This document provides specifications for various types of on-load tap changers (OLTCs) manufactured by CTR Manufacturing Industries Ltd. It lists technical details like rated voltage, number of steps, oil content, and dimensions for OLTC models ranging from 11kV to 132kV. Optional equipment for some models includes remote tap change control cubicles.

Uploaded by

JNP D
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
416 views3 pages

Short Form Catalogue

This document provides specifications for various types of on-load tap changers (OLTCs) manufactured by CTR Manufacturing Industries Ltd. It lists technical details like rated voltage, number of steps, oil content, and dimensions for OLTC models ranging from 11kV to 132kV. Optional equipment for some models includes remote tap change control cubicles.

Uploaded by

JNP D
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Flange

Shortform Catalogue of Mounted


Tapchangers
GENERAL INFORMATION
Manufactured since 1966, to the design of English Electric / UK. Each Tapchanger is type tested as per IS 8468:1977
Amendment 1-1980 / IEC 60214-1:2003. On Load Tapchanger (OLTC) also suitable for Off-Circuit furnace duty
Application.
Optional equipment includes Remote Tapchange Control Cubicle (RTCC) with indicating apparatus.

11 KV Class : 11 KV Class :

CM 08 Catalogue PMTC. 1016 CM 16 Catalogue PMTC. 1014

Rated Voltage : 11 KV Rated Voltage : 11 KV


Max. steps : 8 Max. steps : 16
Max. step voltage : 300 V Max. step voltage : 300 V
Max. rated current : 200 A Max. rated current : 200 A
Oil content : 210 ltrs. Oil content : 210 ltrs.
Tappings : Linear Tappings : Linear
Flange dimensions : 700 x 700 mm Flange dimensions : 700 x 700 mm
SC withstand : 3.5 K Amps for 3 secs SC withstand : 3.5 K Amps for 3 secs
Weight without oil : 370 Kg Weight without oil : 370 Kg

11 KV Class : 11 KV Class : Dry Type

CL 08 Catalogue PMTC. 1004 CK 16 Catalogue PMTC. 1023

Rated Voltage : 11 KV Rated Voltage : 11 KV


Max. Steps : 8 Max. Steps : 16
Max. Step voltage : 600 V Max. step voltage : 220 V
Max. Rated current : 300 A Max. rated current : 70 A 100 A
Oil content : 410 ltrs. Tappings : Coarse fine / plus - minus
Tappings : Linear Flange dimensions : 1050 x 1285 mm
Flange dimensions : 838 x 827 mm SC withstand : 2 K Amps for 2 secs
SC withstand : 4 K Amps for 3 secs Weight without oil : 470 Kg
Weight without oil : 392 Kg

TAPCHANGER DIVISION PHONE : 020 - 26634281 PMTC. 1012


CTR MANUFACTURING INDUSTRIES LTD. : (020) 26633402/5
NAGAR ROAD, POONA 411014, INDIA FAX : (91) 20 26633425
EMAIL : [email protected] APR 2010
22 KV Class : 22 KV Class :

DM 08 Catalogue PMTC. 1017 DM 16 Catalogue PMTC. 1015

Rated Voltage : 22 KV Rated Voltage : 22 KV


Max. Steps : 8 Max. Steps : 16
Max. step voltage : 300 V 450 V 600 V Max. step voltage : 300 V 450 V 600 V
Max. rated current : 300 A 200 A 150 A Max. rated current : 300 A 200 A 150 A
Oil content : 210 ltrs. Oil content : 210 ltrs.
Tappings : Linear Tappings : Linear
Flange dimensions : 700 x 700 mm Flange dimensions : 700 x 700 mm
SC withstand : 4 K Amps for 3 secs SC withstand : 4 K Amps for 3 secs
Weight without oil : 370 Kg Weight without oil : 370 Kg

33 KV Class : 33 KV Class :

EL 08 Catalogue PMTC. 1001 EN 16 Catalogue PMTC. 1002

Rated Voltage : 33 KV Rated Voltage : 33 KV


Max. steps : 8 Max. steps : 16
Max. step voltage : 1200 V 1000 V 750 V Max. step voltage : 1200 V 1000 V 750 V
Max. rated current : 125 A 200 A 300 A Max. rated current : 125 A 200 A 300 A
Oil content : 410 ltrs. Oil content : 700 ltrs.
Tappings : Linear Tappings : Linear
Flange dimensions : 838 x 827 mm Flange dimensions : 1041 x 1033 mm
SC withstand : 4 K Amps for 3 secs SC withstand : 4 K Amps for 3 secs
Weight without oil : 392 Kg Weight without oil : 589 Kg

33 KV Class : 33 KV Class :

EN 20 Catalogue PMTC. 1007 E0 16 Catalogue PMTC. 1008

Rated Voltage : 33 KV Rated Voltage : 33 KV


Max. steps : 20 Max. steps : 16
Max. step voltage : 1200 V 1000 V 750 V Max. step voltage : 1200 V 1000 V 850 V
Max. rated current : 125 A 200 A 300 A Max. rated current : 100 A 200 A 300 A
Oil content : 700 ltrs. Oil content : 380 ltrs.
Tappings : Linear Tappings : Coarse fine / plus-minus
Flange dimensions : 1041 x 1033 mm Flange dimensions : 1066 x 830 mm
SC withstand : 4 K Amps for 3 secs SC withstand : 4 K Amps for 3 secs
Weight without oil : 589 Kg Weight without oil : 393 Kg

33 KV Class : 33 KV Class :

E0 09 Catalogue PMTC. 1013 EQ 16 Catalogue PMTC. 1006

Rated Voltage : 33 KV Rated Voltage : 33 KV


Max. steps : 9 Max. steps : 16
Max. step voltage : 1200 V 1000 V 850 V Max. step voltage : 1000 V 900 V 750 V
Max. rated current : 100 A 200 A 300 A Max. rated current : 300 A 400 A 500 A
Oil content : 380 ltrs. Oil content : 1200 ltrs.
Tappings. : Linear Tappings : Linear
Flange dimensions : 1066 x 830 mm Flange dimensions : 1498 x 1206 mm
SC withstand : 4 K Amps for 3 secs SC withstand : 5.0 K Amps for 3 secs
Weight without oil : 393 Kg Weight without oil : 728 Kg
52 KV Class : 52 KV Class :

K2Q 05 Catalogue PMTC. 1021 K3Q 05 Catalogue PMTC.

Single Phase Off-Circuit Single Phase Off-Circuit


Rated Voltage : 52 KV Rated Voltage : 52 KV
Max. steps : 5 Max. steps : 5
Max. rated current : 2000 A Max. rated current : 3000 A
Oil content : 1200 ltrs. Oil content : 1200 ltrs.
Tappings : Linear Tappings : Linear
Flange dimensions : 1498 x 1206 mm Flange dimensions : 1498 x 1206 mm
SC withstand : 10 K Amps for 5 secs SC withstand : 15 K Amps for 5 secs
Weight without oil : 728 Kg

66 KV Class : 66 KV Class :

FQ 16 Catalogue PMTC. 1003 FR 16 Catalogue PMTC. 1005

Rated Voltage : 66 KV Rated Voltage : 66 KV


Max. Steps : 16 Max. Steps : 16
Max. step voltage : 1200 V 1000 V 750 V Max. step voltage : 1200 V 1000 V 750 V
Max. rated current : 125 A 200 A 300 A Max. rated current : 125 A 200 A 300 A
Oil content : 1200 ltrs. Oil content : 850 ltrs.
Tappings : Linear Tappings : Linear
Flange dimensions : 1498 x 1206 mm Flange dimensions : 1072 x 1110 mm
SC withstand : 4 K Amps for 3 secs SC withstand : 4 K Amps for 3 secs
Weight without oil : 728 Kg Weight without oil : 580 Kg

66 KV Class : 132 KV Neutral End :

FR 20 Catalogue PMTC. 1009 GQ 16 Catalogue PMTC. 1022

Rated Voltage : 66 KV Rated Voltage : 132 KV


Max. steps : 20 Max. steps : 16
Max. step voltage : 1200 V 1000 V 750 V Max. step voltage : 1200 V 750 V
Max. rated current : 125 A 200 A 300 A Max. rated current : 150 A 300 A
Oil content : 850 ltrs. Oil content : 1200 ltrs.
Tappings : Linear Tappings : Linear
Flange dimensions : 1072 x 1110 mm Flange dimensions : 1498 x 1206 mm
SC withstand : 4 K Amps for 3 secs SC withstand : 3.5 K Amps for 3 secs
Weight without oil : 580 Kg Weight without oil : 728 Kg