West Bay Lagoon Villas
Q9971-1 Hot Water
V1
Project No. Date
Alpha MSH DESIGN CALCULATION
Mplumbing and Fire Fighting Department SHEET Sheet No. Computed by
Phnom Penh-Cambodia
Subject Hot Water Demand For Tower Checked by Approved by
Building Apartment
1- Tower
HW Demand Storage
Fixture type Occup NO Total Flow Storage Heater
Demand Factor Factor
lph / fix lph lph liter kW
Toilet
Lavatory Private 300 7.6 2280
Bath Tub Private 300 76 22800
Bidet Private 300 11 3300
Shower Private 300 284 85200
Dishwasher Private 0 57 0
Washing MachinPrivate 0 76 0
Kitchen Sink Private 0 38 0
SSS-SSSSS SSS,SSS S.SS S.S SS,SSS SS,SSS S,SSS
Total Possible max demand 113580 28,395 22,716 1,154
First Hour Probable max. demand 28395 lit/h
Required storage capacity = 22716 lit
Required heater capacity = 1154 kW
NB: Probable max demand = lph * Demand Factor
Required Storage Capacity = Probable max. demand* Storage Factor
Heater Capacity = (Storage capacity/3600)* 4.18*(60-25)
Q9971-1-CLC-ME-01-Rev A 1 of 1