4004R (Simplex Panel)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Release Control Fire Alarm Systems

UL, ULC Listed; FM 4004R Suppression Releasing Panel for Automatic


and CSFM Approved* Extinguishing, Deluge and Preaction Sprinkler Control

Features Agent discharge path

Fire alarm control panel designed specifically for


suppression release operation with: Actuator
Agent
source
Actuator
circuit
• Four initiating device circuits (IDCs)
• Two notification appliance circuits (NACs) Coil
supervisory
RED
N AC+
COIL SUPERVISION MODULE (2 AMP) 2081-9046
INSTALLATION INSTRUCTIONS 574-437 REV
MAINTAIN 1/4" SEPARATION
BETWEEN POW ER LIMITED
(RED /BLK) AND NONPOWER
LIMIT ED (YEL/BLK) W IRING
YEL

• Two releasing appliance circuits (RACs)


DATE CODE: 519-958
BLK
N AC-
BLK SIM P LE X T IM E RECORDE R CO. GA RDNER MA . US A

module

• Two special purpose monitor inputs (SPMs) that accept


manual release request and manual abort request for
Agent Release systems, and waterflow and supervisory
NORMAL

Maintenance Switch
0

DISC./
1
DISABLE

FIRE SUPPRESSION

for Preaction or Deluge systems DISCONNECT / DISABLE

• Three auxiliary relays with selectable functions RAC 1 RAC 2


• Easily selected activity timing options FIRE SUPPRESSION
SYSTEM ABORT SPM 1
NAC 1
Suppression release operation includes: PUSH AND HOLD

• Automatic extinguishing release SPM 2


Alarm
Zone 1
Manual Release

• Deluge and preaction sprinkler system release


Trouble Zone 5 Trouble

Alarm Manual Release

IDC 1 Trouble
Zone 2 Zone 6 Trouble
CAUTION
Alarm NAC 1 Trouble DISCONNECT

Trouble
Zone 3 NAC 2 Trouble

Alarm RAC 1 Trouble

Trouble
Zone 4 RAC 2 Trouble

• Dual or single hazard area protection


BATTERY AND
A. C. POWER
Alarm Silenced Agent Released BEFORE
SERVICING
Supervisory Earth Fault

System Trouble Abort Active

AC Power Relay Disconnect

NAC 2
• IDCs are selectable for cross-zoning or for activation
from a single detection input IDCs 2, 3, and 4

• Short circuit RAC supervision


4004R Suppression Release Panel
Audible Escalation of Events:
4004R Suppression Release Panel
• Temporal or 20 bpm March Time pattern for first One-Line System Reference Drawing
cross-zone alarm
• 120 bpm March Time pattern to indicate release timer Introduction (Continued)
active
Flexible I/O Capabilities. Four IDCs allow for either
• On steady to indicate release timer expired and actuator
four separately monitored zones or two, cross-zoned
is activated
connections. Two SPMs allow dedicated manual inputs for
Operator interface provides: release or abort, or waterflow and supervisory, depending
• Status LEDs per circuit for Alarm, Trouble, and on system type. Two releasing appliance circuits (RACs)
Supervisory (where appropriate) supervise to the actuator coils and activate the actuators
• Acknowledge, Alarm Silence, and System Reset when required. The two NACs and the three panel auxiliary
• Operating mode selection and timer selections when in relays provide status condition information.
programming mode Easy Program Selections. The operator panel has a
Compatible with Listed/Approved 24 VDC or program mode that allows selection of panel operation
2, 12 VDC series connected actuators type and detailed operating selections using an easily
Required system components: selected sequential programming operation.
• Coil supervision module 2081-9046, one per RAC History Log. The last 50 events are stored in
• Maintenance Switch, one per RAC non-volatile memory. This information is accessed by
Recommended accessory (where appropriate): connecting a technician’s computer to the service port
which is also used to set the date and time.
• Abort Switch
Listed to: Panel Feature Description
• UL Standard 864 Operator Panel. The operator panel has alarm and
• ULC Standard S527-99 trouble status indicating LEDs for each input and output,
visible through the locking cabinet door (refer to diagram
Introduction on page 3). Unlocking the door provides access to the
Dedicated for Suppression Release. 4004R Acknowledge, Alarm Silence, and System Reset
Suppression Release Panels provide conventional fire pushbutton switches.
alarm control circuits and are equipped with the features * This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7165-0026:314
required for a wide variety of single or dual hazard for allowable values and/or conditions concerning material presented in this document. It is
suppression release applications. Capabilities include subject to re-examination, revision, and possible cancellation. This product was not approved
by MEA (NYC) as of document revision date. Additional listings may be applicable; contact
automatic extinguishing agent release and deluge and your local Simplex® product supplier for the latest status. Listings and approvals under
preaction sprinkler control. Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster
S4004-0002-1 3/2003
Panel Feature Description (Continued) Two Class B Releasing Appliance Circuits (RACs).
Rated 2 A each, these circuits are dedicated to operating
Four Class B IDCs provide coverage for either two release control actuators. RAC cutout timing is selectable
cross-zoned areas or four separately zoned areas. IDCs are as no cutout, 45 seconds, or 1, 3, 4, 5, 6, or 7 minutes.
capable of supporting up to 30 Simplex current-limited Auxiliary Power Output. Two sets of output terminals
smoke detectors or electronic heat detectors (see list on are provided, one for continuous operation and the other
page 6) as well as manual stations and other compatible for resettable operation, rated for 750 mA combined.
contact closure initiating devices. IDCs are capable of Resettable terminals are provided for 4-wire smoke
Class A operation with an optional adapter module and can detector power.
be programmed as Style C (short or open initiates a trouble) Standard Auxiliary Relay Outputs. Three relay
for use with current limited devices only. Single hazard outputs are available, selectable as normally open or
agent release applications monitor pressure switches with normally closed, rated 2 A @ 30 VDC per below:
IDC 3 and tamper switches with IDC 4. Aux Relay 1 (Trouble) is energized when Normal and is
Two Class B Special Purpose Monitoring de-energized with a Trouble condition.
Circuits (SPMs) are dedicated for manual release or Aux Relays 2 and 3 respond differently depending on the
abort, or waterflow and supervisory, depending on system system type and whether single or dual hazard. Typical
type. Inputs are normally open switches. An abort switch functions are:
stops release while activated and upon deactivation, the For Single Hazard Operation, Aux Relay 2 is the Alarm
release operation occurs after a selectable time delay. relay. Aux Relay 3 can be selected to indicate
Manual release inputs override abort switches and pre-discharge (release time delay started), supervisory,
activate the release after selectable delays of from 0 to 30 waterflow, or pressure switch relay, depending on the
seconds in 5 second increments. For Dual Hazard system type.
applications, current limited abort operation is required.
For Dual Hazard Operation, Aux Relay 2 is for Hazard
SPMs are programmable as Style C and capable of Area 1 Alarm; Aux Relay 3 is for Hazard Area 2 Alarm.
Class A operation with the optional adapter module.
Power Supply and Battery Charger. During alarm,
Two Class B NACs are provided for reverse polarity the power supply provides 3 A at 25.5 VDC, filtered and
notification appliance operation, each rated 2 A. Class A regulated. The temperature compensated battery charger
operation is available with the optional adapter module. provides 27.5 VDC for charging batteries suitable for up to
NAC operation is selectable per application. 90 hour standby and 10 minutes of alarm. External battery
chargers and cabinets can be used for more battery backup.
Product Selection
Release Control Panels
Model Cabinet Color Description
4004-9301 Beige Basic Releasing Panel; operates with AC input of: 120/220/230/240 VAC, 50/60 Hz (auto-select);
includes: four IDCs, two NACs, two SPMs, two RACs, 3 Auxiliary relays, and 3 A power supply
4004-9302 Red with battery charger, cabinet and door
Expansion Modules
Model Description Reference
Auxiliary Relay Module; four relays with dual contacts per relay
4004-9860 selectable as N.O. or N.C.; rated 7 A @ 120 VAC, 5 A @ 30 VDC, Two maximum
unsupervised contacts Select as required
4004-9864 Two Circuit Class A Adapter Module for IDCs, SPMs, or NACs Four maximum
Accessories (Refer to data sheet S4081-0001 for external battery cabinets with chargers and for larger battery sizes)
Model Description Reference
2081-9272 6.2 Ah battery, 12 V Select one battery module per system
2081-9274 10 Ah battery, 12 V standby requirements; two batteries
2081-9288 12.7 Ah battery, 12 V are required
Remote Battery Meter Module, 0-50 VDC voltmeter and Mounting requires a four-gang box,
4001-9811
5-0-5 A ammeter with beige four-gang cover plate 1-3/4” (45 mm) minimum depth
Release Control System Modules
Model Description
2081-9046 Coil Supervision Module, one required per RAC; refer to pages 6 and 7 for detail
Abort Supervision Module; encapsulated 560Ω, 1/2 W resistor; for Dual Hazard SPM; allows non-current limited
2081-9048
Abort and Manual Release stations to be on same circuit; refer to pages 6 and 7 for detail
2080-9059* Maintenance Switch with Indicator Flush mount; mounts in double-gang electrical box 2-3/4” (70 mm) deep
2080-9060* Lamp; one required per RAC Surface mount, includes mounting box
2080 Series* Abort Switches, surface or flush mount; available standard or with internal 1.2 kΩ, 1 W resistor
* Refer to data sheet S2080-0010 for product details.

2 S4004-0002-1 3/2003
Programming Modes and Selection Choices
Sequence Programming Mode Description Choices
Cross-Zoned Combined Release
Single Hazard
Either Zone (RACs activate together)
Agent Release
Cross-Zoned Independent Release
Dual Hazard
Either Zone (RACs are separate)
1 Application Mode (9 choices) Cross-Zoned Combined Release
Single Hazard
Either Zone (RACs activate together)
Preaction/Deluge
Cross-Zoned Independent Release
Dual Hazard
Either Zone (RACs are separate)
Agent Release Single Hazard Cross-Zoned, NYC Abort (not UL listed)
2 IDC and SPM Circuit Style Class B/Class A or Style C
3 Automatic Release Time Delay 0, 10, 20, 30, 40, 50, or 60 seconds
4 RAC Cutout Timer No cutout, 45 seconds, or 1, 3, 4, 5, 6, or 7 minutes
5 Manual Release Time Delay 0, 5, 10, 15, 20, 25, or 30 seconds
UL Standard 864 listed Immediate or 10 seconds remaining
6 Abort Release Time Delay Not UL Standard 864 IRI abort (cross-zoned systems only), NYC abort, or
listed original release delay
7 NAC Coding (where selectable) Temporal pattern or 20 beats per minute (first cross-zone alarm)
No inhibit or one minute inhibit selected as: both on until silence, NAC 1 on until
8 NAC Operation
reset and NAC 2 on until silence, or both on until reset
9 Supervisory Latching Latching or non-latching
LED and tone-alert only, or with: NAC 2 also on; Aux Relay 3 also on; or both
10 Supervisory Notification
NAC 2 and Aux Relay 3 also on

Operator Panel Function Reference

LABEL INSERT selectable for Preaction/Deluge


or Agent Release, UL or ULC versions

Alarm Manual Release RUN MODE: red LEDs


Zone 1 indicate Manual Release
Trouble Zone 5 Trouble activated (for Agent
RUN MODE: LEDs provide Release Applications);
Alarm Manual Release
Alarm (red) and Trouble yellow LEDs indicate
(yellow) status per IDC zone Trouble
Zone 2 Zone 6 Trouble Trouble for SPMs (Zones 5
and 6), NACs, and RACs
Alarm NAC 1 Trouble
PROGRAM MODE: Zone 3
Top ten LEDs indicate
Trouble NAC 2 Trouble PROGRAM MODE:
Programming Mode Category Top nine LEDs provide
Alarm RAC 1 Trouble Programming Selection
Trouble
Zone 4 RAC 2 Trouble

Alarm Silenced Agent Released


Alarm Silenced yellow LED Agent Released red LED
indicates that audible Supervisory Earth Fault indicates RACs are activated
notification appliances are
silenced prior to system reset Earth Fault yellow LED
System Trouble Abort Active
indicates presence of an earth
Supervisory and System AC Power Relay Disconnect fault
Trouble yellow LEDs Abort Active yellow LED
ACK
ALARM SYSTEM tracks state of Abort Switch
AC Power green LED is on SILENCE RESET

with normal power status Relay Disconnect yellow LED


indicates that expansion relays
have been disabled for service

ACK acknowledges status during RUN mode SYSTEM RESET restores the system to
and accepts selection during PROGRAM mode; ALARM SILENCE
normal during RUN mode and toggles
press and hold for 5 sec to perform LAMP TEST silences audible alarms
the selection during PROGRAM mode

3 S4004-0002-1 3/2003
Release Control System Reference Requirements (Continued)
Automatic Extinguishing Release Systems. 4. For FM Approved Automatic Extinguishing Release,
These systems automatically activate actuators for the secondary standby must be a minimum of 24 hours
release of a fire extinguishing agent (such as dry with 5 minutes of alarm.
chemical, water spray, foam, CO2, or Halon) in response 5. For FM Approved Deluge and Preaction Sprinkler
to fire detection device input. operation: IDCs must be Class A, wired to
UL and FM Extinguishing Release System Panels Listed/Approved devices; secondary standby capacity
must have a minimum of 24 hours of standby power. must be a minimum of 90 hours with 10 minutes of
Initiating devices must be Listed/Approved for the alarm; and the specified compatible Automatic Water
application, and may be wired either Class A or B. Control Valves/Actuator must be used. (Refer to list
Actuators must be electrically compatible with the control on page 5.)
panel circuits and power supplies, and are wired Class B 6. Power supply loading and wiring distances must be
to provide coil supervision. per Installation, Programming, and Operating
Instructions 579-354.
Deluge and Preaction Sprinkler Systems
automatically activate water control valves in response to 7. Battery standby must be selected for a minimum
fire detection device input. voltage of 23 VDC to ensure proper valve operation.
(Contact your local Simplex product representative for
UL requirements for Fire Alarm Systems Listed for additional battery selection information, reference
Automatic Release or Deluge and Preaction Sprinkler battery selection chart 900-012.)
Systems are the same as described above for Automatic
8. Maintenance Switches are required, one per RAC, to
Extinguishing Release Systems.
ensure that notification circuits dedicated for releasing
FM Approved requirements for Fire Alarm Systems operation can be properly disabled prior to service.
for Automatic Release of Deluge and Preaction Sprinkler Simplex Maintenance Switches provide a status
Systems require operation of specific compatible FM indicator lamp that requires separate 24 VDC wiring
Approved Automatic Water Control Valves, a minimum and activates when the circuit is disconnected.
secondary power capacity of 90 hours, and all circuits for
the automatic release initiating devices must be capable of Additional System Device Information
operation during a single open circuit fault condition
(Class A). 1. Abort Switches are available when abort operation is
required. When used, wire on Special Purpose
Deluge Sprinkler Systems employ open sprinkler Monitoring Circuits (SPMs) as Class A or Class B.
heads and provide water flow when the fire detection
system activates a common automatic water control valve. 2. Manual Release Stations are used for direct activation
They are used to deliver water simultaneously through all of the release actuators with the appropriate time delay
of the system sprinkler heads. This type of system is implemented by the fire alarm control panel.
applicable where the immediate application of large 3. Reference for additional information is listed on
quantities of water over large areas is the proper fire page 6.
response.
Preaction Sprinkler Systems are similar to deluge Additional Information
systems except that normally closed sprinkler heads are This data sheet is a summary of the extensive operating
used and supervisory air pressure is maintained in the features and options available with the 4004R Release
pipe. Operation requires both an activated sprinkler head Control Panel. Complete details are covered in the 4004R
and an activated fire alarm initiating device. Installation, Programming, and Operating Instructions
manual (publication 579-354) shipped with each 4004R.
Release Control System Requirements Compatible system devices are listed on page 6.
1. Actuators are connected as two-wire, Class B For general information, refer to Factory Mutual Research
notification circuits with only one 24 VDC actuator Corporation (FMRC) “FMRC Approval Guide,” FM
per circuit (or two, 12 VDC actuators in series if Approval standard “Deluge Systems and Preaction
applicable) to ensure supervision. Systems.”
2. Coil Supervision Module, model 2081-9046, must be
PLEASE NOTE: Proper operation of release control
wired electrically before the actuator and located in
systems requires that the system design, installation, and
the actuator wiring junction box. (Refer to Installation
maintenance be performed correctly and in accordance
Reference Diagram on page 7.)
with all applicable local and national codes, and
3. For UL Listed and FM Approved Automatic equipment manufacturer’s instructions. No liability for
Extinguishing Release, actuators must be electrically total system operation is assumed or implied.
compatible.

4 S4004-0002-1 3/2003
Expansion Modules and Accessories
Auxiliary Relay Module 4004-9860 provides four Maintenance Switch with Disconnect Indicator
additional relays. Dual hazard applications will require Lamp. Proper service of release appliance circuits
two modules for auxiliary relay operation. Each relay requires the ability to
module has a manual disconnect switch that controls securely disconnect the
relays 2 through 4. (Trouble Relay 1 is not controlled.) release circuit during
Relay outputs are required to be connected to a 15 A installation and NORMAL
maximum circuit breaker. (Relay specifications are maintenance. This 0

detailed on page 6.) module provides a DISC./


1
DISABLE
Auxiliary Relay Module Operation is per the following: keyswitch with a
disable/disconnect
FIRE SUPPRESSION
Relay 1 activates on any trouble associated with its hazard indicator lamp mounted DISCONNECT / DISABLE
or any system trouble on a stainless steel
Relay 2 activates on any alarm associated with its hazard double-gang plate with
Relay 3 activates for pressure switch, waterflow switch, or clear functional
release timer as required per application type (hazard markings. The indicator lamp is powered from a separate
specific), or activates with the second zone for cross-zoned 24 VDC connection. (See illustration above.)
systems (hazard specific) NOTE: For additional Maintenance and Abort Switch
Relay 4 activates when the hazard specific RAC activates information refer to data sheet S2080-0010.
Dual Circuit Class A Adapter Module 4004-9864. Remote Battery Meter Module 4001-9811 provides
This module converts two Class B circuits to Class A a display of battery voltage and battery charge and
operation. It consumes no additional current and is discharge current. This module mounts within 3 ft (1 m)
compatible with IDCs, SPMs, and NACs. Up to four of the 4004R cabinet using a four-gang electrical box with
modules may be mounted within the 4004 R cabinet. 1-3/4” (45 mm) minimum depth. (See illustration below.)
Abort Switches. For manual abort requests, these abort
switches are available with or F IRE AL ARM S YS TE M
without a built-in 1.2 kΩ, 1 W B AT TE RY MET ER S
resistor and are mounted on
FIRE SUPPRESSION
SYSTEM ABORT single-gang stainless steel plates.
D.C. VOLTS D.C. AMPERES
Abort switches are connected to the
SPM inputs per system 0 5 10 15 20 25 30 35 40 45 50 5 2.5 0 2.5 5

requirements.
Activity abort occurs while the
PUSH AND HOLD switch is pushed and continues after
releasing the switch for the selected
Abort Release Time Delay. (See
illustration to the left.)

FM Approved Water Control Valves


FM Group Manufacturer Model Number Details
A Skinner LV2LBX25 24 VDC, 11 W, 458 mA, 1/2 inch NPS, 1/2 inch orifice
T8210A107
B ASCO R8210A107 24 VDC, 16.8 W, 700 mA, 1/2 inch NPS, 5/8 inch orifice
8210A107
C Star Sprinkler 5550 24 VDC, part of Model D deluge valve
8210G207
D ASCO V2648571, N.C. 24 VDC, 10.6 W, 440 mA, 1/2 inch NPS, 1/2 inch orifice
HV2648581, N.O.
73218BN4UNLVNOC111C2 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice
E Skinner 24 VDC, 10 W, 420 mA, 1/2 inch NPS, 5/8 inch orifice; 5-300
73212BN4TN00N0C111C2
psi rated working pressure
24 VDC, 22 W, 1/2 inch NPS, 920 mA, 250 psi (1725 kPa), 1/2
F Skinner 73212BN4TNLVNOC322C2
inch orifice
24 VDC, 10 W, 420 mA, 1/4 inch NPS, 1/16 inch orifice, 250 psi
G Skinner 71395SN2ENJ1NOH111C2
(1725 kPa) rated working pressure
24 VDC, 22.6 W, 940 mA, 1/2” NPS, 250 PSI (1725 kPa),
H Viking HV-274-060-001
3/4” orifice

5 S4004-0002-1 3/2003
Specifications (Refer to Instructions 579-354 for additional information)
Power Ratings
Voltage Ratings 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select
AC Input
Current Ratings 2 A maximum @ 120 VAC input; 1 A maximum @ 240 VAC input
Power Supply 3 A maximum @ 25.5 VDC in alarm
Temperature compensated, capable of recharging batteries required for 90 hour
Battery Charger
standby and 10 minute alarm (contingent on auxiliary power load)
Standby Current 100 mA; with IDCs fully loaded, tone-alert silenced, trouble LED on, charger off
Standard Circuit Ratings (NOTE: Total DC current = 3 A maximum)
Notification Appliance Circuits (NACs) 2 A maximum @ 24 VDC, per circuit
Release Appliance Circuits (RACs) 2 A maximum @ 24 VDC, per circuit
Supervisory
3 mA maximum
Current
Initiating Device
Circuits (IDCs) Alarm Current 60 mA maximum
Each IDC supports up to 30 detectors (smoke or electronic heat) and manual
Capacity
stations as required; wiring distance is limited to 50 Ÿ maximum
For Manual Release, Abort Switches, or Supervisory functions only; not for
detectors; wiring distance is limited to 50 Ÿ maximum
Special Purpose Monitoring Circuits (SPMs)
Dual Hazard Application Abort Switches require a current limiting resistor of
1.2 kŸ, 1 W, or an external Abort Supervision Module per SPM
Two outputs are available, continuous operation or resettable operation; combined
Auxiliary Power Output
output is 750 mA maximum @ 24 VDC
Auxiliary Relay Outputs
Contacts rated 2 A @ 30 VDC, selectable as N.O. or N.C. by jumper
(Trouble, Aux Relay 2, Aux Relay 3)
Wiring Connections for Above Circuits and
Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
AC Input
Auxiliary Module Ratings
Two circuits per module, rated same as circuits; not applicable to RACs (no
Class A Adapter Module 4004-9684
additional current required)
Relay Type Four relays with two outputs per relay; individually selectable as N.O. or N.C.
AC Ratings 7 A @ 120 VAC, rated for pilot duty @ 0.35 power factor
Auxiliary Relay Module
4004-9860 DC Ratings 5 A @ 30 VDC, rated for pilot duty @ 0.35 power factor
Module Current 12 mA standby; 70 mA with all four relays energized; @ 24 VDC
Wiring Terminals rated for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2 )
2081-9046 Coil Supervision Module and 2081-9048 Abort Supervision Module (see page 7)
Construction Epoxy encapsulated
Dimensions 1-3/8” W x 2-7/16” L x 1-1/16” H (34 mm x 62 mm x 27 mm)
Wiring 18 AWG (0.82 mm2) wire leads, color coded
Coil Supervision Module Current Rating 2 A Maximum
Abort Supervision Module Resistance 560 Ω, 1/2 W
Environmental Ratings
Operating Temperature Range 32° to 120°F (0° to 49° C)
Operating Humidity Range up to 93% RH, non-condensing @ 100.4° F (38° C) maximum

Reference Information, Compatible Simplex Detectors and other System Components


Model Type Description Data Sheet
4098-9601 Standard detector
Photoelectric smoke detectors for 2- S4098-0015
4098-9605 Reduced sensitivity detector
wire and 4-wire bases
4098-9602 Combination smoke and heat detector S4098-0017
4098 Series Duct detector housings 2-wire and 4-wire models S4098-0029
4098 Series Ionization Smoke Detectors 2-wire and 4-wire models S4098-0018
4098-9612 135° F (57°C)
Fixed heat detector
4098-9614 Electronic heat detectors for 2-wire 200° F (93°C)
S4098-0014
4098-9613 and 4-wire bases 135° F (57°C)
Fixed with rate-of-rise heat detector
4098-9615 200° F (93°C)
2099-9149 Manual Release Station with Double action push, Standard
S2099-0010
2099-9152 selectable release labels N.O. contact With 560 Ω internal resistor
2080 Series Abort Switches, and Maintenance Switches with Status Indicator; surface or flush mount S2081-0010

6 S4004-0002-1 3/2003
4004R System Connection Reference

Electrically compatible actuator or


compatible FM Approved Deluge and
Preaction Automatic Water Control
Valve, one per RAC
A

Actuator wiring Coil Supervision Module


junction box 2081-9046
Yel Blk
+ Out - RED
COIL SUPERVISION MODULE (2 AMP) 2081-9046
INSTALLATION INSTRUCTIONS 574-437 REV YEL
NAC+

+ In -
MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
(RED/BLK) AND NONPOWER S
LIMITED (YEL/BLK) WIRING
DATE CODE: 519-958
BLK
NAC-

Abort Supervision Module 2081-9048 Red Blk BLK SIM PLEX TIM E RECORDER CO. GARDNER M A. USA

(for dual hazard mode with non-current


limited devices on the SPM)
Maintenance Switch with
ABORT SUPERVISION MODULE 2081-9048
RED
IN+
INSTALLATION INSTRUCTIONS 579-465 REV
MAINTAIN 1/4" SEPARATION
BETWEEN POWER LIMITED
YEL
OUT +
Indicator Lamp
FM (RED/BLK) AND NONPOWER
LIMITED (YEL/BLK) WIRING NORMAL
DATE CODE: OUT - 0

IN- BLK 1
DISC./
DISABLE
BLK SIMPLEX TIME RECORDER CO. WESTMINSTER MA 01441 USA

FIRE SUPPRESSION
DISCONNECT / DISABLE

Optional 4905-9914 or -9922


RAC 2 Synchronized Flash Module
Abort Switches Manual Release
AUX 24 VDC
(as required) Stations RAC 1 for lamp power
FIRE SUPPRESSION FIRE SUPPRESSION
SYSTEM ABORT SYSTEM ABORT

SPM 1 Typical strobe only NAC


PUSH AND HOLD PUSH AND HOLD
MANUAL
RELEASE
MANUAL
RELEASE
NAC 1
SPM 2
Alarm Manual Release
Zone 1
Trouble Zone 5 Trouble

Alarm Manual Release

Trouble
Zone 2 Zone 6 Trouble
CAUTION
Alarm NAC 1 Trouble DISCONNECT
Zone 3
Trouble NAC 2 Trouble

IDC 1
Alarm RAC 1 Trouble

Trouble
Zone 4 RAC 2 Trouble
BATTERY AND
A. C. POWER
Alarm Silenced Agent Released BEFORE
SERVICING
Supervisory Earth Fault

System Trouble Abort Active

AC Power Relay Disconnect

Manual fire Typical horn only NAC


alarm station NAC 2
Compatible IDCs 2, 3, and 4
detection devices
4004R Suppression
Release Panel

FIRE ALARM S Y ST E M
BATT ER Y ME TE RS Combined operation NAC
D.C. VOLTS D.C. AMPERES

0 5 10 15 20 25 30 35 40 45 50 5 2.5 0 2.5 5

Meter module cable


Optional 4001-9811 (supplied with meter
Meter Module module)
Optional 4905-9938 SmartSync
NOTE: Locate meter module within module for separate horn and
3 ft (1 m) of 4004R cabinet. strobe control over two wires

GENERAL WIRING NOTE:


Wiring shown is for reference only, refer to specific
installation instructions for detailed wiring information.

7 S4004-0002-1 3/2003
Mounting Reference Information

Box width 14-5/8" (372 mm)

Typical conduit entry area (Top and side views are


(cut holes as required) shown with door installed)

Box depth
4-1/4" (108 mm)

11-1/4" (286 mm)

Class A adapter boards Aux. relay


module 1
Door thickness
Relay Relay
Disc 1 Disc 2

5/8" (16 mm)


Aux. relay
module 2
13-1/2" Main board 16"
(343 mm) (483 mm)

AC input

Battery Area
No conduit or wiring in this area

13-1/4" (337 mm)

(Front view module placement reference showing NOTE: For semi-flush mounting, cabinet
mounting hole dimensions, optional Class A must extend 1-1/2" (38 mm)
adapter modules, and optional relay modules) minimum from wall surface

NOTE: A system ground must be provided for Earth Detection and transient protection devices. This connection
shall be made to an approved, dedicated Earth connection per NFPA 70, Article 250, and NFPA 780.

Tyco, Simplex, and the Simplex logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries.

Tyco Safety Products Westminster • Westminster, MA • 01441-0001 • USA S4004-0002-1 3/2003


www.tycosafetyproducts-usa-wm.com
© 2003 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

You might also like