SUMMARY
In the developing countries like India, the primary focus of utility is to make the units
available to its maximum and minimising the maintenance duration. Simultaneously,
these units have to run continuously at base load ensuring the high reliability. The
present IEC standards for Electrical Rotating Machines are referred for testing to
establish the performance and quality of the large electrical machine, however they do
not specify limits or trending of various operating parameters of generator Stator
Water System, which needs to be continuously monitored. The availability of
different designs of turbo-generators Stator Water systems calls for understanding the
basic ingredients of the system, their function and how the system can perform its
best. The paper covers a brief on the types of Generator Stator Water systems, their
advantages and disadvantages, design requirements & monitoring of critical
parameters along with permissible associated limits. The process of corrosion in
hollow strands, crevice corrosion on clip to strand joint and various steps to check
corrosion right at incipient stage have been discussed. A few designs experienced by
the user for stator water system have also been summarised.
KEY WORDS
*[email protected]
DESCRIPTION
The directly cooled generators are provided with roebel bars hollow conductors
connected to common water header at inlet and outlet of the winding. The conductors
as well as the water headers are generally of copper, however in some cases stainless
steel hollow conductor, cooling water header and piping are being provided. The
direct cooled machine are designed generally above 500MW, to ensure quick removal
of majority of heat by the water flowing in direct contact of the winding conductor, in
addition to the removal of heat by hydrogen from the surface of hot winding
insulation. The winding insulation besides having good dielectric strength, has
excellent thermal conductivity to ensure fast removal of heat. All strands of the roebel
bar are brazed together (with BCuP) at the water box connecting to header (Fig.-1) [1].
The flexible connection between the high voltage (e.g. up to 15kVL-N) conductors to
water header is through Teflon tube. Understanding of the water chemistry is very
important for longevity of the machine. Here some important term and the
relationships in the chemical process are described;
Figure-2 shows the corrosion rate of copper bar with dissolved oxygen
Deioniser:
The process of deionising the water is ensures not only removal of soluble ions, but
also filters the insoluble oxides and other particles. The deioniser controls the
conductivity of water, which should be maintained below 2µS/Cm. The conductivity
is determined at reference temperature of 25˚C, which increases with temperature, 2%
per degree Celsius[4] of temperature rise. The conductivity increases suddenly as
NaOH dosing is done in elevated pH type system. The conductivity depends upon the
presence of free ions in the water system. The deionised pure water has poor
conductivity of 0.055 µS/Cm.
The deioniser can be mixed bed type, where water is continuously pass through mixed
bed having both resins in the same vessel. The other system two-bed deioniser
provides larger capacity, where two vessels are used having separate cation and anion
resin beds.
High Oxygen and high pH system is not in use as it cause clip corrosion[5]. The key
issues to be address while designing the stator water system are:
The elevated pH low dissolved oxygen results in formation of Cuprous Oxide Cu3O
layer inside the conductor as the water enters and protects the copper bar from
corrosion. The curve shows that Global corrosion rate at Elevated pH is much lower
that the value at neutral pH. The lower corrosion rate has the advantage of ensuring
better cooling of the stator bars. However, the issue of crevice corrosion at clip to
strand brazing joint needs to be addressed here considering the formation of acidic
solution from the braze material (BCuP & Cu3P) at clip to strand location.
Figure-4 : shows a typical Scheme of Elevated pH type System
The dearated type stator cooling water system was introduced by GE to eliminate the
issue of crevice corrosion at clip to strand joint of the stator bars. The corrosion
initiated in brazed metal (BCuP-1) due to formation of low pH phosphate solution.
The chemical reaction attacks both the brazing alloy BCuP and Cu3P. The
development of cracks results in leakage of hydrogen into water. The leakage of
hydrogen for long duration allows moisture penetration to the insulation (by capillary
action) causing swelling and severe deterioration.
Detraining Tank
The detraining tank is provided in the scheme to remove the dissolved gases from the
cooling water by passing the primary water on a set of baffles. It is important to
ensure that the vent pipe is not closed.
a) Sparger along with nitrogen or hydrogen capping in the stator water storage
tank may be installed. Necessary vent open to atmosphere has to be provided.
b) Oxygen removal system may be used in the makeup line. In case of low DO
system catalyst palladium[5] is used in the deioniser to form water quickly
from the dissolved oxygen. Such provision shall be done with Hydrogen
blanketing in the stator water storage tank to make the dissolve hydrogen
present in the cooling water.
The pH can also be slightly elevated as emergency measure by NaOH dosing to check
the global corrosion rate, but the solution is to be worked out in next overhaul of the
unit. Keeping elevated pH in old system originally designed for low DO neutral pH
will lead to severe crevice corrosion in clip to strand joints.
The continuous trending of Dissolved Oxygen and conductivity is must for neutral pH
operation.
HIGH DISSOLVED OXYGEN TYPE SYSTEM[6]
The figure-6 shows a typical scheme of the high dissolved Oxygen type of stator
cooling water scheme.
The high DO system operates at Oxygen Concentration above 2ppm and neutral pH.
The pH of stator water system has to maintain always at 7 considering the risk of
crevice corrosion at clip to strand joint at elevated pH.
The fig-1 shows the water box connection from the water header to the winding bars.
On one side of the water box the Teflon tube connection is there with washer and nut
to ensure perfect sealing of the flexible joint with the water box, on the other side the
water box is connected to copper conductor strands[1]. These strands are brazed with
the water box. The brazing is done with phosphorous rich braze alloy. If the brazing is
not proper, water may travel to outside the water box due to capillary action damaging
the insulation.
PRECAUTIONS
The aerated as well as deareated type of system have their own benefits, however
deviation from specified requirement can cause severe damage to the winding
conductor as well as the insulation.
All the designs discussed above have their own advantages. However, as seen from
figure-2, the operation close to neutral pH with dissolved oxygen of 200-300ppb can
cause severe plugging of the stator bars requiring Ethylene-Diamine-Tetra acetic Acid
(EDTA) cleaning.
The change of system from one type to other is not advisable rather the operation has
to be ensured as per OEM recommendation for longevity of the units. NTPC has so
far no experience of change of system from one type to other. However, reports
suggest that change of system at later stage requires utmost care and understanding of
the associated process, else results in severe damage to the machine. A few cases has
been summarised below:
These systems worked under neutral pH. As per EPRI report, a large fleet of EDF
units have been converted from low DO to High DO system[8]. The dearated system
was having nitrogen blanket in the stator water storage tank. EDF have problems of
plugging in all of their dearated systems due to ingress of air from joint to the stator
water. This resulted in dissolved oxygen higher than the desired level leading to
plugging of the tubes.
Even after the conversion to high DO type system, the plugging continued due to:
Operation of the units in Intermediate range DO and
Presence of residual of global corrosion occurred earlier.
After thorough cleaning of the system and taking due precaution the system operated
successfully.
One of the nuclear power stations of Europe was having the generator to operate with
high DO level but actually operated as low DO type system. The system was provided
with only conductivity monitoring at inlet & outlet of the deioniser[8]. The clip to
strand leakage resulted in large quantity of dissolved hydrogen in the stator water
system, accumulated at the top of water surface in stator water tank. The capping of
hydrogen also not allowed the air contact to water, which is mandatory to achieve
2000ppb dissolved oxygen level. The dissolved oxygen was consumed in corrosion
process of copper, leading to operation in low oxygen regime. Due to hydrogen
leakage from clip to strand the DO level reached below 10ppb (instead of >2ppm).
After thorough cleaning of the system, the system was converted to dearated type by
taking suitable measures and thereafter run successfully.
LEAK REPAIR
It has been experienced that even in new machine cracks may appear at clip to strand
joint initiating leakage of hydrogen into the primary water. The cause can be one of
the following:
Severe end winding vibration of effected bar causing development of the crack
Any kind of impact the bar subjected during the transportation or installation.
Development of crevice corrosion and
Poor brazed joint with presence of voids.
The thermal profile of cooling water is very important for healthy operation of the
machine. The most critical measurement in this system is the water temperature at the
bar outlet, and hence the same has to be continuously monitored for each bar
individually or common for top & bottom bars. The Embedded temperature Detectors
are placed on the designed hot spot locations and thus have temperature higher than
the water temperature flowing in the conductors. Considering the availability of
excellent insulation tapes of high electric strength, good thermal conductivity and
coefficient of expansion close to the copper, the temperature at ETD locations shall
not exceed in any case more than 95 degree Celsius[7]. As we know that water boiling
point slightly rises with increase of operating pressure (in this case water pressure in
the conductor) and operation close to those limits shall cause bubble formation and
subsequent blockage of cooling water flow. The hot water temperature at outlet shall
generally be kept below 75 degree Celsius.
COMMON FEATURES
The stator water system should have the following to ensure healthiness of the
system:
a) Monitoring of every single or two(top & bottom) bar water outlet temperature
b) Monitoring of Online Dissolve Oxygen
c) Measurement of pH
d) Conductivity Monitoring (should be less than 2µS/Cm.)
e) Differential pressure across stator bars
f) Differential pressure across deioniser
g) Primary water inlet pressure and
h) Regulated alkali dosing for elevated pH (maintaining the conductivity).
In line samples are also taken periodically to check and monitor the values of b), c)
and d) above. The monitoring of differential pressure across stator winding is on
continuous basis. The trend shall clearly show the corrosion or blocking of the bars.
NTPC EXPERIENCE
The NTPC has more than 50 nos. water cooled generator of 200MW and 500MW
ratings in operation for more than 5 years. The available designs provide us with
experience of stator water system of following types: