0% found this document useful (0 votes)
548 views1 page

Design Analysis: Proposed 1 Unit 2 CL Building For Capiniahan Primary School

The document provides design analysis and branch circuit calculations for a building's power and lighting layout. It includes a scale drawing showing the layout of circuits 1-3, which are for light outlets and convenience outlets. It also includes a single line diagram showing the circuit layout and branch circuit protection using 15A and 20A circuit breakers. The design analysis was approved by officials from the Department of Public Works and Highways.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
548 views1 page

Design Analysis: Proposed 1 Unit 2 CL Building For Capiniahan Primary School

The document provides design analysis and branch circuit calculations for a building's power and lighting layout. It includes a scale drawing showing the layout of circuits 1-3, which are for light outlets and convenience outlets. It also includes a single line diagram showing the circuit layout and branch circuit protection using 15A and 20A circuit breakers. The design analysis was approved by officials from the Department of Public Works and Highways.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

REPUBLIC OF THE PHILIPPINES

A B C
DESIGN ANALYSIS DPWH
18.0
BRANCH CIRCUIT CALCULATION OFFICE OF THE BUILDING OFFICIAL

9.0 9.0 CIRCUIT 1 - LIGHT OUTLET CIRCUIT 2 - LIGHT OUTLET

I = 4 X 100 / 0.80 (220) I = 4 X 100 / 0.80 (220)


APPROVED:
= 2.27 AMPERE = 2.27 AMPERE
USE 2-#14 THHN CU.WIRE USE 2-#14 THHN CU.WIRE
BUILDING OFFICIAL
1 BRANCH CIRCUIT PROTECTION BRANCH CIRCUIT PROTECTION
USE 15 AT 2P C.B USE 15 AT 2P C.B
1-14 THHN CU.WIRE (GROUND) 1-14 THHN CU.WIRE (GROUND)
3.50

3.50
CIRCUIT 3 - CONVENIENCE OUTLET CIRCUIT 3 - CONVENIENCE OUTLET

CEMENT FINISHED CEMENT FINISHED I = 3 X 180 / 220 I = 3 X 180 / 220


7.00

7.00
2 = 2.46 AMPERE = 2.46 AMPERE
USE 2-#12 THHN CU.WIRE USE 2-#12 THHN CU.WIRE

BRANCH CIRCUIT PROTECTION BRANCH CIRCUIT PROTECTION


3.50

3.50
USE 20 AT 2P C.B USE 20 AT 2P C.B APPROVED:
1-#12 THHN CU.WIRE (GROUND) 1-#12 THHN CU.WIRE (GROUND)

S2 S2
3 M SECTION CHIEF
9.0 9.0

18.0

C3 C4
C1 C2

POWER & LIGHTING LAYOUT


SCALE 1:100M
SINGLE LINE DIAGRAM GENERAL NOTES
M TO SERVICE DROP

100 AT

15 AT 15 AT
C1 L.O. L.O. C2

20 AT 20 AT
C3 C.O. C.O. C4

LEGENDS
1-#10 THHN CU.WIRE
SYMBOLS DESCRIPTION QUANTITY (GROUND)

LIGHT OUTLET 8PCS.

DUPLEX CONVENIENCE OUTLET 6PCS.


SCHEDULE OF LOADS:
S2 TWO GANG SWITCH 2PCS. CIRCUIT NO. DESCRIPTION UNIT LOAD AMPERE VOLTS CIRCUIT PROTECTION SIZE OF CONDUIT SIZE AND TYPE OF WIRE

CIRCUIT LINE (light oulet) 2- #14 THHN CU.WIRE


CIRCUIT 1 LIGHT OUTLET 4 2.27 220 15 AT 1- #14 THHN CU.WIRE
CIRCUIT LINE (conv. outlet)
2- #14 THHN CU.WIRE
CIRCUIT LINE (Switch outlet) CIRCUIT 2 LIGHT OUTLET 4 2.27 220 15 AT 1- #14 THHN CU.WIRE

PANEL DISTRIBUTION BOARD 2- #12 THHN CU.WIRE


CIRCUIT 3 CONVENIENCE OUTLET 3 2.46 220 20 AT 1- #12 THHN CU.WIRE
CIRCUIT HOMERUN
2- #12 THHN CU.WIRE
SERVICE ENTRANCE CIRCUIT 4 CONVENIENCE OUTLET 3 2.46 220 20 AT 1- #12 THHN CU.WIRE

CIRCUIT BREAKER
2- #30 THHN CU.WIRE
TOTAL CONNECTED LOAD 9.46 220 100 AT 1- #8.0 THHN CU.WIRE
M KILOWATT HOUR METER

DRAFTED AND AUTOCAD BY: CERTIFIED BY: PROJECT TITLE AND LOCATION: SHEET CONTENTS: REVISIONS: SHEET NO.

PRC NO.: LIGHTING LAYOUT DESIGN ANALYSIS

PTR NO.:

DATE ISSUED:
PROPOSED 1 UNIT 2 CL BUILDING
FOR CAPINIAHAN PRIMARY SCHOOL
POWER LAYOUT
E
PAULINE JOY B. AQUINO
DRAFSTMAN
TOMAS LAUREA
CIVIL ENGINEER
PLACE ISSUED:
TIN: BARANGAY CAPINIAHAN,LEMERY ILOILO
LEGEND & SYMBOL
SCHEDULE OF LOADS
SINGLE LINE DIAGRAM