Digital Outputs Schematics
Digital Outputs Schematics
Digital Outputs Schematics
Interface ……… From Turbine& Seq… TO S800 I/O… via relay panel…………….
Cable NO:New……………………. Cores………..
Turbine
Panel
W1143 TB1/2B
Circuit breaker closing circuit modified by to prevent ACB closure from control room when Auto sychn is selected (RL65B energised)
*50V supply fuse and link from J13 and J14 added
J14 -50V
fuse
ACB Turbine panel Sequencer control Room
W12 L211
(-50v)
W12B TB2/79T
Close
RL 72
W11 (+50v)
R.C J.B
(+50v)
Control Room Intake Rem. control Junc. Box Intake Gate Panel
FCB
220Vdc
+ve No Box
Gate Closed Junction
in turbine Hall
To Trip Solenoid
Z165 Z164
Automation
R53
Notes J13
J14
Z161
The gate-trip-interposing relay has polarity: will not work if terminals are reversed
The Intake gate trip circuit picks up the positive supply from Earth as shown in the switch. (The
50V battery positive terminal is earthed.)
L41 has to be connected to –ve(J14) since the other tail of the lamp in CR is conneted to
+ve(old drawing indicates L41 on +ve) 04/01/2002