REF 610 Feeder Protection Relay: Technical Reference Manual - ANSI Version
REF 610 Feeder Protection Relay: Technical Reference Manual - ANSI Version
Content
1. Introduction ...............................................................................6
1.1. About this manual .........................................................................6
1.2. The use of the relay ......................................................................6
1.3. Features ........................................................................................6
1.4. Warranty ........................................................................................8
1.5. Revision history .............................................................................8
2. Safety information .....................................................................9
3. Instructions ..............................................................................10
3.1. Application ...................................................................................10
3.2. Requirements ..............................................................................10
3.3. Configuration ...............................................................................10
4. Technical description .............................................................13
4.1. Functional description .................................................................13
4.1.1. Product functions .............................................................13
4.1.1.1. Protection functions ............................................13
4.1.1.2. Inputs .................................................................13
4.1.1.3. Outputs ...............................................................14
4.1.1.4. Disturbance recorder ..........................................14
4.1.1.5. HMI .....................................................................14
4.1.1.6. Non-volatile memory ..........................................14
4.1.1.7. Self-supervision ..................................................14
4.1.1.8. Time synchronization .........................................15
4.1.2. Measurements .................................................................16
4.1.3. Configuration ....................................................................16
4.1.4. Protection .........................................................................18
4.1.4.1. Block diagram ....................................................18
4.1.4.2. Overcurrent protection .......................................19
4.1.4.3. Ground-fault protection ......................................20
4.1.4.4. Thermal protection for cables .............................21
4.1.4.5. Phase discontinuity protection ...........................26
4.1.4.6. Circuit-breaker failure protection ........................26
4.1.4.7. Arc protection .....................................................27
4.1.4.8. Auto-reclose function .........................................28
4.1.4.9. Inverse definite minimum time characteristics ...34
4.1.4.10.Settings ..............................................................46
4.1.4.11.Technical data on protection functions ..............58
4.1.5. Trip-circuit supervision .....................................................63
1. Introduction
1.3. Features
• Three-phase non-directional overcurrent protection with definite-time or IDMT
(mode) characteristic, low-set element
• Three-phase non-directional overcurrent protection, high-set element
• Three-phase non-directional overcurrent protection, instantaneous element
• Non-directional ground-fault protection with definite-time or IDMT (mode)
characteristic, low-set element
• Non-directional ground-fault protection, high-set element
• Phase discontinuity protection
• Three-phase thermal overload protection for cables
• Arc protection
• two lens sensors for arc detection (optional)
• automatic reference level adjustment based on backlight intensity
• arc detection via a remote light signal
• Automatic reclosing 1...3 shots
• Circuit-breaker failure protection
• Trip counters for circuit-breaker condition monitoring
• Trip-circuit supervision with possibility to route the warning signal to a non-trip
output
1.4. Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
2. Safety information
3. Instructions
3.1. Application
REF 610 is a versatile multifunction protection relay mainly designed for protection
of incoming and outgoing feeders in MV distribution substations. REF 610 can also
be used as back-up protection for motors, transformers and generators, in industrial
as well as in utility applications.
The large number of integrated protection functions, including three overcurrent
protection elements, non-directional ground-fault protection elements as well as
thermal protection, makes REF 610 a complete protection against overcurrent and
ground faults.
The optional arc protection for detection of arc situations in air insulated metal-clad
switchgears and the auto-reclose function for automatic clearing of overhead line
faults increase the range of applications further.
The large number of digital inputs and output contacts allows a wide range of
applications.
3.2. Requirements
To secure correct and safe operation of the relay, preventive maintenance is
recommended to be performed every five years when REF 610 is operating under
the specified conditions; see below and section Technical data.
When being used for real-time clock or recorded data functions, the battery should
be changed every five years.
Environmental conditions
3.3. Configuration
Setting and connection examples
The appropriate configuration of the output contact matrix enables the use of the
signals from the protection elements as contact functions. The pickup signals can be
used for blocking co-operating protection relays and signalling.
Fig. 3.3.-1 and Fig. 3.3.-2 represent REF 610 with the default configuration: all trip
signals are routed to trip the circuit breaker. In Fig. 3.3.-1, the residual current is
measured via a core-balance current transformer and the output contacts are
connected to enable the use of the auto-reclose function. In Fig. 3.3.-2, the residual
current is measured via a summation connection of the phase current transformers
and the output contacts are connected to enable the use of the trip lockout function.
10
A
B
C +
+ +
52a 52b CS
CS T
C
52b 52a
(dc/ac)
U 52 52
aux
CLOSE TC
D15 D14 D13 D12 D11 IRF SO1 SO4 PO3 PO2 PO1 SO5 SO4 SO3
X2.1 7 81 2 3 45 6 X3.1 6 5 4 3 2 1 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 16 17 18 19 20 21 22 23 24 X3.1
50P-1 Pickup 3 3 3 3 3 3 3 3
Blocking Trip 4 4 4 4 4 4 4 4
12 12 12 12 12
50P-2 Pickup
5 5 5 5 5 5 5 5
Trip
Feeder Protection Relay
6 6 6 6 6 6 6 6
51N Pickup
7 7 7 7 7 7 7 7
Blocking Trip
13 13 13 13 13 8 8 8 8 8 8 8 8
50N Pickup 9 9 9 9 9 9 9 9
Blocking Trip
14 14 14 14 14 10 10 10 10 10 10 10 10
46 Pickup
11 11 11 11 11 11 11 11
Blocking Trip
15 15 15 15 15 12 12 12 12 12 12 12 12
49 Alarm
Trip 13 13 13 13 13 13 13 13
X5.1 14 14 14 14 14 14 14 14
Technical Reference Manual - ANSI Version
Light Sensor 1
Light Sensor 2 Arc 51P/51N Arc light output 23 23 23 23 23 23 23 23
9 9 9 9 9 External Arc Trip 22 22 22 22 22 22 22 22
X5.2
Optional
79
18 18 18 18 18 16 16 16 16 16 16 16 16
CB Position Open Open CB Command 17 17 17 17 17 17 17 17
19 19 19 19 19
CB Position Closed Close CB Command 19 19 19 19 19 19 19 19
16 16 16 16 16
AR Disable CB Reclosing Failed 20 20 20 20 20 20 20 20
17 17 17 17 17
20 20 20 20 20 CB Close Disable Shot Due 18 18 18 18 18 18 18 18
External AR Initiation Definite Trip Alarm 21 21 21 21 21 21 21 21
Trip Lockout
8 8 8 8 8
External Triggering
10 10 10 10 10
Reset Trip Lockout
6 6 6 6 6 15 15 15 15 15 15 15 15
External Trip External Trip
CB FAIL
7 7 7 7 7
External Triggering Trip
1 1 1 1 1
Indications Cleared
2 2 2 2 2 Output contacts unlatched
3 3 3 3 3 Memorized values cleared
4 4 4 4 4 Setting group selection
5 5 5 5 5 Time sync
SGF1...SGF5
SGL1...SGL8
ConnDiagr1REF610_a
REF 610
11
12
L1
L2
L3
REF 610
+ +
CS
CS T
C
D15 D14 D13 D12 D11 IRF SO2 SO1 PO3 PO2 PO1 SO5 SO4 SO3
X2.1 7 81 2 3 45 6 X3.1 6 5 4 3 2 1 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 16 17 18 19 20 21 22 23 24 X3.1
(dc/ac)
50P-2 Pickup
5 5 5 5 5 5 5 5
Trip
6 6 6 6 6 6 6 6
51N Pickup
7 7 7 7 7 7 7 7
Blocking Trip
13 13 13 13 13 8 8 8 8 8 8 8 8
50N Pickup 9 9 9 9 9 9 9 9
Blocking Trip
14 14 14 14 14 10 10 10 10 10 10 10 10
46 Pickup
11 11 11 11 11 11 11 11
Blocking Trip
15 15 15 15 15 12 12 12 12 12 12 12 12
Feeder Protection Relay
49 Alarm
Trip 13 13 13 13 13 13 13 13
X5.1 14 14 14 14 14 14 14 14
Light Sensor 1
Light Sensor 2 Arc 51P/51N Arc light output 23 23 23 23 23 23 23 23
9 9 9 9 9 External Arc Trip 22 22 22 22 22 22 22 22
X5.2
Optional
79
18 18 18 18 18 16 16 16 16 16 16 16 16
CB Position Open Open CB Command
19 19 19 19 19 17 17 17 17 17 17 17 17
CB Position Closed Close CB Command
16 16 16 16 16 19 19 19 19 19 19 19 19
AR Disable CB Reclosing Failed
17 17 17 17 17 20 20 20 20 20 20 20 20
CB Close Disable Shot Due
20 20 20 20 20 18 18 18 18 18 18 18 18
External AR Initiation Definite Trip Alarm
21 21 21 21 21 21 21 21
Technical Reference Manual - ANSI Version
AR Lockout
Trip Lockout
8 8 8 8 8
External Triggering
10 10 10 10 10 Trip Lockout
Reset
6 6 6 6 6 15 15 15 15 15 15 15 15
External Trip External Trip
CB FAIL
7 7 7 7 7 External Triggering Trip
1 1 1 1 1
2 2 2 2 2 Indications Cleared
3 3 3 3 3 Output contacts unlatched
Memorized values cleared
4 4 4 4 4
Setting group selection
5 5 5 5 5
Time sync
SGF1 ...SGF5
SFL1 ...SGL8
ConnDiagr2 REF610_a
1MRS 755535
1MRS 755535 Feeder Protection Relay REF 610
Technical Reference Manual - ANSI Version
4. Technical description
4.1.1.2. Inputs
REF 610 is provided with four energizing inputs, two optional light sensor inputs,
two digital inputs and three optional digital inputs controlled by an external voltage.
Three of the energizing inputs are for the phase currents and one for the ground-fault
current. For details, refer to section Input/output connections and tables 4.1.4.10-7,
4.2.1-1 and 4.2.1-5. The functions of the digital inputs are determined with the
SGB switches.
13
4.1.1.3. Outputs
REF 610 is provided with three trip outputs (PO1, PO2 and PO3), two non-trip
outputs (SO1 and SO2) and three optional non-trip outputs (SO3, SO4 and SO5).
Switchgroups SGR1...8 are used for routing internal signals from the protection
elements, the external trip signal and signals from the auto-reclose function to the
desired non-trip or trip output. The minimum pulse length can be configured to be
40 or 80 ms and the trip outputs can all be configured to be latched.
4.1.1.5. HMI
The HMI of REF 610 is equipped with six push-buttons, an alphanumeric
2x16 characters’ LCD, eight programmable target LEDs, three target LEDs with
fixed functionality, and an target LED for front communication. The
push-buttons are used for navigating in the menu structure and for adjusting setting
values.
An HMI password can be set to protect all user-changeable values from being
changed by an unauthorized person. The HMI password will remain inactive and
will thus not be required for altering parameter values until the default HMI
password has been replaced. Entering the HMI password successfully can be
selected to generate an event code. This feature can be used to indicate interaction
activities via the local HMI. For further information on the HMI, refer to the
Operator’s Manual.
4.1.1.7. Self-supervision
The self-supervision system of REF 610 manages run-time fault situations and
informs the user about an existing fault. There are two types of fault targets: internal
relay fault (IRF) targets and warnings.
When the self-supervision system detects a permanent internal relay fault, which
will prevent relay operation, the green target LED (ready) will begin to blink. At the
same time, the IRF contact, which is normally picked up, will drop off and a fault
code will appear on the LCD. The fault code is numerical and identifies the fault
type.
14
INTERNAL FAULT
FAULT CODE :30
IntFault_a
Fig. 4.1.1.7.-1 Permanent IRF
In case of a warning, the relay will continue to operate with full or reduced
functionality and the green target LED (ready) will remain lit as during normal
operation. A fault target message (see Fig. 4.1.1.7.-2), with a possible fault code (see
Fig. 4.1.1.7.-3), will appear on the LCD indicating the type of fault. In case of a
warning due to an external fault in the trip circuit detected by the trip-circuit
supervision, or due to continuous light on the light sensor inputs, SO2 will be
activated (if SGF1/8=1).
WARNING
BATTERY LOW
Warning_a
WARNING
FAULT CODE: 33
WarnREF610_a
15
Time synchronization is always triggered on the rising edge of the digital input
signal. The time is adjusted in steps of five milliseconds per synchronization pulse.
The typical accuracy achievable with time synchronization via a digital input is
+2.5...-2.5 milliseconds for second-pulse and +5...-5 milliseconds for minute-pulse
synchronization.
Note!
The pulse length of the digital input signal does not affect time synchronization.
4.1.2. Measurements
The table below presents the measured values which can be accessed through the
HMI:
4.1.3. Configuration
Fig. 4.1.3.-1 illustrates how the internal and digital input signals can be configured
to obtain the required protection functionality.
16
Fig. 4.1.3.-1
X3.1 6 5 4 3 2 1 X4.1 21 22 23 24 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 16 17 18 19 20 21 22 23 24 X3.1
Self-supervision IRF
Optional Warning
50P-1 Pickup 3 3 3 3 3 3 3 3
12 12 12 12 12 Blocking Trip 4 4 4 4 4 4 4 4
Ia
Feeder Protection Relay
Ib 50P-2 Pickup
Signal diagram
5 5 5 5 5 5 5 5
Icı ı Trip 6 6 6 6 6 6 6 6
51N Pickup 7 7 7 7 7 7 7 7
Blocking Trip 8 8 8 8 8 8 8 8
13 13 13 13 13
In 50N Pickup 9 9 9 9 9 9 9 9
14 14 14 14 14 Blocking Trip 10 10 10 10 10 10 10 10
46 Pickup 11 11 11 11 11 11 11 11
Blocking Trip 12 12 12 12 12 12 12 12
15 15 15 15 15
Technical Reference Manual - ANSI Version
49 Pickup 13 13 13 13 13 13 13 13
X5.1 Trip Trip 14 14 14 14 14 14 14 14
Light Sensor 1 Arc 51P/51N Arc light output
Light Sensor 2 23 23 23 23 23 23 23 23
9 9 9 9 9 External Arc Trip 22 22 22 22 22 22 22 22
X5.2
Optional
79 Arc light output
18 18 18 18 18 16 16 16 16 16 16 16 16
CB Position Open Open CB Command
19 19 19 19 19 17 17 17 17 17 17 17 17
CB Position Closed Close CB Command
16 16 16 16 16 19 19 19 19 19 19 19 19
AR Disable CB Reclosing Failed
17 17 17 17 17 20 20 20 20 20 20 20 20
CB Close Disable Shot Due
20 20 20 20 20 18 18 18 18 18 18 18 18
External AR Initiation Definite Trip Alarm
21 21 21 21 21 21 21 21
AR Lockout
Trip Lockout
8 8 8 8 8
External Triggering
10 10 10 10 10
Reset Trip Lockout
6 6 6 6 6 15 15 15 15 15 15 15 15
External Trip External Trip
CBFAIL
7 7 7 7 7
External Triggering Trip
1 1 1 1 1
2 2 2 2 2 Indications Cleared
3 3 3 3 3 Output contacts unlatched
SGF1 ...SGF5
SFL1 ...SGL8
SignDiagrREF610_a
REF 610
17
REF 610 Feeder Protection Relay 1MRS 755535
The functions of the relay are selected with the switches of switchgroups SGF, SGB,
SGR and SGL. The checksums of the switchgroups are found under SETTINGS in
the HMI menu. The functions of the switches are explained in detail in the
corresponding SG_ tables.
4.1.4. Protection
18
19
Element 50P-2 can be set out of operation in SGF3. This state will be indicated by
dashes on the LCD and by “999” when the set pickup value is read via serial
communication. Elements 50P-1 and 50P-2 will be reset in 50 ms after all three
phase currents have fallen below the set pickup value of the element.
Note!
Elements 51P and 50P-1 can be set to be blocked by the auto-reclose function.
20
2 –t ⁄ τ
θ = ⎛ -------------------------⎞ × ( 1 – e
I
) × 100%
⎝ 1.05 × FLA⎠
where
“When one or several phase currents exceed the set full load current, FLA, element
49 will pickup. At the same time, the thermal capacity will start to increase at a rate
depending on the current amplitude and the prior load of the cable.
When the thermal capacity, influenced by the thermal history of the cable, exceeds
the set alarm level, 49ALARM the element will generate an alarm signal. The
thermal alarm can be used to avoid unnecessary tripping due to a beginning
overload. The thermal level at various constant currents are presented in the table
below:
21
⎧
⎪
t = τ x ln ⎨
( ) I
FLA
2
− ( ) ⎫⎪⎬
I p
FLA
2
⎪⎩ ( )
FLA
I 2
− 1 . 1025 ⎪⎭
The operate time is calculated as follows:
where
FLA = set full load current
Ip = prior load current
t = time (in minutes)
τ = time constant (in minutes)
ln = natural logarithm
At power up, the thermal level will be set to 75 percent of the thermal capacity of
the cable. This will ensure that the element will trip within a safe time span in case
of an overload. The calculated thermal level will approach the thermal level of the
cable.
Element 49 can be set out of operation in SGF3. This state will be indicated by
dashes on the LCD and by “999” when the set full load current is read via serial
communication.
Note!
At an alarm level below 75 percent, connecting the auxiliary supply to the relay will
cause a thermal alarm due to the initialization of the thermal level to 75 percent of
the thermal capacity of the cable. The thermal level can be reset via the HMI during
power up.
Note!
The thermal level can be reset or changed via serial communication, which will
generate an event code.
22
t/s
100000
10000
1000
t[min]
100
90
60
40
25
10 15
10
1
1
1.05
PrLoad0_a
0
1 10 I/I q
CURRENT IN MULTIPLES OF FULL LOAD CURRENT SETTING
23
t/s
100000
10000
1000
t[min]
100
90
60
40
10 25
15
10
5
1
1
PrLoad0.7_a
1.05
0
1 10 I/Iq
CURRENT IN MULTIPLES OF FULL LOAD CURRENT SETTING
24
t/s
100000
10000
1000
t[min]
100
10
90
60
40
25
1
15
10
5
1
1.05
PrLoad1_a
0
1 10 I/Iq
CURRENT IN MULTIPLES OF FULL LOAD CURRENT SETTING
25
I max − I min
I ( unbal ) = x 100%
I max
When the current difference exceeds the set pickup value of the phase discontinuity
element, 46, the element will generate a pickup signal after a ~ 100 ms. When the
set operate time at definite-time characteristic elapses, the element will generate a
trip signal. The element will be reset in 70 ms after the current difference has fallen
below the set pickup value of the element.
The phase discontinuity protection will be disabled when all phase currents fall
below 0.1 x CT.
It is possible to block the tripping of the phase discontinuity element by applying a
digital input signal to the relay.
Element 46 can be set out of operation in SGF3. This state will be indicated by
dashes on the LCD and by “999” when the set pickup value is read via serial
communication.
26
27
The warning signal generated in case of continuous light on the light sensor inputs
can be routed to SO2 by setting switch SGF1/8 to 1.
Arc50P (setting)
0
Arc Trip
25ms
Arc50N (setting)
I0 (measured)
Light sensor 2
28
The initiation of one or several auto-reclose shots can be set to be blocked by trip
signals from certain protection elements. Blocking is also possible via a digital
input. Blocking can be used to limit the number of shots in an auto-reclose sequence,
which may be advantageous with certain types of faults. In case of shot initiation
while a blocking is active, the next shot will be initiated.
The AR function monitors the position and status of the circuit breaker. Information
on the circuit-breaker position is always required whereas circuit-breaker status is
optional. For safety reasons, shot initiation is not possible when the circuit breaker
is open. If the circuit breaker is not ready, due to an discharged spring, for instance,
reclosing can be disabled via a digital input (CB Close Disable). Disable of
reclosing is checked only when necessary and can therefore not be used to prevent
initiation or progression of a shot.
For co-ordination of the other protection devices in the network, such as
down-stream fuses, the AR function supports optional blocking of selectable
overcurrent and ground-fault protection elements (refer to section Blocking of
protection elements). By setting a element with a short operate time to trip and
initiate only the first auto-reclose shot, fast tripping and shot initiation will be
achieved. After this, the element will be blocked to allow selective delayed tripping
of another element in accordance with the time-grading plan of the system.
The typical auto-reclose sequence is as follows: the overcurrent or ground-fault
protection detects a network fault, trips the circuit breaker and initiates the first
auto-reclose shot. At the time of shot initiation, the set open time for shot 1 will
pickup. When the set open time elapses, the blocking of selected protection elements
will be activated and the AR function will issue a reclosing command (Close CB
Command) to the circuit breaker, the duration of which is settable. In addition, the
set reset time and set cutout time will pickup when the set open time elapses. The
blocking of protection elements will be reset on expiration of the cutout time. For
the cutout time, refer to section Fast tripping and initiation of shot 1 using two
protection elements.
If the network fault is cleared, i.e. the auto-reclosure is successful, the set reset time
will expire and the AR function will be automatically reset to the quiescent
condition.
However, if the network fault is not cleared, i.e. the auto-reclosure is unsuccessful,
and the protection trips the circuit breaker before expiration of the set reset time, the
next shot will be initiated (provided that a further auto-reclosure is allowed). At the
time of shot initiation, the set open time for shot 2 will pickup. When the set open
time elapses, the blocking of selected protection elements (may differ from shot 1)
will be activated and the AR function will issue a reclosing command to the circuit
breaker. In addition, the set reset time and set cutout time will pickup when the set
open time elapses. The blocking of protection elements will be reset on expiration
of the set cutout time.
If the network fault is cleared, the AR function will be automatically reset after the
reset time. However, if the fault is not cleared and the protection trips the circuit
breaker before expiration of the reset time, the next shot will be initiated (provided
that a further auto-reclosure is allowed). At the time of shot initiation, the set open
time for shot 3 will pickup. When the set open time elapses, the blocking of selected
protection elements (the same as for shot 2) will be activated and the AR function
29
will issue a reclosing command to the circuit breaker. In addition, the set reset time
and set cutout time will pickup when the set open time elapses. The blocking of
protection elements will be reset on expiration of the set cutout time.
If the network fault has still not been cleared, i.e. all selected auto-reclose shots have
been unsuccessful, and the protection trips the circuit breaker before expiration of
the set reset time, the AR function will generate a definite trip alarm. The circuit
breaker will now remain open and the AR function will be locked out.
As default, the AR function is not in use (number of auto-reclose shots = 0). The AR
function can be activated either via the HMI or with SPA parameter S25 by setting
the number of auto-reclose shots to 1, 2 or 3.
Shot Due
S
Shot 1 t 0
Shot Initiation
Shot 2 t 0
t
Shot 3 0
CB Close Diasable
Close CB Command
S
CB Closed
R
CB Closing Time
t
0
CB Reclosing Failed
30
The AR function will issue an opening command to the circuit breaker at shot
initiation by a pickup or a trip signal.
CB Closed
0
100ms
Shot Due
Shot Initiation
50P-1 Trip
External AR Initiation
Open CB Command
51P Trip
50N Trip
51N Trip
51N pickup delay
51N Pickup t
0
Blocking of shot
SG1/
1..8
31
Note!
In case of shot initiation while a blocking is active, the next shot (if such has been
selected and not blocked) will be initiated. This can be used to skip Shot 1, for
instance.
Disable of the auto-reclose function
The AR function can be disabled (AR Disable) by any of the following signals:
• external AR disable signal
• trip signal from the arc protection element, ARC
• trip signal from the thermal protection element, 49
• trip signal from the CBFAIL
• alarm signal from the thermal protection element, 49
• trip signal from overcurrent element 50P-2
• trip signal from ground-fault element 50N
• trip signal from the phase discontinuity element, 46
The trip signals from elements ARC and 49 and from the CBFAIL are fixed and will
thus always disable the AR function. External AR disable by the digital input signal
is selected in SGB, and the alarm signal from element 49 and the trip signals from
elements 50P-2, 50N and 46 in SG3 (see table 4.1.4.10-12).
Note!
The AR function will remain disabled after all disable signals have been reset for a
time equal in length to the set reset time.
Note!
Disable will always also interrupt any ongoing shot.
Information on the circuit-breaker position
The AR function requires information on the circuit-breaker position. Any digital
input can be selected for the information on the circuit breaker being open (CB
Position Open) and closed (CB Position Closed) in SGB. Normally, two
digital inputs is recommended although either one is enough for the AR function.
Information on the circuit-breaker position is used in the following situations:
• At manual circuit-breaker closing, the AR function will be disabled for the reset
time.
• At manual circuit-breaker closing during an ongoing shot, the shot will be
interrupted and the AR function disabled during the reset time.
• Shot initiation is allowed only when the circuit breaker is closed.
• Reclosing of the circuit breaker is ended immediately after the AR function has
received information that the circuit breaker has been closed.
Circuit-breaker closing
When the set open time elapses, the AR function will issue a reclosing command to
the circuit breaker (Close CB Command). Reclosing can be disabled via a digital
input (CB Close Disable). External disable of reclosing by the digital input
signal is selected in SGB.
32
When reclosing is disabled, or the circuit breaker does not close before expiration of
the set CB closing time, the circuit breaker will remain open and the AR function
will generate a CB Reclosing Failed signal.
Reclosing is disabled and the CB Reclosing Failed signal generated also if
an AR initiation signal is active, i.e. the fault has not been cleared, when reclosing
begins.
The duration of the reclosing command is settable (CB closing time). However,
reclosing of the circuit breaker will end immediately after the AR function has
received information that the circuit breaker has been closed, or if a protection trips
the circuit breaker again.
Blocking of protection elements
In several applications, such as fuse-saving (refer to section Fast tripping and
initiation of shot 1 using two protection elements), the aim is at fast tripping and
initiation of shot 1 and delayed tripping and initiation of shot 2 and 3. Consequently,
if two protection elements are used, one fast and the other one delayed, the fast
element should be set to be blocked by the AR function during shot 2 and 3.
The protection elements can be set to be blocked at shot 1 and/or shot 2 and 3. The
selection is made in SG2 (see table 4.1.4.10-11).
Definite trip alarm
The AR function will generate a definite trip alarm signal after an unsuccessful
auto-reclose sequence, i.e. when no more auto-reclose shots are allowed but the
network fault has not be cleared, the circuit breaker is open and there is no ongoing
shot. The definite trip alarm signal will also be generated in case a protection trips
the circuit breaker while the AR function is disabled.
Note!
The definite trip alarm signal is active for 1 second.
Note!
The definite trip alarm signal will not be generated if the AR function has been set
out of operation.
Lockout of the auto-reclose function
The lockout signal indicates whether the AR function is ready for shot initiation. The
AR function will be locked out in any of the following situations:
• the AR function generates a definite trip alarm
• the AR function is disabled
• circuit-breaker closing fails
• manual circuit-breaker closing is detected
The lockout signal will be reset and the AR function ready for shot initiation on
expiration of the set reset time. The set reset time will pickup when the definite trip
alarm signal, the AR disable signal or the CB reclosing failed signal has
been reset or the circuit breaker closed, depending on the reason for the AR function
being locked.
33
⎛ β ⎞
t [ s ] = ⎜ ------------------ ⎟ × TD
⎝ Mα – 1 ⎠
where
t = operate time
TD = time multiplier
M = multiplies of pickup current
Note!
The actual operate time of the relay (see Fig. 4.1.4.9.-1...Fig. 4.1.4.9.-4), includes an
additional filter and detection time, and the operate time of the trip output contact.
When the operate time of the relay is calculated as above, approximately 30 ms
should be added to the result.
34
According to the standard, the normal current range is 2...20 times the set pickup
value at normal inverse, very inverse or extremely inverse characteristic. The relay
is to pickup before the current exceeds the set pickup value by 1.3 times. At long-
time inverse characteristic, the normal current range is specified to be 2...7 times the
set pickup value, and the relay is to pickup before the current exceeds the set pickup
value by 1.1 times.
Within the normal current range the inverse-time element fulfils the tolerance
requirements of class 5 at all degrees of inversity.
The time/current curve groups based on the IEC standard are illustrated in
Fig. 4.1.4.9.-1...Fig. 4.1.4.9.-4.
Note!
If the ratio between the current and the set pickup value is higher than 20, the operate
time will be the same as when the ratio is 20.
35
t/s
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
3 TD
k
1.0
2 0.9
0.8
0.7
0.6
0.5
1
0.9 0.4
0.8
0.7 0.3
0.6
0.5
0.2
0.4
0.3
0.1
0.2
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
IEC_NoInvREF610_a
0.03
0.02
1 2 3 4 5 6 7 8 910 20 I/I>
CURRENT IN MULTIPLES OF SETTING
36
t/s
t/s
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
1
0.9 k
TD
0.8
0.7 1.0
0.9
0.6 0.8
0.5 0.7
0.6
0.4
0.5
0.3 0.4
0.3
0.2
0.2
0.1
0.09 0.1
0.08
0.07
0.06
0.05
0.05
0.04
IEC_VeInvREF610_a
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
CURRENT IN MULTIPLES OF SETTING
37
t/s
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
TD
k
0.2 1.0
0.8
0.6
0.1
0.09 0.4
0.08
0.07 0.3
0.06
0.2
0.05
0.04
0.1
IEC_ExInvREF610_a
0.03 0.05
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
CURRENT IN MULTIPLES OF SETTING
38
t/s
t/s
t/s
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8 k
TD
7
1.0
6 0.9
5 0.8
0.7
4 0.6
0.5
3
0.4
2
0.3
0.2
1
0.9
0.8
0.7
0.1
0.6
0.5
0.4
IEC_LoInvREF610_a
0.05
0.3
0.2
1 2 3 4 5 6 7 8 910 20 I/I>
CURRENT IN MULTIPLES OF SETTING
39
⎛ ⎞
⎜ A
⎟x
t(s) =
⎜ p
+B
⎟ TD
⎝ ( M ) −1 ⎠
where
t = operate time (in seconds)
TD = time dial
M = multiplies of pickup current
Note!
The actual operate time of the relay (see Fig. 4.1.4.9.-5...Fig. 4.1.4.9.-7), includes an
additional filter and detection time, and the operate time of the trip output contact.
When the operate time of the relay is calculated as above, approximately 30 ms
should be added to the result.
The time/current curve groups based on the IEEE standard are illustrated in
Fig. 4.1.4.9.-5...Fig. 4.1.4.9.-7.
40
t/s
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
1
0.9
0.8 n
0.7
TD
0.6 15
0.5 12
0.4 10
8
0.3
6
5
0.2
4
0.1 2
0.09
0.08
0.07
0.06 1
0.05
0.04
ANSI_ExInvREF610_a
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
CURRENT IN MULTIPLES OF SETTING
41
t/s
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
n
TD
15
1
0.9 12
0.8 10
0.7
0.6 8
0.5 6
0.4 5
4
0.3
3
0.2
2
0.1 1
0.09
0.08
0.07
0.06
0.05
0.04
ANSI_VeInvREF610_a
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
CURRENT IN MULTIPLES OF SETTING
42
t/s
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
TD
n
3
15
2 12
10
8
1 6
0.9
0.8 5
0.7 4
0.6
0.5 3
0.4
2
0.3
0.2
1
0.1
0.09
0.08
0.07
0.06
0.05
0.04
ANSI_MoInvREF610_a
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
CURRENT IN MULTIPLES OF SETTING
43
RI-type characteristic
The RI-type characteristic is a special characteristic which is principally used for
obtaining time grading with mechanical relays. The relationship between time and
current is expressed as follows:
TD
t(s) = 1
0 . 339 − 0 . 236 x
M
where
t = operate time (in seconds)
TD = time dial
M = multiples of pickup current
Note!
The actual operate time of the relay (see Fig. 4.1.4.9.-8), includes an additional filter
and detection time, and the operate time of the trip output contact. When the operate
time of the relay is calculated as above, approximately 30 ms should be added to the
result.
The RI-type characteristic is illustrated in Fig. 4.1.4.9.-8.
44
t/s
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4 k
TD
3 1.0
0.9
0.8
0.7
2
0.6
0.5
0.4
1 0.3
0.9
0.8
0.7
0.6 0.2
0.5
0.4
0.1
0.3
0.2
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
RI_InvREF610_a
0.02
1 2 3 4 5 6 7 8 910 20 I/I>
CURRENT IN MULTIPLES OF SETTING
45
4.1.4.10. Settings
There are two alternative setting groups available, setting groups 1 and 2. Either of
these setting groups can be used as the actual settings, one at a time. Both groups
have their related registers. By switching between the setting groups, a whole group
of settings can be changed at the same time. This can be done in any of the following
ways:
• via the HMI
• entering SPA parameter V150 via serial communication
• via a digital input
Note!
Switching between setting groups via a digital input has higher priority than via the
HMI or with V150.
The setting values can be altered via the HMI or with a PC provided with the Relay
Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read with
the relay trip circuits disconnected or tested with current injection; refer to section
Check lists for additional information.
46
47
48
SGF1...SGF5
Switchgroups SGF1...SGF5 are used for configuring the desired function as follows:
49
50
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
51
SGR1...SGR8
The pickup, trip and alarm signals from the protection elements, the signals from the
auto-reclose function, and the external trip signal are routed to the output contacts
with the switches of switchgroups SGR1...SGR8. The signals are routed to
PO1...PO3 with the switches of switchgroup SGR1...SGR3 and to SO1...SO5 with
those of SGR4...SGR8.
The matrix below can be of help when making the desired selections. The pickup,
trip and alarm signals from the protection elements, the signals from the auto-reclose
function and the external trip signal are combined with the output contacts by
encircling the desired intersection point. Each intersection point is marked with a
switch number, and the corresponding weighting factor of the switch is shown to the
right in the matrix. The switchgroup checksum is obtained by vertically adding the
weighting factors of all the selected switches of the switchgroup.
Note!
The trip lockout signal is always routed to PO3.
Note!
The trip signal from CBFAIL is always routed to PO2.
Note!
The external fault warning is always routed to SO2.
52
SGR1...8/3 50P-1 3 3 3 3 3 3 3 3 4
SGR1...8/5 50P-2 5 5 5 5 5 5 5 5 16
SGR1...8/18 Definate
18 18 18 18 18 18 18 18 131072
Trip Alarm
SGR1...8/19 CB
Reclosing 19 19 19 19 19 19 19 19 262144
Failed
ΣSGR2
ΣSGR3
ΣSGR4
ΣSGR5
ΣSGR6
ΣSGR7
ΣSGR8
Checksum
OutpSignREF610_b
53
SGL1...SGL8
The signals are routed to LED1 with the switches of switchgroup SGL1, to LED2
with those of SGL2, and so forth.
54
Auto-reclose SG1...SG3
Switchgroup SG1 is used for blocking the initiation of one or several auto-reclose
shots, SG2 for blocking of protection elements at one or several auto-reclose shots,
and SG3 for disabling the AR function as follows:
Table 4.1.4.10-10SG1
Default
Switch Function
setting
SG1/1 Blocking of initiation of shot 1 by the trip signal from element 50P-1 0
SG1/2 Blocking of initiation of shot 1 by the external AR initiation signal 0
SG1/3 Blocking of initiation of shot 1 by the trip or delayed pickup signal from 0
element 51P
SG1/4 Blocking of initiation of shot 1 by the trip or delayed pickup signal from 0
element 51N or the trip signal from element 50N
SG1/5 Blocking of initiation of shot 2 and 3 by the trip signal from element 0
50P-1
SG1/6 Blocking of initiation of shot 2 and 3 by the external AR initiation signal 0
SG1/7 Blocking of initiation of shot 2 and 3 by the trip or delayed pickup signal 0
from element 51P
SG1/8 Blocking of initiation of shot 2 and 3 by the trip or delayed pickup signal 0
from element 51N or the trip signal from element 50N
• When the switch is in position 1, shot initiation is blocked.
ΣSG1 0
55
Table 4.1.4.10-11SG2 1)
Switch Function Default setting
SG2/1 Blocking of tripping of element 51P at shot 1 0
SG2/2 Blocking of tripping of element 50P-1 at shot 1 0
SG2/3 Blocking of tripping of element 50P-2 at shot 1 0
SG2/4 Blocking of tripping of element 51N at shot 1 0
SG2/5 Blocking of tripping of element 50N at shot 1 0
SG2/6 Blocking of tripping of element 51P at shots 2 and 3 0
SG2/7 Blocking of tripping of element 50P-1 at shots 2 and 3 0
SG2/8 Blocking of tripping of element 50P-2 at shots 2 and 3 0
SG2/9 Blocking of tripping of element 51N at shots 2 and 3 0
SG2/10 Blocking of tripping of element 50N at shots 2 and 3 0
• When the switch is in position 1, the element is blocked. 0
ΣSG2 0
1) The blocking is active until the set cutout time or the set reclaim time elapses or the AR function is
locked out.
Table 4.1.4.10-12SG3
Switch Function Default setting
SG3/1 Disable of the AR function by the trip signal from element 50P-2 1
SG3/2 Disable of the AR function by the trip signal from element 50N 1
SG3/3 Disable of the AR function by the alarm signal from element 49 1
SG3/4 Disable of the AR function by the trip signal from element 46 1
• When the switch is in position 1, the AR function is disabled.
SG3/5 Resetting targets at CB reclosing 0
• When the switch is in position 1, targets are reset when the AR
function issues a reclosing command to the circuit breaker.
ΣSG3 15
56
Checksum 31
1) The prerequisite is that the battery has been inserted and is charged.
Note!
When all switches have been set to zero, the battery supervision will be disabled.
57
58
59
60
61
ArcSensitREF610_a
62
The circuit breaker is to be provided with two external contacts, one opening and one
closing contact. The closing contact is to be connected in parallel with the external
shunt resistor, which will enable trip-circuit supervision when the circuit breaker is
63
closed. The opening contact, on the contrary, is to be connected in series with the
external shunt resistor, which will enable trip-circuit supervision when the circuit
breaker is open; see Fig. 4.1.5.-1.
Trip-circuit supervision can be selected either via the HMI or with SPA parameter
V113.
X4.1
18 +
PO1
Rint
Rext Rs
19
16
TCS
17 -
7
8
SO2
6
HW
SW SGF1/8
TRIP-CIRCUIT
TCSopenREF610_a
SUPERVISION
TCS STATE WARNING HMI
Fig. 4.1.5.-1 Connecting the trip-circuit supervision using two external contacts
and the external resistor in the trip circuit
64
In case of loss of auxiliary power when the trip lockout function is in use, the
contacts of PO3 will return to the same state as before the loss, provided that the
battery has been inserted and is charged. If no battery has been inserted, the trip
lockout function will be activated and the contacts of PO3 will remain open when
the auxiliary power is switched on again.
65
minute. This value is updated at the expiration of each time range. The third value
shows the highest one-minute average current value measured during the previous
time range. However, if the time range is set to zero, only the one-minute and the
maximum demand value will be shown. The maximum value is the highest
one-minute mean value since the last reset.
The demand values can be set to zero through serial communication using SPA
parameter V102. The demand values will also be reset if SPA parameter V105 is
changed or the relay is reset.
4.1.11.1. Function
REF 610 features an integrated disturbance recorder for recording monitored
quantities. The recorder continuously captures the curve forms of the currents as
well as the status of both internal and digital input signals and stores these in the
memory.
Triggering of the recorder will generate an event code. After the recorder has been
triggered, it will continue to record data for a pre-defined post-triggering time. An
asterisk will be shown on the LCD on completion of the recording. The status of the
recording can also be viewed using SPA parameter V246.
As soon as the recorder has been triggered and the recording has finished, the
recording can be uploaded and analysed by means of a PC provided with a special
program.
66
channels, referred to as digital signals, are pickup and trip signals from the
protection elements, the alarm signal from element 49, the signals from the auto-
reclose function and the digital input signals linked to the relay.
The user can select up to eight digital signals to be recorded. If more than eight
signals are selected, the first eight signals will be stored, beginning with the internal
signals followed by the digital input signals. The digital signals to be stored are
selected with parameters V238 and V243; see tables 4.1.17-6 and 4.1.17-7.
The recording length varies according to the selected sampling frequency. The RMS
curve is recorded by selecting the sampling frequency to be the same as the nominal
frequency of the relay. The sampling frequency is selected with SPA parameter
M15; see the table below for details.
Recording length:
Cycles
[ s ] = ----------------------------------------------------------------
-
Nominal frequency [ Hz ]
Changing the setting values of parameters M15, V238 and V243 is allowed only
when the recorder is not triggered.
The post-triggering recording length defines the time during which the recorder
continues to store data after it has been triggered. The length can be changed with
SPA parameter V240. If the post-triggering recording length has been defined to be
the same as the total recording length, no data stored prior to the triggering will be
retained in the memory. By the time the post-triggering recording finishes, a
complete recording will have been created.
Triggering of the recorder immediately after it has been cleared or the auxiliary
voltage connected may result in a shortened total recording length. Disconnection of
the auxiliary voltage after the recorder has been triggered, but before the recording
has finished, on the other hand, may result in a shortened post-triggering recording
length. This, however, will not affect the total recording length.
At a power reset, triggered recorder data will be retained in the memory provided
that it has been defined non-volatile.
67
has not been triggered or triggered and ready to be uploaded. Event code E31 will
be generated the moment the disturbance recorder is triggered. If the recorder is
ready to be uploaded, this will also be indicated by an asterisk shown in the lower
right-hand corner of the LCD when it is in the idle mode.
Writing the value 1 to SPA parameter M2 will clear the recorder memory, restart the
recording of new data and enable the triggering of the recorder. Recorder data can
be cleared by performing a master reset, i.e. clearing targets and memorized values
and unlatching output contacts. Writing the value 2 to SPA parameter V246 will
restart the unloading process by setting the time stamp and the first data ready to be
read.
4.1.11.4. Triggering
The user can select one or several internal or digital input signals to trigger the
disturbance recorder, either on the rising or falling edge of the signal(s). Triggering
on the rising edge means that the post-triggering recording sequence will start when
the signal is activated. Correspondingly, triggering on the falling edge means that
the post-triggering recording sequence will start when the active signal is reset. The
trigger signal(s) and the edge are selected with SPA parameters V236...V237 and
V241...V242; see tables 4.1.17-6 and 4.1.17-7. The recorder can also be triggered
manually with SPA parameter M1.
Triggering of the disturbance recorder is only possible if the recorder has not already
been triggered.
68
Note!
The number of trips and auto-reclose shots is stored in the non-volatile EEPROM
memory and will thus not be cleared when performing a master reset. The number
of trips can be erased by entering the value 1 and the number of auto-reclose shots
by entering the value 2 into parameter V166.
REF 610 collects data during fault conditions. When all pickup or thermal alarm
signals have been reset or a element trips, the collected data and time stamp will be
stored as “EVENT1” and the previously stored events will move one step forward.
When a sixth event is stored, the oldest event will be cleared.
69
70
FrConREF 610_b
Relay data such as events, setting values and all input data and memorized values
can be read via the front communication port.
When setting values are altered via the front communication port, the relay will
check that the entered parameter values are within the permitted setting range. If an
entered value is too high or too low, the setting value will remain unchanged.
REF 610 has a counter which can be accessed via COMMUNICATION under
CONFIGURATION in the HMI menu. The counter value is set to zero when the relay
receives a valid message.
71
“light on”. To ensure communication, the line-idle state should be the same for both
the master and the slave device. The connection topology can be selected to be either
loop or star, the default being loop, and either via the HMI or the SPA bus. The
selected line-idle state and connection topology apply irrespective of which rear
communication protocol is active.
REF 610 will use the SPA bus protocol as default when the optional communication
module is in use. The protocol selection is memorized and will therefore always be
activated when the rear connection is in use. The baud rate can be selected either via
the HMI or the SPA bus. According to the IEC_103 standard, however, the baud rate
is 9.6 kbps. When the IEC_103 protocol is active, event masks are not in use.
Consequently, all events in the selected configuration set will be included in the
event reporting.
REF 610 is provided with two different selectable configuration sets, of which
configuration set 1 is used by default. Configuration set 1 is intended to be used
when the optional I/O module has not been installed. Configuration set 2 includes
additional information, e.g. output contact events 6...8 (SO3...SO5) and digital input
events 3...5 (DI3...DI5), provided that the optional I/O module has been installed.
Function type and information number have been mapped into configuration sets
according to the IEC_103 standard to the extent that these have been defined by the
standard. If not defined by the standard, the type of function and/or the information
number have/has been mapped into a private range.
The tables below indicate the information mapping of the corresponding
configuration sets. The column GI indicates whether the status of the specified
information object is transmitted within the general interrogation cycle. The relative
time in messages with the type identification 2 is calculated as a time difference
between the occurred event and the event specified in the column Relative time. The
measurand multiplied by the normalize factor is proportional to the rated value.
Therefore, the maximum value of each measurand is the normalize factor multiplied
by the rated value.
72
Configuration
Configuration
identification
Information
Event code
Function
Relative
Event reason
number
set 1
set 2
Type
type
time
GI
Disturbance recorder E31/ X X 178 100 - - 1
Triggered/Cleared E32
73
Configuration
Configuration
identification
Information
Event code
Function
Relative
Event reason
number
set 1
set 2
Type
type
time
GI
Trip Lockout/Reset 1E37/ X X 10 223 X - 1
1E38
74
Configuration
Configuration
identification
Information
Event code
Function
Relative
Event reason
number
set 1
set 2
Type
type
time
GI
Definite Trip Alarm/ 3E9/ X X 169 150 - - 1
Reset 3E10
Configuration
identification
Rated value
Information
Normalize
Function
Measurant
number
factor
set 1
set 2
Type
type
75
The character codings of the link modes follow the protocol definition. The RTU
character format is presented in table 4.1.15.1-1 and the ASCII character format in
table 4.1.15.1-2:
Note!
The turnaround time (response time) of REF 610 depends on the amount of data
requested in a query. Therefore, the turnaround time can vary between
approximately 20 and 100 milliseconds. However, a turnaround timeout no lower
than 150 ms is recommended for the Modbus master.
Note!
The data address range in the Modbus network follows the protocol definition and
picks up from 0. Consequently, the data addresses in table 4.1.15.2-5 will be
decreased by one when transferred over the network.
Note!
The Modbus data type digital input (DI) is commonly also referred to as 1X, coils
as 0X, input register (IR) as 3X and holding register (HR) as 4X, of which the former
will be used here. Thus, HR 123, for instance, can also be referred to as register
400123.
76
The implementation of the Modbus protocol in REF 610 supports the following
functions:
77
78
Note!
If an “Illegal data value” exception response is generated when attempting to preset
multiple registers, the contents of the register to which an illegal value has been
imposed and of the following registers will not be changed. Registers which have
already been preset will not be restored.
User-defined registers
Reading of unwanted data in a data block wastes bandwidth and complicates data
interpretation. For optimum efficiency in Modbus communication, data has
therefore been organized into consecutive blocks. In addition, a set of programmable
user-defined registers (UDR) has been defined in the holding register area.
The first sixteen holding registers, i.e. HR1...16, are user-defined registers. The
UDRs can be linked to any holding register, except for HR721...727, using SPA
parameters 504V1...504V16. However, one UDR cannot be linked to another, i.e.
linking cannot be nested. Each parameter contains the address of the holding register
to which the UDR is linked.
If a UDR is linked to a non-existent holding register, reading from the register will
fail and an “Illegal address exception” response will be sent. Giving the link address
the value 0 will disable the UDR. If the master reads from a disabled UDR, the value
0 will be returned.
The UDRs are mirrored in HR385…400.
Fault records
The data recorded during a fault sequence is called a fault record (FR). The slave
stores the five latest fault records. When a sixth record is stored, the oldest record
will be deleted. To read a fault record:
1. Write a preset single register command (function 06) to HR601 using a selection
code as data value.
2. Read the selected fault record (function 04) from HR601, register count 28.
Alternatively, a fault record can be read using one command (function 23) only.
Selection code 1: The master reads the oldest unread record
Status register 3 (HR403) informs whether there are unread fault records (see Fig.
4.1.15.2.-2). If there is one or several unread fault records, the master can read the
contents using selection code 1.
The fault record contains a sequence number which makes it possible for the master
to determine whether one or several unread fault records have been deleted due to
overflow. The master compares the sequence number to that of the previously read
fault record.
The slave keeps track of which fault record is currently the oldest unread. The master
can continue reading fault records for as long as Status register 3 indicates that there
are unread records.
Special case 1: If there are no unread fault records, the contents of the last read
record will be returned. If the buffer is empty, however, the registers will contain
only zeros. This is the only time when sequence number zero will appear.
79
Special case 2: If the master tries to read the next unread fault record without
entering selection code 1 again, the contents of the last read record will be returned.
Selection code 2: The master reads the oldest stored record
By resetting the read pointer using selection code 2, the master can read the oldest
stored fault record. After this, the master can continue reading the following records
using selection code 1, irrespective of whether they have been read before.
Note!
Resetting the read pointer will not affect the sequence number of the fault record.
Note!
A master reset, i.e. clearing of targets and memorized values and unlatching of
output contacts, will clear the fault records, after which the sequence number will
pickup from 1 again.
Event records
Modbus events are derived from SPA events. With a few exceptions, SPA events
update binary points in the DI and the packed HR area. Simultaneously, a
corresponding Modbus event record will be generated. The event record contains the
Modbus DI/CO data point address and the value to which the point has changed
(0 or 1). SPA events lacking a corresponding DI/CO data point are shown as SPA
channel and event code (informative event) in the event record. The maximum
capacity of the Modbus event buffer is 99 events. The time stamp of Modbus events
is extended to contain complete information, from date to millisecond. To read an
event record:
1. Write a preset single register command (function 06) to HR671 using a selection
code as data value.
2. Read the selected fault record (function 04) from HR672, register count 8.
Alternatively, a fault record can be read using one command (function 23) only.
Selection code 1: reading the oldest unread record
Status register 3 (HR403) informs whether there are unread event records (see Fig.
4.1.15.2.-2). If there is one or several unread event records, the master can read the
contents using selection code 1.
The event record contains a sequence number which makes it possible for the master
to determine whether one or several unread event records have been deleted due to
overflow by comparing it to the sequence number of the previously read event
record.
The slave keeps track of which event record is currently the oldest unread. The
master can continue reading event records for as long as Status register 3 indicates
that there are unread records.
Special case 1: If there are no unread event records, the contents of the last read
record will be returned. If the buffer is empty, however, the registers will contain
only zeros. This is the only time when sequence number zero will appear.
Special case 2: If the master tries to read the next unread event record without
entering selection code 1 again, the contents of the last read record will be returned.
80
Momentary
Change detect
Master reads
Master reads
Master reads
Master reads
ChDet_a
81
Digital data
Pickup signal from element 409.00 1 0/1 1 = activated
51P
82
83
84
85
86
Structure 1
The status registers contain information on unread fault and event records, and relay
status. The registers are arranged as in the figure below.
15 8 7 0
401 Reserved IRF code
403 FR ER Reserved SP MP
StatRegREF610_a
87
Structure 3
This structure contains Modbus event records. Refer to section Event records for the
reading method.
88
Structure 4
The relay's real-time clock is stored in this structure. It can be updated by presetting
the whole register structure in one Modbus transaction.
89
The default class settings of the DNP points within the different event object groups
are:
• binary inputs change events: class 1
• analogue inputs change events: class 2
• counter change events: class 3
All static data points belong to class 0.
Unsolicited reporting is enabled for all event objects as default. However, the
point-specific enable/disable parameters are meaningless unless unsolicited
reporting has been enabled with SPA parameter 503V24.
The pointers to the scaling factors for analogue objects are all 0 as default.
Consequently, the DNP and Modbus analogue values of REF 610 are identical as
default.
All DNP process points can be edited using the Relay Setting Tool. Editing features
include:
• re-organizing, adding and removing DNP points
• assigning event classes to specific DNP points
• DNP point-specific enabling/disabling of unsolicited reporting
• defining deadbands for event reporting
• defining scaling factors for analogue values
90
91
92
DNP V3.00
DEVICE PROFILE DOCUMENT
Vendor Name: ABB Oy, Distribution Automation
Device Name: REF 610
Highest DNP Level Supported Device Function
For Requests lb Slave
For Responses lb
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
Additions to level 2 are marked as shaded in the implementation table.
Maximum Data Link Frame Size (octets) Maximum Application Fragment Size (octets)
Transmitted 292 Transmitted 2048
Received 292 Received 2048
Maximum Data Link Re-tries: Maximum Application Layer Re-tries:
Configurable, range from 0 to 255 with Configurable, range from 0 to 255 with
primary data link layer retransmission count application layer retransmission count
Requires Data Link Layer Confirmation:
Configurable, with confirmation type selector, default NO ACK
Requires Application Layer Confirmation
Configurable with confirmation type selector when reporting Event Data
(Slave devices only)
Always after response to reset request
93
ENABLE/DISABLE UNSOLICITED
Function codes supported
No other options are permitted.
Default Counter Object/Variation Counters Roll Over at
No Counters Reported No Counters Reported
94
95
96
97
98
99
100
Example (class 1)
The events will be reported when the event delay (SPA parameter 503V18) has
elapsed or the defined amount of events (SPA parameter 503V19) have been
generated for class 1.
If send throttles are not desired, the event delay should be set to 0 and the event count
to 1. In this case, the class events will be sent to the host immediately as they occur.
Event buffer overflow
DNP 3.0 event buffer overflow is indicated with the internal target IIN2.3, as
defined by the standard. IIN2.3 can also indicate event buffer overflow in the
internal communication between the DNP3.0 module and the main CPU module of
REF 610. In this case, REF 610 will automatically activate and reset the IIN2.3 bit.
As events have been lost in both cases, the DNP 3.0 master should perform an
integrity scan after the IIN2.3 bit has been reset.
DNP counters and frozen counters
DNP counters in use have a corresponding frozen counter. The frozen counters in
object group 21 have the same DNP point index as the ordinary DNP counters.
Further, frozen counters can only be read as static objects, and frozen counter events
(object group 23) are not supported.
101
Example
102
103
104
Auto-reclose parameters
Table 4.1.17-2 Settings
Parameter
Description (R, W, P), Value
channel 0
CB Closing time V121 0.1...10 s
Pickup delay of element 51P V122 0...300 s
Pickup delay of element 51N V123 0...300 s
Reset time V124 3...300 s
Cutout time V125 0.1...300 s
Open time of shot 1 V126 0.1...300 s
Open time of shot 2 V127 0.1...300 s
Open time of shot 3 V128 0.1...300 s
SG1 V129 0...255
SG2 V130 0...1023
SG3 V131 0...31
The AR function can be activated either via the HMI or with SPA parameter S25 by
setting the number of auto-reclose shots to 1, 2 or 3.
105
Recorded data
Parameter V1 shows the element which has caused the trip, parameter V2 the trip
target code, parameters V3...V8 show the number of pickups of the protection
elements, parameters V9...V12 the number of trips of the protection elements, and
parameters V13...V24 the number of initiated auto-reclose shots.
106
107
108
Disturbance recorder
Table 4.1.17-5 Parameters for the disturbance recorder
Parameter
Description R, W Value
(channel 0)
Remote triggering M1 2) W 1
Clear recorder memory M2 W 1
Sampling rate M15 3) R, W 800/960 Hz
400/480 Hz
50/60 Hz
Station identification/unit number M18 R, W 0...9999
Rated frequency M19 R 50 or 60 Hz
Name of the feeder M20 R, W Max 16 characters
Digital channel texts M40...M47 R
Analogue channel texts M60...M63 R
Analogue channel conversion factor and M80 1) 4) R, W Factor 0...65535, unit
unit for Ia, Ib and Ic M81 and (A, kA), e.g. 10,kA
M82 R
Analogue channel conversion factor and M83 1) R, W Factor 0...65535, unit
unit for the ground-fault current (A, kA), e.g. 10,kA
Internal trigger signals' checksum V236 R, W 0...16383
Internal trigger signal's edge V237 R, W 0...16383
Checksum of internal signal storing mask V238 3) R, W 0...16383
Post-triggering recording length V240 R, W 0...100%
External trigger signal's checksum V241 R, W 0...31
External trigger signal's edge V242 R, W 0...31
Checksum of external signal storing mask V243 3) R, W 0...31
Triggering state, clearing and restart V246 R, W R:
0 = recorder not
triggered
1 = recorder triggered
and recording stored
in the memory
W:
0 = clear recorder
memory
2 = download restart;
sets the first
information and the
time stamp for
triggering ready to be
read
4 = manual triggering
1)
The disturbance recorder requires this parameter to be set. The conversion factor is the
transformation ratio multiplied by the rated current of the relay. If this parameter has been given the
value 0, dashes will be shown on the LCD instead of the primary values and the recorded data will be
redundant.
2)
M1 can be used for broadcast triggering by using the unit address “900”.
3)
Parameters can be written if the recorder has not been triggered.
4)
This value is copied to parameters M81 and M82.
109
Control parameters
Table 4.1.17-8 Control parameters
Description Parameter R, W, P Value
Reading of the event buffer L R Time, channel number and
event code
Re-reading of the event buffer B R Time, channel number and
event code
Reading of relay state data C R 0 = normal state
1 = the relay has been
subject to an automatic
reset
2 = overflow of the event
buffer
3 = both 1 and 2
110
111
The measured currents can be read with parameters I1...I4, the calculated phase
discontinuity value with parameter I5, the status of light detection with parameter I6,
the CB position with parameter I7 and the status of the digital inputs with parameters
I8...I12.
112
Each protection element has its internal output signal. These signals can be read with
parameters O1...O26 and the recorded functions with parameters O61...86. The state
of the output contacts can be read or changed with parameters O41...O49 and the
recorded functions read with parameters O101...O109.
113
Note!
Parameters O41...O49 and O51 control the physical output contacts which can be
connected to circuit breakers, for instance.
Parameters for the IEC 60870-5-103 remote communication
protocol
Table 4.1.17-12Settings
Parameter
Description R, W, P Value
(channel 507)
Unit address of the relay 507V200 R, W 1...254
Data transfer rate (IEC_103), kbps 507V201 R, W 9.6/4.8
114
115
Table 4.1.17-14Settings
SPA
parameter
Description R, W Value range Default Explanation
(channel
503)
Primary data link 503V4 R, W 0...255 0 Number of
layer retransmissions on data
retransmission link layer
count
Application layer 503V6 R, W 0...65535 ms 5000 Used when REF 610
confirmation sends messages with
timeout confirmation request
Application layer 503V7 R, W 0...255 0 Number of
retransmission retransmissions on the
count application layer when
REF 610 sends messages
with confirmation request
Confirmation on 503V9 R, W 0 = enabled only 0 Used to enforce inclusion
application layer for event of confirmation request in
messages all application messages
1 = enabled for (DNP 3.0 standard
all messages requires inclusion of
confirmation request in
event messages only)
Default variation 503V10 R, W 1...2 2
of binary input
objects
Default variation 503V11 R, W 1...2 2
of binary input
change event
objects
Default variation 503V15 R, W 1...4 2
of analogue input
objects
Default variation 503V16 R, W 1...4 2
of analogue input
change event
objects
Default variation 503V13 R, W 1...2 2
of counter objects
Default variation 503V14 R, W 1, 2, 5, 6 2
of counter change
event objects
Default variation 503V30 R, W 1, 2, 5, 6 2
of frozen counter
objects
Class 1 event 503V18 R, W 0...255 s 0
delay
Class 1 event 503V19 R, W 0...255 1
count
Class 2 event 503V20 R, W 0...255 s 0
delay
Class 2 event 503V21 R, W 0...255 1
count
Class 3 event 503V22 R, W 0...255 s 0
delay
116
Table 4.1.17-14Settings
SPA
parameter
Description R, W Value range Default Explanation
(channel
503)
Class 3 event 503V23 R, W 0...255 1
count
Unsolicited 503V24 R, W 0 = UR disabled 0 Refer to section
reporting mode 1 = immediate Unsolicited reporting pick
2 = empty UR up under section Protocol
3 = empty UR parameters of REF 610.
and enable UR
Scaling factor 1 503V101 R, W 0...4294967296 1
Scaling factor 2 503V102 R, W 0...4294967296 1
Scaling factor 3 503V103 R, W 0...4294967296 1
Scaling factor 4 503V104 R, W 0...4294967296 1
Scaling factor 5 503V105 R, W 0...4294967296 1
Baud rate 503V211 R, W 4.8/9.6/19.2/38.4 9.6
Number of stop 503V212 R, W 1...2 1
bits
Parity 503V230 R, W 0 = no parity 0
1 = odd
2 = even
Silent interval 503V232 R, W 0...65535 ms 20
Time slot width 503V233 R, W 0...255 ms 10
Number of time 503V234 R, W 0...255 8
slots
Collision 503V235 R, W 0 = disabled 0
detection enabled 1 = enabled
DNP module 503V168 R Bit coded
warning register 0 = OK
DNP module 503V169 R Bit coded
status register 0 = OK
Measurements
Table 4.1.17-15 Measured values
Parameter
Description R, W, P Value
(channel 0)
Thermal level V60 R, W (P) 0...106% 1) 3)
One-minute demand value V61 R 0...50 x In (CT)
Demand value during the specified time range V62 R 0...50 x In (CT)
117
Channel 0
Events always included in the event reporting:
118
Channel 1
Table 4.1.17.1-5 Event codes E1...E12
Weighting
Channel Event Description Default value
factor
1 E1 Pickup signal from element 51P activated 1 1
1 E2 Pickup signal from element 51P reset 2 0
1 E3 Trip signal from element 51P activated 4 1
1 E4 Trip signal from element 51P reset 8 0
1 E5 Pickup signal from element 50P-1 activated 16 1
1 E6 Pickup signal from element 50P-1 reset 32 0
1 E7 Trip signal from element 50P-1 activated 64 1
1 E8 Trip signal from element 50P-1 reset 128 0
1 E9 Pickup signal from element 50P-2 activated 256 1
1 E10 Pickup signal from element 50P-2 reset 512 0
1 E11 Trip signal from element 50P-2 activated 1024 1
1 E12 Trip signal from element 50P-2 reset 2048 0
Default value of event mask 1V155 1365
119
Channel 2
Table 4.1.17.1-8 Event codes E1...E16
Weighting
Channel Event Description Default value
factor
2 E1 PO1 activated 1 1
2 E2 PO1 reset 2 1
2 E3 PO2 activated 4 0
2 E4 PO2 reset 8 0
2 E5 PO3 activated 16 0
2 E6 PO3 reset 32 0
2 E7 SO1 activated 64 0
2 E8 SO1 reset 128 0
2 E9 SO2 activated 256 0
2 E10 SO2 reset 512 0
2 E11 SO3 activated 1024 0
2 E12 SO3 reset 2048 0
2 E13 SO4 activated 4096 0
2 E14 SO4 reset 8192 0
2 E15 SO5 activated 16384 0
2 E16 SO5 reset 32768 0
Default value of event mask 2V155 3
120
Channel 3
Table 4.1.17.1-10Event codes E1...E12
Weighting
Channel Event Description Default value
factor
3 E1 Shot 1 initiated 1 1
3 E2 Shot 1 ended 2 1
3 E3 Shot 2 Initiated 4 1
3 E4 Shot 2 ended 8 1
3 E5 Shot 3 initiated 16 1
3 E6 Shot 3 ended 32 1
3 E7 CB position open 64 1
3 E8 CB position closed 128 1
3 E9 Definite trip alarm signal activated 256 1
3 E10 Definite trip alarm signal reset 512 1
3 E11 AR lockout signal activated 1024 0
3 E12 AR lockout signal reset 2048 0
Default value of event mask 3V155 1023
121
122
For further information on internal relay faults, refer to the Operator’s Manual.
Warnings
In case of a warning, the relay will continue to operate except for those protection
functions possibly affected by the fault, and the green target LED (ready) will
remain lit as during normal operation. Further, a fault target message, which
depending on the type of fault includes a fault code, will appear on the LCD. If more
than one type of fault occur at the same time, one single numeric code which
indicates all the faults will be displayed. The fault target message cannot be
manually cleared but will disappear with the fault.
When a fault appears, the fault target message is to be recorded and stated when
ordering service. The fault codes are listed in the following table:
123
External parameterization
The Relay Setting Tool is used for parameterizing the relay units. Adjusting the
parameter values using the Relay Setting Tool is done off-line, after which the
parameters can be downloaded to the relay via a communication port.
124
The IRF contact functions as an output contact for the self-supervision system of the
protection relay (see table 4.2.1-3). Under normal operating conditions the relay is
energized and the contact closed (X4.1/3-5). When a fault is detected by the
self-supervision system or the auxiliary voltage is disconnected, the output contact
will drop off and the contact close (X4.1/3-4).
Fig. 4.2.1.-1...Fig. 4.2.1.-3 present a rear view of REF 610, showing four connecting
sockets: one for measuring transformers, one for the optional I/O module, one for
power supply and one for optional serial communication.
X2.1
X3.1
11 12
X4.1
1 1
2 2
X5.1 3 3
10
4 4
5 5
9
X5.2 6 6
7 7
DANGER - RISK OF ELECTRIC SHOCK
8 8
8
TX 9 9
NEAR INSTRUMENT TERMINALS
X5.3 10 10
7
11 11
RX 12 12
13 13 6
14 14
TX 15 15
5
16 16
X5.4 17 17
18 18
4
RX
19 19
20 20
3
21 21
22 22
23 23
!
24 24
RearArcGlass_a
1
Fig. 4.2.1.-1 Rear view of REF 610 with the fibre-optic communication module
for plastic and glass fibre with light sensor inputs
125
X2.1
X3.1
11 12
X4.1
1 1
2 2
3 3
10
4 4
5 5
9
6 6
7 7
8
9 9
7
11 11
12 12
13 13
6
14 14
15 15
5
X5.5 16 16
17 17
6 18 18
4
5 19 19
4
3 20 20
3
2 21 21
1 22 22
23 23
!
24 24 2
RearRS_RE_61_a
1
Fig. 4.2.1.-2 Rear view of REF 610 with the RS-485 communication module
126
X2.1
X3.1
11 12
X4.1
1 1
2 2
3 3
10
4 4
5 5
9
6 6
7 7
8
9 9
7
11 11
12 12
13 13
6
14 14
15 15
5
16 16
8 17 17
7
6 18 18
4
X5.8 5 19 19
4
3 20 20
3
2 21 21
1 22 22
23 23
!
2
24 24
1
RearDNP_a
Fig. 4.2.1.-3 Rear view of REF 610 with the DNP 3.0 communication module
for RS-485
REF610A15xxxx
REF610A51xxxx
REF610A52xxxx
REF610A55xxxx
REF610A11xxxx
Terminal
X2.1-1 la 1 A la 1 A la 1 A la 5 A la 5 A la 5 A
X2.1-2
X2.1-3 lb 1 A lb 1 A lb 1 A lb 5 A lb 5 A lb 5 A
X2.1-4
X2.1-5 lc 1 A lc 1 A lc 1 A lc 5 A lc 5 A lc 5 A
X2.1-6
X2.1-7 In 1 A In 0.2 A In 5 A In 1 A In 0.2 A In 5 A
X2.1-8
X2.1-9 - - - -
X2.1-10 - - - -
X2.1-11 - - - -
X2.1-12 - - - -
1)
The value denotes the rated current for each input.
127
128
129
RS-485 connection
If REF 610 is provided with the optional RS-485 communication module, the cable
is connected to terminals X5.5/1-2 and X5.5/4-6. The connection socket is a 6-pin
header-type socket and the terminals are of screw compression type.
The RS-485 communication module follows the TIA/EIA-485 standard and is
intended to be used in a Daisy-chain bus wiring scheme with 2-wire, half-duplex,
multi-point communication. The maximum number of devices (nodes) connected to
the bus where REF 610 is being used is 32, and the maximum length of the bus is
1200 meters.
When connecting REF 610 to the bus, a quality twisted pair shielded cable is to be
used. The conductors of the pair are connected to A and B. If signal ground is being
used for balancing potential differences between devices/nodes, a quality dual
twisted pair shielded cable is to be used. In this case, one pair is connected to A and
B, and one of the conductors of the other pair to signal ground. When connecting
one device to another, A is connected to A and B to B.
The cable shield is to be connected directly to ground (shield GND) in one point/
device of the bus. Other devices connected to the bus should have the cable shield
connected to ground via a capacitor (shield GND via capacitor).
Note!
Signal ground can only be used for balancing potential differences between devices/
nodes if all devices connected to the bus have isolated RS-485 interfaces.
The RS-485 communication module is provided with jumpers for setting bus
termination and fail-safe biasing. The bus is to be terminated at both ends, which can
be done by using the internal termination resistor on the communication module.
The termination resistor is selected by setting jumper X5 to the ON position. If the
internal termination resistor of 120 Ω is used, the impedance of the cable should be
the same.
The bus is to be biased at one end to ensure fail-safe operation, which can be done
using the pull-up and pull-down resistors on the communication module. The
pull-up and pull-down resistors are selected by setting jumpers X3 and X4 to the ON
position.
The jumpers have been set to no termination (X5 in the OFF position) and no biasing
(X3 and X4 in the OFF position) as default.
130
off
on X3
off X4
on
off
X5
on
RS_JumpersREF610_a
131
X5.3-TX(plastic)
X5.3-RX(plastic)
Fibre-optic Interface
X5.3 TX
X5.4 TX X6
X5.3 RX
X5.4 RX X2
X6
X2
X5.4-TX(glass)
X5.4-RX(glass)
JunpersMixREF610_a
Fig. 4.2.3.-2 Jumper location on the communication module for plastic and
glass fibre
132
When connecting REF 610 to the bus, a quality twisted pair shielded cable is to be
used. The conductors of the pair are connected to A and B. If signal ground is being
used for balancing potential differences between devices/nodes, a quality dual
twisted pair shielded cable is to be used. In this case, one pair is connected to A and
B, and one of the conductors of the other pair to signal ground. When connecting
one device to another, A is connected to A and B to B.
When using a 4-wire bus, one pair is connected to +RX and -RX and the other to
+TX and -TX. If signal ground is being used, a quality cable with three or several
pairs is to be used and one of the conductors of a pair connected to signal ground.
The cable shield is to be connected directly to ground (shield GND) in one
point/device of the bus. Other devices connected to the bus should have the cable
shield connected to ground via a capacitor (shield GND via capacitor).
Note!
Signal ground can only be used for balancing potential differences between
devices/nodes if all devices connected to the bus have isolated DNP interfaces.
The DNP communication module is provided with jumpers for setting bus
termination and fail-safe biasing. The bus is to be terminated at both ends, which can
be done by using the internal termination resistor on the DNP communication
module. The termination resistor is selected by setting jumper X6 or/and X12 to the
ON position. If the internal termination resistor of 120 Ω is used, the impedance of
the cable should be the same.
The bus is to be biased at one end to ensure fail-safe operation, which can be done
using the pull-up and pull-down resistors on the communication module. The
pull-up and pull-down resistors are selected by setting jumpers X8, X7, X13 and
X11 to the ON position.
The jumpers have been set to no termination (X5 in the OFF position) and no biasing
(X8, X7, X13 and X11 in the OFF position) as default.
133
ON X13
X8 ON
ON X12
X6 ON
ON X11
X7 ON
X14
DNP_JumpersREF610_a
4-Wire
2-Wire
134
Table 4.2.4-6 Non-trip output SO1 and optional SO4 and SO5
Rated voltage 250 V ac/dc
Continuous carry 5A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time 1 A/0.25 A/0.15 A
constant L/R <40 ms, at 48/110/220 V dc (5 A/3 A/1 A for series connection of
SO4 and SO5)
Minimum contact load 100 mA at 24 V ac/dc
135
Table 4.2.4-7 Non-trip output SO2, optional SO3, and IRF output
Rated voltage 250 V ac/dc
Continuous carry 5A
Make and carry for 3.0 s 10 A
Make and carry for 0.5 s 15 A
Breaking capacity when the control-circuit time 1 A/0.25 A/0.15 A
constant L/R <40 ms, at 48/110/220 V dc
Minimum contact load 100 mA at 24 V ac/dc
Table 4.2.4-9 Lens sensor and optic fibre for arc protection
Normal service temperature range -40...+100°C
Maximum service temperature range, max 1 h +140°C
Minimum permissible bending radius of the 100 mm
connection fibre
136
137
Auxiliary voltage
REF 610 requires a secured auxiliary voltage supply to operate. The internal power
supply of the relay forms the voltages required by the relay electronics. The power
supply is a galvanically isolated (flyback-type) DC/DC converter. When the
auxiliary voltage is connected, the green target LED (ready) on the front panel will
be on. For detailed information on power supply, refer to table 4.2.4-2.
The primary side of the power supply is protected with a fuse located on the PCB of
the relay.
138
5. Application examples
Open CB
Close CB
79
Trip Close CB
51P
Block 50P-1 at
Shot 1,2 and 3
SG2/2=1 Block 50P-1
SG2/7=1
50P-1 Trip
CB Open
Shot 1 Shot 2 Shot 3 Definite Trip
Fig. 5.1.1.-1 Fast initiation of shot 1 using one fast and one delayed element
In case of a short-circuit in the network, element 50P-1 will trip the circuit breaker
and initiate shot 1. At the time of shot initiation, the blocking of element 50P-1 will
be activated. If the network fault is not cleared, element 51P will trip the circuit
breaker and continue the auto-reclose sequence to shot 2, shot 3 and finally definite
tripping.
139
As the set pickup value of element 51P in this example is higher than that of element
50P-1, as sometimes is the case, it is possible that the current will not exceed the set
pickup value of element 51P while the blocking of element 50P-1 is active. This will
lead to a pumping effect when the AR function is reset (the blocking of element 50P-
1 included), i.e. the AR sequence will pickup over and over again.
To avoid such a pumping effect, a cutout time is used. The cutout time, like the reset
time, will pickup when the set open time elapses and the AR function issues a
reclosing command to the circuit breaker. By setting the cutout time to be shorter
than the reset time (e.g. half of the reset time), the blocking of element 50P-1 (in this
case) will be reset before the AR function. Element 50P-1 will now be able to
continue the AR sequence and the pumping effect will thus be avoided.
Open CB
79
CB Closed
CB Open
Shot 1 Shot 2 Shot 3 Definite Trip
140
Shot initiation by a pickup signal applies only to shot 1, and to definite tripping, i.e.
when no more shots are allowed but the network fault has not been cleared. In this
case, the AR function will trip the circuit breaker on expiration of AR 51P Pickup
Delay and AR 51N Pickup Delay.
Note!
The signal Open CB Command must be routed to the output contact used for
tripping the circuit breaker.
Note!
At the factory default delay of 300 s for AR 51P Pickup Delay and AR 51N
Pickup Delay, the pickup signals will, in practise, not be used for shot initiation.
However, if elements 51P or 51N have been given an IDMT (mode) characteristic,
the factory default delay of 300 s will function as a trip time limiter. With small
currents, the operate time at IDMT (mode) characteristic may be relatively long.
However, since the pickup signals are always routed to the AR function, the circuit
breaker will be tripped and a shot initiated (provided that the signal Open CB
Command has been routed to the trip output contact) on expiration of the factory
default delay.
Note!
When using AR 51P Pickup Delay and AR 51N Pickup Delay for shot
initiation and the signal Open CB Command has been routed to the trip output
contact, elements 51P and 51N should not be used for blocking of shot 1.
Settings Function
SG1/1=1 Blocking of initiation of shot 1 by the trip signal from element 50P-1
SG3/1=1 Disable of the AR function by the trip signal from element 50P-2
Number of shots = 3
141
Element 50P-2 should have the shortest and element 51P the longest operate time.
Example 2
Pickup by checking that the switches have been properly set:
Settings Function
SG1/5=1 Blocking of initiation of shot 2 and 3 by the trip signal from element
50P-1
SG3/1=1 Disable of the AR function by the trip signal from element 50P-2
Number of shots = 3
142
52
PO3
REF 610
PO1
52
52 52 52 52
143
52
PO3 DI1
REF 610
PO1 SO1
52
Q3
52 52 52 52
144
5.2.3. Arc protection with several REF 610 relays and one REA 101
When realizing an arc protection with both REF 610 relays and an REA 101 (see Fig.
5.2.3.-1), the cable terminations of outgoing feeders are protected by REF 610 relays
using one lens sensor for each relay. The busbar and the incoming feeder is protected
by the sensor loop of the REA 101.
On arc detection at the cable terminations, REF 610 will trip the circuit breaker of
the outgoing feeder. However, on detection of an arc on the busbar, REA 101 will
trip the circuit breaker of the incoming feeder and generate an external trip signal to
all REF 610 relays protecting outgoing feeders, which in turn will result in tripping
of all circuit breakers of outgoing feeders.
52
HSO2
REA 101
HSO1 TRIP3
52
Q3
52 52 52 52
Fig. 5.2.3.-1 Arc protection with REF 610 and REA 101
145
6. Ordering information
When ordering REF 610 protection relays and/or accessories, please specify the
following:
• Order number
• Quantity
The order number identifies the protection relay type and hardware as described in
the figures below and is labelled on the marking strip under the lower handle of the
relay.
Use the ordering key in Fig. 6.-1 to generate the order number when ordering
complete protection relays. HMI language set numbers, and corresponding
terminology and languages included, are described in Table 6-1.
REF610B55HCNP XX
Language set: HMI language set number
OrdInfo1REF610_b
3xPO, 2xSO
Revision
146
REF610B55HSNS XX
Language set: HMI language set number
OrdInfo2REF610_b
Ground-fault current input: 5 = 5A, 1=1A, 2=0.2A
Revision
Table 6.-1
Language set number Terminology Languages
11 ANSI English, Español, Portuguese
147
Table 7.1.-1
Product Revision Release
REF 610 A Q4/2004
REF 610 B Q1/2005
148
8. References
Other available manuals:
• Operator’s Manual, 1MRS 755311
• Installation Manual, 1MRS 752265-MUM
149
9. Abbreviations
ANSI American National Standards Institute
AR Auto-reclose
ASCII American Standard Code for Information Interchange
AWG American wire gauge
CB Circuit breaker
CBFAIL Circuit-breaker failure protection
CD Change detect
CPU Central Processing Unit
CRC Cyclical Redundancy Check
CT Current transformer
DI Digital input
EEPROM Electrically erasable programmable read-only memory
EMC Electromagnetic compatibility
EPA Enhanced Performance Architecture
ER Event record
FR Fault record
GI General interrogation
HMI Human-Machine Interface
HR Holding register
IDMT (mode) Inverse definite minimum time
IEC International Electrotechnical Commission
IEC_103 Standard IEC 60870-5-103
IEEE Institute of Electrical and Electronics Engineers, Inc.
IR Input registers
IRF Internal relay fault
ISO International Organization for Standardization
LCD Liquid Crystal Display
LED Light-emitting diode
LRC Longitudinal Redundancy Check
LSB Least significant bit
MP Minute-pulse
MSB Most significant bit
MV Medium Voltage
NC Normally closed
NO Normally open
OSI Open System Interconnection
PC Personal Computer
PCB Printed Circuit Board
PLC Programmable Logical Controller
PO1, PO2, PO3 Trip outputs
RMS Root Mean Square
RTU Remote Terminal Unit
150
151
152
153
154
155
156
157