Fire-Safety Requirement For Function Halls

The document outlines the minimum firefighting requirements for bars, restaurants, and function halls of varying heights in India. For buildings less than 10 meters high and holding less than 300 people, requirements include fire extinguishers, hose reels, downcomers, sprinklers if the cellar is over 200 sqm, an alarm system, overhead water tanks of 10,000-15,000 liters, and a booster pump. Larger capacity buildings require additional equipment like larger water tanks and pumps. Buildings over 10 meters also require wet risers, detection systems, underground water storage, and fire pumps. All buildings must indicate transformers, have safety circuits, emergency lighting, trained staff, and openable stairwell windows.

Uploaded by

naseerpasha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
337 views1 page

Fire-Safety Requirement For Function Halls

The document outlines the minimum firefighting requirements for bars, restaurants, and function halls of varying heights in India. For buildings less than 10 meters high and holding less than 300 people, requirements include fire extinguishers, hose reels, downcomers, sprinklers if the cellar is over 200 sqm, an alarm system, overhead water tanks of 10,000-15,000 liters, and a booster pump. Larger capacity buildings require additional equipment like larger water tanks and pumps. Buildings over 10 meters also require wet risers, detection systems, underground water storage, and fire pumps. All buildings must indicate transformers, have safety circuits, emergency lighting, trained staff, and openable stairwell windows.

Uploaded by

naseerpasha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

7) Minimum requirements for fire fighting installations for Bar & Restaurant and

Function Hall (Table 23 part – 4N.B.C Of India 2005.

Bar & Restaurant and Function Halls (Less than 15 Meters Hiehght)
1) Less than 10 Meters in height & up to 300 Person capacity.
Sl. No Particulars of fire fighting installations
1. Fire Extinguishers Required
(ABC Powder 5 KG capacity 2.Nos for every 600 Sq.Meter built up area with
minimum 4.Nos per floor.)
2. Hose Reel (1.Nos for ever 1000 Sq.Meter built up area) Required
3. Down Comer (1.Nos for ever 1000 Sq.Meter built up area) Required
4 Automatic Sprinkler System in cellar (If the Cellar area exceeds 200 Sq.Meters) Required
5. Manually Operated Electrical Alarm System Required
6 Over Head Tank 10,000 Liters if there is no cellars area exceeds 200 Sq.Meters & Required
15,000 Liters if the cellar area exceeds 200 Sq.Meters.
7 Booster Pump of 450 LPM if there is no cellar or cellar area is less than 200 Required
Sq.Meters (900 LPM if Basement area exceed 200.Sq.Meters).
8 Location of Transformer to be indicated in plan and fire protection to be Provided Required
9 MCB Circuit breakers and Electrical Safety Required
10 Emergency Lighting with 2 Hours Backup& Auto Glow signs Required
11 Whether the staff trained in evacuation/ handling Fire Equipment. Required
12 Provision of openable windows in staircase landing Required

2) Less than 10 Meters and More than 300 Persons capacity.


1. Fire Extinguishers Required
(ABC Powder 5 KG capacity 2.Nos for every 600 Sq.Meter built up area with
minimum 4.Nos per floor.)
2. Hose Reel (1.Nos for ever 1000 Sq.Meter built up area) Required
3. Down Comer (1.Nos for ever 1000 Sq.Meter built up area) Required
4. Automatic Sprinkler System in cellar (If the Cellar area exceeds 200 Sq.Meters) Required
5. Manually Operated Electrical Alarm System Required
6 Over Head Tank 15,000 Liters if there is no cellar or cellar area less than 200 Required
Sq.Meters ( 20,000 Liters if the cellar area exceeds 200 Sq.Meters.)
7 Booster Pump of 900 LPM at terrace level. Required
8 Location of Transformer to be indicated in plan and fire protection to be provided Required
9 MCB Circuit breakers and Electrical Safety Required
10 Emergency Lighting with 2 Hours Backup& Auto Glow signs Required
11 Whether the staff trained in evacuation/ handling Fire Equipment. Required
12 Provision of openable windows in staircase landing Required

3) Above 10 Meters nut not exceeding 15 Meters height.


1. Fire Extinguishers Required
(ABC Powder 5 KG capacity 2.Nos for every 600 Sq.Meter built up area with
minimum 4.Nos per floor.)
2. Hose Reel (1.Nos for ever 1000 Sq.Meter built up area) Required
3. Wet riser (1.Nos for ever 1000 Sq.Meter built up area). Required
4. Automatic Sprinkler System in cellar (If the Cellar area exceeds 200 Sq.Meters) Required
5 Automatic Detection and Alarm System Required
6. Manually Operated electrical Alarm System Required
7 Under Ground Water Sump of 50,000 Liters. Required
8 Terrace Tank of 5,000 Liters of there is no cellar or cellar area is less than 200 Required
Sq.Meter and 10,000 Liters if the cellar area exceeds 200 Sq.meters.
9 Fire Pump Required
One Electrical & One Diesel Pump of 2280 LPM & One Jockey Pump of 180
LPM near underground sump.&Booster pump of 450LPM(900LPM if cellar area
exceeds 200 SQm)
10 Location of Transformer to be indicated in plan and fire protection to be provided Required
11 MCB Circuit breakers and Electrical Safety Required
12 Emergency Lighting with 2 Hours Backup& Auto Glow signs Required
13 Whether the staff trained in evacuation/ handling Fire Equipment. Required