Mitsubishi: CC-Link System Compact Remote Type Input/Output Module
Mitsubishi: CC-Link System Compact Remote Type Input/Output Module
2000 No.127E
MITSUBISHI NEW PRODUCT RELEASE
CC-LINK
GENERAL-PURPOSE
PROGRAMMABLE CONTROLLERS
AJ65SBTB2N-8A,AJ65SBTB2N-16A,AJ65SBTB3-8D,AJ65SBTB3-16D,AJ65SBTB2-8T,
AJ65SBTB2-16T,AJ65SBTB2N-8R,AJ65SBTB2N-16R,AJ65SBTB2N-8S,AJ65SBTB2N-16S,
AJ65SBTB1-16DT,AJ65SBTB1-16DT1,AJ65SBTB1-32DT,AJ65SBTB32-8DT,AJ65SBTB32-16DT
CC-Link System Compact Remote Type Input/Output Module
New!
A total of 15 types including four types of input modules, six types of output
modules and five types of input/output combined modules have been added to
the line up of the popular CC-Link system compact remote type input/output
modules.
[Features]
1) Powerful line up with 1-wire type, 2-wire type and 3-wire type terminal blocks.
Part name Type Details
Input module AJ65SBTB2N-8A 8 points AC100V(7mA) 2-wire type response time 20ms terminal block type
AJ65SBTB2N-16A 16 points AC100V(7mA) 2-wire type response time 20ms terminal block type
AJ65SBTB3-8D 8 points DC24V(7mA) 3-wire type response time 1.5ms terminal block type
AJ65SBTB3-16D 16 points DC24V(7mA) 3-wire type response time 1.5ms terminal block type
Output module AJ65SBTB2-8T 8 points DC12/24V 2-wire type transistor output terminal block type
AJ65SBTB2-16T 16 points DC12/24V 2-wire type transistor output terminal block type
AJ65SBTB2N-8R 8 points AC240V/DC24V 2-wire type relay output terminal block type
AJ65SBTB2N-16R 16 points AC240V/DC24V 2-wire type relay output terminal block type
AJ65SBTB2N-8S 8 points AC100-240V 2-wire type TRIAC output terminal block type
AJ65SBTB2N-16S 16 points AC100-240V 2-wire type TRIAC output terminal block type
Input/output AJ65SBTB1-16DT 8 input points DC24V(7mA) 1-wire type response time 1.5ms
combined 8 output points DC24V(0.5A) 1-wire type transistor output terminal block type
module AJ65SBTB1-16DT1 8 input points DC24V(5mA) 1-wire type response time 0.2ms
8 output points DC24V(0.5A) 1-wire type transistor output terminal block type
AJ65SBTB1-32DT1 16 input points DC24V(5mA) 1-wire type response time 0.2ms
16 output points DC24V(0.5A) 1-wire type transistor output terminal block type
AJ65SBTB32-8DT 4 input points DC24V(7mA) 3-wire type response time 1.5ms
4 output points DC24V(0.5A) 2-wire type transistor output terminal block type
AJ65SBTB32-16DT 4 input points DC24V(7mA) 3-wire type response time 1.5ms
4 output points DC24V(0.5A) 2-wire type transistor output terminal block type
COM A
input points 60 % simultaneous ON (at 132 V AC)
PW L RUN L ERR X0 1 2 3 4 5 6 7
Inrush current Max. 200 mA within 1 ms (at 132 V AC)
X7
ON voltage/ON current 80 V AC or higher/5 mA or higher
OFF voltage/OFF current 30 V AC or lower/1 mA or lower
Approx. 15 k Ω (60 Hz), Approx. 18 k Ω (50 Hz)
X6
Input resistance
Response OFF ON 20 ms or lower (at 100 V AC 60 Hz)
X5
time ON OFF 20 ms or lower (at 100 V AC 60 Hz)
Common method 8 points/1 common (terminal block 2-wire type)
X4
Number of stations occupied 1 station 32 points assignment (use 8 points)
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
X3
power supply Current 35 mA or lower (24 V DC and all point is ON)
Noise durability Simulator noise 1500 Vp-p, noise width 1 µs, noise carrier
frequency 25 to 60 Hz (noise simulator condition)
B RATE
40 20 10 8 4 2 1 4 2 1
X2
Fast transient/noise burst IEC61000-4-4 : 1 kV
Withstand voltage 1780 V AC between all AC external terminals and ground,
X1
rms/ 3 cycles (2000 m above sea level)
STATION NO.
500 V AC for 1 minutes between all DC external terminals and
X0
ground
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance
tester between all AC external terminals and ground
10 M Ω or higher, measured with a 500 V DC insulation resistance
ON
(FG)
24G
tester between all DC external terminals and ground
Weight (kg)(lb.) 0.2 (0.44)
+24V
External wiring system 7-point 2-piece terminal block (transmission circuit, module power AJ65SBTB2N-8A
SLD
supply terminal), Direct-type 18-point terminal block (I/O power
DG
MITSUBISHI
DB
Applicable solderless • RAV1.25-3.5 (in conformance with JIS-C2805) DA
terminal 2
[Applicable wire size: 0.3 to1.25 mm ]
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.)
2
[Applicable wire size: 1.25 to 2.0 mm ]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
1 DA TB2 DB
2 DB
Insulation
TB3 DG
3 DG
4 SLD
TB4 SLD
5 +24V TB5 +24V
DC/DC
Module
6 FG TB6 FG
7 24G
power TB7 24G
supply
TB8 X0
8 X0 R R TB9 COMB
9 COM B TB10 X1
R
10 X1
TB11 COMB
11 COM B
12 X2 TB12 X2
13 COM B TB13 COMB
14 X3
TB14 X3
15 COM B
16 X4
TB15 COMB
17 COM B TB16 X4
18 X5 TB17 COMB
19 COM B
TB18 X5
20 X6
21 COM B
TB19 COMB
22 X7 TB20 X6
23 COM B TB21 COMB
24 COM A
TB22 X7
25 COM B
100 V AC
TB23 COMB
TB24 COMA
The COM terminals are all connected inside the module. (Shared commons) TB25 COMB
2) AJ65SBTB2N-16A 100 V AC input module
Form AC input module
Specification AJ65SBTB2-16A Outline
Number of input points 16 points
Insulation method Photocoupler
Rated input voltage 100 to 120 V AC 50/60 Hz
Rated input current Approx. 7 mA (100 V AC 60 Hz)
Operating voltage range 85 to 132 V AC (50/60 Hz ±5 %)
COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B
COM A
Max. simultaneous input 100 % simultaneous ON (at 100 V AC)
8 9 A B C D E F
points 60 % simultaneous ON (at 132 V AC)
XF
Inrush current Max. 200 mA within 1 ms (at 132 V AC)
ON voltage/ON current 80 V AC or higher/5 mA or higher
XE
OFF voltage/OFF current 30 V AC or lower/1 mA or lower
XD
PW L RUN L ERR X0 1 2 3 4 5 6 7
Input resistance Approx. 15 k Ω (60 Hz), Approx. 18 k Ω (50 Hz)
XC
Response OFF ON 20 ms or lower (at 100 V AC 60 Hz)
time ON OFF 20 ms or lower (at 100 V AC 60 Hz)
XB
Common method 16 points/1 common (terminal block 2-wire type)
XA
Number of stations
1 station 32 points assignment (use 16 points)
X9
occupied
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
X8
power supply Current 40 mA or lower (24 V DC and all point is ON)
X7
Noise durability Simulator noise 1500 Vp-p, noise width 1 µs, noise carrier
X6
frequency 25 to 60 Hz (noise simulator condition)
Fast transient/noise burst IEC61000-4-4 : 1 kV
X5
Withstand voltage 1780 V AC between all AC external terminals and ground,
X4
rms/ 3 cycles (2000 m above sea level)
500 V AC for 1 minutes between all DC external terminals and
X3
ground
B RATE
4 2 1
X2
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance
tester between all AC external terminals and ground
X1
40 20 10 8 4 2 1
STATION NO.
10 M Ω or higher, measured with a 500 V DC insulation resistance
X0
tester between all DC external terminals and ground
Weight (kg)(lb.) 0.25 (0.55)
ON
(FG)
24G
External wiring system 7-point 2-piece terminal block (transmission circuit, module power
supply terminal), Direct-type 34-point terminal block (I/O power
+24V
supply area) (M3 screw)
SLD
AJ65SBTB2N-16A
DG
MITSUBISHI
Applicable solderless • RAV1.25-3.5 (in conformance with JIS-C2805)
DB
2
DA
terminal [Applicable wire size: 0.3 to1.25 mm ]
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES 2
Co., Ltd.)
[Applicable wire size: 1.25 to 2.0 mm ]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
TB2 DB
TB3 DG
TB4 SLD
1 DA TB5 +24V
2 DB
3 DG Insulation TB6 FG
4 SLD TB7 24G
5 +24V
Module DC/DC TB8 X0
6 FG
power 7 24G TB9 COMB
supply
TB10 X1
8 X0 R R TB11 COMB
9 COM B
R
TB12 X2
10 X1
11 COM B
TB13 COMB
12 X2 TB14 X3
13 COM B
TB15 COMB
14 X3
15 COM B TB16 X4
16 X4 TB17 COMB
17 COM B
18 X5
TB18 X5
19 COM B TB19 COMB
20 X6 TB20 X6
21 COM B
22 X7 TB21 COMB
23 COM B TB22 X7
24 X8
25 COM B TB23 COMB
26 X9 TB24 X8
27 COM B TB25 COMB
28 XA
29 COM B TB26 X9
30 XB TB27 COMB
31 COM B
32 XC TB28 XA
33 COM B TB29 COMB
34 XD
TB30 XB
35 COM B
36 XE TB31 COMB
37 COM B TB32 XC
38 XF
39 COM B TB33 COMB
40 COM A TB34 XD
41 COM B TB35 COMB
100 V AC TB36 XE
TB37 COMB
The COM terminals are all connected inside the module. (Shared commons) TB38 XF
TB39 COMB
TB40 COMA
TB41 COMB
3) AJ65SBTB3-8D 24 V DC input module (Sink/source loading)
Form DC input module
Specification AJ65SBTB3-8D Outline
Number of input points 16 points
Insulation method Photocoupler
Rated input voltage 24 V DC
Rated input current Approx. 7 mA
Operating voltage range 19.2 to 26.4 V DC
(ripple ratio: within 5 %)
DC24A
input points
B RATE
40 20 10 8 4 2 1 4 2 1
ON voltage/ON current 14 V or higher/3.5 mA or higher
X7
OFF voltage/OFF current 6 V or lower/1.7 mA or lower
STATION NO.
Input resistance Approx. 3.3 kΩ
X6
Response OFF ON 1.5 ms or lower (when 24 V DC)
X5
time ON OFF 1.5 ms or lower (when 24 V DC)
ON
Common wiring method 8 points/1 common
X4
(terminal block B-wire type)
X3
Input method Sink/source shared type
Number of stations occupied 1 station 32 points assignment (use 8 points)
X2
I/O module Voltage 20.4 to 26.4 V DC (ripple rate: within 5 %)
X1
power supply Current 40 mA or lower (when 24 V DC and all point is ON)
Noise durability DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier
AJ65SBTB3-8D
X0
frequency 25 to 60 Hz (noise simulator condition)
PW L RUN L ERR X0 1 2 3 4 5 6 7
Withstand voltage 500 V AC for 1 minute between all DC external terminals and
ground
(FG)
24G
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance
MITSUBISHI
+24V
tester
SLD
Weight (kg) 0.18
DG
7-point 2-piece terminal block (transmission circuit, module power
DB
External wiring system
DA
supply terminal), Direct-type 18-point terminal block (I/O power
supply area) (M3 screw)
Applicable solderless • RAV1.25-3.5 (in conformance with JIS-C2805)
terminal [Applicable wire size: 0.3 to1.25 mm2]
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.)
2
[Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
TB2 DB
1 DA
2 DB
TB3 DG
3 DG Insulation TB4 SLD
4 SLD TB5 +24V
5 +24V
Module power 6 FG
DC/DC TB6 FG
supply 7 24G TB7 24G
TB8 X0
TB9 COMA
3-wire type 8 X0 R
sensor 9 COMA TB10 X1
10 X1 R TB11 COMB
2-wire type 11 COMB TB12 X2
sensor 12 X2
13 COMA TB13 COMA
14 X3 TB14 X3
15 COMB TB15 COMB
16 X4
17 COMA
TB16 X4
18 X5 TB17 COMA
19 COMB TB18 X5
20 X6
21 COMA
TB19 COMB
22 X7 TB20 X6
Source Sink 23 COMB TB21 COMA
24 DC24A
TB22 X7
25 DC24B
24 V DC TB23 COMB
TB24 DC24A
TB25 DC24B
4) AJ65SBTB3-16D 24 V DC input module (Sink/source loading)
Form DC input module
Specification AJ65SBTB3-16D Outline
Number of input points 16 points
Insulation method Photocoupler
Rated input voltage 24 V DC
Rated input current Approx. 7 mA
COMA COMB COMA COMB COMA COMB COMA COMB COMA COMB COMA COMB COMA COMB COMA COMB DC24B
DC24A
B RATE
4 2 1
Operating voltage range 19.2 to 26.4 V DC (ripple ratio: within 5 %)
Max. simultaneous ON
XF
40 20 10 8 4 2 1
100 %
STATION NO.
input points
XE
ON voltage/ON current 14 V or higher/3.5 mA or higher
XD
OFF voltage/OFF current 6 V or lower/1.7 mA or lower
ON
Input resistance Approx. 3.3 kΩ
XC
Response OFF ON 1.5 ms or lower (When 24 V DC)
XB
time ON OFF 1.5 ms or lower (When 24 V DC)
YA
Common wiring method 16 points/1 common
(terminal block 3-wire type)
Y9
Input method Sink/source shared type
X8
Number of stations
1 station 32 points assignment (use 16 points)
X7
occupied
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
X6
power supply Current 45 mA or lower (when 24 V DC and all point is ON)
X5
Noise durability DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier
X4
frequency 25 to 60 Hz (noise simulator condition)
X3
Withstand voltage 500 V AC for 1 minute between all DC external terminals and
X8 9 A B C D E F
ground
X2
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance
X1
tester
AJ65SBTB3-16D
Weight (kg) 0.25
X0
PW L RUN L ERR X0 1 2 3 4 5 6 7
External wiring system 7-point 2-piece terminal block (transmission circuit, module power
supply terminal), Direct-type 34-point terminal block (I/O power
(FG)
24G
supply area) (M3 screw).
MITSUBISHI
DA DG +24V
Applicable solderless • RAV1.25-3.5 (in conformance with JIS-C2805)
SLD
2
terminal [Applicable wire size: 0.3 to1.25 mm ]
DB
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.)
[Applicable wire size: 1.25 to 2 mm2]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
TB2 DB
TB3 DG
TB4 SLD
TB5 +24V
1 DA TB6 FG
2 DB TB7 24G
3 DG Insulation TB8 X0
4 SLD
5 +24V
DC/DC
TB9 COMA
Module power 6 FG
TB10 X1
7 24G
supply TB11 COMB
TB12 X2
3-wire type 8 X0 R
sensor 9 COMA TB13 COMA
10 X1 R TB14 X3
2-wire type 11 COMB
sensor 12 X2 TB15 COMB
13 COMA TB16 X4
14 X3
15 COMB TB17 COMA
16 X4 TB18 X5
17 COMA
18 X5 TB19 COMB
19 COMB TB20 X6
20 X6
21 COMA TB21 COMA
22 X7 TB22 X7
23 COMB
24 X8 TB23 COMB
25 COMA TB24 X8
26 X9
27 COMB
TB25 COMA
28 XA TB26 X9
29 COMA
30 XB
TB27 COMB
31 COMB TB28 XA
32 XC
33 COMA
TB29 COMA
34 XD TB30 XB
35 COMB
36 XE
TB31 COMB
37 COMA TB32 XC
38 XF TB33 COMA
Source Sink 39 COMB
40 DC24A TB34 XD
41 DC24B TB35 COMB
24 V DC
TB36 XE
TB37 COMA
TB38 XF
TB39 COMB
TB40 DC24A
TB41 DC24B
5) AJ65SBTB2-8T transistor output module (Sink type)
Form Transistor output module
Specification AJ65SBTB2-8T Outline
Number of output points 8 points
Insulation method Photocoupler
Rated load voltage 12/24 V DC
Operating load voltage
10.2 to 26.4 V DC (ripple ratio: within 5 %)
range
Max. load current 0.5 A/point (when all point 5 are ON: 0.3 A/point)
COM DC24G
2.4 A/1 common
DC24V
Max. inrush current 1.0 A 10 ms or lower
B RATE
40 20 10 8 4 2 1 4 2 1
Leakage current at OFF 0.25 mA or lower
Voltage drop at ON 0.3 V or lower (TYP) 0.5 A
Y7
COM
STATION NO.
0.6 V or lower (MAX) 0.5 A
Response OFF ON 0.5 ms or lower
Y6
COM
time ON OFF 1.5 ms or lower (resistive load)
Y5
External Voltage 10.2 to 26.4 V DC (ripple ratio: within 5 %)
COM
ON
Power supply Current 17.8 mA or lower (TYP.24 V DC/1 common)
Y4
for output Not including external load current
COM
Surge suppression Zener diode
Y3
Common wiring method 8 points/1 common
COM
(terminal block 2-wire type)
Y2
Number of stations 1 station 32 points assignment
COM
occupied (use 8 points)
I/O module Voltage 20.4 to 26.4 V DC (ripple ratio: within 5 %)
Y1
COM
power supply Current 45 mA or lower (when 24 V DC and all point is ON)
DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier
A J65SBTB2-8T
Noise durability
Y0
frequency 25 to 60 Hz (noise simulator condition)
PW L RUN L ERR Y0 1 2 3 4 5 6 7
Withstand voltage 500 V AC for 1 minute between all DC external terminals and
ground
Insulation resistance 10 MΩ or higher, measured with a 500 V DC insulation resistance
(FG)
24G
tester
MITSUBISHI
Weight (kg) 0.18
+24V
SLD
External wiring system 7-point 2-piece terminal block (transmission circuit, module power
DG
supply terminal), Direct-type 18-point terminal block (I/O power
DB
supply area) (M3 screw)
DA
Applicable solderless • RAV1.25-3.5 (in conformance with JIS C 2805)
terminal 2
[Applicable wire size: 0.3 to1.25 mm ]
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3 (Japan Terminal Co., Ltd.)
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.)
2
[Applicable wire size: 1.25 to 2 mm ]
Accessory User’s Manual
External connection
Terminal number Signal name
TB1 DA
TB2 DB
TB3 DG
1 DA TB4 SLD
2 DB TB5 +24V
3 DG Insulation TB6 FG
4 SLD
5 +24V TB7 24G
DC/DC
Module power 6 FG
TB8 Y0
7 24G
supply TB9 COM
TB10 Y1
TB11 COM
L 8 Y0
9 COM
TB12 Y2
10 Y1 TB13 COM
11 COM
12 Y2
TB14 Y3
13 COM TB15 COM
14 Y3 TB16 Y4
15 COM
16 Y4 TB17 COM
17 COM TB18 Y5
18 Y5
19 COM TB19 COM
20 Y6 TB20 Y6
21 COM
22 Y7
TB21 COM
23 COM Constant TB22 Y7
24 DC24V voltage circuit
25 DC24G
TB23 COM
I/O power supply TB24 DC24V
(external supply power) TB25 DC24G
6) AJ65SBTB2-16T transistor output module (Sink type)
Form Transistor output module
Specification AJ65SBTB2-16T Outline
Number of output points 16 points
Insulation method Photocoupler
Rated load voltage 12/24 V DC
Operating load voltage
10.2 to 26.4 V DC (ripple ratio: within 5 %)
range
Max. load current 0.5 A/point (when all point is ON: 0.22 A/point)
3.6 A/1 common
COM DC24G
DC24V
1 4 2 1
B RATE
Max. inrush current 1.0 A 10 ms or lower
Leakage current at OFF 0.25 mA or lower
YF
COM
40 20 10 8 4 2
STATION NO.
Voltage drop at ON 0.3 V or lower (TYP) 0.5 A
YE
COM
0.6 V or lower (MAX) 0.5 A
YD
Response OFF ON 0.5 ms or lower
COM
ON
YC
time ON OFF 1.5 ms or lower (resistive load)
COM
External Voltage 10.2 to 26.4 V DC (ripple ratio: within 5 %)
YB
COM
Power supply Current 24.2 mA or lower (TYP.24 V DC/1 common)
YA
COM
for output Not including external load current
Y9
COM
Surge suppression Zener diode
Y8
Common wiring method 16 points/1 common
COM
Y7
(terminal block 2-wire type)
COM
Occupied station number 1 station 32 points assignment
Y6
COM
(use 16 points)
Y5
COM
I/O module Voltage 20.4 to 26.4 V DC (ripple ratio: within 5 %)
Y4
COM
power supply Current 55 mA or lower (when 24 V DC and all point is ON)
Y3
DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier
Y8 9 A B C D E F
Noise durability
COM
Y2
frequency 25 to 60 Hz (noise simulator condition)
COM
Withstand voltage 500 V AC for 1 minute between all DC external terminals and
Y1
COM
AJ65SBTB2-16T
ground
Y0
PW L RUN L ERR Y0 1 2 3 4 5 6 7
Insulation resistance 10 MΩ or higher, measured with a 500 V DC insulation resistance
tester
(FG)
24G
Weight (kg) 0.25
MITSUBISHI
+24V
External wiring system 7-point 2-piece terminal block (transmission circuit, module power
SLD
DA DG
supply terminal), Direct-type 34-point terminal block (I/O power DB
COM A
Electrical Rated switching voltage⋅current load 10 million times or more
200 V AC 1.5 A, 240 V AC 1 A (cosφ = 0.7)
PW L RUN L ERR Y0 1 2 3 4 5 6 7
10 million times or more
Y7
200 V AC 1 A, 240 V AC 0.5 A (cosφ = 0.35)
10 million times or more
Y6
24 V DC 1 A, 100 V DC 0.1 A (L/R = 7 ms)
10 million times or more
Y5
Max. switching frequency 3600 times/hour
Y4
Surge suppression None
Common method 8 points/1 common (terminal block 2-wire type)
Y3
Number of stations
1 station 32 points assignment (use 8 points)
occupied
B RATE
40 20 10 8 4 2 1 4 2 1
Y2
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
power supply Current 85 mA or lower (when 24 V DC and all point is ON)
Y1
Simulator noise 1500 Vp-p, noise width 1 µs, noise carrier
STATION NO.
Noise durability
frequency 25 to 60 Hz (noise simulator condition)
Y0
Fast transient/noise burst IEC61000-4-4 : 1 kV
Withstand voltage 2830 V AC between all AC external terminals and ground,
rms/ 3 cycles (2000 m above sea level)
ON
(FG)
24G
500 V AC for 1 minutes between all DC external terminals and
ground
+24V
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance
AJ65SBTB2N-8R
SLD
tester between all AC external terminals and ground
10 M Ω or higher, measured with a 500 V DC insulation resistance
DG
MITSUBISHI
DB
tester between all DC external terminals and ground
DA
Weight (kg) (lb.) 0.25 (0.55)
External connection method 7-point 2-piece terminal block (transmission circuit, module power
supply terminal), Direct-type 18-point terminal block (I/O power
supply area) (M3 screw)
Applicable solderless • RAV1.25-3.5 (in conformance with JIS 2
C 2805)
terminal [Applicable wire size: 0.3 to1.25 mm ]
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3 (Japan Terminal Co., Ltd.)
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES
2
Co., Ltd.)
[Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
1 DA TB2 DB
2 DB TB3 DG
Insulation
3 DG TB4 SLD
4 SLD TB5 +24V
5 +24V
DC/DC TB6 FG
6 FG
TB7 24G
7 24G
TB8 Y0
Module power
supply TB9 COMB
L 8 Y0
TB10 Y1
9 COM B RA
TB11 COMB
10 Y1
TB12 Y2
11 COM B TB13 COMB
12 Y2 TB14 Y3
13 COM B TB15 COMB
14 Y3 TB16 Y4
15 COM B TB17 COMB
16 Y4 TB18 Y5
17 COM B
TB19 COMB
18 Y5
TB20 Y6
19 COM B
TB21 COMB
20 Y6
21 COM B
TB22 Y7
L 22 Y7
TB23 COMB
23 COM B TB24 COMA
24 COM A TB25 COMB
25 COM B
100/200 V AC
The COM terminals are all connected inside the module. (Shared commons)
8) AJ65SBTB2N-16R relay output module
Form Relay output module
Specification AJ65SBTB2N-16R Outline
Number of output points 16 points
Insulation method Relay
Rated load voltage⋅current 24 V DC (resistive load), 240 V AC (cosφ = 1)/
COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B
COM A
2 A/point 8 A/1 common
8 9 A B C D E F
Min. switching load 5 V DC 1 mA
YF
Max. switching voltage 264 V AC 125 V DC
Response OFF ON 10 ms or lower
YE
time ON OFF 12 ms or lower
YD
Life Mechanical 20 million times or more
PW L RUN L ERR Y0 1 2 3 4 5 6 7
Electrical Rated switching voltage⋅current load 10 million times or more
YC
200 V AC 1.5 A, 240 V AC 1 A (cosφ = 0.7) 10 million times or more
200 V AC 1 A, 240 V AC 0.5 A (cosφ = 0.35) 10 million times or more
YB
24 V DC 1 A, 240 V DC 1 A (L/R = 7 ms) 10 million times or more
YA
Max. switching frequency 3600 times/hour
Surge suppression None
Y9
Common method 16 points/1 common (terminal block 2-wire type)
Y8
Number of stations occupied 1 station 32 points assignment (use 16 points)
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
Y7
power supply Current 120 mA or lower (when 24 V DC and all point is ON)
Simulator noise 1500 Vp-p, noise width 1 µs, noise carrier frequency 25
Y6
Noise durability
to 60 Hz (noise simulator condition)
Y5
Fast transient/noise burst IEC61000-4-4 : 1 kV
Withstand voltage 2830 V AC between all AC external terminals and ground,
Y4
rms/ 3 cycles (2000 m above sea level)
Y3
500 V AC for 1 minutes between all DC external terminals and ground
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance tester
B RATE
1 4 2 1
Y2
between all AC external terminals and ground
10 M Ω or higher, measured with a 500 V DC insulation resistance tester
Y1
40 20 10 8 4 2
STATION NO.
between all DC external terminals and ground
Y0
Weight (kg) (lb.) 0.35 (0.77)
External wiring system 7-point 2-piece terminal block (transmission circuit, module power
supply terminal), Direct-type 34-point terminal block (I/O power supply
ON
(FG)
24G
area) (M3 screw)
Applicable solderless terminal • RAV1.25-3.5 (in conformance with JIS-C2805)
+24V
[Applicable wire size: 0.3 to1.25 mm2]
SLD
AJ65SBTB2N-16R
DG
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
MITSUBISHI
DB
RAP2-3S RAP2-3 (Japan Terminal Co., Ltd.)
DA
2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.)
[Applicable wire size: 1.25 to 2 mm2]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
TB2 DB
TB3 DG
TB4 SLD
1 DA TB5 +24V
2 DB TB6 FG
3 DG Insulation
4 SLD
TB7 24G
5 +24V
DC/DC
TB8 Y0
6 FG
7 24G
TB9 COMB
Module power TB10 Y1
supply TB11 COMB
L 8 Y0
9 COM B TB12 Y2
RA
10 Y1 TB13 COMB
11 COM B
12 Y2
TB14 Y3
13 COM B TB15 COMB
14 Y3
15 COM B
TB16 Y4
16 Y4 TB17 COMB
17 COM B TB18 Y5
18 Y5
19 COM B TB19 COMB
20 Y6 TB20 Y6
21 COM B
22 Y7 TB21 COMB
23 COM B TB22 Y7
24 Y8
25 COM B
TB23 COMB
26 Y9 TB24 Y8
27 COM B
28
TB25 COMB
YA
29 COM B TB26 Y9
30 YB
31 COM B
TB27 COMB
32 YC TB28 YA
33 COM B TB29 COMB
34 YD
35 COM B TB30 YB
36 YE TB31 COMB
37 COM B
L 38 YF TB32 YC
39 COM B TB33 COMB
40 COM A
41 COM B TB34 YD
TB35 COMB
100/200 V AC
TB36 YE
The COM terminals are all connected inside the module. (Shared commons) TB37 COMB
TB38 YF
TB39 COMB
TB40 COMA
TB41 COMB
9) AJ65SBTB2N-8S triac output module
Form Triac output module
Specification AJ65SBTB2N-8S Outline
Number of output points 8 points
Insulation method Photocoupler
Rated load voltage⋅ 100 to 240 V AC 50/60 Hz ± 5 %
Max. load voltage 264 V AC
Max. load current 0.6 A/point, 2.4 A/1 common
Min. load voltage⋅current 50 V AC 100 mA, 100 V AC 10 mA, 240 V AC 10 mA
COM A
Leakage current at OFF 1.5 mA rms or lower (100 V AC rms 60 Hz),
3 mA rms or lower (200 V AC rms 60 Hz)
PW L RUN L ERR Y0 1 2 3 4 5 6 7
Max. voltage drop at ON 1.5 V rms or lower (at 0.6 A)
Y7
Response OFF ON 1 ms or lower
time 1/2 cycle + 1 ms or lower
Y6
ON OFF
Surge suppression C·R absorver (0.01 µF + 47 Ω)
Y5
Common method 8 points/1 common (terminal block 2-wire type)
Number of stations
1 station 32 points assignment (use 8 points)
Y4
occupied
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
Y3
power supply Current 55 mA or lower (when 24 V DC and all point is ON)
Noise durability Simulator noise 1500 Vp-p, noise width 1 µs, noise carrier
B RATE
40 20 10 8 4 2 1 4 2 1
Y2
frequency 25 to 60 Hz (noise simulator condition)
Fast transient/noise burst IEC61000-4-4 : 1 kV
Y1
Withstand voltage 2830 V AC between all AC external terminals and ground,
STATION NO.
rms/ 3 cycles (2000 m above sea level)
Y0
500 V AC for 1 minutes between all DC external terminals and
ground
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance
ON
(FG)
24G
tester between all AC external terminals and ground
10 M Ω or higher, measured with a 500 V DC insulation resistance
+24V
tester between all DC external terminals and ground
AJ65SBTB2N-8S
Weight (kg) (lb.) 0.25 (0.55)
SLD
DG
External connection method 7-point 2-piece terminal block (transmission circuit, module power
MITSUBISHI
supply terminal), Direct-type 18-point terminal block (I/O power
DB
DA
supply area) (M3 screw)
Applicable solderless • RAV1.25-3.5 (in conformance with JIS C 2805)
terminal 2
[Applicable wire size: 0.3 to1.25 mm ]
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3 (Japan Terminal Co., Ltd.)
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.)
2
[Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
1 DA
TB2 DB
2 DB
TB3 DG
3 DG
Insulation TB4 SLD
4 SLD TB5 +24V
5 +24V TB6 FG
DC/DC
6 FG TB7 24G
7 24G TB8 Y0
Module power TB9 COMB
supply
surge suppression TB10 Y1
L 8 Y0
TB11 COMB
9 COM B
R TB12 Y2
10 Y1
TB13 COMB
11 COM B Triac
12 Y2
TB14 Y3
13 COM B
TB15 COMB
14 Y3 TB16 Y4
15 COM B TB17 COMB
16 Y4 TB18 Y5
17 COM B TB19 COMB
18 Y5 TB20 Y6
19 COM B TB21 COMB
20 Y6 TB22 Y7
21 COM B
TB23 COMB
L 22 Y7
23 COM B
TB24 COMA
24 COM A
TB25 COMB
25 COM B
100 V AC
The COM terminals are all connected inside the module. (Shared commons)
10) AJ65SBTB2N-16S triac output module
Form Triac output module
Specification AJ65SBTB2N-16S Outline
Number of output points 16 points
Insulation method Photocoupler
Rated load voltage 100 to 240 V AC 50/60 Hz ± 5 %
Max. load voltage 264 V AC
COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B COM B
COM A
Max. load current 0.6 A/point, 4.8A/1 common
8 9 A B C D E F
Min. load voltage⋅current 50 V AC 100 mA, 100 V AC 10 mA, 240 V AC 10 mA
YF
Max. inrush current 25 A 10 ms or lower
YE
Leakage current at OFF 1.5 mA rms or lower (100 V AC rms 60 Hz),
3 mA rms or lower (200 V AC rms 60 Hz)
YD
PW L RUN L ERR Y0 1 2 3 4 5 6 7
Max. voltage drop at ON 1.5 V rms or lower (at 0.6 A)
YC
Response OFF ON 1 ms or lower
time ON OFF 1/2 cycle + 1 ms or lower
YB
Surge suppression C·R absorver (0.01 µF + 47 Ω)
YA
Common method 16 points/1 common (terminal block 2-wire type)
Number of stations occupied 1 station 32 points assignment (use 16 points)
Y9
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
Y8
power supply Current 85 mA or lower (when 24 V DC and all point is ON)
Simulator noise 1500 Vp-p, noise width 1 µs, noise carrier
Y7
Noise durability
frequency 25 to 60 Hz (noise simulator condition)
Y6
Fast transient/noise burst IEC61000-4-4 : 1 kV
Y5
Withstand voltage 2830 V AC between all AC external terminals and ground,
rms/ 3 cycles (2000 m above sea level)
Y4
500 V AC for 1 minutes between all DC external terminals and
Y3
ground
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance
4 2 1
B RATE
Y2
tester between all AC external terminals and ground
10 M Ω or higher, measured with a 500 V DC insulation resistance
Y1
40 20 10 8 4 2 1
STATION NO.
tester between all DC external terminals and ground
Y0
Weight (kg) (lb.) 0.35 (0.77)
External connection method 7-point 2-piece terminal block (transmission circuit, module power
ON
(FG)
24G
supply terminal), Direct-type 34-point terminal block (I/O power
supply area) (M3 screw)
+24V
Applicable solderless • RAV1.25-3.5 (in conformance with JIS C 2805)
SLD
AJ65SBTB2N-16S
[Applicable wire size: 0.3 to1.25 mm2]
DG
terminal
MITSUBISHI
DB
DA
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3 (Japan Terminal Co., Ltd.)
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.)
[Applicable wire size: 1.25 to 2 mm2]
Accessory User's Manual
External connection
Terminal number Signal name
TB1 DA
TB2 DB
1 DA
TB3 DG
2 DB
3 DG Insulation TB4 SLD
4 SLD TB5 +24V
5 +24V
DC/DC
TB6 FG
6 FG TB7 24G
7 24G TB8 Y0
Module power
Surge suppression TB9 COMB
supply
L 8 Y0 TB10 Y1
9 COM B TB11 COMB
10 Y1 R TB12 Y2
11 COM B TB13 COMB
12 Y2 TB14 Y3
13 COM B Triac
14 Y3
TB15 COMB
15 COM B TB16 Y4
16 Y4 TB17 COMB
17 COM B TB18 Y5
18 Y5 TB19 COMB
19 COM B
20
TB20 Y6
Y6
21 COM B TB21 COMB
22 Y7 TB22 Y7
23 COM B TB23 COMB
24 Y8 TB24 Y8
25 COM B TB25 COMB
26 Y9
27 COM B TB26 Y9
28 YA TB27 COMB
29 COM B TB28 YA
30 YB
31 COM B TB29 COMB
32 YC TB30 YB
33 COM B TB31 COMB
34 YD
35 COM B TB32 YC
36 YE TB33 COMB
37 COM B TB34 YD
L 38 YF
39 COM B TB35 COMB
40 COM A TB36 YE
41 COM B TB37 COMB
100/200 V AC TB38 YF
TB39 COMB
The COM terminals are all connected inside the module. (Shared commons) TB40 COMA
TB41 COMB
11) AJ65SBTB1-16DT combined module
Form DC input transistor output combined module
Specification AJ65SBTB1-16DT Outline
Input specification Output specification
Number of input points 8 points Number of output points 16 points
Insulation method Photocoupler Insulation method Photocoupler
Rated input voltage 24 V DC Rated load voltage 24 V DC
Rated input current Approx. 7 mA Operating load voltage range 19.2 to 26.4 V DC(ripple ratio: within 5 %)
Operating voltage range 19.2 to 26.4 V DC Max. load current 0.5 A/point
(when all point 5 are ON : 0.225 A/1
(ripple ratio: within 5 %) point) 3.6 A/common
Max. simultaneous input Max. inrush current
100 % 1.0 A 10 ms or lower
COM-
points
COM+
B RATE
40 20 10 8 4 2 1 4 2 1
ON voltage/ON current 14 V or higher/3.5 mA or higher Leakage current at OFF
0.25 mA or lower
YF
OFF voltage/OFF current Voltage drop at ON
0.3 V or lower (TYP)0.5 A
YE
6 V or lower/1.7 mA or lower
0.6 V or lower (MAX)0.5 A
STATION NO.
YD
Input resistance Output form
YC
Sink type with overload protection
9B
A pprox. 3.3 k Ω frunction, overvoltage protection
YA
function, overheat protection function.
ON
Y9
Y8
Response OFF ON 1.5 ms or lower (when 24 V DC) Response OFF ON 0.5 ms or lower
X7
time ON OFF 1.5 ms or lower (when 24 V DC) time ON OFF 1.5 ms or lower (resistive load)
X6
External Voltage 19.2 to 26.4 V DC (ripple ratio: within 5 %)
X5
Power supply Current 110 mA or lower
Y8 9 A B C D E F
X4
for output (Per 24 V DC/1 common)
X3
Not including external load current
X2
Input form Sink type Surge suppression Zener diode
X1
AJ65SBTB1-16DT
X0
Common wiring method 16 points/1 common (Terminal block single wire type)
Number of stations occupied 1 station 32 points assignment (use 16 points)
PW L RUN L ERR X0 1 2 3 4 5 6 7
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
power supply Current 50 mA or lower (when 24 V DC and all point is ON)
(FG)
24G
Noise durability DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier frequency 25 to 60 Hz(noise simulator
MITSUBISHI
+24V
condition)
SLD
Withstand voltage 500 V AC for 1 minute between all DC external terminals and ground
DG
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance tester between all DC external
DB
DA
terminals and ground
Weight (kg) (lb.) 0.18 (0.4)
External wiring system 7-point 2-piece terminal block (transmission circuit, module power supply terminal),
Direct-type 18-point terminal block (I/O power supply area) (M3 screw)
Applicable solderless 2
• RAV1.25-3.5(in conformance with JIS-C2805) [Applicable wire size: 0.3 to1.25 mm ]
terminal
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
2
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.) [Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection (Sink input)
Terminal Terminal
1 DA number Signal name number Signal name
2 DB
3 DG Insulation TB1 DA TB8 X0
4 SLD
5 +24V
TB2 DB TB9 X1
DC/DC
Module power 6 FG TB3 DG TB10 X2
7 24G
supply TB4 SLD TB11 X3
8 X0 R TB5 +24V TB12 X4
9 X1 R
TB6 FG TB13 X5
10 X2
11 X3 TB7 24G TB14 X6
12 X4
13 X5 TB15 X7
14 X6
15 X7 TB16 X8
L 16 Y8 TB17 X9
17 Y9
18 YA TB18 XA
19 YB
20 YC TB19 XB
21 YD
22 YE TB20 XC
23 YF TB21 XD
I/O power supply
(external supply TB22 XE
power) TB23 XF
Constant voltage
24 COM+ circuit
25 COM-
TB24 COM+
Load power supply TB25 COM-
COM-
Max. simultaneous input Max. inrush current
100 % 1.0 A 10 ms or lower
COM+
B RATE
40 20 10 8 4 2 1 4 2 1
points
YF
ON voltage/ON current 15 V or higher/3.0 mA or higher Leakage current at OFF 0.25 mA or lower
YE
OFF voltage/OFF current Voltage drop at ON 0.3 V or lower (TYP)0.5 A
STATION NO.
YD
3 V or lower/0.5 mA or lower
0.6 V or lower (MAX)0.5 A
YC
Input resistance A pprox. 4.7 k Ω Output form Sink type
9B
YA
Response OFF ON 0.2 ms or lower (when 24 V DC) Sink type OFF ON 0.5 ms or lower
ON
Y9
time ON OFF 0.2 ms or lower (when 24 V DC) ON OFF 1.5 ms or lower (resistive load)
Y8
External Voltage 19.2 to 26.4 V DC (ripple ratio: within 5 %)
X7
Power supply Current
17.8 mA or lower
X6
for output (When 24 V DC and all point is ON)
X5
Not including external load current
Y8 9 A B C D E F
X4
Input form Sink type Surge suppression Zener diode
X3
X2
Common wiring method 16 points/1 common (Terminal block single wire type)
X1
AJ65SBTB1-16DT1
Number of stations occupied 1 station 32 points assignment (use 16 points)
X0
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
PW L RUN L ERR X0 1 2 3 4 5 6 7
power supply Current 55 mA or lower (When 24 V DC and all point is ON)
Noise durability DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier frequency 25 to 60 Hz(noise simulator
condition)
(FG)
24G
Withstand voltage 500 V AC for 1 minute between all DC external terminals and ground
MITSUBISHI
+24V
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance tester between all DC external
SLD
terminals and ground
DG
DB
Weight (kg) (lb.) 0.18 (0.4)
DA
External wiring system 7-point 2-piece terminal block (transmission circuit, module power supply terminal),
Direct-type 18-point terminal block (I/O power supply area) (M3 screw)
Applicable solderless 2
• RAV1.25-3.5(in conformance with JIS-C2805) [Applicable wire size: 0.3 to1.25 mm ]
terminal
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
2
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.) [Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection (Sink input)
Terminal Terminal
number Signal name number Signal name
1 DA
2 DB TB1 DA TB8 X0
3 DG Insulation TB2 DB TB9 X1
4 SLD
TB3 DG TB10 X2
5 +24V
DC/DC TB4 SLD TB11 X3
Module power 6 FG
COM-
Operating voltage range 19.2 to 26.4 V DC Max. load current 0.5 A/point
COM+
1
B RATE
2
(ripple ratio: within 5 %) 3.6 A/common
YF
2 1 4
YE
Max. simultaneous input Max. inrush current
STATION NO.
YD
100 % 1.0 A 10 ms or lower
4
points
YC
40 20 10 8
YB
ON voltage/ON current 15 V or higher/3.0 mA or higher Leakage current at OFF 0.25 mA or lower
YA
Y19
OFF voltage/OFF current Voltage drop at ON 0.3 V or lower (TYP)0.5 A
ON
3 V or lower/0.5 mA or lower
Y18
0.6 V or lower (MAX)0.5 A
Y17
A pprox. 4.7 k Ω
Y16
Input resistance Output form Sink type
Y15
Response OFF ON 0.2 ms or lower (when 24 V DC) Sink type OFF ON 0.5 ms or lower
Y14
Y13
time ON OFF 0.2 ms or lower (when 24 V DC) ON OFF 1.5 ms or lower (resistive load)
Y12
Y1819 1A 1B 1C 1D 1E 1F
Y11
External Voltage 19.2 to 26.4 V DC (ripple ratio: within 5 %)
Y10
Power supply Current 24.2 mA or lower
XF
XE
for output (When 24 V DC and all point is ON)
XD
Not including external load current
XC
Y1011 12 13 14 15 16 17
XB
Input form Sink type Surge suppression Zener diode
XA
Common wiring method 32 points/1 common (Terminal block single wire type)
X9
X8
Number of stations occupied 1 station 32 points assignment (use 32 points)
X7
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
X6
X8 9 A B C D E F
X5
power supply Current 60 mA or lower (When 24 V DC and all point is ON)
X4
Noise durability DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier frequency 25 to 60 Hz(noise simulator
X3
X2
A J65SBTB1-32DT1
condition)
X1
Withstand voltage 500 V AC for 1 minute between all DC external terminals and ground
X0
PW L RUN L ERR X0 1 2 3 4 5 6 7
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance tester between all DC external
terminals and ground
(FG)
24G
Weight (kg) (lb.) 0.25 (0.55)
MITSUBISHI
+24V
External wiring system 7-point 2-piece terminal block (transmission circuit, module power supply terminal),
SLD
DG
Direct-type 34-point terminal block (I/O power supply area) (M3 screw)
DB
DA
Applicable solderless 2
• RAV1.25-3.5(in conformance with JIS-C2805) [Applicable wire size: 0.3 to1.25 mm ]
terminal
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
2
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.) [Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection (Sink input)
Terminal Terminal
number Signal name number Signal name
1 DA
2 DB
3 DG Insulation TB1 DA TB22 XE
Module power 4 SLD TB2 DB TB23 XF
5 +24V
suooky DC/DC TB3 DG TB24 Y10
6 FG
7 24G
TB4 SLD TB25 T11
TB5 +24V TB26 Y12
8 X0 R
9 X1 R TB6 FG TB27 Y13
10 X2
11 X3 TB7 24G TB28 Y14
12 X4 Terminal TB29 Y15
13 X5
number Signal name
14 X6 TB30 Y16
15 X7
16 X8
TB8 X0 TB31 Y17
17 X9 TB9 X1 TB32 Y18
18 XA
19 XB TB10 X2 TB33 Y19
20 XC
21 XD
TB11 X3 TB34 Y1A
22 XE TB12 X4 TB35 Y1B
23 XF
L 24 Y10 TB13 X5 TB36 Y1C
25 Y11 TB14 X6 TB37 Y1D
26 Y12
27 Y13 TB15 X7 TB38 Y1E
28 Y14
29 Y15 TB16 X8 TB39 Y1F
30 Y16 TB17 X9 TB40 COM+
31 Y17
32 Y18 TB18 XA TB41 COM-
33 Y19
34 Y1A
TB19 XB
I/O power supply 35 Y1B TB20 XC
(external supply 36 Y1C
37 Y1D TB21 XD
power) 38 Y1E
39 Y1F Constant voltage
40 COM+ circuit
41 COM-
Load power supply
B RATE
40 20 10 8 4 2 1 4 2 1
100 % 1.0 A 10 ms or lower
points
ON voltage/ON current 14 V or higher/3.5 mA or higher Leakage current at OFF 0.25 mA or lower
YB
STATION NO.
OFF voltage/OFF current Voltage drop at ON 0.3 V or lower (TYP)0.5 A
6 V or lower/1.7 mA or lower
YA
0.6 V or lower (MAX)0.5 A
Input resistance A pprox. 3.3 k Ω Output form Sink type
Y9
Response OFF ON 1.5 ms or lower (when 24 V DC) Response OFF ON 0.5 ms or lower
ON
time ON OFF 1.5 ms or lower (when 24 V DC) time ON OFF 1.5 ms or lower (resistive load)
Y8
COM-
External Voltage 19.2 to 26.4 V DC (ripple ratio: within 5 %)
X3
Power supply Current 14.6 mA or lower
COM+
for output (When 24 V DC and all point is ON)
X2
Not including external load current
COM-
Input form Sink type Surge suppression Zener diode
X1
COM+
Common wiring method 8 points/1 common (3-wire type terminal block: input, 2-wire type terminal block: output)
AJ65SBTB32-8DT
Number of stations occupied 1 station 32 points assignment (use 8 points)
X0
PW L RUN L ERR X0 1 2 3 Y8 9 A B
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
power supply Current 45 mA or lower (When 24 V DC and all point is ON)
Noise durability DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier frequency 25 to 60 Hz(noise simulator
(FG)
24G
condition)
Withstand voltage 500 V AC for 1 minute between all DC external terminals and ground
MITSUBISHI
+24V
10 M Ω or higher, measured with a 500 V DC insulation resistance tester
SLD
Insulation resistance
DG
Weight (kg) (lb.) 0.18 (0.4)
DB
DA
External wiring system 7-point 2-piece terminal block (transmission circuit, module power supply terminal),
Direct-type 18-point terminal block (I/O power supply area) (M3 screw)
Applicable solderless 2
• RAV1.25-3.5(in conformance with JIS-C2805) [Applicable wire size: 0.3 to1.25 mm ]
terminal
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
2
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.) [Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection (Sink input)
Terminal Terminal
number Signal name number Signal name
1 DA TB1 DA TB8 X0
2 DB TB2 DB TB9 COM+
3 DG Insulation TB3 DG TB10 X1
4 SLD
5 +24V TB4 SLD TB11 COM-
DC/DC
Module power 6 FG TB5 +24V TB12 X2
supply 7 24G TB6 FG TB13 COM+
TB7 -24G TB14 X3
8 X0 R TB15 COM-
3-wire type 9 COM+ R TB16 X8
sensor 10 X1
11 COM-
TB17 COM+
12 X2 TB18 X9
13 COM+ TB19 COM+
14 X3
TB20 XA
15 COM-
L 16 Y8 TB21 COM+
17 COM+ TB22 YB
18 Y9
TB23 COM+
19 COM+
20 YA TB24 DC24V
21 COM+ TB25 DC24G
22 YB
23 COM+ Constant voltage
24 DC24V circuit
25 DC24G
I/O power supply
(external supply power)
15) AJ65SBTB32-16DT combined module
Form DC input transistor output combined module
Specification AJ65SBTB32-16DT Outline
Input specification Output specification
Number of input points 8 points Number of output points 8 points
Insulation method Photocoupler Insulation method Photocoupler
Rated input voltage 24 V DC Rated load voltage 24 V DC
Rated input current Approx. 7 mA Operating load voltage range 19.2 to 26.4 V DC(ripple ratio: within 5 %)
COM- COM+ COM+ COM+ COM+ COM+ COM+ COM+ COM+ DC24G
Operating voltage range 19.2 to 26.4 V DC Max. load current 0.5 A/point
DC24V
1
B RATE
2
(ripple ratio: within 5 %) 2.4 A/common
2 1 4
YF
Max. simultaneous input Max. inrush current
STATION NO.
100 % 1.0 A 10 ms or lower
4
points
YE
40 20 10 8
ON voltage/ON current 14 V or higher/3.5 mA or higher Leakage current at OFF 0.25 mA or lower
YD
OFF voltage/OFF current Voltage drop at ON 0.3 V or lower (TYP)0.5 A
ON
6 V or lower/1.7 mA or lower
YC
0.6 V or lower (MAX)0.5 A
A pprox. 3.3 k Ω
YB
Input resistance Output form Sink type
Response OFF ON 1.5 ms or lower (when 24 V DC) Response OFF ON 0.5 ms or lower
YA
time ON OFF 1.5 ms or lower (when 24 V DC) time ON OFF 1.5 ms or lower (resistive load)
Y9
External Voltage 19.2 to 26.4 V DC (ripple ratio: within 5 %)
Y8
Power supply Current 17.8 mA or lower
X7
for output (When 24 V DC and all point is ON)
COM+
Not including external load current
X6
COM-
Input form Sink type Surge suppression Zener diode
X5
Common wiring method 16 points/1 common (3-wire type terminal block: input, 2-wire type terminal block: output)
COM+
X4
Number of stations occupied 1 station 32 points assignment (use 16 points)
COM-
I/O module Voltage 20.4 to 26.4 V DC(ripple ratio: within 5 %)
X3
Y8 9 A B C D E F
COM+
power supply Current 50 mA or lower (When 24 V DC and all point is ON)
X2
COM-
Noise durability DC type noise voltage 500 Vp-p, noise width 1 µs, noise carrier frequency 25 to 60 Hz(noise simulator
X1
A J65SBTB32-16DT
condition)
COM+
Withstand voltage 500 V AC for 1 minute between all DC external terminals and ground
X0
PW L RUN L ERR X0 1 2 3 4 5 6 7
Insulation resistance 10 M Ω or higher, measured with a 500 V DC insulation resistance tester between all DC external
terminals and ground
(FG)
24G
Weight (kg) (lb.) 0.25 (0.55)
MITSUBISHI
+24V
External wiring system 7-point 2-piece terminal block (transmission circuit, module power supply terminal),
SLD
DG
Direct-type 34-point terminal block (I/O power supply area) (M3 screw)
DB
DA
Applicable solderless 2
• RAV1.25-3.5(in conformance with JIS-C2805) [Applicable wire size: 0.3 to1.25 mm ]
terminal
• V2-MS3 (Japan Solderless Terminal Mfg. Co., Ltd.),
RAP2-3S RAP2-3SL (Japan Terminal Co., Ltd.)
2
• 2-3N, 2-3S (NICHIFU TERMINAL INDUSTRIES Co., Ltd.) [Applicable wire size: 1.25 to 2 mm ]
Accessory User's Manual
External connection (Sink input)
Terminal Terminal
number Signal name number Signal name
1 DA
2 DB
3 DG Insulation TB1 DA TB21 COM+
4 SLD TB2 DB TB22 X7
5 +24V
DC/DC TB3 DG TB23 COM-
Module power 6 FG
7 24G
supply TB4 SLD TB24 Y8
TB5 +24V TB25 COM+
8 X0 R
9 COM+ TB6 FG TB26 Y9
3-wire type 10 X1
R
sensor 11 COM-
TB7 24G TB27 COM+
12 X2 Terminal TB28 YA
13 COM+
number Signal name
14 X3 TB29 COM+
15 COM-
16 X4
TB8 X0 TB30 YB
17 COM+ TB9 COM+ TB31 COM+
18 X5
19 COM- TB10 X1 TB32 YC
20 X6 TB11 COM- TB33 COM+
21 COM+
22 X7 TB12 X2 TB34 YD
23 COM-
L 24 Y8 TB13 COM+ TB35 COM+
25 COM+ TB14 X3 TB36 YE
26 Y9
27 COM+ TB15 COM- TB37 COM+
28 YA
29 COM+ TB16 X4 TB38 YF
30 YB TB17 COM+ TB39 COM+
31 COM+
32 YC TB18 X5 TB40 DC24V
33 COM+
34 YD TB19 COM- TB41 DC24G
35 COM+ TB20 X6
36 YE
I/O power supply 37 COM+
(external supply power) 38 YF
39 COM+ Control voltage
40 DC24V circuit
41 DC24G
[External Dimensions]
AJ65SBTB2(N)-8!, AJ65SBTB3-8! AJ65SBTB2(N)-16!, AJ65SBTB1-32DT
AJ65SBTB1-16DT, AJ65SBTB32-8DT AJ65SBTB32-16DT
50
50
40 179 40
118
+1 +2 +0.04
109 0 (4.29 +0.04
0
) Mounting pitch 170 0 (6.7 0 ) Mounting pitch
M4 mounting screw M4 mounting screw
Unit’mm (in.)
[Manual]
Manual name Manual shipment type IB/SH No. Type code
AJ65SBTB2N-8A CC-Link System Small Type Remote I/O MODULE USER’S
Enclosed with product IB-0800124 -
MANUAL
AJ65SBTB2N-16A CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800125 -
USER’S MANUAL
AJ65SBTB3-8D CC-Link System Small Type Remote I/O MODULE USER’S
Enclosed with product IB-0800101 -
MANUAL
AJ65SBTB3-16D CC-Link System Small Type Remote I/O MODULE USER’S
Enclosed with product IB-0800109 -
MANUAL
AJ65SBTB2-8T CC-Link System Small Type Remote I/O MODULE USER’S
Enclosed with product IB-0800108 -
MANUAL
AJ65SBTB2-16T CC-Link System Small Type Remote I/O MODULE USER’S
Enclosed with product IB-0800107 -
MANUAL
AJ65SBTB2N-8R CC-Link System Small Type Remote I/O MODULE USER’S
Enclosed with product IB-0800128 -
MANUAL
AJ65SBTB2N-16R CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800129 -
USER’S MANUAL
AJ65SBTB2N-8S CC-Link System Small Type Remote I/O MODULE USER’S
Enclosed with product IB-0800126 -
MANUAL
AJ65SBTB2N-16S CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800127 -
USER’S MANUAL
AJ65SBTB1-16DT CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800102 -
USER’S MANUAL
AJ65SBTB1-16DT1 CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800104 -
USER’S MANUAL
AJ65SBTB1-32DT1 CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800103 -
USER’S MANUAL
AJ65SBTB32-8DT CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800106 -
USER’S MANUAL
AJ65SBTB32-16DT CC-Link System Small Type Remote I/O MODULE
Enclosed with product IB-0800105 -
USER’S MANUAL
CC-Link System Compact Type Remote I/O Module User’s Manual Sold separately SH-4007 13JM93
Country/Region Sales office Tel/Fax
U.S.A Mitsubishi Electric Automation Inc. Tel : 1-847-478-2100
500 Corporate Woods Parkway Vernon Hills, IL 60061 Fax : 1-847-478-0328
Brazil MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda. Tel : 55-21-221-8343
Av. Rio Branco, 123-15 ,and S/1507, Rio de Janeiro, RJ CEP 20040-005, Brazil Fax : 55-21-221-9388
Germany Mitsubishi Electric Europe B.V. German Branch Tel : 49-2102-486-0
Gothaer Strasse 8 D-40880 Ratingen, GERMANY Fax : 49-2102-486-717
U.K Mitsubishi Electric Europe B.V. UK Branch Tel : 44-1707-276100
Travellers Lane, Hatfield, Herts., AL10 8XB,UK Fax : 44-1707-278695
Italy Mitsubishi Electric Europe B.V. Italian Branch Tel : 39-039-6053301
Centro Dir. Colleoni, Pal. Perseo - Ingr.2 Fax : 39-039-6053206
Via Paracelso 12, 20041 Agrate B., Milano, Italy
Spain Mitsubishi Electric Europe B.V. Spanish Branch Tel : 34-935-653135
Pol. Ind. "Can Magi"- C/.Joan Buscalla, 2-4-A.C.420 Fax : 34-935-891579
08190 Sant Cugat del Valles, Barcelona, Spain
South Africa MSA Manufacturing (Pty) Ltd. Tel : 27-11-444-8080
P O Box 39733 Bramley 201 8 Johannesburg, South Africa Fax : 27-11-444-8304
Hong Kong Ryoden International Ltd. Tel : 852-2887-8870
10th Floor, Manulife Tower, 169 Electric Road, North Point, HongKong Fax : 852-2887-7984
China Ryoden International Shanghai Ltd. Tel : 86-21-6475-3228
3F Block5 Building Automation Instrumentation Plaza 103 Cao Bao Rd. Shanghai Fax : 86-21-6484-6996
200233 China
Taiwan Setsuyo Enterprise Co., Ltd. Tel : 886-2-2299-2499
6F., No.105 Wu-Kung 3rd.RD, Wu-Ku Hsiang, Taipei Hsine, Taiwan R.O.C. Fax : 886-2-2299-2509
Korea STC Techno Seoul Co., Ltd. Tel : 82-2-3668-6567
1F Dong Seo Game Channel Bldg., 660-11,Deungchon-dong Kangsec-ku, Fax : 82-2-3664-8335
Seoul, Korea
Singapore Mitsubishi Electric Asia Pte, Ltd. Tel : 65-473-2480
307 ALEXANDRA ROAD #05-01/02, Fax : 65-476-7439
MITSUBISHI ELECTRIC BUILDING SINGAPORE 159943
Thailand F. A. Tech Co.,Ltd. Tel : 66-2-295-2861
1138/33-34 Rama 3 Road, Yannawa, Bangkok 10120, Thailand Fax : 66-2-295-2865
Indonesia P.T. Autoteknindo SUMBER MAKMUR Tel : 62-21-336292
Kompleks Agung Sedayu Propertindo (Harco Mangga Dua) Fax : 62-21-330378
Blok H No.4 JI Mangga Dua Raya Jakarta Pusat 10730-Indonesia.
India Messung Systems Put,Ltd. Tel : 91-20-7128927
Electronic Sadan NO:111 Unit No15, M.I.D.C BHOSARI,PUNE-411026 Fax : 91-20-7128108
Australia Mitsubishi Electric Australia Pty. Ltd. Tel : 61-2-9684-7777
348 Victoria Road, PostalBag, No 2, Rydalmere, N.S.W 2116, Australia Fax : 61-2-9684-7245
HEAD OFFICE:MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 TELEX:J24532 CABLE MELCO TOKYO