Spec Technical Dry TRafo EAton
Spec Technical Dry TRafo EAton
Spec Technical Dry TRafo EAton
6 Transformers
Transformer Standards, Technical Data and Accessories
Typical Data for 600-Volt Class General-Purpose Dry-Type Transformers, Aluminum Wound
9
9 Type DS-3 150°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20º) % Regulation Inrush
9 No Total at Full 100% 80%
% Imp.
Trise
X
Trise
R
Trise Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF +20 +20 +20 Level dB Efficiency Max. Max.
9 15 246 80 549 97.6 97.6 97.2 96.6 2.0 2.9 4.3 3.0 3.1 45 97.70 737 245
25 359 300 848 97.7 98.1 97.9 97.5 1.4 2.7 3.5 2.8 2.2 45 98.00 1139 379
9
37.5 374 125 1314 98.1 97.8 97.2 96.6 2.2 4.6 5.8 4.8 3.2 45 98.20 1066 355
9 50 555 300 1668 98.2 98.1 97.6 97.0 1.9 4.0 5.1 4.3 2.7 45 98.30 1585 528
75 740 170 2266 98.4 98.2 97.6 97.0 2.3 5.3 6.9 6.3 2.8 50 98.50 2105 701
9 100 841 260 2543 98.5 98.4 98.0 97.6 1.9 4.7 6.1 5.6 2.3 50 98.60 2834 944
167 1610 900 3987 68.7 98.7 98.4 98.0 1.4 6.8 9.7 9.5 1.8 55 98.70 1250 416
9
9 Type DS-3 115°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20º) % Regulation Inrush
9 No Total at Full 100% 80%
% Imp.
Trise
X
Trise
R
Trise Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF +20 +20 +20 Level dB Efficiency Max. Max.
9 15 246 80 519 97.8 97.8 97.3 96.8 2.1 3.1 3.9 2.6 2.9 45 97.70 773 244
9 25 373 300 766 97.7 98.1 98.0 97.7 1.4 2.8 3.3 2.8 1.9 45 98.00 1102 367
37.5 380 125 1182 98.2 98.4 98.1 97.8 2.0 3.1 4.1 2.9 2.8 45 98.20 616 205
9 50 590 300 417 98.4 98.3 97.9 97.4 1.8 4.1 5.2 5.2 0.2 45 98.30 1553 511
75 689 170 2356 98.5 98.2 97.6 97.0 2.7 5.6 6.9 6.3 2.9 50 98.50 1717 572
9
9 Type DS-3 80°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20º) % Regulation % Imp. X R Inrush
9 No Total at Full 100% 80% Trise Trise Trise Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF +20 +20 +20 Level dB Efficiency Max. Max.
9 15 360 115 269 97.4 98.3 98.4 98.4 0.8 1.7 2.0 1.8 1.0 45 97.70 1381 460
25 370 120 580 97.8 98.2 98.0 97.8 1.5 3.2 3.9 3.4 1.8 45 98.00 1046 348
9 37.5 565 150 834 98.1 98.4 98.1 97.8 1.5 3.3 4.1 3.6 1.8 45 98.20 1471 490
9 50 680 175 1014 98.4 98.5 98.4 98.1 1.5 3.4 4.2 3.9 1.7 45 98.30 1733 577
75 900 260 1387 98.3 98.6 98.5 98.2 1.4 3.5 4.3 4.0 1.5 50 98.50 2423 807
9
9 Type DT-3 150°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20º) % Regulation % Imp. X R Inrush
9 No Total at Full 100% 80% Trise Trise Trise Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF +20 +20 +20 Level dB Efficiency Max. Max.
9 15 204 95 778 96.6 96.7 96.0 95.1 4.8 4.0 4.8 1.4 4.6 45 97.00 382 127
30 291 165 1207 97.2 97.3 96.9 96.2 3.7 5.6 4.6 3.0 3.5 45 97.50 479 159
9 37.5 381 210 1428 97.5 97.5 97.0 96.4 3.5 5.5 4.5 3.1 3.2 45 97.70 484 161
45 351 210 1911 97.5 97.4 96.7 96.0 3.8 6.3 5.1 3.4 3.8 45 97.70 564 188
9 50 531 270 1316 97.7 98.1 97.9 97.5 2.2 4.0 3.2 2.4 2.1 45 98.00 999 333
9 75 553 300 2917 97.9 97.7 97.0 96.3 3.6 6.6 5.3 4.0 3.5 50 98.00 561 187
112.5 793 400 3693 98.0 98.0 97.5 96.9 3.2 7.5 6.0 5.2 2.9 50 98.20 1049 350
9 150 913 490 4923 98.2 98.0 97.5 96.9 3.2 6.5 5.3 4.4 3.0 50 98.30 1518 506
225 1343 650 6476 98.4 98.2 97.8 97.2 2.8 6.3 5.1 4.4 2.6 55 98.50 2204 734
9 300 1597 750 8239 98.5 98.3 97.9 97.3 2.9 8.9 7.6 7.2 2.5 55 98.60 2097 699
500 2590 1400 9782 98.6 98.7 98.5 98.1 1.9 8.2 7.2 7.0 1.7 60 98.70 3769 1256
9
750 3340 1800 12,692 98.8 98.9 98.7 98.4 1.8 8.9 8.0 7.9 1.5 64 98.80 4521 1507
9
Typical Data for 600-Volt Class General-Purpose Dry-Type Transformers, Aluminum Wound
9
9 Type KT-4 115°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20º) % Regulation Inrush
9 No Total at Full 100% 80%
% Imp.
Trise
X
Trise
R
Trise Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF +20 +20 +20 Level dB Efficiency Max. Max.
9 15 307 135 394 96.3 97.5 97.6 97.5 1.8 2.7 2.2 1.4 1.7 45 97.00 491 163
30 313 165 1344 97.4 97.3 96.6 95.9 4.1 5.1 4.6 2.4 3.9 45 97.50 584 194
9
45 400 220 1463 97.8 97.9 97.5 97.0 3.0 6.1 5.2 4.4 2.8 45 97.70 591 197
9 75 587 285 2355 97.9 97.9 97.5 97.0 2.9 6.7 5.9 5.2 2.8 50 98.00 823 274
112.5 947 470 2910 97.9 98.1 97.9 97.5 2.4 5.0 4.3 3.7 2.2 50 98.20 1447 482
9 150 1243 560 4119 98.1 98.2 97.8 97.4 2.5 6.6 5.7 5.2 2.4 50 98.30 1468 489
225 1680 700 5413 98.3 98.3 98.1 97.7 2.3 7.5 7.0 6.7 2.1 55 98.50 1719 573
9 300 2480 1100 5735 98.4 98.7 98.5 98.2 1.8 6.7 6.3 6.1 1.5 55 98.60 2547 849
9
Type KT-4 80°C Rise NEMA TP-1 Efficient
9
Losses in Watts Efficiency (Trise +20º) % Regulation % Imp. X R Inrush
9 kVA Weight
No
Load
Total at
Rise +20 25% 50% 75%
Full
Load
100%
PF
80%
PF
Trise
+20
Trise
+20
Trise
+20
Sound
Level dB
TP1
Efficiency
Absolute
Max.
Practical
Max.
9 15 378 165 416 96.4 97.6 97.7 97.6 1.7 2.9 2.5 1.9 1.7 45 97.00 482 160
30 365 188 877 97.2 97.7 97.6 97.2 2.4 3.9 3.5 2.6 2.3 45 97.50 583 194
9 45 550 285 1055 97.4 98.1 98.0 97.8 1.8 3.7 3.4 2.9 1.7 45 97.70 708 236
75 774 360 1784 97.8 98.2 98.0 97.7 2.0 4.7 4.5 4.0 1.9 50 98.00 986 328
9 112.5 1380 550 1872 97.9 98.5 98.5 98.4 1.3 4.2 4.2 4.1 1.2 50 98.20 1577 525
150 1604 700 2728 98.0 98.5 98.5 98.3 1.4 4.4 4.5 4.3 1.4 50 98.30 1880 626
9 225 2336 850 3728 98.4 98.7 98.6 98.4 1.4 5.0 5.2 5.1 1.3 55 98.50 2647 882
9 300 2689 1100 4589 98.4 98.8 98.7 98.5 1.4 5.5 5.8 5.6 1.2 55 98.60 2610 870
9
Type KT-13 150°C Rise NEMA TP-1 Efficient
9 Losses in Watts Efficiency (Trise +20º) % Regulation % Imp. X R Inrush
No Total at Full 100% 80% Trise Trise Trise Sound TP1 Absolute Practical
9 kVA Weight Load Rise +20 25% 50% 75% Load PF PF +20 +20 +20 Level dB Efficiency Max. Max.
15 271 165 604 96.7 97.3 97.0 96.5 3.1 4.2 3.6 2.1 2.9 45 97.00 379 126
9 30 365 198 977 97.1 97.6 97.3 96.9 2.7 4.3 3.5 2.4 2.6 45 97.50 565 188
45 545 280 1215 97.5 98.0 97.8 97.4 2.2 4.2 3.3 2.6 2.1 45 97.70 890 277
9 75 812 360 2139 97.7 98.0 97.8 97.4 2.6 5.9 4.9 4.3 2.4 50 98.00 907 302
112.5 920 490 3059 98.0 98.2 97.8 97.4 2.4 5.0 4.1 3.4 2.3 50 98.20 1513 504
9 150 1221 530 4297 98.1 98.1 97.7 97.2 2.7 6.5 5.3 4.6 2.5 50 98.30 1790 597
9 225 1960 830 4461 98.3 98.6 98.3 98.0 1.9 6.6 6.1 5.9 1.6 55 98.50 1771 590
300 2358 1100 5931 98.4 98.6 98.4 98.2 1.9 7.2 6.3 6.0 1.6 55 98.60 2543 847
9
9
9
9
9
9
9
kVA Weight
No
Load
Total at
Rise +20 25% 50% 75%
Full
Load
100%
PF
80%
PF
Trise
+20
Trise
+20
Trise
+20
Sound
Level dB
TP1
Efficiency
Absolute
Max.
Practical
Max.
9
15 315 165 536 96.4 97.3 97.2 96.9 2.5 3.9 3.6 2.5 2.5 45 97.00 375 125
9
30 408 188 854 97.4 97.9 97.7 97.3 2.3 4.0 3.6 2.8 2.2 45 97.50 497 166
45 555 280 982 97.6 98.2 98.2 98.0 1.6 3.2 3.0 2.5 1.6 45 97.70 656 218 9
75 838 400 1289 97.8 98.4 98.5 98.4 1.3 3.0 2.9 2.6 1.2 50 98.00 1624 541
112.5 1367 550 1905 97.9 98.5 98.5 98.4 1.3 4.2 4.4 4.2 1.2 50 98.20 1171 390 9
150 1607 668 2474 98.2 98.6 98.6 98.4 1.4 4.6 4.7 4.5 1.2 50 98.30 1562 520
225 2582 850 3471 98.3 98.7 98.7 98.5 1.3 5.1 6.3 6.2 1.2 55 98.50 2159 719
9
300 3228 1100 3978 98.3 98.8 98.8 98.7 1.1 4.2 4.5 4.3 1.0 55 98.60 3255 1085 9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Typical Data for 600-Volt Class General-Purpose Dry-Type Transformers, Copper Wound
9
9 Type DS-3 150°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 No Total at Full 100% 80% % Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF Imp. X R Level dB Efficiency Max. Max.
9 15 270 80 605 97.6 97.5 96.9 96.3 3.5 4.2 4.2 2.3 3.5 45 97.70 551 183
25 406 115 732 97.9 98.1 97.7 97.3 — — 3.5 2.5 2.5 45 98.00 1379 459
9
37.5 453 125 1154 98.2 98.1 97.6 97.0 2.7 3.7 4.8 4.0 2.7 45 98.20 1321 440
9 50 657 160 1159 98.3 98.4 98.1 97.7 2.0 3.3 3.8 3.8 2.0 45 98.30 1321 440
75 803 175 2259 98.5 98.3 97.7 97.1 2.8 4.8 6.5 5.8 2.8 50 98.50 2133 711
9 100 960 250 2504 98.6 98.4 98.0 97.5 2.3 4.3 5.5 5.0 2.3 50 98.60 2779 926
167 1665 570 3094 98.7 98.8 98.6 98.3 1.5 6.3 9.0 8.8 1.5 50 98.70 2865 955
9
9 Type DS-3 115°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 No Total at Full 100% 80% % Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF Imp. X R Level dB Efficiency Max. Max.
9 15 264 80 437 97.8 98.1 97.8 97.3 2.4 2.2 3.3 2.2 2.4 45 97.70 718 239
9 25 420 110 603 97.9 98.2 98.0 97.7 2.0 2.9 3.2 2.6 2.0 45 98.00 862 287
37.5 450 125 1217 98.2 98.0 97.5 96.9 2.9 4.5 5.9 5.1 2.9 45 98.20 1300 433
9 50 703 300 1409 98.4 98.4 98.0 97.6 2.2 3.8 4.7 4.1 2.2 — 98.30 1498 499
75 793 175 2178 98.5 98.3 97.8 97.2 2.7 4.7 6.2 5.6 2.7 50 98.50 2107 702
9
9 Type DS-3 80°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 No Total at Full 100% 80% % Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF Imp. X R Level dB Efficiency Max. Max.
9 15 407 115 293 97.3 98.2 98.3 98.2 1.2 1.7 1.8 1.4 1.2 45 97.70 375 125
25 430 300 679 97.9 98.4 98.3 98.1 1.5 2.6 3.0 2.6 1.5 45 98.00 494 164
9 37.5 685 300 729 98.1 98.6 98.6 98.5 1.1 2.2 2.6 2.3 1.1 45 98.20 617 205
9 50 799 180 1013 98.3 98.6 98.4 98.1 1.7 2.9 3.4 2.9 1.7 45 98.30 989 329
75 1042 250 1447 98.3 98.6 98.4 98.1 1.6 3.4 3.8 3.5 1.6 50 98.50 1015 338
9
9 Type DT-3 150°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 No Total at Full 100% 80% % Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF Imp. X R Level dB Efficiency Max. Max.
9 15 250 150 755 98.9 97.0 96.4 95.7 4.2 5.3 4.8 2.6 4.0 45 97.00 321 107
30 350 165 1100 97.3 97.5 97.0 96.5 3.2 4.5 5.2 4.1 3.1 45 97.50 614 204
9 37.5 415 210 1382 97.5 97.6 97.1 96.5 3.2 4.8 4.0 2.5 3.1 45 97.70 639 213
45 416 215 1786 97.4 97.4 96.9 96.2 3.6 5.5 4.6 3.0 3.5 45 97.70 637 212
9 50 647 270 1220 97.7 98.2 98.0 97.7 2.0 3.5 2.8 2.0 1.9 45 98.00 1072 357
9 75 643 320 2903 97.9 97.5 97.1 96.4 3.6 7.4 4.3 2.5 3.4 50 98.00 1015 338
112.5 876 420 3699 97.9 97.9 97.4 96.8 3.0 6.7 5.1 4.2 2.9 50 98.20 1185 395
9 150 1064 530 4269 98.1 98.2 97.8 97.3 2.7 5.3 4.3 3.5 2.5 50 98.30 1752 584
225 1569 560 7124 98.4 98.1 97.5 97.0 3.2 8.7 7.4 6.8 2.9 55 98.50 2498 832
9 300 2050 730 7959 98.4 98.3 97.9 97.4 2.6 6.7 5.5 4.9 2.4 55 98.60 2872 964
500 3681 1400 8292 98.8 98.9 98.7 98.4 1.6 7.4 6.8 6.7 1.4 60 98.70 3839 1279
9
9
Typical Data for 600-Volt Class General-Purpose Dry-Type Transformers, Copper Wound
9
9 Type KT-4 115°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 No Total at Full 100% 80% % Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF Imp. X R Level dB Efficiency Max. Max.
9 15 256 95 702 96.7 96.9 96.3 95.6 4.2 5.7 5.0 2.9 4.0 45 97.00 279 93
30 341 165 1007 97.4 97.6 97.3 96.8 3.0 4.8 4.2 3.1 2.8 45 97.50 466 155
9
45 526 220 1200 97.9 98.1 97.9 97.5 2.3 5.0 4.1 3.5 2.2 50 97.70 633 211
9 75 759 300 1715 98.1 98.3 98.1 97.8 1.9 5.0 4.5 4.1 1.9 50 98.00 929 309
112.5 1030 470 2735 98.0 98.3 98.0 97.7 2.2 4.4 3.8 3.2 2.0 50 98.20 1171 390
9 150 1631 650 3076 98.2 98.5 98.3 98.1 1.7 4.9 4.5 4.2 1.6 50 98.30 1250 416
225 1965 690 4434 98.5 98.6 98.4 98.1 1.9 5.6 5.3 5.0 1.7 55 98.50 1979 659
9 300 2337 830 6127 98.6 98.7 98.4 98.0 2.0 5.2 4.7 4.3 1.8 55 98.60 2187 729
9
Type KT-4 80°C Rise NEMA TP-1 Efficient
9
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 kVA Weight
No
Load
Total at
Rise +20 25% 50% 75%
Full
Load
100%
PF
80%
PF
%
Imp. X R
Sound
Level dB
TP1
Efficiency
Absolute
Max.
Practical
Max.
9 15 365 165 371 97.0 98.0 98.1 98.0 1.5 2.3 2.1 1.5 1.4 45 97.00 499 166
30 424 210 787 97.3 97.9 97.8 97.6 2.0 3.2 2.9 2.2 1.9 45 97.50 659 219
9 45 653 290 977 97.4 98.1 98.1 98.0 1.6 3.1 3.0 2.5 1.5 45 97.70 925 308
75 640 350 1951 97.8 98.1 97.8 97.5 2.2 5.2 4.9 4.4 2.1 50 98.00 854 284
9 112.5 1264 560 2009 98.2 98.7 98.6 98.4 1.4 4.3 4.2 4.0 1.3 50 98.20 1449 483
150 1825 650 2873 98.5 98.7 98.5 98.2 1.6 6.1 6.4 6.3 1.5 50 98.30 1288 429
9 225 2096 890 4449 98.3 98.6 98.4 98.1 1.8 6.5 6.6 6.4 1.6 55 98.50 2292 764
9
Type KT-13 150°C Rise NEMA TP-1 Efficient
9
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 kVA Weight
No
Load
Total at
Rise +20 25% 50% 75%
Full
Load
100%
PF
80%
PF
%
Imp. X R
Sound
Level dB
TP1
Efficiency
Absolute
Max.
Practical
Max.
9 15 346 165 461 96.2 97.4 97.5 97.3 2.1 3.0 2.5 1.6 2.0 45 97.00 527 176
30 390 190 908 97.2 97.7 97.5 97.1 2.6 4.0 3.3 2.3 2.4 45 97.50 579 193
9 45 623 235 1328 97.6 97.9 97.6 97.2 2.5 3.2 2.8 1.4 2.4 45 97.70 854 285
75 848 370 2402 97.7 97.9 97.5 97.0 2.8 5.7 4.5 3.6 2.7 50 98.00 1046 348
9 112.5 1080 455 2991 98.0 98.2 97.9 97.4 2.4 4.3 3.5 2.7 2.3 50 98.20 1180 393
150 1431 600 3686 98.2 98.3 98.1 97.7 2.3 5.1 4.2 3.7 2.1 50 98.30 1250 416
9 225 2129 830 4250 98.4 98.6 98.4 98.2 2.0 6.3 5.4 5.1 1.5 55 98.50 2771 923
9
9 Type KT-13 115°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 kVA Weight
No
Load
Total at
Rise +20 25% 50% 75%
Full
Load
100%
PF
80%
PF
%
Imp. X R
Sound
Level dB
TP1
Efficiency
Absolute
Max.
Practical
Max.
9 15 341 165 378 96.6 97.8 97.9 97.9 1.5 2.4 2.1 1.6 1.4 45 97.00 472 157
30 444 188 824 97.1 97.8 97.6 97.3 2.2 3.6 3.1 2.2 2.1 45 97.50 620 206
9 45 598 250 1476 97.4 97.7 97.4 96.9 2.8 4.6 4.0 2.9 2.7 45 97.70 939 313
75 894 350 2128 97.9 98.1 97.9 97.5 1.9 5.1 4.6 4.0 2.4 50 98.00 847 282
9 112.5 1054 460 2612 98.1 98.3 98.1 97.8 2.0 4.3 3.3 2.6 1.9 50 98.20 1375 458
150 1399 600 3185 98.2 98.5 98.3 98.0 2.0 5.9 5.4 5.1 1.7 50 98.30 1379 460
9
225 2088 890 4382 98.3 98.6 98.4 98.2 1.8 6.1 5.7 5.5 1.6 55 98.50 2490 830
9
kVA Weight
No
Load
Total at
Rise +20 25% 50% 75%
Full
Load
100%
PF
80%
PF
%
Imp. X R
Sound
Level dB
TP1
Efficiency
Absolute
Max.
Practical
Max.
9
15 335 78 353 97.4 98.0 98.0 97.7 2.0 3.7 3.2 2.6 1.8 45 98.00 287 96
9
30 406 125 670 98.0 98.3 98.1 97.8 1.9 2.7 2.4 1.5 1.8 45 98.30 780 260
45 635 135 1075 98.6 98.5 98.2 97.7 2.3 4.1 3.5 2.8 2.1 45 98.50 603 201 9
75 870 210 1551 98.5 98.6 98.3 98.0 1.9 4.0 3.6 3.1 1.8 50 98.60 958 319
112.5 1526 350 1583 98.6 98.9 98.8 98.6 1.2 3.0 2.7 2.5 1.1 50 98.80 2480 827 9
150 1665 350 2463 98.8 98.9 98.7 98.4 1.6 4.5 4.2 4.0 1.4 50 98.90 1930 643
225 2094 650 3766 98.8 98.9 98.7 98.4 1.7 5.5 5.2 5.0 1.4 55 99.00 2778 926
9
9
9
9
9
9
9
9
9
Typical Data for 600-Volt Class General-Purpose Dry-Type Transformers, Copper Wound
9
9 Type NON HMT 115°C Rise NEMA TP-1 Efficient
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 No Total at Full 100% 80% % Sound TP1 Absolute Practical
kVA Weight Load Rise +20 25% 50% 75% Load PF PF Imp. X R Level dB Efficiency Max. Max.
9 15 362 80 527 97.6 97.7 97.3 96.7 3.2 5.9 5.1 4.2 3.0 45 97.00 — —
30 430 100 1040 98.3 98.0 97.4 96.7 3.2 6.2 5.4 4.4 3.1 45 97.50 — —
9
45 627 170 1368 98.3 98.2 97.7 97.2 2.8 6.0 5.2 4.4 2.7 45 97.70 — —
9 75 926 250 2096 98.4 98.3 97.9 97.4 2.6 7.0 6.2 5.7 2.5 50 98.00 — —
112.5 1628 400 2515 98.4 98.5 98.3 97.9 2.0 5.5 4.9 4.5 1.9 50 98.20 — —
9 150 2001 500 2688 98.5 98.7 98.6 98.3 1.6 5.6 5.2 5.0 1.5 50 98.30 — —
225 3596 590 3310 98.8 98.9 98.8 98.6 1.5 6.2 6.0 5.9 1.2 55 98.50 — —
9 300 3891 800 4854 98.7 98.9 98.7 98.4 1.7 7.1 7.0 6.8 1.4 55 98.60 — —
9
Type THR HMT 115°C Rise NEMA TP-1 Efficient
9
Losses in Watts Efficiency (Trise +20°) % Regulation Inrush
9 kVA Weight
No
Load
Total at
Rise +20 25% 50% 75%
Full
Load
100%
PF
80%
PF
%
Imp. X R
Sound
Level dB
TP1
Efficiency
Absolute
Max.
Practical
Max.
9 15 — 80 708 97.1 97.0 96.4 95.5 4.3 7.4 6.3 4.7 4.2 45 97.00 — —
30 450 100 1409 98.0 97.4 96.5 95.6 4.7 8.0 6.8 5.2 4.4 45 97.50 — —
9 45 610 170 1374 98.2 98.1 97.7 97.1 2.8 4.8 4.2 3.2 2.7 45 97.70 — —
75 868 250 2341 98.2 98.1 97.6 97.0 2.9 6.6 5.8 5.0 2.8 50 98.00 — —
9 112.5 1643 400 2685 98.3 98.4 98.1 97.7 2.2 5.5 5.0 4.6 2.0 50 98.20 — —
150 — 500 3304 98.5 98.6 98.3 97.9 2.0 6.7 6.3 6.0 1.9 50 98.30 — —
9 225 3370 590 3712 98.7 98.8 98.7 98.4 1.7 6.6 6.4 6.2 1.4 55 98.50 — —
9 300 3894 800 4688 98.9 99.0 98.8 98.5 1.7 7.4 7.2 7.1 1.3 55 98.60 — —
9
9
9
9
9
9
9
9
9
9
9
9
9
9
Note
9
1 Currently being reviewed and revised by NEMA.
9
9
9
9
9
Typical Specifications—
9 Dry-Type Transformers for Nonlinear Loads
9 General Core and Coil Assemblies Enclosures Nonlinear Ratings
Furnish and install, Transformer core shall be The enclosure shall be made Harmonic K-4 K-13
9 individually mounted dry-type constructed with high-grade, of heavy gauge steel and
Fundamental 100.0% 100.0%
transformers of the two- non-aging, silicon steel with shall be finished utilizing a
continuous process of 3rd 34.0% 70.0%
9 winding type, self-cooled,
with ratings and voltages as
high magnetic permeability,
and low hysteresis and eddy degreasing, cleaning and 5th 22.0% 42.0%
indicated on the drawings. current losses. Maximum phosphatizing, followed by
9 magnetic flux densities electrostatic deposition of a
7th 3.0% 5.0%
Transformers shall be shall be substantially below polymer polyester powder 9th 1.0% 3.0%
9 manufactured by Eaton. the saturation point. The coating and baking. The 11th 0.7% 3.0%
Transformers shall be transformer core volume shall coating color shall be ANSI 61 13th 0.5% 1.0%
9 designed, manufactured allow efficient transformer and shall be UL recognized
15th 0.3% 0.7%
and tested in accordance operation at 10% above the for outdoor use. The
nominal tap voltage. The core maximum temperature
9 with all the latest applicable
laminations shall be tightly on top of the enclosure
17th 0.3% 0.6%
ANSI, NEMA and IEEE
Standards. All 600-volt clamped and compressed. shall not exceed 90°C. Tests
9 class transformers through The following tests shall be
Transformer coils shall be The enclosure construction
500 kVA shall be UL listed shall be ventilated, NEMA 2, performed as standard on all
9 as suitable for non-sinusoidal
wound of electrical-grade
[aluminum] [copper] drip-proof, with lifting transformers:
current loads with K factor conductor with continuous provisions. All ventilation
9 not to exceed [4] [13] [20]. wound construction. An openings shall be protected
1. Ratio tests at the rated
voltage connection and
electrostatic shield consisting against falling dirt. On at all tap connections.
9 Insulation Systems of a single turn of aluminum outdoor units, provide
Transformers shall be shall be placed between the suitable weathershields 2. Polarity and phase
9 insulated with a UL
recognized 220°C
primary and secondary over ventilation openings. To relation tests on the
rated voltage connection.
winding and grounded to the ensure proper ventilation,
insulation system. Winding transformer core. BIL (basic locate the unit at least 6
9 temperature rise shall be impulse level) for all 600-volt inches (152.4 mm) from the 3. Applied potential tests.
[80°C] [115°C] [150°C]. class windings shall be 10 kV. adjacent wall or structure. 4. Induced potential test.
9
Required performance The core and coil assembly Nonlinear Ratings 5. No-load and excitation
shall be obtained without
9 exceeding the above
shall be installed on vibration-
absorbing pads.
The transformers shall be current at rated voltage
specifically designed to on the rated voltage
indicated temperature rise in connection.
9 a 40°C maximum ambient, The neutral conductor shall supply circuits with a
with a 30°C average. be rated to carry 200% of harmonic profile equal to or
less than a K-factor of 4 or 13 Sound Levels
9 All insulation materials shall
normal phase current.
as described below without Transformer average sound
be flame-retardant and shall exceeding [80°C] [115°C] levels shall not exceed the
9 not support combustion as [150°C] temperature rise. following ANSI and NEMA
defined in ASTM Standard levels for self-cooled ratings
9 Test Method D635. measured in accordance with
NEMA ST-20.
9
Average Sound Levels 1
9 NEMA ST-20 Average Sound Level in dB
Up to 1.2 kV Above 1.2 kV
9 kVA Ventilated Encapsulated Ventilated
0–9 40 45 45
9 10–50 45 50 50
51–150 50 55 55
9 151–300 55 57 58
9 301–500 60 59 60
501–700 62 61 62
9 701–1000 64 63 64
1001–1500 65 64 65
9 Note
1 Currently being reviewed and revised by NEMA.
9
9
Typical Specifications—
9 Mini–Power Centers (3–30 kVA)
9 General Core and Coil Assemblies Tests
Furnish and install, single- 1. All interconnecting wiring Transformer core shall be The following tests shall be
9 phase and three-phase between the primary constructed with high-grade, performed as standard on all
general-purpose individually breaker and transformer, non-aging, silicon steel with transformers:
9 mounted mini–power centers secondary main breaker high magnetic permeability,
and low hysteresis and eddy 1. Ratio tests at the rated
of the two-winding type, and transformer, and
current losses. Maximum voltage connection and
self-cooled, with ratings distribution section shall
9 and voltages as indicated be factory installed. Main magnetic flux densities shall at all tap connections.
on the drawings. Mini– primary, secondary and be substantially below the 2. Polarity and phase
9 power centers shall be feeder breakers shall saturation point. relation tests on the
manufactured by Eaton. be enclosed with a rated voltage connection.
The transformer core
9 Units shall be designed,
padlockable hinged door.
volume shall allow efficient 3. Applied potential tests.
manufactured and tested in 2. The secondary transformer operation at
9 accordance with all the latest distribution section shall 10% above the nominal tap 4. Induced potential test.
applicable ANSI, NEMA, accommodate one-inch, voltage. The core laminations
5. No-load and excitation
9 IEEE, CSA and UL standards, plug-in breakers with shall be tightly clamped and
current at rated voltage
and shall be UL listed and 10 kA interrupting compressed. Coils shall be
on the rated voltage
9 CSA certified and bear the capacity. wound of electrical-grade
connection.
UL and CSA labels. aluminum (copper) with
3. On the all-copper, bolt-on continuous wound
9 Units shall be designed for designs, the secondary construction. BIL (basic
Sound Levels
continuous operation at distribution section shall impulse level) for all 600-volt Transformer average sound
9 rated kVA, 24 hours a day, accommodate bolt-on class windings shall be 10 kV. levels shall not exceed the
365 days a year, with normal breakers with 10 kA following ANSI/NEMA levels
life expectancy as defined in interrupting capacity. The core and coil assembly for self-cooled ratings
9 ANSI C57.96. shall be completely measured in accordance
Insulation System encapsulated in a with NEMA ST-20.
9 Each mini–power center shall
Transformers shall be proportioned mixture
include a main primary breaker of resin or expoxy and
insulated with a 180°C Average Sound Levels 1
9 with an interrupting rating aggregate to provide a
insulation system.
of 14 kA at 277/480 volts; moisture-proof, shock- NEMA Average
an encapsulated dry-type kVA Sound Level in dB
Required performance resistant seal. The core
9 transformer and a secondary shall be obtained without and coil encapsulation 0–9 45
panelboard with main breaker exceeding the above system shall minimize the
9 rated 10 kA interrupting rating indicated temperature rise sound level.
10–30 50
24 hours. by NEMA.
The enclosure shall be made
9 All insulation materials shall of heavy-gauge steel and
be flame-retardant and shall shall be finished using a
9 not support combustion as continuous process of
degreasing, cleaning, and
defined in ASTM Standard
phosphatizing, followed by
9 Test Method D635.
electrostatic deposition of
a thermosetting polymer
9 polyester powder coating
and subsequent baking. The
9 coating color shall be ANSI 61
and shall be UL recognized
9 for outdoor use. Mini–power
centers shall be equipped
with a wiring compartment
9 suitable for conduit entry
and large enough to allow
9 convenient wiring. The
maximum temperature on
9 top of the enclosure shall
not exceed 90°C. The core
of the transformer shall be
9 grounded to the enclosure.
The enclosure shall be totally
9 enclosed, non-ventilated,
NEMA 3R, with lifting eyes.
9
Low voltage winding: In a Phase: Type of AC electrical Sound levels: All Transformer tests:
9 two-winding transformer, the circuit; usually single-phase transformers make some Per NEMA ST-20, routine
winding intended to have two- or three-wire, or three- sound mainly due to the transformer production
9 the lesser voltage. Usually phase three- or four-wire. vibration generated in its tests are performed on
marked with “X” core by alternating flux. All each transformer prior to
designations. Polarity test: A standard test Eaton general-purpose dry- shipment. These tests are:
9 on transformers to determine type distribution transformers Ratio tests on the rated
Mid-tap: See center tap. instantaneous direction of are designed with sound voltage connection; Polarity
9 Noise level: The relative
the voltages in the primary levels lower than NEMA and Phase Relation tests on
compared to the secondary. ST-20 maximum levels. the rated connection; No-
intensity of sound, measured
9 in decibels (dB). NEMA Primary taps: Taps added to Star connection: Same as a
Load and Excitation Current
Standard ST-20 outlines the primary (input) winding. tests at rated voltage on the
wye connection.
9 the maximum allowable See Tap. rated voltage connection and
noise level for dry-type Step-down transformer: Applied Potential and Induced
Primary voltage: The input Potential tests. Special tests
9 transformers.
circuit voltage.
A transformer where the
include sound level testing.
input voltage is greater than
Nonlinear load: A load the output voltage.
9 where the current waveform Power factor: The cosine of Transverse mode: Electrical
does not conform to that of the phase angle between a Step-up transformer: noise or voltage disturbance
voltage and a current. that occurs between phase
9 the applied voltage, or where A transformer where the
and neutral, or from spurious
a change in current is not Ratio test: A standard test of input voltage is less than
proportional to a change in the output voltage. signals across metallic hot
9 applied voltage.
transformers to determine
line and the neutral
the ratio of the input (primary) T-T connection: See Scott T conductor.
9 Non-ventilated voltage to the output connection.
transformer: A transformer (secondary) voltage. Turns ratio: The ratio of the
Tap: A connection brought out number of turns in the high
9 where the core and coil
assembly is mounted inside
Reactance: The effect of of a winding at some point voltage winding to that in the
inductive and capacitive between its extremities,
an enclosure with no low voltage winding.
9 openings for ventilation. Also
components of a circuit
producing other than unity
usually to permit changing
the voltage or current ratio. Typical test data: Tests that
referred to as totally enclosed power factor. were performed on similar
9 non-ventilated (TENV). Taps are typically used to
units that were previously
Reactor: A single winding compensate for above or
No load losses: Losses in a below rated input voltage, manufactured and tested.
9 transformer that is excited at
device with an air or iron
in order to provide the rated
core that produces a UL (Underwriters
rated voltage and frequency specific amount of inductive output voltage. See FCAN Laboratories): An
9 but that is not supplying a reactance into a circuit. and FCBN. independent safety
load. No load losses include Normally used to reduce testing organization.
9 core losses, dielectric losses Temperature class: The
of control current. maximum temperature that
and conductor losses in the Universal taps: A
Regulation: Usually the insulation system of a
9 winding due to the exciting
current. Also referred to as expressed as the percent transformer can continuously
combination of six primary
voltage taps consisting of
excitation losses. change in output voltage withstand. The common 2 at +2-1/2% FCAN and
9 when the load goes from insulation classes are 105, 4 at -2-1/2% FCBN.
Overload capability: Short- full load to no load. 150, 180 (also 185) and 220.
9 term overload capacity is
Scott T connection: Temperature rise: The
Watt: A unit of electrical
designed into transformers as power when the current in a
required by ANSI. Continuous Connection for three-phase increase over ambient circuit is one ampere and the
9 overload capacity is not transformers. Instead of temperature of the windings voltage is one volt.
deliberately designed into using three sets of coils due to energizing and loading
9 a transformer because the for a three-phase load, the the transformer. Wye connection: A standard
design objective is to be transformer uses only two three-wire transformer
Total losses: The sum connection with similar
9 within the allowed winding sets of coils. of the no-load losses and ends of single-phase coils
temperature rise with load losses.
Series/multiple winding: connected together. The
9 nameplate loading.
A winding consisting of two Totally enclosed non- common point forms the
Percent IR (% resistance): or more sections that can ventilated enclosure: The electrical neutral point and
9 Voltage drop due to be connected for series core and coil assembly is may be grounded. Also
resistance at rated current operation or multiple (parallel) installed inside an enclosure referred to as three-phase
9 in percent of rated voltage. operation. Also called series-
parallel winding.
that has no ventilation to four-wire. To obtain the line-
cool the transformer. The to-neutral voltage, divide the
Percent IX (% reactance): line voltage by 3 ( 1.732 ) .
9 Voltage drop due to Short circuit: A low transformer relies on heat
to radiate from the enclosure
reactance at rated current resistance connection,
for cooling.
9 in percent of rated voltage. usually accidental, across
part of a circuit, resulting in
Percent IZ (% impedance): excessive current flow.
9 Voltage drop due to
impedance at rated current
9 in percent of rated voltage.
Can transformers be connected Why is the impedance of a What clearances are required
9 in parallel? transformer important? around transformers when they
Yes, with certain restrictions. The impedance of a are installed?
9 For single-phase transformers transformer is important All dry-type transformers
being connected in parallel, because it is used to depend upon the circulation of
9 the voltages and impedances determine the interrupting air for cooling; therefore, it is
of the transformers must be rating and trip rating of the important that the flow of air
equal (impedances must be circuit protection devices on around a transformer not be
9 within 7.5% of each other). the load or line side of the impeded. UL 1561 requires
For three-phase transformers, transformer. To calculate that there be no less than
9 the same restrictions apply as the maximum short circuit 6 inches (152.4 mm)
for single-phase transformers, current on the load side of clearance between any
9 plus the phase shift of the a transformer, use the side transformer with
transformers must be the following formula: ventilation openings and
any wall or obstruction.
9 same. For example, a delta-
wye–connected transformer Maximum Short Circuit = In compliance with
Load Current (Amps) NEC 450-9, Eaton’s ventilated
(30° phase shift) must be
9 connected in parallel with Full Load Current (Amps) transformers have a note on
another delta-wye–connected Transformer Impedance their nameplates requiring
9 transformer, not a delta-delta
Full load current for single-
a minimum of 6 inches
connected–transformer (152.4 mm) clearance from
phase circuits is:
9 (0° phase shift). the ventilation openings and
walls or other obstructions.
Nameplate Volt-Amps
--------------------------------------------------------------------- This clearance only addresses
9 Load (output) Voltage
the ventilation needs of the
and for three-phase circuits, transformer. There may
9 the full load current is: be additional local codes
and standards that affect
Nameplate Volts-Amps
9 ---------------------------------------------------------- installation clearances.
Load (output) Volts × 3
Transformers should not be
9 Example: For a standard mounted in such a manner
three-phase, 75 kVA that one unit will contribute
9 transformer, rated 480 volt to the additional heating
delta primary and 208Y/ of another unit, beyond
9 120 volt secondary (catalog
number V48M28T75J) and
allowable temperature limits,
for example, where two units
impedance equal to 5.1%, are mounted on a wall one
9 the full load current is: above the other.
9 75,000 VA
------------------------------- 208.2A
208V × 1.732
9 The maximum short circuit
load current is:
9 208.2A
----------------------- = 4, 082.4A
0.051
9
The circuit breaker or fuse
9 on the secondary side of this
transformer would have to
have a minimum interrupting
9 capacity of 4083 amperes at
208 volts. NEMA ST-20 (1992).
9 A similar transformer with
lower impedance would
9 require a primary circuit
breaker or fuse with a higher
9 interrupting capacity.
9
9
9
9