Generator Automatic Voltage Regulator
Operation Manual
2. WIRING
3. F+, F- terminals connect to the generator field. ( J
and K )
In a standard AVR, when the generator has
an unbalanced load, the NEUTRAL conducts 4.- For use with independet power winding see Fig 10
the current from this unbalance load, and
the voltage from the N to the 3 phases constantly EXT.VR is rated at (1K Ohm 1W) Keep terminals
changes the sensing reference input voltage to shorted when the external pot is not used.
the AVR making it hard to have a constant
output voltage on the generator. P.S. : A, B, C, F+, F- usage AWG 16 1.25 mm 2
wire gauge are 85o C above 600V.
This model AVR corrects this problem by sensing
directly from the output of the generator being The EXT.VR connection wires must be insulated.
being it 220, 380, or 490 volts.
3. ADJUSTMENTS
1. When the rated phase voltage of the generator is
220VAC, the input terminals B, C and sensing Set voltage setting for 220V / 380V / 440V and
terminals A, C are the same (as in frequency setting for 50/60HZ is show in figure7.
figure 3. factory setting). or connect double check the voltage/frequency setting
independent. (as show as figure 2). before start the generator.
2. But when the voltage of the generator is 380V,
CAUTION :
480V, the power input terminals B, Cand sensing
terminals A, C are c o n n e c t e d separatel y THE GENERATOR OR AVR MAY BE DAMAGED
(as show in Figure 4 or figure 5). Power inputs IF THE VOLTAGE / FREQUENCY SELECTOR
B and C must never go over 300 VAC. SETTING IS SET WRONG.
2 AVR 63-5
UFRO DIP: build-up voltage for the regulator. If reversing the field
Close - refer to solid curve in Figure 8. wires does not induce build-up, and the
Open - refer to dotted curve in Figure 8. residual voltage is less than then 5 Vac, stop
the engine and proceed with the next steps
5. TROUBLE SHOOTING
AVR 63-5 3
6. FIGURE AND SIZE
220/208V-50/60HZ
Single Phase
N
R
S G
T
~
UFRO
Field
DIP
Fig.1
220V/50HZ
N
ON
R C B A F+ F-
S G 1 2 3 Volt Fig
~ Frequency
123
ON
T Selector
220V/60HZ
ON
Field
1 2 3
1000 OHM
EXT. VR
Selector
220V/60HZ
ON
N 380/480V-50/60HZ
12 3
1000 OHM R
EXT. VR
S G
U/F STAB VOLT UFRO T
~
Fig. 2 DIP
Field
N
R
S G
T
~ 380/480V-50HZ
ON
Auxiliary C B A F+ F-
Winding Field 1 2 3 Volt /
Frequency
123
ON
Selector
380/480-60HZ
ON
220V/50HZ 1 2 3
1000 OHM
ON EXT. VR
C B A F+ F-
12 3 Volt / U/F STAB VOLT UFRO
Frequency DIP
1 2 3
Selector
220V/60HZ
Fig. 4
ON
12 3
1000 OHM
EXT. VR
DIODE
BATT.
Field
440V/50HZ
ON
C B A F+ F- C B A F+ F-
123 Volt / Volt /
Frequency
1 2 3
Frequenc y
1 2 3
ON
ON
Selector Selector
440V/60HZ
ON
12 3 1000 OHM
EXT.
100 VR
0 OHM EXT. VR
12 3 12 3 12 3 12 3 12 3 12 3
Figure 7
120 120
GENERATOR OUTPUT VOLTAGE
100 100
( % OF MONINAL)
( % OF MONINAL)
80 80
50HZ
60HZ
60 60
40 40
20 20
0 10 20 30 40 50 60 0 1 2
FREQUENCY (HZ) SOFT START (V/Sec)