DHL Revised Electrical Load
DHL Revised Electrical Load
DHL Revised Electrical Load
Dear Sir:
Sending herewith at your end is the final load computation and design of tenant “DHL” including the additional
load at zone-4 and DHL office located at Admin Office.
Page 1 of 2
COMPUTATION:
IT = 1.732 [48.78 + (0.25 x 17.00)] x 0.70 D.F.
= 91.85 AMPS.
SIZE OF WIRE : 3-30 MM2 THW CU. WIRE
PROTECTION : USE 150AT225AF. 2P, 240V CIRCUIT BREAKER
II. REMARKS:
1. In the previous set-up, the total connected load of DHL is 10.357 kilowatts
2. The type of service for the previous set-up is single phase system, 220 volts, 60 Hz with
2-22 mm2 THW copper wire power supply coming from the source.
3. In the current set-up, the total connected load increases to 24.329 kilowatts, meaning the total
Connected, double compared to the previous set-up
4. Due to the increase of connected load, the existing 2-22 mm2 single phase feeder line of DHL is no
longer sufficient to carry the entire load of the present set-up
III. RECOMMENDATIONS:
1. Convert the single phase system feeder line of DHL to three-phase system, 220 volts, 60 Hz..
2. Provide 3-30 mm2 THW copper wire from the Electrical Room to the Main Circuit breaker of DHL
3. Provide three-phase kilowatt-hour meter to DHL as the prescribe kwhr meter
SUBMITTED BY:
Page 2 of 2