in ˚ C
Compressor capacity decreases with the decrease in evaporator temperature, because of the fact
for the low evaporator temperature, the vaporizing pressure is low and therefore the density of
suction vapour entering the compressor is low [32&61]. Hence the mass of refrigerant circulated
through the compressor per unit time decreases in suction temperature for given piston
displacement. It is always necessary to change the capacity of compressor according to the load
162
on the evaporator otherwise it will be difficult to maintain the required temperature in the
evaporator.
6. 8 Compressor Power
Fig. 6.26 shows the power consumption of selected refrigerants with the decrease in evaporator
temperature, the work of compressor increases and mass of refrigerant circulated per minute
decreases which results in increase of compressor power, it has been observed that the power
consumption for refrigerant 22 is very high where as R32 and R410A consumes low power for
fixed condenser temperature and for different evaporating temperatures.R22 requires 1.76kW
1.9
Compressor Power Consumption
1.7
1.5
Power in kW
1.3
R22
1.1 R410A
0.9 R32
0.7
0.5
-10 -5 0 5 10
Evaporator temperature in ˚C
The rating of any air conditioning system is evaluated in terms of energy ratio, as shown in Fig.
6.27 the energy efficiency ratio plots are in increasing with evaporator temperature for the fixed
condenser temperature and by varying the evaporator temperature the trend of plot increases with
increasing of evaporator temperature. For evaporator temperature of +10˚C, the values of EER
the R22 is 11 Btu/W for R410A is 10 Btu/W and for R32 Btu/W refrigerant is 11.84. EER can be
increased by increasing Cooling capacity and by reducing the compressor power [6&47].
14
12
10
EER in Btu/W
8 R22
R410A
6
R32
4
0
-10 -5 0 5 10
Evaporator Temperatore˚C
Once the test is complete, the output recorded by DAQ, and is tabulated for 5 sets of results can
be obtained and generally results known as Present Values (P.V). The average of all 5 sets will
give the exact output results. The program not only can create a report, but also can be setup
automatically print report at any time. The results obtained as per the requirements of air-
conditioned space and the specified temperatures achieved in the evaporator were illustrated in
following tables.
Tables from 6.1 to 6.6 the input parameters for the test component are given as Set Values (S.V)
like suction and discharge pressure, evaporator temperature, condensing temperature, degree of
sub cooling and superheating, return gas temperature, compressor chamber temperature,
The following present values (P.V) also known as actual values can seen from the calorimeter
test measurements for R22, R410A and R332 refrigerants for different models and they are listed
below.
outlet temperature 8.Air flow, 9.compressor power, 10.Refrigerant mass flow rate,
performance.
165
Table 6.3 Test measurements Refrigerant 410A (Sample 1, Test no 6739) RNA5528BXC
Table 6.4 Test measurements Refrigerant 410A (Sample 2, Test no 6740) RNA5528BXC
Calorimeter Test Report for R410A, Model No. RNA5528BXC
The window air conditioner under test with different capacities has been normalized to 1 TR
“Ton of Refrigeration” capacity for all three refrigerants (R22, R410A and R32) for fixed
condenser and evaporator temperatures and the following performance parameters have been
selected for comparison of both experimental and simulated results from the set values [8, 21,
&71]. Fig. 6.28 shows the experimental suction and discharge pressures at evaporator
temperature of 7.2˚C and condenser temperature of 54.5˚C, the results obtained with respect to
the pressure, from the plot for both the cases i.e suction and discharge pressure are as follows for
R22 suction and discharge pressures 619.9 kPa and 2145 kPa for R410A suction and discharge
pressures 988.4 kPa and 3387 kPa and for R32 the suction and discharge pressures are 1015.8
kPa and 3387 kPa, it is observed that; for all the cases the R32 attains higher suction and
discharge pressures.
The design of condenser and evaporator should be a compromise between economy and safe
operating pressures. The evaporator should normally be sized to ensure that the refrigerant return
to the compressor in completely gases state. The configuration of the condenser and evaporator
is depends on the pressure ratio. Normally in window air conditioner the compression ratio
should be below 4. This is one of the design considerations for developing an air conditioning
system from the Fig.6.29 the pressure ratio for R22 is 3.46, for R410A is 3.42 and for R32 is
3.33.
172
3500
3000 Discharge
Pressures
SET 1
Pressure in kPa
2500
SET 2
2000 Suction
SET 3
Pressures
1500 SET 4
1000 SET 5
500
0
R22 R410A R32 R22 R410A R32
3.47
3.46 Variation of pressure ratio (Pr)
3.45
3.44
Pressure ratio (Pr)
3.43
3.42
Experimental
3.41
Simulated
3.4
3.39
3.38
3.37
R22 R410A R32
refrigerant
The latent heat of any refrigerants determines the mass of circulation required per ton of
refrigeration. High latent’s results in high refrigerant effect per kg of refrigerant circulated. The
173
fig.6.30 shows the quantity of refrigerant charged in the cycle the experimental values for R22 is
0.9 kg, R410A 0.85 kg and for R32 is 0.65 kg. With compare to R22 and R410A the R32
Fig.6.31 shows the amount of mass flow required for 1 “Ton of Refrigeration” (TR) for the R32
required amount of mass flow rate is 0.0302 kg/s, R4410A is 0.0307 kg/s and R22 is 0.032 kg /s.
For the same cooling capacity with compare to R22 and R410A refrigerants R32 is 5.6% and
4%is less.
The measured COP for the refrigerants are plotted and shown in Fig. 6.32 for condenser
temperature of 54.5˚C and evaporator temperature of 7.2˚C, the R32 performs better than R R22
and 410A.COP for R32 is 3.37 where as R22 Cop is 3.11 and for R410A COP is 2.86,
consumption of power also low for R32 refrigerant. As R32 is having more refrigeration effect,
the mass flows rate of refrigerant for R32 also less with compare to R410A [46].
Fig. 6.33 show the Power consumption for selected refrigerants for constant condenser and
evaporator temperature i.e. Tc = 54.5˚C and Te = 7.2˚C. In all the cases the simulated power
required is less than the experimental values. As per experimental analysis per 1 TR capacity the
power consumption for three refrigerants R22, R410A and R32 are 1.122kW, 1.225kW and
1.038 kW, with compare to R22 and R410A, the refrigerant R32 requires 7.84% and 15% less
power.
174
R32
Refrigerant
Experimental
R410A
Simulated
R22
0.03
0.025
Mass flow rate kg/s
0.02
Simulated
0.015
Experimental
0.01
0.005
0
R22 R410A R32
Refrigerant
3.5
Coefficient of Performanc/TR
3.4
3.3
3.2
3.1
COP
3 Simulate
2.9 Experimental
2.8
2.7
2.6
R22 R410A R32
Refrigerant
1.4
Power consumption per TR
1.2
1
Power in kW
0.8
0.6
Simulate
experimental
0.4
0.2
0
R22 R410A R32
Refrigerant
High compression ratio, consequently higher discharge gas temperature, if not controlled by
proper system, may result in oil and refrigerant break down, forming carbon deposits on the
valve plate which results choking of compressor[74&91]. From the Fig. 6.34 the discharge line
temperature for R32 is 112˚C where as R22 is 89.7˚C and R410A is 99.3˚C, with compare to
other two refrigerants R32 discharge temperature 19% and 12% higher. While designing the
system it should be seen that the compressor discharge temperatures should not exceed 130˚C.
SET 5
SET 4
SET 3 R32
R410A
SET 2
R22
SET 1
0 20 40 60 80 100 120
Compressor Discharge Temperature˚C
The condenser is an important device used in high pressure and temperature side of the
refrigeration system. Its function of is to remove the heat of vapour refrigerant. The selection of
condensing depends upon the capacity of the refrigerating system, type refrigerant used,
As shown in Fig. 6.35 for the different set values the condenser temperature for R22 is 53.2˚C,
53.5
53
Condenser Outlet temperature ˚C
52.5
R22
52
R410A
R32
51.5
51
50.5
50
SET 1 SET 2 SET 3 SET 4 SET 5
The Energy Efficiency ratio (EER) is the ratio between the cooling capacity and the power
consumption of the air conditioner, the EER can be increased by increasing Cooling capacity and
by reducing the compressor power. The Fig. 6.36 shows the Energy Efficiency Ratios for R22 is
10.91 Btu/ W, for R32 is 11.79 Btu/ W and for R410A is 10 Btu / W , the EER for the refrigerant
12
Energy efficiency ratio /TR
11.5
11
EER in (Btu/ W)
10.5 Simulate
experimental
10
9.5
9
R22 R410A R32
Table 6.7 & Table 6.8 shows, the different condenser and evaporator temperatures for both
simulated and measured results of selected refrigerants, the performance parameters, like COP,
Cooling capacity and Refrigerant mass flow rate are simulated. It has been observed that; from the
simulation analysis the R32 is yields better Coefficient of Performance with compare to other
refrigerants. The cooling capacity decreases as the ambient temperatures increases, mass flow of
refrigerant is less for R32. It observed that for evaporator temperature of 10˚C and condenser
temperature of 55˚C COP of R22 is 2.901, for R410A 3.134 and for R32 is 3.367. The cooling
capacity for R22 is 4.53kW, forR410a 6.146 kW and for R32 is 7kW.
179
Suction Pressure (Ps) kPa 623.2 993.5 993.48 623.4 992 1015
Discharge Pressure (Pd) kPa 2146.4 3386.2 3386.4 2148 3383 3480
Evaporator Temp. (Te)˚ C 7.1 7.1 7.1 7.1 7.1 7.1
Pressure Ratio (Pr) 3.44 3.408 3.409 3.45 3.41 3.43
Condensing Temperature(Tc)˚ C 54.5 54.5 54.5 54.5 54.5 54.5
Degree of superheat (∆Tsup) 27.9 27.9 27.9 27.9 27.9 27.9
Degree of Sub cooling(∆Tsc) 8.5 8.5 8.4 8.5 8.5 8.5
Return gas Temperature˚ C 35 35 35 35 35 35
Displacement( m3 /hr) 5.89 4.8384 3.9744 5.89 4.84 3.97
Phase Single Single Single Single Single Single
Frequency (Hz) 50 50 50 50 50 50
Compressor voltage(Volts) 230 230 230 230 230 230
Motor rpm 2880 2880 2880 2880 2880 2880
Mass flow rate (kg /s) 0.0324 0.0383 0.0335 0.0375 0.0387 0.023
Capacity (Watts) 5565.2 6848.28 6018.85 5565.2 6848 6018
Compressor power(Watts) 1764 2368.09 2006.08 1676 2255 1907
Volumetric Efficiency (η vol %) 86.04 89.7 95.97 86.04 89.7 89.2
Isentropic Efficiency (η vol %) 65.58 65.13 67.58 65.58 65.1 67.7
EER (Btu/W) 10.91 10 10.79 10.92 10.5 11.83
Coefficient Performance (COP) 3.11 2.886 3.37 3.12 3 3.38
180
Table 6.8 Simulated Results for different condenser and evaporator temperatures
Cond Evapo C.O.P Cooling capacity(kW) Maas flow (kg/s)
enser rator
Temp Temp. R22 R410A R32 R22 R410A R32 R22 R10A R32
. (°C) (°C)
-10 1.9 1.94 1.98 2.64 3.89 4.16 0.021 0.0151 0.015
-10 2.01 2.33 2.55 2.544 3.7 4.04 0.0208 0.0151 0.015
-10 2.01 2.11 2.22 2.44 3.5 3.86 0.0208 0.0151 0.015
-10 2.44 2.46 2.55 2.343 3.31 3.71 0.0208 0.0151 0.015
-10 2.5 2.66 2.77 2.23 3.01 3.54 0.0208 0.0151 0.015
From the Table 6.9 to 6.12 shows the selected appliance details with test report for IDU and
ODU for defined dry bulb and wet bulb temperatures once the specified temperatures are
achieved for IDU (DBT-27˚C; WBT-19˚C) and ODU (DBT-35˚C; WBT-24˚C) [56]. In order to
maintain the conditions stipulated by BIS, suitable equipments for cooling, humidification and
dehumidification are required. To monitor all the above equipments as well as for the recording
of the performance of test, a control panel is to be provided preferably outside. The values are
monitored until they stabilized, once the stabilized the lab view generates the test reports which
When the test is being performed, the attainment of steady state of the system can be checked.
The on-line test conditions for different parameters like discharge pressure, compressor
discharge line temperature, return gas temperature of the compressor; condenser temperature and
evaporator suction pressure can be analyzed with help of DAQ directly with respect to time. All
the graph shows the stabilization time, in all cases the time taken to stabilize within the time
interval of 15 to 25 minutes.
It is observed from the Fig. 6.37 to Fig.6.41 of stabilisation plot that the compressor midle shell
temperature is stabilised within a span of 15 to 20 minutes, where top shell temperature has been
stabilised after 20 minutse and liquid expansion has stabilised after 25 minutes[44].For
compressor suction line , compressor discharge line , condenser outlet temperature, evaporator
outlet temperature , mass flow rate , return gas temperature , sub-cooled liquid temperature ,
super heat vapour refrigerant, suction pressure and discharge pressuresis observed that after
initial steady state conditions which are obtained within 15 to 20 minutes all the above
mentioned parameters have deviation of only 2% to 4% for the entair test period. However
DAQ system takes the mean value of the parameters and records for every 15 minutes.hence
Time in HH:MM:SS
Fig. 6.37 Time response graph of compressor discharge pressure
Time in HH:MM:SS
Fig. 6.38 Compressor Discharge line Temperature
186
Time in HH:MM:SS
Fig. 6.39 Return Gas temperatures
Time in HH:MM:SS
Fig. 6.40 Time response graph of condenser outlet temperatures
187
Time in HH:MM:SS
Fig. 6.41 Time response plot of suction pressure
In order to maintain the conditions stipulated by BIS or ASHRAE for window air conditioning,
the air conditioning equipments and accessories should function properly. With the sophisticated
equipments and automatic controls the following stabilization plots has been obtained for the test
Fig. 6.42 shows the plot of stabilization when the test is being performed the steady state
analysis of the system is to be checked.The DAQ system directly analyses the time response of
various parameters for obtaining steady state. IDU (BDT-27˚C;WBT-19˚C) and ODU (DBT-
188
35˚C; WBT-24˚C). Its observed that for all the plots the parameters initially the steady state is
obtained within 15 to 25 minutes. As the time progress the stability of the values clearly
observed.
Fig. 6.42 Stabilization Control plot screen (indoor wet bulb temperature)