100% found this document useful (1 vote)
254 views1 page

Battery Testing Schedule IEEE NERC

This document provides recommended testing schedules for various types of batteries based on standards from IEEE and NERC. It lists monthly, quarterly, yearly, and other periodic tests that should be performed on vented lead acid batteries, nickel cadmium batteries, and valve regulated lead acid batteries. These tests include visual inspections, recording voltage, current, temperatures, specific gravities, and conducting load tests. The schedules are intended to meet minimum regulatory requirements and IEEE recommendations.

Uploaded by

nasrun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
254 views1 page

Battery Testing Schedule IEEE NERC

This document provides recommended testing schedules for various types of batteries based on standards from IEEE and NERC. It lists monthly, quarterly, yearly, and other periodic tests that should be performed on vented lead acid batteries, nickel cadmium batteries, and valve regulated lead acid batteries. These tests include visual inspections, recording voltage, current, temperatures, specific gravities, and conducting load tests. The schedules are intended to meet minimum regulatory requirements and IEEE recommendations.

Uploaded by

nasrun
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SBS’s Recommended Testing Schedule  – Meets the minimum requirements of NERC PRC-005-2*

Based on IEEE & NERC PRC-005  or  – Meets IEEE Recommendations*

IEEE 450-2010
Vented / Flooded Lead Acid Batteries (VLA) Test Equipment
Monthly Quarterly Yearly 5 Years
Visually inspect batteries, rack, charger, room.   
Record battery system float voltage and current at battery terminals. SBS-600   
Record charger output voltage and current. Correct if needed. SBS-600   
Check electrolyte levels. Fill with distilled water to 'max' line if necessary.   
Record ambient/room temperature.   
Make sure ventilation system is operational.   
Inspect system for unintentional battery grounds. SBS-600   
Record pilot cell(s) or block(s) voltage, electrolyte temperature and specific gravity †. SBS-2003 and SBS-600 
Record voltage of ALL cells/blocks. SBS-600, SBS-6500 
Record specific gravity of 10% of the cells†. SBS-2003, SBS-2500, SBS-3500 
Record temperature of 10% of the cells. 
Record specific gravity of ALL cells†. SBS-2003, SBS-2500, SBS-3500 
Record the internal resistance value of ALL cells/blocks. SBS-6500  
Record temperature of ALL cells/blocks. SBS-6500 
Record internal resistance value of ALL cell-to-cell and terminal connections. SBS-6500 
Conduct load test two years after installation and then every five years. When the
SBS-8400, SBS-1230, SBS-1110 
system’s capacity falls below 90% load test annually.

Specific gravity should be temperature-corrected to 77°F.
BATTERY TESTING SCHEDULE

IEEE 1106-2005
Nickel Cadmium Batteries Test Equipment Semi-
Quarterly Yearly 5 Years
Yearly
Visually inspect batteries, rack, charger, room.   
Record battery system float voltage and current at battery terminals. SBS-600   
Record charger output voltage and current. Correct if needed. SBS-600   
Check electrolyte levels. Fill with distilled water to 'max' line if necessary.   
Record ambient/room temperature.   
Make sure ventilation system is operational.   
Inspect system for unintentional battery grounds. SBS-600   
Record voltage of ALL cells/blocks. SBS-600, SBS-6500  
Record temperature of 10% of the cells. SBS-6500   
Record the internal resistance value and temperature of ALL cells/blocks. SBS-6500 
Record internal resistance value of ALL cell-to-cell and terminal connections. SBS-6500 
Conduct load test two years after installation and then every five years. When
SBS-8400 
excessive capacity loss is noticed load test annually.

IEEE 1188-2005
Valve Regulated Lead Acid Batteries (VRLA) Test Equipment
Monthly Quarterly Yearly 2 Years
Visually inspect batteries, rack, charger, room.   
Record battery system float voltage and current at battery terminals. SBS-600   
Record charger output voltage and current. Correct if needed. SBS-600   
Record ambient/room temperature.   
Make sure ventilation system is operational.   
Inspect system for unintentional battery grounds. SBS-600   
Record voltage and temperature of ALL cells/blocks at the negative terminal. SBS-6500  
Record the internal resistance value of ALL cells/blocks. SBS-6500  
Record internal resistance value of ALL cell-to-cell and terminal connections. SBS-6500 
Conduct load test after initial installation and then every two years or 25% of
SBS-8400 
expected battery life.

*The above testing schedules are based on SBS’s interpretations of both IEEE and NERC PRC-005-2. This information should be used for guidance
purposes only and SBS can’t be held responsible if the information is incorrect or if other parties interpret the information differently.

ii www.sbsbattery.com 1-800-554-2243 [email protected]