Maxdna Distributed Control System: Max Station 1 Max Station 2 Max Station 3

The document describes the maxDNA distributed control system and its components. The system uses maxSTATIONS connected over maxNET networks. I/O is handled by maxPAC I/O systems which connect the maxDNA DCS to real-world process control I/O using I/O modules and DPUs mounted in I/O racks. Common I/O modules described include analog input, digital input/output, and RTD modules.

Uploaded by

Pradeep Tripathi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
709 views78 pages

Maxdna Distributed Control System: Max Station 1 Max Station 2 Max Station 3

The document describes the maxDNA distributed control system and its components. The system uses maxSTATIONS connected over maxNET networks. I/O is handled by maxPAC I/O systems which connect the maxDNA DCS to real-world process control I/O using I/O modules and DPUs mounted in I/O racks. Common I/O modules described include analog input, digital input/output, and RTD modules.

Uploaded by

Pradeep Tripathi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 78

maxDNA DISTRIBUTED CONTROL SYSTEM

m a x S T A T IO N 1 m a x S T A T IO N 2 m a x S T A T IO N 3

N e tw o r k A S w i tc h e d N e tw o r k A
1 0 /1 0 0 M b p s H u b A -1 10/100 M bps

N e tw o r k B S w i tc h e d N e tw o r k B
1 0 /1 0 0 M b p s H u b B -1 10/100 M bps

N e t w o rk A N e t w o rk B
1 0 0 /1 0 0 0 M b p s 1 0 0 /1 0 0 0 M b p s
F u ll D u p le x F u ll D u p le x

N e t w o rk A N e t w o rk A
100M bps 100M bps
S w i tc h e d
D P U 4 F 1 -1 H u b A -2 DP U 4F 2-1

S w i tc h e d
D P U 4 F 1 -2 DP U 4F 2-2
H u b B -2
N e t w o rk B N e t w o rk B
100M bps 100M bps
R e m ote R e m o te
P r o c e ss i n g P ro ce s s in g
U n it 1 U n it 2
DPU 4F CONNECTIVITY OVER maxNET

I I D PU
Switch A O O 4F

Switch B
I I D PU
O O 4F

I I I
O O O
maxPAC I/O SYSTEM

• maxPAC I/O SYSTEM LINKS THE maxDNA DCS WITH REAL


WORLD PROCESS CONTROL I/O.
• THE I/O SYSTEM COMPRISES THE I/O MODULES & THE DPU.
• THE I/O MODULES & DPU ARE MOUNTED IN A I/O RACK
ASSEMBLY.
• THE RACK ASSEMBLY CARRIES A BACKPLANE WHICH
PROVIDES THE I/O BUS .THE I/O BUS IS THE
COMMUNICATION BUS BETWEEN THE DPU & THE I/O
MODULES. ALL I/O MODULES COMMUNICATE WITH THE
DPU THRO’ THE I/O BUS.THE COMMUNICATION IS CLOSELY
CONTROLLED BY THE DPU.
• THE RACK USED IN THE maxDNA SYSTEM IS A 8 PAC.
I/O SYSTEM RACK ASSEMBLY –8 PAC RACK
I/O SYSTEM BACKPLANE & I/O BUS

• PROVIDES THE SYSTEM POWER & FIELD POWER CONNECTIONS


TO THE I/O MODULES & THE DPU.
• CARRIES THE I/O BUS OVER WHICH THE DPU & THE I/O MODULES
COMMUNICATE.
• I/O MODULES & THE DPU PLUG INTO CONNECTORS IN THE I/O
BACKPLANE.
• ON ANY I./O BUS, ONLY ONE / ONE REDUNDANT PAIR OF DPUs
CAN RESIDE .
• UPTO 60 I/O MODULES CAN RESIDE ON A I/O BUS.
• THE I/O BUS CAN EXTEND TO A MAXIMUM LENGTH OF 30 FT.
• MULTIPLE I/O RACKS THAT SHARE THE I/O BUS CAN BE
INSTALLED IN A CABINET.
IOP382 – 8 PAC Rack
INTERCONNECTING maxPAC I/O RACKS FOR I/O BUS EXTENSION
I/O SYSTEMS RACKS MOUNTED IN CABINET
I/O BUS SIGNALS
(SYSTEM GND) P1A P22B (SYSTEM GND)
(SYSTEM +24V) P2A
P21B (SYSTEM +24V )
P3A
P20B
P4A
P19B
P5A P18B
P6A
P17B (ADDRESS`)
P7A
P16B ( DATA`)

I/O BUS CONNECTOR


P8A P15B ( LATCH`)
P9A P14B ( IN/OUT`)
P10A P13B (HI/LO`)
P11A
P12B (INT`)
P12A P11B (ACK`)
P13A
P10B (XACK`)
P14A P9B (D0)
( LOOP 48V +) P15A P8B (D1)
(LOOP 48V +) P16A
P7B (D2)
P17A P6B (D3)
(LOOP 24V +) P18A
P5B (D4)
(LOOP 24V +) P19A
P4B (D5)
P20A
P3B (D6)
(LOOP GND) P21A
P2B (D7)
(LOOP GND) P22A
P1B (PARITY)
maxPAC- I/O modules
Analog Input/Output modules
IOP301- Isolated Analog Input; 16 channels
IOP302- 4-20mA, common Input; 16 channels
IOP303- 3-wire RTD input; 8 channels
69230S303A – 4-wire RTD module 8 channel
IOP304- Thermocouple /emf Input; 16 channels
IOP305- Voltage common Input; 16 channels
IOP320- (4-20)mA Common Output; 8 Channels
IOP321- Isolated (4-20)mA Output; 8 Channels
69230R306A– Resistors & Thermistor assembly
for IOP301 & IOP305 modules.
maxPAC- I/O modules
Digital Input/Output modules:
IOP330 – 24Vdc common input; 16 Channels
IOP331 – 48Vdc common input; 16 Channels
IOP332 – 120Vac/dc isolated input; 16 Channels
IOP333 – 240Vac/dc isolated input; 16 Channels
IOP334 – 24Vdc isolated input; 16 Channels
IOP350 – Form C Relay output; 10 Channels
IOP351 – Form A/B Relay Output; 16 Channels
maxPAC- I/O modules
Other Modules :
IOP371 – Optical Bus Extender module
IOP382 – 8 PAC Rack
CPO401– Y-Adaptor for mixed I/O racks
CPO402– I/O Bus Terminator
TYPICAL I/O MODULE FRONT PANEL
I/O MODULE CONFIGURATION OPTION – SHARED(COMMON)
CONFIGURATION
Network

D D
Back-up
P P
Cable
U U
IO Bus

I I I ••• I I I
O O O O O O

Redundant DPUs,
Common I/O Bus
I/O MODULE CONFIGURATION OPTION – REDUNDANT CONFIGURATION

Network

D D
Back-up
P P
Cable
U U
IO Bus

I I ••• I I I ••• I
O O O O O O

Redundant DPUs,
Separate I/O Bus,
Redundant I/O

CPO309
I/O MODULE CONFIGURATION OPTION – MIXED CONFIGURATION

Network

Back-up
D Cable D
P Y P
U Cable U
IO Bus

I I I I I I
O O O O O O

Common IO Bus

I I I I
O O O O

Redundant DPUs,
Mixed I/O Bus
MIXED I/O WITH Y ADAPTER
IOP301- Isolated Analog Input; 16 channels

• 4-20mA or 0.4 to 2.0V input


• Isolation between inputs and logic
• Digital value: 15 bit data and 1 bit sign
• 100 msec scan time.
• Diagnostics and self calibration on Power-up.
• Periodic online recalibration.
• Open input detection.
• Can be used in redundant application along with
69230R306A module (4 to 20mA will be converted into
0.4 to 2.0 V externally using 69230R306A)
IOP301- Isolated Analog Input; 16 channels
IOP301- Isolated Analog Input; 16 channels
IOP301-JUMPER CONFIGURATIONS
IOP301 –INPUT CIRCUIT CONFIGURATIONS
IOP301—FIELD WIRING
IOP301 – FIELD WIRING FOR REDUNDANT MODULES
IOP301 – FIELD WIRING FOR REDUNDANT MODULES
IOP302- 4 to 20mA Analog Input; 16 channels
IOP305- 0.4 to 2.0V Analog Input; 16 channels

• 4-20mA (IOP302) or 0.4 to 2.0V(IO305) input


• Isolation between inputs and logic
• 20 msec scan time.
• Diagnostics and self calibration on Power-up.
• Periodic online recalibration.
• Open input detection.
IOP302- 4 to 20mA Analog Input; 16 channels
IOP305- 0.4 to 2.0V Analog Input; 16 channels
IOP302/IOP305 –ANALOG I/P MODULES
IOP302- 4 to 20mA Analog Input; 16 channels
IOP302 – JUMPER SETTING INFORMATION
IOP302–FIELD WIRING
IOP305–FIELD WIRING
IOP303- 3 wire RTD module: 8 channels
69230S303A- 4 wire RTD module: 8 channels
• 8 Channels of RTD inputs with different configuration for
each channel.(10R Cu,Pt; 25R Pt;100R Cu,Pt,Ni; 1000R Pt)
• Self calibartion on power-up.
• Periodic online recalibration.
• Channel to Channel and Channel to Logic isolation.
• Open RTD detection.
IOP303- 3 wire RTD module: 8 channels
69230S303A- 4 wire RTD module: 8 channels
IOP303 – RTD INPUT MODULE
IOP303- 3 wire RTD module: 8 channels
69203S303A- 4 wire RTD module: 8 channels
RTD INPUT MODULE – JUMPER SETTING INFORMATION
IOP303- 3 wire RTD module: 8 channels
69203S303A- 4 wire RTD module: 8 channels
IOP303 --- FIELD WIRING FOR REDUNDANT MODULES
IOP304- TC input : 16 channels
IOP304- TC input : 16 channels
• 16 Channels of TC inputs with different configuration for
each channel.(Type B,D,E,G,J,K,N,R,S,T)
• Self calibartion on power-up.
• Periodic online recalibration.
• Channel to Channel and Channel to Logic isolation.
• Open TC detection.
IOP304- TC input : 16 channels
IOP304 – JUMPER SETTING INFORMATION
IOP304 -- FIELD WIRING
IOP304 – FIELD WIRING FOR REDUNDANT MODULES WITH COMMON TC
IOP320/IOP321- 4-20mA Current Output : 8 channels
IOP320/IOP321- 4-20mA Current Output : 8 channels

• 8 Channels of 4-20mA current output


• Channel to Logic isolation.
• Open Output detection.
• Load impedance 0 to 800 ohms.
• Jumper setting to select Run mode, Calibrate mode, Hold or
reset output mode, common or redundant output mode,
primary or secondary output mode.
MODULE SPECIFICATIONS
IOP320/IOP321- (4-20)mA Current Output : 8 channels
IOP320/IOP321 – JUMPER SETTING INFORMATION
IOP320/IOP321 – FIELD WIRING
IOP 320/IOP321 – FIELD WIRING FOR REDUNDANT MODULES WITH COMMON END
ELEMENT
IOP330 – 24Vdc common input; 16 Channels
IOP331 – 48Vdc common input; 16 Channels
IOP330 – 24Vdc common input; 16 Channels
IOP331 – 48Vdc common input; 16 Channels
• 1ms scan rate for SOE
• Field wetting voltage through fuse
• 16 common input channels
• High level at 40% to 150% of rated voltage
• Field to logic isolation
IOP330 – 24Vdc common input; 16 Channels
IOP331 – 48Vdc common input; 16 Channels
IOP330 / IOP331 – FIELD WIRING
IOP330 / IOP331 – FIELD WIRING FOR REDUNDANT
MODULES WITH COMMON DI
IOP332 – 120Vac/dc isolated input; 16 Channels
IOP333 – 240Vac/dc isolated input; 16 Channels
IOP334 – 24Vdc isolated input; 16 Channels
• 1ms scan rate for SOE
• Jumper setting for AC input for modules IOP332 /IOP333
• 16 isolated (channel to channel) channels
• High level at 40% to 150% of rated voltage
• Field to logic isolation
• LED indication for HIGH input
IOP332 – 120Vac/dc isolated input; 16 Channels
IOP333 – 240Vac/dc isolated input; 16 Channels
IOP334 – 24Vdc isolated input; 16 Channels
IOP333 – DIGITAL INPUT MODULE.
IOP332 – 120Vac/dc isolated input; 16 Channels
IOP333 – 240Vac/dc isolated input; 16 Channels
IOP334 – 24Vdc isolated input; 16 Channels
IOP332 – 120Vac/dc isolated input; 16 Channels
IOP333 – 240Vac/dc isolated input; 16 Channels
IOP334 – 24Vdc isolated input; 16 Channels
IOP332/333/334 – FIELD WIRING FOR REDUNDANT MODULES
IOP350 – Form C Relay output; 10 Channels
IOP351 – Form A/B Relay Output; 16 Channels

• 10(IOP350)/16 (IOP351) isolated (channel to channel)


channels
• Contact rating: 5A at 250Vac, 3A at 30Vdc.
• Field to logic isolation
• IOP351 can be changed from Form A to Form B by
changing a set of resistors.
• Maximum speed 20 CPM.
IOP350 – Form C Relay output; 10 Channels
IOP351 – Form A/B Relay Output; 16 Channels
IOP351 – 16 CHANNEL DIGITAL OUTPUT MODULE
IOP350 – Form C Relay output; 10 Channels
IOP351 – Form A/B Relay Output; 16 Channels
IOP351 – FIELD WIRING
IOP350 – FIELD WIRING
IOP350/ IOP351 – FIELD WIRING FOR REDUNDANT MODULES
WITH COMMON END ELEMENT
IOP371 – Optical Bus Extender module

• Extends DPU bus up to 2000 meters through Optical links


• Digital output indication for link failure indication
• Jumper setting for remote, local, common or redundant
application.
IOP371 – Optical Bus Extender module
IOP371 – Optical Bus Extender module connectivity
IOP371 – Optical Bus Extender module connectivity

D Back-up D
P Cable P
U U

Common Local I/O Bus

I I I B B B
O O O E E E
M M M

6,500 ft. 6,500 ft.


F.O. Link F.O. Link
To Remote
Location #3

B B
E Remote Location #1 E Remote Location #2
M M
Common Remote I/O Bus Common Remote I/O Bus

I I I I I I I I
O O O O O O O O

Redundant DPUs, Common I/O Bus, Common I/O,


Multiple Remote Locations
IOP371 WITH MIXED I/O
BEM – FUNCTIONAL BLOCK DIAGRAM
IOP371 – JUMPER CONFIGURATION
TERMINATION OF LOCAL & REMOTE I/O BUSES