1 s2.0 S030142151830692X Main
1 s2.0 S030142151830692X Main
1 s2.0 S030142151830692X Main
Energy Policy
journal homepage: www.elsevier.com/locate/enpol
School of Mechanical and Automotive Engineering, South China University of Technology, Guangzhou, Guangdong 510641, PR China
Keywords: Energy efficiency standards have crucial roles in reducing the energy consumption of room air conditioners
Energy efficiency standards (RACs) in many countries around the world. In this paper, a review of the policy rules of energy efficiency
Room air conditioners standards is presented. The characteristics and rationality for the evaluation metrics in various countries are
Development trends analyzed. The difference between the energy efficiency standards for RACs in China and those for other countries
China
are discussed. The development trends for the energy efficiency standards of Chinese RACs are provided in this
paper. The division of temperature zones, various operation modes and the long-term performance of RACs
should be considered when establishing the energy efficiency standards of RACs. Note that the improvement in
the energy efficiency standards of RACs is a vital measure for energy conservation and environmental protection.
Therefore, the environmental impact of the energy efficiency standards for RACs with refrigerants will become a
major direction in the enhancement of future standards of RACs. Finally, two methods based on a logarithmic
function and a linear function are proposed in this paper, which combine global warming potential (GWP) and
energy efficiency evaluation metrics. This paper will significantly contribute to the formulation and revision of
the energy efficiency standards of RACs and provide guidance to manufacturers of air conditioners.
Abbreviations: ACOP, Annual Coefficient of Performance (W/W); AEER, Annual Energy Efficiency Ratio (W/W); APF, Annual Performance Factor; CC, Cooling
Capacity (W); CFRACs, Constant Frequency Room Air Conditioners; CO2, Carbon Dioxide; COP, Coefficient of Performance (W/W); CSPF, Cooling Season
Performance Factor; CSTE, Cooling Seasonal Total Electricity Consumption; CSTL, Cooling Seasonal Total Load; EER, Energy Efficiency Ratio (W/W); EU, European
Union; GWP, Global Warming Potential; HFC, Hydrofluorocarbons; HSPF, Heating Seasonal Performance Factor; HSTE, Heating Seasonal Total Electricity
Consumption; HSTL, Heating Seasonal Total Load; LTPP, Long-term Pavement Performance; PLF, Part Load Factor; RACs, Room Air Conditioners; SEER, Seasonal
Energy Efficiency Ratio; SCOP, Seasonal Coefficient of Performance; TAPF, Total Annual Performance Factor; Temp, Temperature; VFRACs, Various Frequency Room
Air Conditioners
⁎
Corresponding author.
E-mail address: [email protected] (J. Wu).
https://doi.org/10.1016/j.enpol.2018.10.038
Received 14 June 2018; Received in revised form 3 October 2018; Accepted 22 October 2018
Available online 16 November 2018
0301-4215/ © 2018 Elsevier Ltd. All rights reserved.
J. Wu et al. Energy Policy 125 (2019) 368–383
frequency regulation characteristics of VFRACs, the outdoor environ- environmental impact of GB19577-2004 and GB19576-2004.
ment, cooling and heating load and the using habits should be con- However, the current RACs standards cannot fully satisfy the de-
sidered. In most cases, RACs do not work at the design cooling condi- mand of energy saving and environment protection. Note that minimal
tions. To rate the energy efficiency of RACs, seasonal evaluation metrics comprehensive work has focused on the analysis and development
were adopted in energy efficiency standards. In early 1975, the seasonal tendency of the energy efficiency standards of RACs. The rationality
energy efficiency ratio (SEER) and heating seasonal performance factor and problems encountered in the energy efficiency standards of RACs
(HSPF) were defined by American scholars, which can be expressed need to be discussed. In this paper, the global development of the en-
according to the following equations: ergy efficiency standards of RACs is reviewed. The characteristics of the
standards for RACs and the difference among China and other countries
CSTL 1
SEER = are analyzed. In addition, two methods—the first method is based on a
CSTE 2 (1)
logarithmic function, and the second method is based on a linear
HSTL function—which combine the refrigerant global warming potential
HSPF = (GWP) value with the energy efficiency standards of RACs, are pro-
HSTE (2)
posed. The development tendency and improvement of Chinese RACs
The comprehensive calculation method, which is described by standards are suggested for future revisions. This paper will contribute
American standards AHRI 210/240, enables the assessment of these to the revised standards for policy makers and the enhancement of air
efficiency metrics, which considers the effect of temperature and energy conditioners for manufacturers to save energy and mitigate greenhouse
load variations on performance. Compared with nominal energy effi- gas emission.
ciency, seasonal energy efficiency does not consider the rated operating
condition in isolation but also considers the high-temperature condi-
2. Review of energy efficiency standards for RACs in the world
tion, low-temperature condition and intermittent condition. The change
in room cooling and heating load is expressed by a linear function. The
2.1. Chinese standards
difference in the using habits is reflected by the running times of RACs
for different ambient temperatures. To reflect the on-off energy losses of
Regarding standards for CFRACs, GB/T 7725 Room air conditioners
RACs, the part load factor (PLF) and the degradation coefficient (CD ) are
was established and revised to evaluate the performance of CFRACs.
considered. Although the calculation of the energy efficiency of RACs
GB12021.3 The minimum allowable value of the energy efficiency and
becomes complex with the consideration of previously mentioned fac-
energy efficiency grades for room air conditioners was proposed to regulate
tors, the characteristics of various frequency, on-off energy losses and
the test method of power consumption and the allowable minimum
the differences in cooling and heating load can be accurately reflected
performance coefficient of CFRACs. In these standards, the EER is ap-
to ensure that seasonal energy efficiency metrics become the most
plied to evaluate the performance of CFRACs. In addition to setting the
important standards for evaluating whether the performance of RACs
minimum efficiency threshold of RACs, the classification requirements
are excellent.
for the established Energy Information Label are also included in
In 2006, Japan passed the second Japanese Top Runner Program,
Chinese standards for RACs. The Chinese Energy Information Label is
which adopted the annual performance factor (APF) as an energy effi-
similar to the Australian and EU energy labels.
ciency evaluation metric of RACs. The APF can be formulated as fol-
The latest CFRACs standard GB 12021.3–2010 (GB 12021.31-2010,
lows:
2010b) stipulates that the EER is the energy efficiency evaluation me-
CSTL + HSTL tric for CFRACs. Compared with the previous standard GB 12021.3-
APF =
CSTE + HSTE (3) 2004, GB 12021.3–2010 has reduced the energy efficiency grades from
5 grades to 3 grades and improved the threshold energy efficiency
Compared with seasonal evaluation metrics, a comprehensive con-
grade, which can be stated as follows: for packaged air conditioners, the
sideration of cooling energy efficiency and heating energy efficiency in
allowable EER has been increased from 2.3 to 2.9; for split air condi-
an entire year is proposed by the APF (Zhu et al., 2015); GB 12021.3-
tioners whose rated cooling capacity (CC) is less than 4500 W, the en-
2010 (GB 12021.3-2010, 2010a), which reflects the annual perfor-
ergy efficiency grade allowed to enter the market has been improved
mance of RACs. The redundancy of evaluating the same RAC by SEER
from grade 5 (EER is 2.60) to grade 3 (EER is 3.20), with an increase in
and HSPF can be avoided by the application of the APF, especially for
the allowable energy efficiency to 23%. The new energy efficiency
heat pump RACs. The evaluation metrics are simplified to ensure their
grades for CFRACs are listed in Table 1.
understanding by consumers. Therefore, the APF has been extensively
The energy efficiency standards for RACs have been improved with
applied by various RACs standards, including standards in China,
the advent and development of VFRACs. Therefore, the APF, which uses
Japan, America and the ISO.
a “two point” method in the cooling season and a “three point” method
In conclusion, the energy efficiency standard is not the single test
in the heating season is adopted to evaluate VFRACs. The first standard
result of energy efficiency for RACs in standard operating conditions.
GB 21455-2008.The minimum allowable values of the energy efficiency and
The annual operating consumption, in which the ambient temperature
energy grades for variable speed room air conditioners (GB 21455-2008,
difference, energy consumption in active mode and standby mode, and
2008) was issued in 2008. In this standard, the SEER, which is divided
long-term performance of RACs are included, should be considered.
into 5 grades, is applied to be the evaluation index of VFRACs. Grade 1
Research has been performed to evaluate the energy savings and the
environmental impact on the energy efficiency of RACs. Lin and
Table 1
Rosenquist (Lin and Rosenquist, 2008) considered that Chinese stan- Energy efficiency grade specifications for CFRACs in GB 23021.3-2010.
dards for RACs (with the first tier going into effect on March 1, 2005
and the second tier taking effect on January 1, 2009) are expected to Category Rated cooling capacity CC Energy efficiency grades EER W/
(W) W
yield cumulative national energy savings greater than 330 billion kWh
that translate into a reduction of carbon emissions from power plants by 3 2 1
323 million tons of CO2 by 2020. Yu and Tang (Yu and Tang, 2015)
investigated the electricity savings and CO2 emission reduction from Single-package 2.90 3.10 3.30
Split CC≤ 4500 3.20 3.40 3.60
RACs for the period 2005–2015 in China. They suggested that the
4500 < CC≤ 7100 3.10 3.30 3.50
standards should be revised every 4 or 5 years. Lu (Lu, 2007) estab- 7100 < CC≤ 14,000 3.00 3.20 3.40
lished a mathematic model to evaluate the potential energy savings and
369
J. Wu et al. Energy Policy 125 (2019) 368–383
Table 2
Distribution of cooling hours within the cooling season temperature bins (GB 21455-2008, 2008).
Temp 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 Total
(°C)
is the highest efficiency level, and grade 5 is the lowest efficiency level. Table 4
Grade 2 is the certification requirement for the energy conservation Energy efficiency grades for single-cold VFRACs (GB 21455-2013, 2013).
label. Grades 3 and 4 represent the average efficiency of the products. Type Cooling Capacity/W SEER/[(W h)/(W h)]
Grade 5 is a benchmark for air conditioning equipment that enters the
market (Wei, 2007). The distribution of cooling hours within the Energy efficiency grades
cooling season temperature bins has been presented in GB 21455-2008
Grade 1 Grade 2 Grade 3
and is listed in Table 2.
In 2013, the latest standard GB 21455–2013 Minimum allowable Split CC≤ 4500 5.40 5.00 4.30
values of the energy efficiency and energy efficiency grades for variable 4500 < CC≤ 7100 5.10 4.40 3.90
speed room air conditioners (GB 21455-2013, 2013) was issued to replace 7100 < CC≤ 14,000 4.70 4.00 3.50
GB 21455-2008. This standard stipulates that SEER and APF are applied
as the energy efficiency metrics for single-cold RACs and heat pump
Table 5
RACs, respectively. Compared with GB 21455-2008, GB 21455-2013
Energy efficiency grades for heat pump VFRACs (GB 21455-2013, 2013).
has added heating hours within the heating season temperature bins
(Table 3) and further improved the benchmark for air conditioning Type Cooling Capacity/W HSPF/[(W h)/(W h)]
equipment that enters the market. The energy efficiency grades have
Energy efficiency grades
reduced from five grades to three grades, where grade 2 is defined as
the energy-saving level for VFRACs in this new energy efficiency grade. Grade 1 Grade 2 Grade 3
Tables 4 and 5 present the allowable value of the SEER and the al-
lowable value of the APF, respectively. Split CC≤ 4500 4.50 4.00 3.50
4500 < CC≤ 7100 4.00 3.50 3.30
The testing methods are a continuation of the “two point” method
7100 < CC≤ 14,000 3.70 3.30 3.10
and the “three point” method, as presented in GB/T 7725 2004 Room
air conditioners. The “Two-point” method tests the cooling capacity and
cooling power input in the rated operating condition when the com- 2006; Wu, 2013). In this standard, the cooling season performance
pressor operates with rated capacity and half capacity in the cooling factor (CSPF), HSPF and APF are applied as the evaluation metrics of
season. The “three-point” method tests the heating capacity and the RACs, and the testing method is also presented in this standard.
heating power input when the compressor is at rated capacity and half In the calculation of CSPF and HSPF, Japan is divided into 5 regions.
capacity for not only the high-temperature operating condition but also In the cooling season, the temperature zones and cooling time are di-
the low-temperature operating condition when the compressor is at vided according to a unified region with 15 temperature zones from
rated capacity in the heating season. In addition, −8.5 °C~5.5 °C is 24 °C to 38 °C. In the heating season, the second and third regions are
defined as the frosting interval, where the heating capacity of RACs will merged into the cold zone, and the fourth and fifth regions are merged
significantly degrade. Throughout these testing methods, the cooling into the temperate zone. Each zone has independent heating hours. The
and heating hours and the energy efficiency (SEER, HSPF and APF) of heating temperature in the cold zone ranges between −14 °C and 16 °C,
RACs can be easily calculated. whereas the heating temperature in the temperate zone ranges from
−-6 °C to 16 °C.
2.2. Japanese standard In the current Japanese RACs standard JISC 9612:2013 Room air
conditioner (JISC 9612:2013, 2013), two calculating methods for the
Japan has been performing research on seasonal evaluation metrics. energy efficiency metrics of RACs were proposed. The first calculating
The testing and calculation methods of SEER were inserted in the ap- method is the “two-point” method, which is based on the temperature
pendix of Japanese standards in 1994. JISC 9612 and JAR 4046 were bins in Tokyo (JISC 9612 Tokyo). The second calculating method is the
formed after a large number of modifications (Li and Cheng, 2008). “three-point” method, which is based on the average temperature bins
JISC 9612 is a comprehensive standard that addresses thermal perfor- in Japan (JISC 9612 Japan). The “three-point” method adds the cooling
mance, safety, noise, and test procedures. Consistent with international and heating tests for the lowest capacity condition to enhance the
standards, the independent standard JISB 8615 was launched to reg- precision compared with the “two point” method. By these two testing
ulate the test procedures of RACs according to ISO 5151 in 1999. Prior methods, the APF can be calculated to evaluate the performance of
to 2006, the evaluation metrics of RACs in Japan primarily comprised RACs. The testing and calculating methods in JISC 9612:2013 are si-
seasonal power consumption. In September 2005, JRA 4048 and JRA milar to those in GB/T 7725-2004. The main difference between the
4055 were combined to become the new standard JRA 4048:2006 methods pertains to the cooling/heating hours in the cooling/heating
Annual performance factor of package air conditioners (JRA 4048:2006, season, which are listed in Table 6. The weighted mean temperature in
Table 3
Distribution of heating hours within the heating season temperature bins (GB 21455-2013, 2013).
Temp -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Total
(°C)
370
J. Wu et al. Energy Policy 125 (2019) 368–383
Table 6 Table 7
Weighted mean temperature in cooling and heating seasons in China and Japan. Representative cooling and heating load hours for each generalized climatic
region (ANSI/AHRI 210/240-2008, 2008).
GB/T 7725–2004 JISC 9612:2013
Region I II III IV V VI
Weighted mean temperature in heating 4.31 °C 8.84 °C
season CLHR/h 2400 1800 1200 800 400 200
Weighted mean temperature in cooling 29.62 °C 27.09 °C HLHR/h 750 1250 1750 2250 2750 2750
season
the cooling season in JSIC 9612:2013 is lower than that in GB/T 7725- where
2004, whereas the weighted mean temperature in heating season is the
opposite. APFR ——representative regional annual performance factors.
CLHR ——representative cooling hours for each generalized climatic
region (Table 7), h.
2.3. American standards QCk (95)——space cooling capacity of the unit as determined from the
A or A2 Test, Btu/h.
The seasonal energy efficiency ratio was proposed in ASHRAE 58 HLHR ——representative heating hours for each generalized climatic
(ANSI/ASHRAE 58-1986 (RA 2014), 2014) first. ANSI/AHRI 214/240 region (Table 7), h.
Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump DHR ——design heating requirement used to determine the HSPF,
((ANSI/AHRI 210/240-2008, 2008)) stipulates the performance re- Btu/h.
quirements and test methods of fixed frequency air conditioners and C ——0.77, a correction factor that tends to improve the agreement
variable speed air conditioners. Particularly, the calculation method of between the calculated building load and the measured building
SEER was presented. This standard has laid a foundation for the de- load, dimensionless.
velopment of variable-speed air conditioners and promoted the devel-
opment of RACs standards in the majority of the countries. In the process of calculating the APF, the influence of the cooling
In American RACs standards, the “two-point” method and the “three and heating hours in different regions is carefully considered. The de-
point” method are applied to evaluate the energy efficiency of CFRACs sign heating requirement instead of the heating capacity is used to
in the cooling season and the heating season, respectively. The “five- determine the HSPF for different operating conditions. This method can
point” method is applied to evaluate VFRACs in both the cooling season reduce the complexity of calculating the APF and the precision of the
and the heating season. In particular, two testing conditions—the high- results. As shown in Table 7, using one region to unify the cooling and
temperature and low-temperature conditions when RACs operate with heating hours is difficult due to the large difference among the various
the lowest capacity—are added to the “five point” method. The APF is regions. Therefore, the method of distinguishing the regions adopted in
calculated by combining these test methods and the cooling/heating the American standard can veritably reflect the annual performance for
hours, which vary between areas. In ANSI/AHRI 214/240–2008 (ANSI/ RACs in actual operation.
AHRI 210/240-2008, 2008), the calculating methods of SEER, HSPF In addition, the DOE replaced the EER with the combined energy
and APF, which are similar to those in GB/T 7725-2004, are proposed. efficiency ratio (CEER) in the energy efficiency assessment of window
The main difference among these methods pertains to the heating hours air conditioners in regulation 10 CFR PART 430 (10 CFR PART 430).
within the heating season temperature bins. In the heating season, The measured standby/off-mode power consumption is added to the
America is divided into 6 zones, where the outdoor design temperature CEER compared with the EER. The minimum CEER value of window air
and heating hours are independent in the calculation of the HSPF conditioners is specified in Energy Star Program Partner Commitments and
(Fig. 1). In the cooling season, the weighted average cooling hours Eligibility Criteria for Room Air Conditioners (ENERGY STAR), which is
throughout America are adopted to calculate the SEER. the threshold for products that enter the market.
Although the calculating methods of the SEER and HSPF are similar
to those in GB/T 7725-2004, some difference exists in computing the
APF according to the following expressions: 2.4. European Union (EU) standards
CLHR QCk (95) + HLHR DHR C
APFR = The energy efficiency of RACs was characterized by the EER and
CLHR QCk (95) HLHR DHR C
SEER
+ HSPF (4) COP in EU standards first. Then the standard was updated with two
seasonal performance metrics: SEER and SCOP (seasonal coefficient of
performance) (Grignon-Masse et al., 2011). Although the SEER and
SCOP are applied to evaluate the performance of RACs, the effects of
temperature and energy load variations on performance and electricity
consumption in various modes are also considered. European seasonal
efficiencies are used to evaluate the average energy efficiency of air
conditioners. In 2012, BS EN 14825-2012 Air conditioners, liquid chilling
packages and heat pumps, with electrically driven compressors, for space
heating and cooling-Testing and rating at part load conditions and calcu-
lation of seasonal performance ((BS EN 14825-2012, 2012)), which
presents the calculating methods of the SEER and SCOP, was issued.
These two metrics can be formulated as
QC
SEER = QC
SEERon
+ HTO × PTO + HSB × PSB + HCK × PCK + HOFF × POFF
Fig. 1. Distribution of heating hours within heating season temperature bins in (5)
America (ANSI/AHRI 210/240-2008, 2008).
371
J. Wu et al. Energy Policy 125 (2019) 368–383
SCOP =
Qh two metrics can be calculated using the following equations in the is-
Qh
+ HTO × PTO + HSB × PSB + HCK × PCK + HOFF × POFF sued AS/NZS 3823.2:2013 Performance of electrical appliances—Air
SCOPon
conditioners and heat pumps Part 2: Energy labeling and minimum energy
(6)
performance standards (MEPS) requirements ((AS/NZS 3823.2:2013,
where 2013)) in Australia in 2013.
Table 8
Minimum requirements for air-to-air heat pumps and air conditioners at rated capacity (MEPS).
Greenhouse and Energy Minimum Standards (GEMS) product class Product description Minimum AEER/ACOP
372
J. Wu et al. Energy Policy 125 (2019) 368–383
373
J. Wu et al. Energy Policy 125 (2019) 368–383
Table 11
Summary of international RAC standards.
Standard category Test Performance calculation method standard Energy efficiency standard Energy efficiency index
method standard
250
are substantially longer than the cooling hours in Japan due to the Table 12
smaller territory and higher latitude. Zero-load base temperature for Chinese, Japanese and American RAC stan-
dards.
Formula (11) (Qi and Li, 2011) and formula (12) (Wang, 2013)
provide the calculation equations of the APF in Japan and China, re- Cooling season Heating season
spectively. These formulas indicate the difference in the weights of the
China 23 °C 17 °C
rated condition, middle-temperature condition and low-temperature
Japan 23 °C 17 °C
condition due to the different climates between Japan and China. The America 18.3 °C 18.3 °C
RACs in Japan primarily operate in the middle-temperature, which
374
J. Wu et al. Energy Policy 125 (2019) 368–383
Table 13
Test procedure differences between EN 14825-2010 and GB/T 7725-2004.
Parameter EN 14825-2010 GB/T 7725-2004
specified. The speed of the compressor is determined according to the considerable difference exists in each temperature zone, and a central
percentage of building load, and the outdoor temperature varies with heating system is extensively employed in most cities in northern China
the speed of the compressor. The differences in the testing methods (Fig. 5):
between the Chinese standards and the EU standards are primarily re- Due to extremely low temperatures in the majority of the areas
flected in the outdoor temperature and the setting point of the com- north of the Qinling Mountains and the Huaihe River, a central heating
pressor speed. system is extensively employed to maintain room temperature in the
For the Chinese standards, only active mode is considered, whereas winter. Regarding the differences in climate, the heating season varies
inactive mode is considered in the EU, Australian and ISO standards. among cities in China. The heating season in the “cold” zone extends
For EU standard BS 14825, additional operating modes, including from November 15 to March 15, whereas the heating season in the
thermostat off mode, standby mode, crankcase heater mode and off “severe cold” zone ranges from mid-October to mid-April of the fol-
mode, are considered. In EN 14825, the standby energy consumption lowing year. In Fig. 5, six cities with central heating systems represent
and inactive mode energy consumption of a VFRAC are 0.0020 kW/24 h different climates. Zhengzhou, Shijiazhuang and Beijing are in the
and 0.0296 kW/24 h respectively. The SEER is 8.56 if inactive mode is “cold” zone, whereas Xining, Changchun and Harbin are in the “severe
considered; otherwise, the SEER is 9.57. cold” zone. As shown in Fig. 5, when the use of central heating starts in
October and November, the temperature ranges from 4 °C to 8 °C in the
“severe cold” zone and the “cold” zone. The green shadow represents
4. Development trends for Chinese RACs standards the average monthly temperature when the use of central heating starts.
The use of central heating starts from 4 °C to 8 °C in the “severe cold”
4.1. Combination of temperature zone and standards and “cold” zones.
The outdoor environment can produce an effect on the operating
The equation of the APF indicates that the cooling and heating times time and the calculation of the APF. Therefore, two suggestions for
are key factors for the final value. In the EU and American standards, a Chinese RACs standards are described according to the previously dis-
country is divided into several regions, in which each region has in- cussed characteristics:
dependent heating hours in the heating season. Conversely, for the
Chinese standards, the same operating time is applied to represent the (1) The cooling hours should be divided into the “hot summer and
climate characteristics in China. This method does not reflect the dif- warm winter” zone and the non-“hot summer and warm winter”
ference between the energy efficiency and the consumption of RACs in zone when calculating the SEER;
different regions in China due to the variation in climates and habits. (2) The heating hours should be divided into the “hot summer and
The annual cooling times and heating times of RACs in different tem- warm winter” zone, “hot summer and cold winter” zone, “mod-
perature zones obtained by investigating hundreds of typical air con- erate” zone and “central heating” zone. For the “central heating”
ditioners in 6 representative cities in China during the process of setting zone, the time when RACs operate below 15 °C, as regulated in
VFRACs standard GB21455-2013 are shown in Fig. 4. Chinese standards, is not applied as long as the heating hours. The
China has five major climate zones which can be distinguished temperature 6 °C, which is the average value of 4 °C and 8 °C, is
based on the average outdoor air temperatures of the coldest and hot- adopted as the ending heating temperature, and 15 °C remains as
test months (Yan and Hong, 2017): the severe cold zone (average the starting heating temperature, as regulated in Chinese standards.
temperature of the coldest month is less than 10 °C and that of the The operating time between these two temperatures is used as the
highest month is less than 25 °C), the cold zone (average temperature of heating hours for “central heating” zone.
the coldest month ranges from −10 °C to 0 °C and that of the highest
month ranges from 18 °C to 28 °C), the hot summer and cold winter
zone (average temperature of the coldest month ranges from 0 °C to 4.2. Combination of RACs long-term performance and standards
10 °C and that of the highest month ranges from 25 °C to 30 °C), the hot
summer and warm winter zone (average temperature of the coldest In other fields, the long-term performance has been directly linked
month is higher than 10 °C and that of the highest month ranges from to standards, such as road, bridge, and composite materials. For road
25 °C to 29 °C), and the moderate zone (average temperature of the and bridge construction, scientific researchers and administrative de-
coldest month ranges from 0 °C to 13 °C and that of the highest month partments have considered research on long-term performance. More
ranges from 18 °C to 25 °C). In these 6 cities, Guangzhou is in the “hot than 20 countries have participated in the long-term pavement per-
summer and warm winter” zone; Chengdu, Wuhan and Shanghai are in formance (LTPP) international research scheme. In China, GB/T 50082-
the “hot summer and cold winter” zone; and Qingdao and Beijing are in 2009 (GB/T 50082-2009, 2009) has been issued to limit the long-term
the “cold” zone. The climate condition has a significant effect on the performance and durability performance of concrete. The noise gener-
operating times of RACs. However, the zones based on operating time ated by the friction between the road surface and the tires will increase
differ from traditional temperature zones, which can be described as with the length of driving time. Therefore, the EU has passed BS EN
follows: for cooling hours, the operating times of RACs in the “hot 14389-2-2004 (BS EN 14389-2-2004, 2004) and DIN EN 14389-2-2004
summer and warm winter” zone is very long with minimal differences (DIN EN 14389-2-2004, 2004) to regulate the change in road traffic
among the remaining temperature zones; for heating hours, a noise. In the area of composite materials, both dynamic mechanical
375
J. Wu et al. Energy Policy 125 (2019) 368–383
500 500
400 400
300 300
200 200
100 100
0 0
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Temperature(°C) Temperature(°C)
500 500
400 400
300 300
200 200
100 100
0 0
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Temperature(°C) Temperature(°C)
500 500
400 400
300 300
200 200
100 100
0 0
-10 -5 0 5 10 15 20 25 30 35 40 -10 -5 0 5 10 15 20 25 30 35 40
Temperature(°C) Temperature(°C)
properties and static mechanical properties are relevant to time, such as the use of the device; thus, establishing long-term performance stan-
the phenomenon of creepage and fatigue under long-term loads. dards in different areas is critical.
America has issued ANSI/UL 746B-2013 to evaluate the long-term The design life-span for RACs is usually 8–10 years. During its
performance of polymeric material. ISO (ISO 10467-2004, 2004) and running period, the performance of the main components after a long
ASTM have also passed several standards (ASTM D2992, 2006) (ASTM operation will decline, such as a decline of cooling capacity and energy
D5365, 2006) to predicate material properties via the long-term testing efficiency due to wear of the compressor, the leakage of refrigerant, the
of data using the method of linear regression to redesign its structure. fatigue of the fan blade, and the attenuation of heat transfer perfor-
The original performance of a device will changed with an increase in mance (Ahn et al., 2003). CQC 9202-2012 The technology requirements
376
J. Wu et al. Energy Policy 125 (2019) 368–383
35 Zhengzhou Xining
30 Shijiazhuang Changchun
Beijing Harbin
25
20
central heating central heating
15
Temperature(°C)
10
5
0
-5
-10
-15
-20 central heating central heating
-25
-30
0 1 2 3 4 5 6 7 8 9 10 11 12
Month
Fig. 5. Temperature distribution of central heating system in China.
and a decline in the performance of RACs. These RACs have been tested
in the rated cooling condition, high-temperature condition, rated
heating condition and low-temperature condition. To ensure the re-
Fig. 6. Surface of condenser. presentation and omnipotence of the testing results, the chosen units
377
J. Wu et al. Energy Policy 125 (2019) 368–383
4.0
decrease value of APF
3.5 APF after using
3.0
2.5
1.5
1.0
0.5
0.0
ho an
ng g
n
Ku ing
Sh ing
Be i
N ou
Sh ning
ng
ng
a
na
gh
Xi
ya
qi
zh
j
j
nm
i
an
Ji
an
an
ng
en
N
ua
C
G
Fig. 11. Decrease in APF for RACs in 10 cities.
Guangzhou, Nanning and Shenyang have the same service time, the
average attenuation rate of the performance in Beijing and Shenyang is
larger than that in Guangzhou and Nanning. As shown in Fig. 11, the
APF of the RACs in Beijing demonstrate the largest decrease, followed
by Shenyang. The main reason is the significant difference in climate
and air quality between the northern and southern regions. Beijing and
Shenyang are located in northern China, whereas Guangzhou and
Nanning are located in southern China. The air quality in northern
Fig. 9. Wind turbine of indoor unit. China is worse than that in southern China with a greater amount of
dust and haze; thus, the outdoor units of RACs are prone to gather dirt,
which contributes to a decline in performance.
60%
rated cooling Service life If the energy efficiency in the factory state is always adopted in RAC
rated heating standards, air conditioner manufacturers will focus on the factory
Attenuation rate of performance
10
50%
performance and disregard the abrasion of the compressors, the leakage
high-temp cooling
low-temp heating
8 of refrigerants, the distortion of fans and the decline in the performance
Service life (year)
40%
of the heat exchangers. In the long term, this approach will not favor
6 the development of energy savings and environmental protection. In
addition, Wu (Wu et al., 2015) et al. proposed a comprehensive eva-
30%
4 luation of long-term performance for RACs (Eq. (13)), which is sim-
20%
plified using the method of a BP neural network. The comprehensive
2 evaluation is simplified as the weighted energy efficiency value for
10% different operating conditions (Eq. (14)).
0
APFo
0% =
APFn (13)
ho ian
u a ijing
n
Ku ing
Sh ing
Be i
N ou
ng
ng
Sh n i n g
a
na
gh
ya
zh
qi
X
j
nm
an
Ji
an
an
ng
en
ng
where
N
C
G
Fig. 10. Long-term performance of RACs in 10 cities. ——synthetical evaluation of long-term performance of RACs.
o——subscript, long-term operating state.
n ——subscript, factory state.
are distributed among 10 cities in each temperature zone. The testing
= 0.187EERr + 0.312EERh + 0.298COPl + 0.203COPr (14)
results and comparison with the factory performance (one unit per city)
are shown in Fig. 10. where
The varying degree of performance degradation were observed after
long-term use; the performance of the RACs demonstrated a substantial EERr ——the retention rate of energy efficiency for rated cooling
decrease with an increase in the operating time. For example, the APF condition.
of the RAC in Chongqing, which has operated for 11 years, for the rated EERh ——the retention rate of energy efficiency for high-tempera-
cooling condition, high-temperature cooling condition, rated heating ture cooling condition.
condition and low-temperature heating condition has reduced by COPl ——the retention rate of energy efficiency for low-temperature
41.28%, 38.59%, 14.86% and 21.86%, respectively, and the range of heating condition.
decline was significant. The comparison of the APF between the factory COPr ——the retention rate of energy efficiency for rated heating
and the current state is shown in Fig. 11. Throughout the RACs in 10 condition.
cities, the performance of the RACs showed a significant decrease,
especially in Chongqing, of which the APF decreased to 0.8328. To optimize RAC standards, the long-term energy efficiency of RACs
The service life and the performance degradation of RACs are clo- that have operated for 5 years, 10 years and 15 years can be added to
sely related to the climate. As shown in Fig. 10, although Beijing, pre-existing standards with the calculating method of comprehensive
378
J. Wu et al. Energy Policy 125 (2019) 368–383
30000
30 RACs charged with new refrigerants, which is beneficial to the reduc-
tion of carbon emissions and greenhouse effects.
million tons
million kWh
Table 14
Regulation for air conditioners that enter the European market.
product date
Movable room air conditioning equipment (hermetically sealed equipment that is movable between rooms by the end user) that contains HFCs with minimum 1 January 2020
GWP of 150
Single split air conditioning systems that contain less than 3 kg of fluorinated greenhouse gases, that contain, or whose functioning relies upon, fluorinated 1 January 2025
greenhouse gases with a minimum GWP of 750
379
J. Wu et al. Energy Policy 125 (2019) 368–383
Table 15 where
Requirements of minimum energy efficiency of air condition units with cooling
capacity less than 12 kW in the European market according to the EU regula- f (x ) ——energy efficiency of RACs, SEER is adopted in this equa-
tion. tion.
Air conditioners (with the exception of single x ——environmental values of refrigerants, GWP is adopted in this
and double duct air conditioners) equation.
SEER SCOP
Because both the first-order derivative and the second-order deri-
GWP > 150, CC < 6 kW 4.6 3.8 vative of the logarithmic function are positive, the allowable energy
GWP≤ 150, CC < 6 kW 4.14 3.42 efficiency has a positive correlation with the environmental protection
GWP > 150, 6 kW ≤CC ≤ 12 kW 4.3 3.8 properties of refrigerants. Compared with the original standard, a tol-
GWP≤ 150, 6 kW ≤ CC≤ 12 kW 3.87 3.42
erance value, which reflects the difference between the specified value
and the calculated f (x ) , can be obtained using new refrigerants. An
increase in the environmental protection properties will cause an in-
Table 16
EU standard for the energy efficiency of variable speed room air conditioners. crease in the tolerance value. The square roots of the environmental
protection values renders f (x ) more sensitive to x . Considering the
GWP EN2013-1-1 EN2014-1-1 EN1019-1-1 SEER grade in Directive 2010/30/EU as an example, the benchmark
SEER SEER SEER
refrigerant is R410a (GWP=2100). According to these conclusions, a
GWP>150 3.60 4.30 7.00 tolerance value of the energy efficiency will be obtained when the RAC
GWP≤ 150 3.06 3.66 7.00 is charged with new refrigerants. However, this decreased allowable
energy efficiency value should not be less than the upper value in the
previous energy efficiency grade. Considering RACs whose CC≤ 12 kW
EERalt ref ——the threshold value of energy efficiency for RACs with as an example, the lower value of a C grade energy efficiency after
alternative refrigerants. optimizing can decrease to 3.6, which is the upper value of a D grade
EERbaseline ——the threshold value of energy efficiency for RACs with energy efficiency prior to optimization (GWP of new refrigerant is 0 at
traditional refrigerants. this stage). The upper value of C grade can decrease to 4.1, which is the
GWPalt ref ——the GWP of alternative refrigerants. lower value of a C grade energy efficiency prior to optimization (GWP
GWPbaseline ——the GWP of traditional refrigerants. of new refrigerant is 0 at this stage). The optimized upper and lower
values of a C grade energy efficiency can be formulated as follows:
The feasibility of the two proposals is validated by experiments of
R134a and R404a alternative refrigerants conducted by Alex Alvey SEERupper = ln( GWP + 70.64) 0.16 (18)
(Alvey, 2014). The alternative refrigerants against R134a and R404a
are listed in Tables 17 and 18, respectively, and the validation results SEERlower = ln( GWP + 70.64) 0.66 (19)
are shown in Fig. 13. The comparison between the logarithmic function and linear func-
As shown in Fig. 13, the optimization proposal that applies the tion of SEER and GWP are shown in Table 19.
logarithmic function is satisfied with a decreasing rate of energy effi- As shown in Table 19, the difference in the energy efficiency cannot
ciency for different evaporating temperatures, with the exception of be increased using better refrigerants, such as R290 and R1234yf, based
AC5X. This result can be explained by the GWP of AC5X and N-13a, on the linear function method. For refrigerant R32, whose environ-
which is approximately 600 and yields the same tolerance value, mental protection properties are general, the tolerance value is slightly
whereas the declining rate of energy efficiency in AC5X is significantly larger. However, these problems can be solved using a logarithmic
higher than that in N-13a, which almost reaches 8%. Thus, AC5X is not function.
suitable as an alternative refrigerant for RACs without optimizing an air To validate the feasibility of the previously mentioned optimization
conditioning system. The tolerance value with the method of loga- proposal with a logarithmic function, the experimental data reported by
rithmic function is unable to satisfy the energy efficiency of RACs using Larry D. Burns (Larry, 2014) on the AHRI's Low-GWP AREP Conference
new refrigerants in addition to the refrigerant with a small GWP. is adopted. As shown in Fig. 14, in addition to DR-5, the energy effi-
Regarding the setting threshold value of the energy efficiency, the ciency for RACs with alternative refrigerants has declined to various
method that combines the maximum tolerance value of 10% and a degrees, which indicates the need to optimize the grade value of the
linear function can satisfy the requirement of the energy efficiency energy efficiency for refrigerant environmental characteristics.
decreasing rate for RACs with alternative refrigerants. Compared with the optimized SEER in Table 19, the SEER for all
RACs with alternative refrigerants that operate at C grade adopted the
4.3.2.2. Optimization proposal to combine refrigerants’ environmental method of logarithmic function, whereas the RACs with L-41a directly
protection properties and grade value of energy efficiency. For the energy improve to a B grade using a linear function without any improvement
efficiency limit value of RACs, the grade value is as important as the in the original refrigeration system. For alternative refrigerants, which
threshold value. Based on the GWP value of refrigerant, an optimization will decrease the energy efficiency of a refrigeration system, improving
proposal to limit the allowable energy efficiency is expressed as the energy efficiency grade is not reasonable due to the environmental
properties.
f (x ) = ln( x + a) + b (17) Above all, using linear function to combine environmental
Table 17
R134a alternative refrigerants.
Baseline Alternative refrigerants Composition (Mass%) Classification GWP100
380
J. Wu et al. Energy Policy 125 (2019) 368–383
Table 18
R404a alternative refrigerants.
Baseline Alternative refrigerants Composition (Mass%) Classification GWP100
(based on R134a)
-3%
-6% -4%
-5%
-8%
-6%
-10%
logarithmic function R1234yf -7% logarithmic function N-13a
linear function linear function
-12% -8%
(a) Validation of tolerance value of R1234yf (b) Validation of tolerance value of N-13a
-2%
-2%
-4%
(based on R134a)
(based on R134a)
-4%
-6%
-6%
-8%
-8%
-10%
logarithmic function AC5X logarithmic function R1234ze
linear function linear function
-10% -12%
(c) Validation of tolerance value of AC5X (d) Validation of tolerance value of R1234ze
-1%
-2%
-2%
(based on R404a)
-4%
(based on R404a)
-3%
-4% -6%
-5%
-8%
-6%
-10%
-7% logarithmic function N-40a logarithmic function D2Y-65
linear function linear function
-8% -12%
(e) Validation of tolerance value of N-40a (f) Validation of tolerance value of D2Y-65
Fig. 13. Validation of tolerance value of energy efficiency based on different alternative refrigerants.
381
J. Wu et al. Energy Policy 125 (2019) 368–383
Table 19 paper to present the tolerance value for RACs by adopting alter-
Comparison between the logarithmic function and linear function of SEER and native refrigerants. The validation results indicate that the opti-
GWP. mized energy efficiency can not only solve the problem of the de-
SEERupper SEERlower clining energy efficiency of RACs with alternative refrigerants but
also properly classify the energy efficiency grade.
Refrigerants GWP Logarithmic Linear Logarithmic Linear
function function function function
The existing Chinese RACs standards have some limitations. Thus,
R410A 2100 4.60 4.60 4.10 4.10 the standards should be revised to provide more accurate, en-
R32 675 4.41 4.26 3.91 3.76 vironmentally friendly and efficient standards. This paper contributes
L41b 494 4.37 4.22 3.87 3.72 to the promotion of Chinese RACs standards and provides guidance for
L41a 494 4.37 4.22 3.87 3.72
manufacturers who aim to design and perfect products.
DR5 490 4.37 4.22 3.87 3.72
ARM-70a 482 4.37 4.21 3.87 3.71
R290 20 4.16 4.10 3.66 3.60 Acknowledgments
R1234yf 4 4.13 4.10 3.63 3.60
The author is grateful for the financial support from the National
Natural Science Foundation of China [grant number 51776076] and the
Cooling Seasonal Efficiency
16.0 Program of International Science and Technology Cooperation of China
[grant number 2016YFE0118100].
4.6
15.5
References
15.0 14.61 14.70 4.4
14.51 14.50
14.5 10 CFR PART 430. Energy Conservation Program for Consumer Products.
Ahn, Y.C., Cho, J.M., Shin, H.S., Hwang, Y.J., Lee, C.G., Lee, J.K., et al., 2003. An ex-
SCOP
13.95
SEER
13.91 4.2
perimental study of the air-side particulate fouling in fin-and-tube heat exchanger of
14.0
air conditioners. Korean J. Chem. Eng. 20 (5), 873–877.
Alvey A., 2014. Compressor Calorimeter Tests of Low GWP Refrigerants. AHRI’s Low-
13.5 4.0
GWP AREP Conference. New York, USA.
ANSI/AHRI 210/240-2008, 2008. Performance Rating of Unitary Air-Conditioning & Air-
13.0 Source Heat Pump Equipment. Air-Conditioning, Heating, and Refrigeration Institute,
3.8
Arlington, VA.
12.5 ANSI/ASHRAE 58-1986 (RA 2014), 2014. Method of Testing for Rating Room Air
R-410A R-32 L-41b L-41a DR-5 ARM-70a Conditioner and Packaged Terminal Air Conditioner Heating Capacity. American
Refrigerant Society of Heating, Refrigeration and Air-Conditioning Engineers.
AS/NZS 3823.2:2013, 2013. Performance of electrical appliances—Air conditioners and
Fig. 14. Performance results of low GWP R-410A alternative testing (Larry, heat pumps Part 2: Energy labelling and minimum energy performance standards
2014). (MEPS) requirements. Standards Australia International, Sydney; Standards New
Zealand, Wellington.
ASTM D2992, 2006. Standard Practice for Obtaining Hydrostatic or Pressure Design Basis
The energy efficiency standards comprise the foundation of sustainable for "Fiberglass"(Glass-Fiber-Reinforced Thermosetting Resin) Pipe. American Society
for Testing and Materials, West Conshohocken, Pennsylvania.
development. Therefore, perfecting the standards is imperative. Based ASTM D5365, 2006. Standard Test Method for Long-Term Ring-Bending Strain of
on the literature, the following conclusions are obtained: "Fiberglass" (Glass-Fiber-Reinforced Thermosetting Resin) Pipe and Fittings.
American Society for Testing and Materials, West Conshohocken, Pennsylvania.
BS EN 14389-2-2004, 2004. Road Traffic Noise Reducing Devices – Procedures for
(1) With the energy efficiency development of RACs from EER/COP to Assessing Long Term Performance - Non-Acoustical Characteristics. British Standards
APF, the comprehensiveness of the evaluation metrics is enhanced, Institution, London.
and the evaluation metrics resemble actual operating conditions; BS EN 14825-2012, 2012. Air conditioners, liquid chilling packages and heat pumps, with
electrically driven compressors, for space heating and cooling-Testing and rating at
(2) RACs standards in each country have independent characteristics:
part load conditions and calculation of seasonal performance. British Standards
The “two-point”, “three-point” and “five-point” testing methods are Institution, London.
commonly employed in many countries to evaluate the perfor- CQC 9202–2012, 2012. The Technology Requirements for Long-term Energy
Conservation Evaluation of Air Conditioner. China Quality Certification Center.
mance of VFRACs. To accurately reflect the performance of RACs,
DIN EN 14389-2-2004, 2004. Road Traffic Noise Reducing Devices - Procedures for
the division of temperature zones and energy consumption in var- Assessing Long Term Performance - Part 2: Non-Acoustic characteristics; German
ious modes has been considered in some areas; version EN 14389-2:2004. German Institute forStandardization, Berlin.
(3) Compared with RAC standards in other countries, RAC standards in Directive 2006/40/EC, 2006. Directive 2006/40/EC of the European Parliament and the
Council, Administrative Provisions for the EC type-approval of vehicles, and a
China have the following optimizations: In the cooling season, Harmonised Test for Measuring Leakages from Certain Air Conditioners. European
China should be incorporate a “hot summer and warm winter” zone Commission.
to calculate the cooling hours. In the heating season, China should ENERGY STARVersion 4.0. Energy Star Program Partner Commitments and Eligibility
Criteria for Room Air Conditioners.
be separated into the “hot summer and warm winter” zone, “hot EU NO 517/2014, 2014. REGULATION (EU) No 517/2014 on Fluorinated Greenhouse
summer and cold winter” zone, “moderate” zone and “central Gases and Repealing Regulation (EC) No 824/2006. European Commission.
heating” zone. G/TBT/N/EEC/362, 2011. Draft Commission Regulation Implementing Directive 2009/
125/EC of the European Parliament and of the Council with regard to ecodesign
(4) Long-term performance should be considered in the Chinese RAC requirements for air conditoners and comforts. European Commission.
standards, which can be described as follows: the long-term energy G/TBT/N/EEC/363, 2011. Draft Commission Delegated Regulation supplementing
efficiency of RACs that have operated for 5 years, 10 years and 15 Directive 2010/30/EU of the European Parliament and of the Council with regard to
energy labelling of air conditioners. European Commission.
years should be added to the pre-existing standards with the cal- GB 12021.3-2010, 2010a. The Minimum Allowable Value of the Energy Efficiency and
culating method of synthetical evaluation of the long-term perfor- Energy Efficiency Grades for Room Air Conditioners. Standards Press of China,
mance . Only the RACs that satisfy the allowable energy efficiency Beijing.
GB 12021.3-2010, 2010b. The Minimum Allowable Value of the Energy Efficiency and
both in the factory state and the long-term operating state should be
Energy Efficiency Grades for Room Air Conditioners. Standards Press of China,
produced or sold; Beijing.
(5) The final purpose of the optimization of RAC standards is to protect GB 21455-2008, 2008. The Minimum Allowable Values of the Energy Efficiency and
the environment. Thus, the environmental protection properties Energy Grades for Variable Speed Room Air Conditioners. Standards Press of China,
Beijing.
should considered. Two optimization proposals are proposed in this GB 21455-2013, 2013. Minimum Allowable Values of the Energy Efficiency and Energy
382
J. Wu et al. Energy Policy 125 (2019) 368–383
Efficiency Grades for Variable Speed Room Air Conditioners. Standards Press of standards for air conditioners. Energy Policy 36 (1095-1095).
China, Beijing. Lu, Wei, 2007. Potential energy savings and environmental impacts of energy efficiency
GB/T 50082-2009, 2009. Standard for Test Methods of Long-term Performance and standards for vapor compression central air conditioning units in China. Energy
Durability of Ordinary Concrete. Standards Press of China, Beijing. Policy 35, 1709–1717.
Grignon-Masse, Laurent, Riviere, Philippe, Adnot, Jerome, 2011. Strategies for reducing Peng, R.C., 2010. The new national air conditioner energy efficiency standard comes into
the environmental impacts of room air conditioners in Europe. Energy Policy 39, effect on June 1. Power Demand Side-. Manag. 12, 3.
2152–2164. Qi W.D., Li J.B., 2011. The standard of energy evaluation efficiency of inverter air-con-
Hung M.P., Autumn N.N., 2014. Compressor Tests with Low GWP Refrigerants for Air ditioner and contrastive studies of APF. In: Proceedings of the 10th Refrigerator, Air
Conditioning and Refrigeration. AHRI’s Low-GWP AREP Conference. New York, USA. conditioner and Compressor Academic Conference. Qingdao, China.
ISO 10467-2004, 2004. Plastic piping systems for pressure and non-pressure drainage and Rosenquist G., Lin J., 2005. Chinese Room Air-Conditioning Heat Pumps: An Engineering
sewerage Glass-reinforced thermosetting plastics(GRP) system based on unsaturated and Life-Cycle Cost Analysis of 3500W and 7100W Cooling Capacity Units, LBNL-
polyester(UP) resin. International Organization for Standardization. 57992, Berkeley, CA.
ISO 16358-1-2013, 2013. Air-cooled air conditioners and air-to-air heat pumps—Testing Wang, S.Y., 2013. The difference between APF of Chinese and Japanese standard. China
and calculating methods for seasonal performance factors—Part1: Cooling seasonal Appl. Technol. (09), 38–40.
performance factor. International Organization for Standardization. Wei, L., 2007. Potential energy savings and environmental impacts of energy efficiency
ISO 16358-2-2013, 2013. Air-cooled air conditioners and air-to-air heat pumps—Testing standards for vapor compression central air conditioning units in China. Energy
and calculating methods for seasonal performance factors—Part2: Heating seasonal Policy 35 (3), 1709–1717.
performance factor. International Organization for Standardization. Wu, C.B., 2013. Seasonal Performance Evaluation of Refrigeration Equipment Used for
ISO 16358-3-2013, 2013. Air-cooled air conditioners and air-to-air heat pumps—Testing Air-conditioning. Tsinghua University, Beijing, China.
and calculating methods for seasonal performance factors—Part3: Annual perfor- Wu, J.H., Liu, C.P., Liang, Z.H., Zhang, C.J., 2015. Research on the room air conditioner
mance facto. International Organization for Standardization. long-term performance prediction and optimization strategy. J. Mech. Eng. 18,
ISO 5151:2017, 2017. Non-ducted air conditioners and heat pumps—Testing and rating 158–166.
for performance. Wu, X.L., Cai, N., Hu, Z.Q., 2014. Comparative analysis of testing and calculating methods
JISC 9612:2013, 2013. Room Air Conditioner. Japanese Industrial Standards Committee, for seasonal performance factors of air conditioner. China Appl. Technology 04,
Tokyo. 40–42.
JRA 4048:2006, 2006. Annual Performance Factor of Package Air Conditioners. The Yan, Da, Hong, Tianzhen, et al., 2017. A thorough assessment of China's standard for
Japan Refrigeration and Air Conditioning Industry Association, Tokyo. energy consumption of buildings. Energy Build. 143, 114–128.
Larry D.B., 2014. Air Conditioning and Heat Pumps Session I. AHRI’s Low-GWP AREP Yu, Hao, Tang, Bao-Jun, 2015. How do the appliance energy standards work in China?
Conference. New York, USA. Evidence from room air conditioners. Energy Build. 86, 833–840.
Li, H.Q., Cheng, J.H., 2008. Variable Speed Room Air Conditioners and Energy Efficiency Zhu J.D., Chen Z., Liu R., 2015. Research Status and Development Trend of Evacuation
Grades. Standards Press of China, Beijing. System of Long-term Energy Conservation for Room Air Conditioners. Electrical
Lin, J., Rosenquist, G., 2008. Stay cool with less work: China's new energy-efficiency Appliances; (02): 17-23.
383