Wiring Modifiacations For Automation
Wiring Modifiacations For Automation
Modifications in sequencer
Sequencer out put Q45-Q59 to be assigned to the following sequencer states. This requires software
modification as shown
Note that N/O contacts of the relays RL45 –RL59 & RL61-RL62 are already wire to TB2 terminal
45T&B – 59T&B
To generate the following indications wire the Extra N/O contact of the following relays to TB2 the
sequencer failure alarm still has to be engineered
On the circuit Breaker control supply cct change the ferrule L200 (TB2 /112T+TB2/113B) and Link
terminal (LK17) to L210 and L201 (TB2/ 94b +TB2/24B) and fuse terminal (FS17) to L211. This is
R6
9 11 To New relay panel
R7 B50X1.116 L4
R8
To New relay panel
L1 B50X1.118
Single pair twisted screened cables to be used for the transducer out puts the cable s to run
from the transducers to the S800 remote I/O box
Temperature Indications
Check the indicator manual for terminal Numbers for the analogue outputs
Temperature Indicator
Temperature sensor
Pressure indications
The pressure traducers available are the Two wire transducers rated for 24 V input and 4-20
ma output connections as shown below.
+24V Trans
ducer
-VE Bn 4-20mA signal
4-20mA
S800
analogue
Input An
Channel-n
n
For the following signals going to the control room loop from the terminals indicated to the
spare cores in the 37 core linking the remote control junction box to the Annanciator
terminate the spare cores on free terminal on the Annanciator
For the Alarm supply fail alarm wire the N/O contact on the DCF (terminal 9&11) relay
wire No’s Ax7 & Ax8
For the Emergency drain pump Running Alarm supply fail alarm wire the N/O contact on
the EDPRR(terminal 9&11) wire No’s ax9 & ax10
For the SDR operated alarm use the spare contacts on the SDR wire No Z79 and Z100
Use one N/O contact on the TCHWL relay or wire another relay of there is no volt free
contact available .Use wire No’s Ax5 & Ax6
Auto/Manual Indication
Use free N/O contact on 43A wire No’s Ax1& Ax2 to be wired to TB1on turbine panel
Use free N/C contact on 43B wire No’s Ax3& Ax4 to be wired to TB1on turbine panel
Modify the wiring for the sequence input I03 so as to introduce a relay contact in serIes as
shown below to facilitate reset of the auto-synch from remote
43B
W1143
The output of the water flow transmitter is to be connected in series with one analogue input
channel ch14 as shown below
Protronic
Display Unit
Water 1
flow
transmit 2 3
ter
S800
Terminal 2 &3 to remain Analogue
Bridged until S800 is powered input
channel
The signal for the lake level and the Tailrace level to be connected to the S800 on Unit one.
AI channels 15 & 16. These are two wire transducers to be connected the same way as the
pressure transducers show above.
Road
Existing Holes
- - - - - - - - -
- - - - - - -
Water in Tail Race
- - - - - - - - -
- - - - - -
- - - - - - -
- - - - - -
Level sensor Shielding Pipe
- - - - - - -
- - - - - -
Water At intakes
- - - - - - -
- - - - - -
- - - - - - -
- - - - - -
Level sensor Shielding Pipe
1.0
------------ - - - - - - - - - - - - - - -
- - - - - - - - - - - -- -- -- ---
-- - ----- -- --- - - sensor cable
Sensor
Intake tunnel
Intake rake
Original
DI Description ca Alarm Name in Dbase Dbase Channel Relay Test Points Test Points S800
No ble /indic No Relay coil Relay coil ccabl
ation e
termi
nal
14 Trip CCT fail Alarm 2 Alarm G5A51-PROT6 DI800_51.14 R14 U1007 U1008 566 569 566 569
19 Excitation Build up failure 3 Alarm G5AG6-EX1 DI800_52.3 31TX N/A N/A 1721 1722 572 586
26 Air flow failure 3 Alarm G5AG6-EX8 DI800_52.10 44AAF& N/A N/A U1021 U1022 579 586
44BAF
37 Field contactor closed 3 Ind G5AG6- DI800_53.5 41X & N/A N/A 1723 1724 591 603
EXFCC Q61
38 POWER SYSTEM Stabiliser 3 Alar G5AG6- DI800_53.6 98F N/A N/A U1051 U1052 592 603
failed EXFCO
39 Standby control/ manual 3 Ind G5AG6-EX19 DI800_53.7 43SXE N/A N/A Ax23 Ax24 593 603
control
56 Speed signal fault 4 Ind G5A32-SEQ17 DI800_54.8 Q56 N/A N/A 1711 1712 611 620
58 Battery Faulty 4 Ind G5A32-SEQ19 DI800_54.10 Q58 N/A N/A 1715 1716 613 620
97 Alarm supply fail 6 Alar G5A14-COM7 DI800_57.1 DCFFl Ax7 Ax8 650 654
m
93 Unit Txco2 isolated 6 Ind G5A51- DI800_56.13 R49
PROT12
58 Battery Faulty 4 Ind G5A32-SEQ19 DI800_54.10 Q58 N/A N/A 1715 1716 613 620
Q62 1721 1722
93 Alarm supply fail- Unit 6 Alar G5A51- DI800_56.13 DI800_57.1 R49
97 Txco2 isolated m PROT12
G5A14-COM7
97 Unit Txco2 isolated Alarm 6 Ind G5A14-COM7 DI800_57.1 DI800_56.13 DCFFl Ax7 Ax8 650 654
93 supply fail- G5A51-
PROT12