ELECTRICAL LOAD SCHEDULE
Date Revision Status Description Prepared by Checked by Approved by
E
DOCUMENT NO. :
ABSORBED MOTOR LOAD FACTOR EFFICIENCY POWER FACTOR
EQUIPMENT LOAD RATING =A/B at load at load factor C kW = A/D
factor C
Description
Continuous
Essential
A B C D E
Normal
Equipment
Duty
Vital
No.
kW kW In decimals In decimals Cos φ kW kVAr
NORMAL LOAD BUS - A
MCC-001 MCC 001 X - - - - - 120.37 72.43
General X 12.91 9.68
Max. of normal running plant load: x= 100
133 kW, 82 kVAr, √(kW² + kVAr²) = 157 kVA TOTAL 133 82
(Est. x %E + y %F) y= 50
Peak load: z= 10
(Est. x %E + y %F + z%G)
133 kW, 82 kVAr, √(kW² + kVAr²) = 157 kVA
kVA=√(kW²+kVAr²) 157
Coincidence factors x, y and z shall be defined for each separate case, subject to Principal's approval.
TRANSFORMER/MAIN GENERATOR RECOMMENDATIONS
SUMMARY KW KVAR KVA
Normal running load 133 82 157
250KVA GENATOR IS RECOMMENDED FOR THE MAIN OPE
TWO BOOSTER PUMPS.
Running Load With 20% for Future expansion
160 99 188
( Contigency)
20% allowance since the generator can not be
operated beyond 80% of their capacity at peak 192 118 225 OPERATING PHILOSOPHY
load
kVAr = kW*tan j
Intermittent Stand-by
Remarks
kW kVAr kW kVAr
0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00
0 0 0 0
kVAr
0 0
ATIONS
FOR THE MAIN OPERATION OF THE
R PUMPS.
HILOSOPHY
EQUIPMENT ABSORBED MOTOR LOAD FACTOR EFFICIENCY POWER FACTOR
LOAD RATING =A/B at load at load factor C kW = A/D*C
Operating Voltage
factor C
Essential
Normal
Equipment Continuous Intermittent
Duty
Vital
Description A
E
No. B C D
kW kW In decimals In decimals Cos φ kW kVAr kW
PBA-0201 BOOSTER PUMP C X 380 63.46 75.00 0.85 0.96 0.86 56.17 33.33
PBA-0202 BOOSTER PUMP C X 380 63.46 75.00 0.85 0.96 0.86 56.17 33.33
P-005 GENERATOR HOUSE C X 240 1.24 0.80 0.80 0.80 1.93 1.15
P-007 BOOSTER PUMP HOUSE C X 240 0.80 0.80 0.80 0.80 1.25 0.76
P-006 24VDC UNITERRUPTIBLE POWER SUPPLY UPS C X 240 1.00 0.80 0.80 0.80 1.00 1.56
P-007 CONTROL SWITCH DB C X 415 1.24 0.80 0.80 0.80 1.93 1.15
P-008 GENERAL SERVICE DB C X 415 1.24 0.80 0.80 0.80 1.93 1.15
Max. of normal running plant load: x= 100
120 kW, 72 kVAr, TOTAL 120 72 0
(Est. x %E + y %F) y= 50
140.48
√(kW² + kVAr²) = KVA
Peak load: 120 kW, 72 kVAr, z= 10
√(kW² + kVAr²) = 140 KVA
kVA=√(kW²+kVAr²) 140 0
Coincidence factors x, y and z shall be defined for each separate case, subject to Principal's approval.
NOTES: b) Absorbed loads: c) Consumed loads:
a) Load classification: - for pumps, shaft load on duty point. C - ''Continuous"; all loads that may
"Vital", "Essential" and - for lighting, during dark hours. continuously be required for normal operation
' Normal Load '' operation including lighting
kVAr = kW*tan j
Intermittent Stand-by Remarks
FLA 1.25*FLA BREAKER
RATING
kVAr kW kVAr
121.33 151.66 200.00
121.33 151.66 200.00
3.73 4.66 6.00
1.39 1.74 4.00
3.01 3.76 5.00
3.73 4.66 6.00
3.73 4.66 6.00
0 0 0
209 261 400 0.85686
power factor for the MCC
0 0
ABSORBED EQUIPMENT LOAD FACTOR EFFICIENCY POWER FACTOR
EQUIPMENT LOAD RATING =A/B at load at load factor C
factor C
Operating Voltage
Load Duty
Essential
Normal
Equipment
Vital
Description A B C D E
No.
kW kW In decimals In decimals Cos φ
LIGHTING (SWITCHGEAR ROOM) C X 240 0.60 NA 1.00 1.00 0.80
13A SOCKET OUTLET (SWITCHGEAR ROOM) C X 240 0.30 NA 0.80 1.00 0.80
15A SOCKET OUTLET (SWITCHGEAR ROOM) C X 240 1.50 NA 0.80 1.00 0.80
30A SOCKET OUTLET (SWITCHGEAR ROOM) C X 240 3.00 NA 0.80 1.00 0.80
LIGHTING (GENERATOR HOUSE) C X 240 1.12 NA 0.80 1.00 0.80
13A SOCKET OUTLET (GENERATOR HOUSE) C X 240 0.30 NA 0.80 1.00 0.80
30A SOCKET OUTLET (GENERATOR HOUSE) C X 240 3.00 NA 0.80 1.00 0.80
1.25KW UPS(LOCATED IN SWITCH GEAR ROOM) -UPS 004 C X 240 1.26 NA 0.80 0.80 0.80
LIGHTING (BOOSTER PUMP HOUSE) C X 240 0.80 NA 0.80 1.00 0.80
LIGHTING (BOOSTER PUMP HOUSE) C X 240 0.40 NA 1.00 1.00 0.80
13A SOCKET OUTLET (BOOSTER PUMP HOUSE) C X 240 0.30 NA 0.80 1.00 0.80
30A SOCKET OUTLET (BOOSTER PUMP HOUSE) C X 240 3.00 NA 0.80 1.00 0.80
Max. of normal running plant load: x= 100
13 kW, 10 kVAr, √(kW² + kVAr²) = 16 kVA TOTAL
(Est. x %E + y %F) y= 50
Peak load: z= 10
13 kW, 10 kVAr, √(kW² + kVAr²) = 16 kVA
(Est. x %E + y %F + z%G)
kVA=√(kW²+kVAr²)
Coincidence factors x, y and z shall be defined for each separate case, subject to Principal's approval.
NOTES: b) Absorbed loads: c) Consumed loads: S-''Stand - by"; loads required in
a) Load classification: - for pumps, shaft load on duty point. C - ''Continuous"; all loads that may emergencies only, such as Spare
"Vital", "Essential" and - for instrumentation, computers, communication, & air continuously be required for normal operation pumps or those of not normally
' Normal Load '' condit'g, the required load during full operation of plant. operation including lighting and workshops running electrically driven units &
- for lighting, during dark hours. I - ''Intermittent and spares"; the loads required for electrical stand - by (rarely operate
- for workshops, the average total load in normal full intermediate pumping, storage, loading, etc normal conditions (e.g.spare produ
operation. products standby pumps)
kW = A/D*C kVAr = kW*tan j
Continuous Intermittent Stand-by Remarks
FLA 1.25*FLA BREAKER
RATING
kW kVAr kW kVAr kW kVAr
0.60 0.45 3.13 3.91 4.00
0.24 0.18 1.56 1.95 2.00
1.20 0.90 7.81 9.77 10.00
2.40 1.80 15.63 19.53 20.00
0.90 0.67 5.83 7.29 4.00
0.24 0.18 1.56 1.95 2.00
2.40 1.80 15.63 19.53 20.00
1.26 0.94 6.54 8.17 40.00
0.64 0.48 4.17 5.21 6.00
0.40 0.30 2.08 2.60 4.00
0.24 0.18 1.56 1.95 2.00
2.40 1.80 15.63 19.53 20.00
13 10 0 0 0 0
22 28 25
22 28
16 0 0
Stand - by"; loads required in
ergencies only, such as Spare
mps or those of not normally
nning electrically driven units &
ctrical stand - by (rarely operate under
rmal conditions (e.g.spare products pumps)
oducts standby pumps)