Adaptive Protection Notes
Adaptive Protection Notes
In modern digital relays, a tripping short-circuit current can be set for a wide range, e.g. 0.6-15*CB rated
current
A use of power electronics (PE) interfaces leads to a number of challenges in microgrid protection,
especially in the islanded mode.
F1
CB1 should operate if no MV tripping, sensitivity problems microgrid contribution to SCC 1.1-
1.2*IDERrated A directional OC relay acting on CB1 is a feasible solution the setting has to be continuously
monitored and adapted when microgrid generation undergoes considerable changes (related to the number
and type of connected DERs)
Distribution Network Operators (DNO)
F2
a distribution transformer OC protection clears the fault by opening CB0. CB1 is opened simultaneously
by “follow-me” function (hardware lock) of CB0. In case of hardware lock failure, a possible fault
sensitivity problem can arise as in the case of fault F1. Typical solutions are similar to the F1 case,
F3-Grid Connected
disconnect the smallest possible portion of the LV feeder by CB1.2 and CB2.1
CB1.2 is opened due to a high level of short-circuit current supplied by the main MV grid
CB 1.1 is the backup for 1.2
If there is a synchronous DER between CB1.1 and fault the fault current can become smaller. (protection
blinding) may result in a delayed CB1.1 tripping
CB1.2 operates first then part is islanded with the fault CB2.1 can have sensitivity issue should have a
“follow me” function for CB1.2 and CB2.1
F4 -Grid Connected
High fault current CB2.4 trip, if not SWB2 isolated by CB2.5 and DER is cut off
F3-Islanded
Absence of high-level SCC, directional OC required to detect the fault location
There are two possible ways to address the problem of absence of a high level short-circuit current:
1. Install a source of high short-circuit current (e.g. a flywheel or a supercapacitor) In case such
source of high short-circuit current is installed, it would be typically connected to the LV bus bar.
2. Install an adaptive microgrid protection using on-line data on microgrid topology and status of
available micro-sources/loads.
F4-Islanded
Low SCC with only DER contribution CB2.4 settings selected for the main grid connected mode are just
slightly higher than rated load current It assures that the end-customer site will be disconnected even if
only DERs with PE interfaces are available in the microgrid.
Adaptive Protection
Use of numerical directional OC relays
several settings groups that can be parameterized locally or remotely automatically or manually.
Use of new/existing communication infrastructure
Directional interlock
if The fault current direction is opposite to the present interlock direction
then Keep present port assignment
and Relay sends locking signal to the present interlock direction
if The fault current direction is similar to the present interlock direction
then switch output/input ports, i.e. interlock direction
And relay sends locking signal to the new interlock direction (opposite to the present interlock
direction)
Simulation
Assumptions
Over current protection trip curves have similar shape for each breaker
L part - protection against overloads
S part – protection against short circuit with short time
delay trip
I part – instantaneous protection against short circuit
ts is changed to provide selective operation
The instantaneous tripping part I is removed from all
curves for a simplification purpose
Implementation of Dijkstra’s Algorithm in a Dynamic Microgrid for Relay Hierarchy Detection Taha
Selim Ustun, Cagil Ozansoy, Aladin Zayegh
Disadvantages of above
implements an algorithm which includes a look-up table. This is a large set-back because it requires the
knowledge of all possible microgrid configurations beforehand, plus human input for the preparation of
this table ,any kind of a new deployment, which is very common to microgrids, requires that the whole
selectivity table should be re-written
Selectivity hierarchy changes with the change in microgrid topology eg. Case 1 CB 5 open – two
branches, case 2CB 4 open CB5 closed – single branch
CB 2 should operate for faults in the utility grid, need two different time delays one for upstream and one
for downstream
t base = tmax/n
t relay of nth level =t base x S relay
N value is found with dij for each node (breaker) and time delay is calculated
ENs. IEC 61850, for example, is an international standard for substation automation
ISSN 1816-949X
Fredman-Tarjan algorithm
Graph theory based, minimum spanning tree,
Conclusion – Dijkstra is faster than fredman tarian algo
introduction of DG increase fault current, reduces the CTI may cause to unnecessary removal of a larger
portion of the system
Therefore, the operating parameters of OCRs must be correctly adjusted and that is carried out by the
adaptive algorithm implementation
1) Power Grid without DG.
2)Power Grid with all DG.
3) Power Grid with different capacity of DG.
4) Power Grid with different fault location.
Not completed……
IEEE Elect r i f icat ion Magazine / MARCH 2014
Adaptive Protection System for Microgrids By Liang Che, Mohammad E. Khodayar, and Mohammad
Shahidehpour
IEEE Standard 1547 requires DER units to stop energizing the distribution system when the system is de-
energized due to faults.
Possible solutions
Synchronous generators, including permanent magnet synchronous generators (PMSGs), and fly wheels
are suitable choices for increasing fault currents in microgrids.
Differential protection schemes, either centralized, or localized