Condensate Recovery Solutions SB S71 02 en
Condensate Recovery Solutions SB S71 02 en
Condensate Recovery Solutions SB S71 02 en
3
c o n d e n s a t e r e c o v e r y s o l u t i o n s
Spirax Sarco offer a complete range of mechanical fluid pumps specifically designed to remove and recover condensate
under all operating conditions, optimising plant efficiency and product quality throughout your plant.
Mechanical fluid pumps are typically installed with a receiver vented to the atmosphere – in what is usually termed an ‘open’
system - where condensate is collected from multiple steam traps and is pumped to the boiler feedwater tank.
Mechanical fluid pumps are best used where multiple condensate sources are present and where it is practical to install
a vent pipe.
TABLE
1” (DN25) 1” (DN25) ●
1 ½”(DN40) 1 ½”(DN40) ●
2” (DN50) 2” (DN50) ● ● ●
Size
3” (DN80) 2” (DN50) ● ●
4” (DN100) 4” (DN100) ●
PMO Maximum operating
13.8 bar g 10.9 bar g 13.8 bar g 13.8 bar g 20.7 bar g
pressure
TMO Maximum operating
198ºC 188ºC 198ºC 198ºC 343ºC
temperature
Maximum
Max 19.3 litres 12.8 litres 12.8 litres 102 litres 60.6 litres
pump discharge/cycle
Maximum nominal capacity
Maximum 5 500 Maximum Maximum Maximum Maximum
(at 8 bar g operating pressure
kg/h 3 300 kg/h 3 300 kg/h 21 000 kg/h 8 000 kg/h
and 1 bar g backpressure)
Note: Pump capacities are only for comparison between pump models. Please refer to product specific technical information sheets
(TI’s) for the full capacities of each model.
spiraxsarco.com
• Intrinsically safe
- versions available for use
in hazardous environments
5
c o n d e n s a t e r e c o v e r y s o l u t i o n s
Condensate
collecting receiver
Condensate
Condensate removal from process vessels and heat exchangers (pump / trap combination, closed system)
Removal of condensate under all pressure conditions ensures stable temperatures. It also prevents bottom end tube corrosion
and potential waterhammer and freezing.
Heat exchanger
Condensate
collecting receiver
spiraxsarco.com
7
c o n d e n s a t e r e c o v e r y s o l u t i o n s
®
The Pivotrol PTF4 high-capacity pump is capable of
pumping up to 40,000 lb/hr in rapid-cycling process
environments and under elevated pressure and
temperature conditions. Designed as a solution to
excessive maintenance and energy consumption
common with high-capacity condensate pumps used
in large commercial and industrial facilities, the PTF4
offers higher performance than conventional technology,
yet in a smaller package.
• Maximum operating pressure of 200 psig (13.8 barg) - high motive pressure increases pumps capacity rating
• Option to install cycle counter - allows energy returned to the boiler house to be monitored
9
c o n d e n s a t e r e c o v e r y s o l u t i o n s
Spirax Sarco’s range of automatic pump traps have been designed to help you achieve optimum performance from all types of
temperature controlled process equipment, by removing condensate under all operating conditions.
Automatic pump traps are typically used to drain a single piece of heat transfer equipment, such as a heat exchanger,
which usually involves fitting a small condensate collecting receiver between the equipment and the pump-trap. Since the
receiver is not vented, this is most often referred to as a closed system.
The equipment is drained under all operating conditions, so it will not be susceptible to waterlogging or stall. The condensate is
usually recovered and returned to the boiler feedwater tank.
Automatic pump traps should be used when the operation of temperature controls on plant equipment such as heat exchangers
can create a ‘stall’ condition, whereby insufficient differential pressure is available for effective condensate discharge.
spiraxsarco.com
Cold air
Waterlogged
The ultimate effect of stall is increased condensate
Steam trap set
• When the steam pressure is sufficient to overcome the total backpressure (including static lift) the pump function will be
inactive. The trap will modulate to match the load and allow smooth condensate discharge.
• When the upstream steam pressure falls below the total backpressure, the pump will automatically detect a rise in
condensate level and discharge the condensate utilising the motive supply, thus preventing waterlogging of the steam space.
Steam
Cold air
Cold air
APT
11
c o n d e n s a t e r e c o v e r y s o l u t i o n s
1½”(DN40) 1” (DN25) ●
2” (DN50) 1½”(DN40) ● ●
PMO Maximum operating pressure 4.5 bar g 13.8 bar g 13.8 bar g 13.8 bar g
TMO Maximum operating temperature 155ºC 198ºC 198ºC 198ºC
Maximum pump discharge / cycle 2.1 litres 5.0 litres 8.0 litres 8.0 litres
Maximum trapping capacity
1000 kg/h 3000 kg/h 7000 kg/h 7000 kg/h
(at 4.5 bar differential pressure)
Maximum pumping capacity
(at 4.5 bar g motive pressure 330 kg/h 620 kg/h 1000 kg/h 1000 kg/h
and 2.5 bar g backpressure)
Note: Pump capacities are only for comparison between pump models. Please refer to product specific technical information sheets (TI’s)
for the full capacities of each model.
Automatic pump traps - Typical installation
13
c o n d e n s a t e r e c o v e r y s o l u t i o n s
Our packaged pumping units (PPU’s) are made to fit directly into your
system with minimal interruption to your process. As the package is
pre-assembled, installation is fast and easy, ensuring you receive the
benefits associated with efficient condensate removal sooner.
• Increased capacity - Standard solution for systems with large condensate return.
spiraxsarco.com
15
spiraxsarco.com
SB-S71-02 ST Issue 1 © Copyright 2015 Spirax Sarco is a registered trademark of Spirax-Sarco Limited