Inverter
Inverter
Inverter
Frequency Inverter
Serie CV/3CV 200-240V/380 – 480V 0,37 bis 55kW
z Check inverter and motor nameplates to determine that they have the same
HP and voltage ratings. (Ensure that full load motor amps do not exceed
that of the inverter.)
z Remove the terminal cover to expose the motor and power terminals.
i
Step 2 Apply Power to the Drive
z Apply AC power to the Drive and observe Operator. Four 7-segment
Display should read Power Voltage for 3~5 seconds and then read
Frequency/Speed, 05.00. Four 7-segment Display and FWD LED should be
flashed all the time.
ii
Table of Content
Quick Start Guide i
Chapter 0 Preface 0-1
0.1 Preface 0-1
0.2 Products Inspection 0-1
Chapter 1 Safety Precautions 1-1
1.1 Operation Precaution 1-1
1.1.1 Before Power ON 1-1
1.1.2 During Power ON 1-2
1.1.3 Before Operation 1-2
1.1.4 During Operation 1-3
1.1.5 During Maintenance 1-3
Chapter 2 Definition of Model 2-1
Chapter 3 Ambient Environment and Installation 3-1
3.1 Environment 3-1
3.2 Environmental Precautions 3-2
3.3 Inflammable Materials 3-3
3.3.1 Notice for Wiring 3-3
3.3.2 Applicable Specification of Magnetic Contactor and Wires 3-5
3.3.3 Precautions for Peripheral Applications 3-6
3.4 Specifications 3-9
3.4.1 Products Individual Specifications 3-9
3.4.2 General Specifications 3-10
3.5 Wiring Diagram 7300CV Series Inverter 3-12
3.6 Description of Terminals Troubleshooting Inverter 3-13
3.7 Outline Dimension 3-15
Chapter 4 Software Index 4-1
4.1 Keypad Description 4-1
4.1.1 Keypad Display and Operation Instruction 4-1
4.1.2 Operation Instruction of the Keypad 4-2
4.1.3 Operation Instruction of the LED Keypad 4-3
4.1.4 Operation Instruction of the LCD Keypad 4-4
4.1.5 Keypad Operating Example 4-5
4.2 Control Mode Selection 4-7
4.3 7300CV Programmable Functions List 4-8
4.4 Parameter Function Description 4-20
4.5 Specification Description on Built-in PLC Function 4-63
4.5.1 Basic Instruction 4-63
4.5.2 Function of Basic Instruction 4-64
4.5.3 Application Instructions 4-65
Chapter 5 Troubleshooting and Maintenance 5-1
5.1 Error Display and Remedy 5-1
5.1.1 Error which can not be Recovered Manually 5-1
5.1.2 Error which can be recovered manually and automatically 5-2
5.1.3 Error which can be recovered manually but not auto matically 5-3
5.1.4 Special Conditions 5-4
5.1.5 Operation Errors 5-5
5.2 General Troubleshooting 5-6
5.3 Quick Troubleshooting 7300CV Series 5-7
5.4 Routine Inspection and Period Inspection 5-13
iii
5.5 Maintenance and Inspection 5-14
Chapter 6 Peripheral Components 6-1
6.1 Reactor Specification at Input Side 6-1
6.2 Reactor Specification at DC Side 6-1
6.3 Braking Resistor 6-2
6.4 Digital Operator and Extension Cable 6-3
6.5 EMC Filter 6-5
6.6 Interface Card 6-7
6.6.1 RS-485 Interface Card 6-7
6.6.2 RS-232 Interface Card 6-8
6.6.3 Program Copy Unit 6-9
6.6.4 PDA Link 6-9
AppendixⅠ 7300CV Motor Internal Parameter List App1
iv
Chapter 0 Preface
Chapter 0 Preface
0.1 Preface
To extend the performance of the product and ensure your safety, please read this manual
thoroughly before using the inverter. Should there be any problem in using the product
and can not be solved with the information provided in the manual, contact your nearest
Teco’s distributor or our sales representatives who will be willing to help you. Please
keep using Teco’s products in the future.
※Precautions
The inverter is an electrical electronic product. For your safety, there are symbols such as
“Danger”, “Caution” in this manual to remind you to pay attention to safety instructions
on handling, installing, operating, and checking the inverter. Be sure to follow the
instructions for highest safety.
Danger
z Do not touch any circuit boards or components if the charging indicator is still lit after
turned the power off.
z Do not wire when the inverter is electrified. Do not check parts and signals on circuit boards
during the inverter operation.
z Do not disassemble the inverter and modify internal wires, circuits and parts.
Ground the ground terminal of the inverter properly. As for 200V class ground to 100 Ω or
below, 400v class ground to 10Ω or below.
Caution
z Do not perform a voltage test on parts inside the inverter. High voltage will easily destroy
these semiconductor parts.
z Do not connect T1 (U), T2 (V), and T3 (W) terminals of the inverter to AC power supply.
z CMOS ICs on the inverter’s main board are susceptible to static electricity. Do not touch
the main circuit board
0-1
Chapte 1 Safety Precautions
Caution
The line voltage applied must comply with the inverter’s specified input voltage.
Danger
Make sure the main circuit connections are correct. L1(L), L2 and L3(N) are power-input
terminals and must not be mistaken for T1, T2 and T3. Otherwise, the inverter might be
damaged.
Caution
z To avoid the front cover from disengaging, do not pull the cover during handling for
the heat sink should be fallen off. Accident falling down will damage the inverter or
injure to person, which should be avoided.
z To avoid the risk of fire, do not install the inverter on a flammable object. Install it on
nonflammable object such as metal.
z If several inverters are placed in the same control panel, add extra heat sink to keep
the temperature below 40 to avoid overheat or fire.
z When removing or installing the operator, turn OFF the power first, and manipulate
the operator following the instruction of the diagram to avoid operator error or no
display caused by bad contact.
Warning
This is a product of the restricted sales distribution class according to IEC 61800-3. In a
domestic environment this product may cause radio interference in which case the user
may be required to take adequate measures.
1-1
Chapte 1 Safety Precautions
Danger
z Do not plug or unplug the connectors on the inverter when electrified to avoid the
control panel damage resulting from erratic transition voltage surge due to contact
bounce.
z When momentary power loss is longer than 2 seconds (the larger of horse power, the
longer of time), the inverter does not have enough storage power to control the circuit;
Therefore, when power is regenerated, the operation of the inverter is based on the
setup of 1-00 / 2-05 and the condition of external switch, this is considered to be
「restart」in the following paragraphs.
z When the momentary power loss is short, the inverter still has enough storage power
to control the circuit. Therefore, when power is regenerated, the inverter will
automatically restart depending on the setup of 2-00/2-01.
z When restart the inverter, the operation of the inverter is based on the setup of 1-00
and 2-05 and the condition of external switch (FWD/REV button). Attention: the
start operation is irrelevant with 2-00/2-01/2-02/2-03.
1. When 1-00=0000, the inverter will not automatically run after restart.
2. When 1-00=0001 and the external switch (FWD/REV button) is OFF, the inverter
will not run after restart.
3. When 1-00=0001, the external switch (FWD/REV button) is ON, and 2-05=0000,
the inverter will run automatically after restart. Attention: In the sake of safety,
please turn off the external switch (FWD/REV button) after power loss to avoid
underling damage to the machine and the human body after sudden regeneration of
power.
z To ensure the safety of people and machine, please refer to the description and
suggestion of 2-05
Danger
Make sure the model and capacity are the same as those set by 15-0.
Caution
The inverter will flash the power voltage set by 0-07 for 5 seconds when applying power.
1-2
Chapte 1 Safety Precautions
Danger
Do not engage or disengage the motor during operation. Otherwise, the over-current will
cause the inverter to disconnect or the main circuit to burn.
Danger
z To avoid electric shock, do not take the front cover off during electrifying
z The motor will restart automatically after stop when auto-restart function is on. In this
case, do not get close to the machine.
z Note: The stop switch is different from the usage of the emergency stop switch. It must
be set first to be effective.
Caution
z Do not touch heat-generating components such as heat sink and braking resistor.
z The inverter can drive the motor running from low speed to high speed. Verify the
allowable capacities range of the motor and the mechanism.
z Note the settings related to the braking reactor.
z Do not check signals on circuit boards while the inverter is running.
Caution
It is after 5 minutes that disassembling or checking the components could be performed as
power supply OFF and the indicator turned off.
Caution
The inverter should be used in a non-condensed environment with temperature from –10
to +40 and relative humidity of 95% non-condense.
Caution
When the inverter top cover has removed, it can be used in a non-condensed environment
with temperature from –10 to +50 and relative humidity of 95%, but the environment
should be free from water and metal dust.
1-3
Chapter 2 Description of models
200~240V 50/60Hz
JNTH BC BA 0001 AC - U F
Series:
BG:LCD 0001:1.0 HP
-:None
0002:2.0 HP Power supply:
BE Th h 440V
BA:Open chassis type 7R50:7.5 HP
0010:10 HP
2-1
Chapter 3 Ambient Environment and Installation
Air convection
-10oC - +40oC
(a) Front view (b) Side view
3-1
Chapter 3 Ambient Environment and Installation
3.2 Environmental precautions
Do not use the inverter in an environment with the following conditions:
Oil
Salt
3-2
Chapter 3 Ambient Environment and Installation
B. Power wires:
Power wires are connecting to L1, L2, L3, T1, T2, T3, P, BR and P1. Choose wires in
accordance with the following criteria:
(1) Use copper wires only. Deciding diameters of wires should be based on rating working at
105oC.
(2) For rating voltage of wires, the minimum voltage of 230VAC type is 300V, and 460VAC
type is 600V.
(3) For safety reason, the power wires should be fixed by type terminal.
C. Control wires:
Control wires are wires connecting to TM2 control terminal. Choose the wire in accordance with
the following criteria:
(1) Use copper wires only. Deciding diameters of wires should be based on rating working at
105oC.
(2) For rating voltage of wires, the minimum voltage of 230VAC type is 300V, and 460VAC
type is 600V.
(3) To avoid noise interference, do not route the control wires in the same conduit with power
wires and motor wires.
220V class(3φ)
100% CONT Max.RK5 Max.CC or T
JNTHBCBA HP KW KVA
Output AMPS (A) FUSE Rating(A) FUSE Rating(A)
R500BC 0.5 0.4 1.2 3.1 8 10
0001BC 1 0.75 1.7 4.5 12 15
0002BC 2 1.5 2.9 7.5 15 20
0003BC 3 2.2 4.0 10.5 20 30
0005BC 5 3.7 6.7 17.5 30 50
7R50BC 7.5 5.5 9.9 26 50 60
0010BC 10 7.5 13.3 35 60 70
0015BC 15 11.0 20.6 48 80 100
0020BC 20 15.0 27.4 64 100 125
0025BC 25 18.5 34.0 80 125 150
0030BC 30 22.0 41.0 96 160 200
0040BC 40 30.0 54.0 130 200 250
440V class(3φ)
100% CONT Max.RK5 Max.CC or T
JNTHBCBA- HP KW KVA
Output AMPS (A) FUSE Rating(A) FUSE Rating(A)
0001BE 1 0.75 1.7 2.3 6 10
0002BE 2 1.5 2.9 3.8 10 15
0003BE 3 2.2 4.0 5.2 10 20
0005BE 5 3.7 6.7 8.8 20 30
7R5BE 7.5 5.5 9.9 13 25 35
0010BE 10 7.5 13.3 17.5 30 50
0015BE 15 11.0 20.6 25 50 60
0020BE 20 15.0 27.4 32 60 70
0025BE 25 18.5 34.0 40 70 80
0030BE 30 22.0 41.0 48 80 100
0040BE 40 30.0 54.0 64 100 125
0050BE 50 37.0 68.0 80 125 150
0060BE 60 45.0 82.0 96 150 200
0075BE 75 55.0 110.0 128 200 250
*Fuse ratings are based upon 300V fuses for 230V inverter, and 500V for 460V inverters
3-4
Chapter 3 Ambient Environment and Installation
Notice
z To avoid shock hazards, do not touch any electrical component when the power is applied or
just after five minutes the power plug is unplugged. The other action should be performed
after the charge indicator went off.
z Do not perform wiring on the inverter while it is still electrified. Disregard of this notice
could cause serious injure or death to persons.
JNTHBCBA□□□□BE
7300CV model
0001/ 0002/ 0003/ 0005 7R50 0010 0015 0020 0025 0030 0040 0050 0060 0075
Molded-case circuit TO-50E TO-50E TO-50E TO-50E TO-100S TO-100S TO-100S TO-100S TO-125S TO-225S TO-225S
breaker made by Teco 15A 20A 30A 50A 50A 75A 100A 100A 125A 175A 175A
Magnetic contactor
CN-11 CN-16 CN-18 CN-25 CN-35 CN-50 CN-50 CN-65 CN-80 CN-100 CN-125
(MC) made by Teco
Wire Wire Wire Wire
Main circuit terminals Wire gauge Wire gauge Wire gauge
Wire gauge 2.0mm2 gauge gauge gauge gauge
(TM1) 3.5mm2 8mm2 22mm2
5.5mm2 14mm2 38mm2 60mm2
z Use three-phase cage induction motor with capacity suitable for the inverter.
z One inverter is driving several motors, the total current of all motors running simultaneously
must be less than the rated current of the inverter, and each motor has to be equipped with a
proper thermal relay.
z Do not add capacitive component, such as a phase capacitor, LC or RC, between the inverter
and the motor.
3-5
Chapter 3 Ambient Environment and Installation
Ground
3-6
Chapter 3 Ambient Environment and Installation
Make external connections according to the following instruction. Check connections after
wiring to make sure all connections are correct. (Do not use the control circuit buzzer to check
connections)
z The inverter uses dedicated power line A general noise filter may not provide
rightful results
(A) Main circuit’s wiring must separate from other high voltage or high current power line to
avoid noise interference. Refer to the figures below:
z A noise filter in the output of the main circuit can suppress conductive noise. To prevent radiative noise,
the wires should be put in a metal pipe and distance from signal lines of other control machines for more
than 30 cm.
Signal Wire
Controller
3-7
Chapter 3 Ambient Environment and Installation
z When the connection between the inverter and the motor is too long, consider the
voltage drop of the circuit. Phase-to-phase voltage drop (V) =
3 ×resistance of wire (Ω/km)×length of line (m)×current×10-3. And the number of
carriers must be adjusted based on the length of the line.
The length of the line between
Below 25m Below 50m Below 100m Over 100m
the inverter and the motor
Number of carriers allowed Below 16KHz Below 12KHz Below 8KHz Below 5KHz
Settings of 3-22parameter 16 12 8 5
(B) The wiring of the control circuit must be separated and routed away from the main circuit
control line or other high voltage or current power lines to avoid noise interference
z To avoid error actions caused by noise interference, shield the control circuit wiring
with a twisted wire, and connect the shielded wire to a ground terminal. Refer to the
figure below.
The wiring distance should not exceed 50 m.
Protective
Shielding Wire
(C) Ground the ground terminal of the inverter properly. For 200V class ground 100Ω or less;
for 400V class ground 10Ω or less.
z Ground wiring is based on the electrical equipment technical basis (AWG). The shorter,
the better.
z Do not share the ground of the inverter to other high current loads (welding machine,
high power motor). Connect the terminals to ground respectively.
z Do not make a loop when several inverters share a common ground point.
3-8
Chapter 3 Ambient Environment and Installation
3.4 Specifications
3.4.1 Products Individual Specifications
Single phase, 200-240V model
J N T H BC B A□ □ □ □ AC - U ( F ) R500 0001 0002 0003
Horsepower(HP) 0.5 1 2 3
Suitable Motor Capacity(KW) 0.4 0.75 1.5 2.2
Rated Output Current(A) 3.1 4.5 7.5 10.5
Rated Capacity(KVA) 1.2 1.7 2.9 4.0
Max. Input Voltage Sing le Phase: 200 ~240V +10% -15%,50 /60H Z ± 5 %
Max. Output Voltage Th ree Phases: 0 ~240V
Input Current(A) 8.5 12 16 23.9
Net Weight(KG) 1.2(1 .3) 1.2(1 .3) 1.5(1 .8) 1.9(2 .3)
Allowable momentary power loss
1.0 1.0 2.0 2.0
time (second)
Three phases, 200 – 240V model
0 00 0 00 0 00 0 01 0 01 0 02 0 02 0 03 0 04
JNTHBC BA□□□□BC-U R500 0 00 5 7 R 50
1 2 3 0 5 0 5 0 0
Horsepower(HP) 0.5 1 2 3 5 7.5 10 15 20 25 30 40
Suitable Motor Capacity(KW) 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30
Rated Output Current(A) 3.1 4.5 7.5 10.5 17.5 26 35 48 64 80 96 130
Rated Capacity(KVA) 1.2 1.7 2.9 4.0 6.7 9.9 13.3 20.6 27.4 34 41 54
Max. Input Voltage Th ree Vo ltag e : 200 ~240V +10% -15% ,50 /60H Z ± 5 %
Max. Output Voltage Th ree Vo ltag e : 0 ~240V
Input Current(A) 4.5 6.5 11 12.5 20.5 33 42 57 70 85 108 138
Net Weight(KG) 1.2 1.2 1.2 1.75 1.9 5.6 5.6 15 15 15 33 34
Allowable momentary power
1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
loss time (second)
Three phases, 380 – 480V model
0 00 0 00 0 00 0 00 7 R 5 0 01 0 01 0 02 0 02 0 03 0 04 0 05 0 06 0 07
J N T H BC B A□ □ □ □ B E-U ( F )
1 2 3 5 0 0 5 0 5 0 0 0 0 5
Horsepower(HP) 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75
Suitable Motor Capacity(KW) 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55
Rated Output Current(A) 2.3 3.8 5.2 8.8 13.0 17.5 25 32 40 48 64 80 96 128
Rated Capacity(KVA) 1.7 2.9 4.0 6.7 9.9 13.3 19.1 27.4 34 41 54 68 82 110
Max. Input Voltage Th ree Vo ltag e :380~480V +10% -15%, 50 /60H Z ± 5 %
Max. Output Voltage Th ree Vo ltag e : 0 ~480V
Input Current(A) 4.2 5.6 7.3 11.6 17 23 31 38 48 56 75 92 112 142
1.2 1.2 1.8 1.8 5.6 5.6 5.6
Net Weight(KG) 15 15 15 33 33 50 50
(1.3 ) (1.3 ) (2.2 ) (2.2 ) (6.6 ) (6.6 ) (6.6 )
Allowable momentary power loss
1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
time (second)
NOTE1: DC Reactor is built-in for 30hp above in 200V class series.
NOTE2: DC Reactor is built-in for 40hp above in 400V class series.
3-9
Chapter 3 Ambient Environment and Installation
3.4.2 General Specifications
Item 7300CV TYPE
Range 0.1~650.0 Hz
Four digital LED (or 2×16 LCD) and status indicator; display
frequency/ speed/ line speed/ DC voltage/ Output voltage/ Current/
Display Function
Rotation direction/ Inverter parameter/ Trouble Log/ Program
Version
1. External variable resistor/ 0-10V/ 0-20mA/ 10-0V/ 20-0mA
2. Performs up/down controls, speed control or automatic procedure
External signal setting control with multifunctional contacts on the terminal block
(TM2)
Frequency Limit Function Respectively setting upper/lower frequency limits and three-stage
prohibited frequencies
Carrier frequency 2 ~ 16 kHz
output
Multifunctional input 30 functions (refer to description on 5-00~5-06)
3-10
Chapter 3 Ambient Environment and Installation
Item 7300CV TYPE
Communication Control 1. Control by RS232 or RS485
2. One to one or One to more (RS485 ONLY) control.
3. BAUD RATE/STOP BIT/PARITY/bit can be set
Braking Torque About 20﹪, the model built-in braking transistor and connected
braking resistor is 100%
Operation temperature -10 ~ 50℃(note 2)
The relays to protect the motor (the curve can be set) and the inverter
Overload protection
(150 % / 1min)
Momentary Power Stop for more than 15ms-power-loss can be restarted with spin start
Loss Restart after momentary power loss in Max 2 sec.
Stall Prevention Stall prevention for Acceleration/ Deceleration/ Operation.
Note 1: The setting resolution of above 100Hz is 0.1Hz when controlled with operation keypad,
and 0.01 Hz when controlled using computer PC or programmable controller (PLC).
3-11
Chapter 3 Ambient Environment and Installation
Note 3: 220V 15HP and above capacity are not CE complied
3-12
Chapter 3 Ambient Environment and Installation
3.5 Wiring diagram 7300CV series inverter
Wiring diagram I:
DC Braking
reactor Resistor(note1)
(
L1(R) T1(U) motor
AC
Power Power T2(V)
(
Power L2(S)
input output
source
( L3(T) T3(W)
200V:Class 3 ground
PE
ON-OFF 400V: Special ground
MC
Burst absorber
CON 2
RS485
TM2
RS232 (Option Card)
Multifunction input terminal
Digital
Control Memory Card
Forward/stop or run/stop S1
panel
Reverse/stop or reverse/forward S2
S3 CON1
Speed control S4
S5
PE R1A
R1B
+ FM+
FM
V NPN SW2: AIN 0~10V/0~20mA selective
Frequency indicator - COM SW3: S6/AI2 0~10V/0~20mA selective
SW2 SW3 SW1
0~10VDC or 2~10V/4~20mA (after Ver.2.3)
PNP I POSITION: 0~20mA signal
I
V POSITION: 0~10V signal
SW1: NPN/PNP selective
Note 1: Please refer to description of main circuit terminals (P1, BR) and specification of braking
resistor for value selection.
Note 2: Above wiring diagram refers for 0.4~1.5KW at 220V and 0.75~1.5KW at 440V only.
3-13
Chapter 3 Ambient Environment and Installation
Wiring diagram II:
Note 1: Please refer to description of main circuit terminals (P1, BR) and specification of braking
resistor for value selection.
Note 2: Above wiring diagram refers for 2.2~7.5KW at 220V and 2.2~11KW at 440V only.
3-14
Chapter 3 Ambient Environment and Installation
3.6 Description of terminals of troubleshooting inverter
Descriptions of main circuit terminals
Symbol Description
R / L1 ( L )
Main power input Single-phase: L/N
S / L2 Three-phase: L1/L2/L3
T / L3 ( N )
P1 Braking resistor or connecting terminal: Used in cases where the inverter
For
frequently disconnects due to large load inertia or short deceleration time
BR 220V:0.5~10HP,
(refer to specifications of braking resistor)
440V:1~15HP
P1/ P DC reactor connecting terminals
B1/P z B1 /P- Ө : DC pow er supp ly inpu t -
B2 B1 /P- B2 : Ex ternal br aking r e sistor
Ө Fo r 220V : 15 ~20HP and 440V : 20HP z ⊕- Ө : D C pow er supp ly inpu t or Exte rna l
br ak ing un it. Check Chapter 6.3
⊕ -
Fo r 220V : 25 ~40HP and 440V : 25~75HP
U / T1
V / T2 Inverter outputs
W / T3
Descriptions of 7300CV control circuit terminals
Symbol Description
R2A
Multifunctional terminal – Normal open Contact rated capacity:
R2B
(250VAC/1A or 30VDC/1A)
R1C Common contact
Contact using description:(refer to 8-
R1B Normal close contact Multifunctional output terminals 02, 8-03)
R1A Normal open contact
10V Frequency knob (VR) power source terminal (pin 3)
Analog frequency signal input terminal or multifunction input terminals S7 (H level:>8V, L level:<2V,
AIN PNP only) (refer to5-06 description)
Common contact for S1~S5 (S6, S7) in PNP (Source) input. Shift to PNP position (refer to wiring
24V diagram) of SW1 when used PNP input
1. Common contact and analog input /output signal for S1~S5 in NPN (Sink) input.
COM Shift to NPN position (refer to wiring diagram I) of SW1 when used NPN input.
24G 2. AGND for AIN,AI2 and FM+ (analog input /output signal) & 24G for S1~S6 (digital input /output
AGND signal in NPN (Sink) input). Shift to NPN position (refer to wiring diagram II) of SW1 when used
NPN input.
The positive analog output for multifunction (refer to 8-00 description), the signal for output terminal is
FM+ 0-10VDC (below 2mA).
.220V: 15 ~ 20 HP 440V: 20HP
3-15
Chapter 3 Ambient Environment and Installation
3-16
Chapter 3 Ambient Environment and Installation
3.7 Outline Dimensions
(1) Frame1 : Single phase JNTHBCBA__AC: R500, 0001
Three phase JNTHBCBA__BC/BE: R500, 0001, 0002
(2) Frame2 : Single phase JNTHBCBA__AC: 0002, 0003
Three phase JNTHBCBA__BC/BE: 0003, 0005
4-Ø5.5
B
A
C
D
E
F
G
Unit : mm/inch
LENGTH
A B C D
MODEL
Frame 1 163/6.42 150/5.9 78/3.07 90/3.54
Frame 2 187.1/7.36 170.5/6.71 114.6/4.51 128/5.04
LENGTH
E F G
MODEL
Frame 1 147/5.79 141/5.55 7/0.28
Frame 2 148/5.83 142.1/5.59 7/0.28
3-17
Chapter 3 Ambient Environment and Installation
(3) Frame3 : Three phase JNTHBCBA__BC: 7R50, 0010
JNTHBCBA __BE: 7R50, 0010, 0015
4-Ø5.5
B
A
C
D
E
F
Unit : mm/inch
LENGTH
A B C D E F
MODEL
Frame 3 260/10.24 244/9.61 173/6.81 186/7.32 195/7.68 188/7.4
3-18
Chapter 3 Ambient Environment and Installation
(4) Frame4 : Three phase JNTHBCBB __ BC: 0015, 0020, 0025
JNTHBCBB __ BE: 0020, 0025, 0030
E
D 4-Ø7.0
A
B
C
F
(5) Frame5 : Three phase JNTHBCBA __ BC: 0030, 0040
JNTHBCBA __ BE: 0040, 0050
(6) Frame6 : Three phase JNTHBCBA __ BE: 0060, 0075
E 4-Ø10
C
A
B
F
3-19
Chapter 3 Ambient Environment and Installation
3-20
Chapter 4 Software Index
5. Four action of FUN、Hz/RPM、VOLT、AMP LED and display of four 7-segment display, refer to
Caution
To avoid impairing the keypad, do not operate it with screwdriver or sharp and hard tool.
Remote/Local Mode
To Change the Remote/Local mode, you must push FWD/REV and《/RESET key at the same time.
The Remote /Local mode of change can used in STOP mode, it can’t used in Run mode.
4-2
Chapter 4 Software Index
4.1.2 Operation Instruction of the keypad
Frequency/Speed
HZ/RPM v < Frequency/Speed/
/Line Speed HZ/RPM
^ Line Speed
RUN/STOP (*3)
Frequency/Speed
HZ/RPM
/Line Speed READ/
ENTER (*2)
DSP
DSP
DSP
Build-in PLC Status DSP
Output Current AMP
(*4)
*1:The inverter will flash the current setting of 0-07 (power supply voltage) after power up.
*3:It is not necessary to press ENTER key when stopped for modification. Refer to example 1, 2.
4-3
Chapter 4 Software Index
Power On
● : LED Light Lit
: LED Light Flash
5 seconds later or Enter operation signal or Press DSP to modify the display frequency.
HZ/RPM ‧
^ v <
HZ/RPM ‧
RUN/STOP
HZ/RPM ‧ READ/
ENTER
READ/
ENTER
FUN ☉
DSP — FUN
^ v ^ v
DSP
☉
FUN — FUN
READ/
ENTER
DSP
DSP
VOLT VOLT
DSP
DSP
AMP
4-4
Chapter 4 Software Index
4.1.4 Operation Instruction of the LCD keypad
Power On
Power Source
220 V
5 second later or Enter operation signal or Press DSP to modify frequency
Master Freq.
60.00 Hz ^ v ^ < Setting Freq.
060.00Hz
RUN/STOP
READ/
Output Freq.
ENTER
50.99 Hz
DSP
READ/
00- 00=Vector(CT) 00-06= 0
ENTER
Control Mode Disabled
^ v ^ v
00- 06=Disabled DSP 00-06= 1
Auto Tuning Enabled
END READ/
ENTER
DSP DSP
DSP
PLC State
DSP Output Current
Stop
3.1 Amp
4-5
Chapter 4 Software Index
4-6
Chapter 4 Software Index
6-00
6-00
Power On
FWD LED ~ { { ● ~
REV LED { ~ ● { {
4-7
Chapter 4 Software Index
V/F Control
Control mode selection 0-00=2 Control mode selection
0-00=0
Set the following parameter: 0-00=1
V/F Pattern 10-0
Torque Boost 10-1
Set the following parameter:
Motor no load current 10-2 (<=0-02)
Motor rated voltage 0-01
Motor Rated Slip 10-3
Motor rated current 0-02
Max output frequency 10-4
Motor power 0-03
Max output voltage 10-5
Motor rated Speed 0-04
Medium output Frequency 10-6
Motor rated Frequency 0-05
Medium output voltage 10-7
Power Voltage
Min output frequency 10-8
Min output voltage 10-9 Perform Auto tuning (0-06=1)
Suitable motor capacity 0-02 (OL1 reference index)
End
※Note:
Parameter
Description
Group No.
0- Drive Operation Mode
1- Start/Stop and Frequency Control Modes
2- Manual/Automatic Restart Modes
3- Operating Parameters
4- Digital Display Operation Mode
5- Multifunction Input Terminals (MFIT)
6- Jog, and Preset (MFIT) Speed Setting on Keypad
7- Analog Input Signal Operation
8- Multifunction Output Relays and Output Signal Operation
9- Drive and Load Protection Modes
10- Volts/Hz Pattern Operation Mode
11- PID Operation Mode
12- PID "Limits" and "Out of Range" Mode
13- Communication Mode
14- Motor Auto-Tuning Parameters
15- Drive Status and Function Reset
4-9
Chapter 4 Software Index
0- Drive Operation Mode
Function Factory
LCD Display Description Range/Code Remarks
Code No. Setting
0000: Vector (General Purpose)
0001: Vector (Variable Torque)
0-00 (Control Mode) Control Mode 0000 *3
0002: Volts/Hz (Refer to Parameter
Group 10- Volts/Hz Mode)
0-01 (Motor Rated Volt) Motor Rated Voltage (Vac) ----- *3*5
0-02 (Motor Rated Amp) Motor Rated Current (Amp) ----- *3*5
0-03 (Motor Rated KW) Motor Rated Power (kW) ----- *3*5
(Motor Rated RPM) Motor Rated Speed *3*5
0-04 -----
(RPM)X100*7
0-05 (Motor Rated Hz) Motor Rated Frequency (Hz) ----- *3*5
0000: Invalid
0-06 (Auto Tuning) Motor Parameter Auto Tuning 0000
0001: Valid
220V SERIES:170.0~264.0
0-07 (AC Input Volt) AC Line Input Voltage (Vac) *3
440V SERIES:323.0~528.0
0000: English
0001: German Only for
0-08 (Select Language) Language Selection 0002: French 0000 LCD
0003: Italian keypad
0004: Spanish
4-10
Chapter 4 Software Index
0000: Keypad
0001: Potentiometer on Keypad
0002: External Analog Signal Input
or Remote Potentiometer
0003: Up/Down Frequency
Frequency Command Source
1-06 (Frequency Source) Control Using MFIT (S1 - 0000
Selection
S6)
0004: Communication setting
frequency
0005: Impulse (S5) setting
frequency (ver2.3)
0000: ‘Enter’ must be pressed after
frequency change with
Keypad Operation with Up/Down Up/Down Keys on keypad.
1-07 (Keypad Up/Down) 0000
Keys in Run Mode 0001: Frequency will be changed
directly when Up/Down
Keys are Pressed
4-11
Chapter 4 Software Index
3- Operating Parameters
Function LCD Factory
Description Range/Code Remarks
Code No. Display Setting
50.00/
3-00 (Freq Upper Limit) Frequency Upper Limit (Hz) 0.01 - 650.00 *4
60.00
3-01 (Freq Lower Limit) Frequency Lower Limit (Hz) 0.00 - 650.00 0.00
Acceleration Time # 1
3-02 (Accel Time 1) 0.1 – 3600.0 10.0 *1
(Seconds)
Deceleration Time # 1
3-03 (Decel Time 1) 0.1 – 3600.0 10.0 *1
(Seconds)
3-04 (S-Curve 1) S-Curve Acc/Dec # 1 (Seconds) 0.0 - 4.0 0.2
3-05 (S-Curve 2) S-Curve Acc/Dec # 2(Seconds) 0.0 - 4.0 0.2
Acceleration Time # 2 (MFIT)
3-06 (Accel Time 2) 0.1 – 3600.0 10.0 *1
(Seconds)
Deceleration Time # 2 (MFIT)
3-07 (Decel Time 2) 0.1 – 3600.0 10.0 *1
(Seconds)
Jog Acceleration Time (MFIT)
3-08 (Jog Acc Time) 0.1 - 25.5 0.5 *1
(Seconds)
Jog Deceleration Time (MFIT)
3-09 (Jog Dec Time) 0.1 - 25.5 0.5 *1
(Seconds)
DC Injection Brake Start
3-10 (DCInj Start Freq) 0.1 - 10.0 1.5
Frequency (Hz)
3-11 (DCInj Level) DC Injection Brake Level (%) 0.0 – 20.0 5.0 *7
DC Injection Brake Time
3-12 (DCInj Time) 0.0 - 25.5 0.5
(Seconds)
3-13 (Skip Freq 1) Skip Frequency # 1 (Hz) 0.00 - 650.00 0.0 *1
3-14 (Skip Freq 2) Skip Frequency # 2 (Hz) 0.00 - 650.00 0.0 *1
3-15 (Skip Freq 3) Skip Frequency # 3 (Hz) 0.00 - 650.00 0.0 *1
Skip Frequency Bandwidth(±
3-16 (Skip Bandwidth) 0.00 - 30.00 0.0 *1
Hz)
0000: Enable all Functions
0001: 6-00 - 6-08 cannot be changed
3-17 (Parameter Lock) Parameter Lock 0002: All Functions Except 6-00 - 0000
6-08 cannot be changed
0003: Disable All Function
0000: Disable
0001: Inverter to Copy Unit
3-18 (ROM Pack Operate) Copy Unit 0000
0002: Copy Unit to Inverter
0003: Verify
0000: Auto (Depend on temp.)
0001: Operate while in RUN mode
3-19 (Fan Control) Fan Control 0000
0002: Always Run
0003: Always Stop
0000: Disabled
3-20 (Energy Save Mode) Energy Saving Mode *1 0001: Controlled by MFIT at Set 0000 *6
Frequency
3-21 (Energy Save Gain) Energy Saving Gain (%)*1 0 - 100 80 *6
3-22 (Carrier Freq) Carrier Frequency (kHz) 2 - 16 10
3-23 reserved
4-12
Chapter 4 Software Index
3-24 reserved
3-25 reserved
3-26 reserved
3-27 reserved
3-28 reserved
3-29 reserved
※ Notes: 1. Energy Saving Mode is available only under Volts/Hz Mode (0-00 = 0002).
4-13
Chapter 4 Software Index
0000: Forward/Stop Command *1
0001: Reverse/Stop Command *2
5-00 (MFIT S1 Sel) Multifunction Input Term. S1 0002: Preset Speed # 1 (6-02) 0000
0003: Preset Speed # 2 (6-03)
0004: Preset Speed # 3 (6-05) *3
0005: Jog
5-01 (MFIT S2 Sel) Multifunction Input Term. S2 0006: Acc/Dec # 2 0001
0007: Emergency Stop A Contact
0008: Base Block
0009: Speed Search
0010: Energy Saving
5-02 (MFIT S3 Sel) Multifunction Input Term. S3 0002
0011: Control Signal Selection
0012: Communication Selection
0013: Acc/Dec Disabled
0014: Up Command
5-03 (MFIT S4 Sel) Multifunction Input Term. S4 0015: Down Command 0003
0016: Master/Auxiliary Speed
0017: PID Function Disabled
0018: Reset
5-04 (MFIT S5 Sel) Multifunction Input Term. S5 0019: Encoder input terminal 0004
( terminal S5 )
0020: PID feedback signal A12
(terminal S6)
0021: AI2 Bias signal 1 input
5-05 (MFIT S6 Sel) Multifunction Input Term. S6 0018
(terminal S6)
0022: AI2 Bias signal 2 input
(terminal S6)
0023: Analog input(terminal AIN)
0024: PLC Application
0025: Traverse Run
5-06 (MFIT AIN Sel) Multifunction Input Term. AIN 0026: Traverse run upper deviation 0023
0027: traverse run lower deviation
0028: Power Source Detect for KEB
Function
0029: Emergency Stop B Contact *7
Multifunction Input Term. S1 -
5-07 (MFIT Scan Time) S6 Signal Verification Scan 1 – 100 5
Time (mSec X 4 )
4-14
Chapter 4 Software Index
0000: When the MFITs are
Programmed for Up/Down
Frequency Control, the Set
Frequency will remain when
the Drive stops. And when the
Drive stops, Up/Down
Function Disabled.
0001: Up/Down is used. The preset
5-08 (Stop Sel by MFIT) Stop Mode Using MFIT frequency is reset to 0 Hz as 0000
the inverter stops.
0002: When the MFITs are
Programmed for Up/Down
Frequency Control, the Set
Frequency will remain when
the Drive stops. And when the
Drive stops, Up/Down
Function Enabled. *7
5-09 (Step Up/Down Fun) Step of Up/Down Function (Hz) 0.00 – 5.00 0.00
5-10 (Pulse Inp. Mult.) Encoder Impulse Ratio 0.001 – 9.999 1.000 *7
Select the source of auxiliary
5-11 (Ref.Source2) 0-4 0 *7
frequency command
※Notes: 1. To switch to Run/Stop with Function 1-01 = 0001.
2. To switch to Forward/Reverse with Function 1-01 = 0001.
3. Preset Speed # 3 is obtained by activating Terms. S3 and S4 simultaneously.
6- Jog, and Preset (MFIT) Frequency Setting on Keypad
Function LCD Factory
Description Range/Code Remarks
Code No. Display Setting
6-00 (Keypad Freq) Keypad Frequency (Hz) 0.00 - 650.00 5.00 *1
6-01 (Jog Freq) Jog Frequency (Hz) 0.00 - 650.00 2.00 *1
6-02 (Preset Speed #1) Preset Speed # 1 (Hz) 0.00 - 650.00 5.00 *1
6-03 (Preset Speed #2) Preset Speed # 2 (Hz) 0.00 - 650.00 10.00 *1
6-04 (Preset Speed #3) Preset Speed # 3 (Hz) 0.00 - 650.00 20.00 *1
6-05 (Preset Speed #4) Preset Speed # 4 (Hz) 0.00 - 650.00 30.00 *1
6-06 (Preset Speed #5) Preset Speed # 5 (Hz) 0.00 - 650.00 40.00 *1
6-07 (Preset Speed #6) Preset Speed # 6 (Hz) 0.00 - 650.00 50.00 *1
6-08 (Preset Speed #7) Preset Speed # 7 (Hz) 0.00 - 650.00 60.00 *1
7- Analog Input Signal Operation
Function LCD Factory
Description Range/Code Remarks
Code No. Display Setting
7-00 (AIN Gain) AIN Gain (%) 0 - 200 100 *1
7-01 (AIN Offset) AIN Bias (%) 0 - 100 0 *1
0000: Positive
7-02 (AIN Bias) AIN Bias Selection 0000 *1
0001: Negative
0000: Positive
7-03 (AIN Slope) AIN Slope 0000 *1
0001: Negative
AIN Signal Verification Scan
7-04 (AIN Scan Time) Time (AIN, AI2) 1 - 100 50
(mSec x 2)
4-15
Chapter 4 Software Index
7-05 (AI2 Gain) AI2 Gain (%)(S6) 0 - 200 100 *1
※ Notes: Group 7 is available when 5-06=0023 (AIN term.=Analog input)
8- Multifunction Output Relays and Output Signal Operation
Function LCD Factory
Description Range/Code Remarks
Code No. Display Setting
0000: Output Frequency
0001: Frequency Setting
Analog Output Voltage Mode 0002: Output Voltage
8-00 (AO Mode Sel) 0000 *1
(0 - 10 VDC, Term. FM+) 0003: DC Voltage
0004: Output Current
0005: PID Feedback *7
8-01 (AO Gain) Analog Output Gain (%) 0 - 200 100 *1
0000: Run
0001: Frequency Reached
(Frequency Command) (Set
Frequency ± 8-05)
0002: Set Frequency (8-04 ± 8-05)
Output Relay R1 Operation 0003: Frequency Threshold Level (>
8-02 (Relay R1 Sel) 0006
Mode 8-04) - Frequency Reached
0004: Frequency Threshold Level (<
8-04) - Frequency Reached
0005: Over torque Threshold Level
0006: Fault
0007: Auto Restart
0008: Momentary AC Power Loss
0009: Rapid Stop Mode
0010: Coast-to-Stop Mode
Output Relay R2 Operation 0011: Motor Overload Protection
8-03 (Relay R2 Sel) 0000
Mode 0012: Drive Overload Protection
0013: PID Feedback Signal Loss
0014: PLC Operation
0015: Power On *7
Frequency Reached (Hz)
8-04 (Freq Agree) 0.00 - 650.00 0.00 *1
(Refer to 8-02: 0001)
Frequency Reached Bandwidth
8-05 (Freq Agree width) 0.00 - 30.00 2.00 *1
(± Hz)
9- Drive and Load Protection Modes
Function LCD Factory
Description Range/Code Remarks
Code No. Display Setting
0000: Enable Trip Prevention During
Trip Prevention Selection Acceleration
9-00 (Trip ACC Sel) 0000
During Acceleration 0001: Disable Trip Prevention
During Acceleration
Trip Prevention Level During
9-01 (Trip ACC Level) 50 - 300 200
Acceleration (%)
0000: Enable Trip Prevention During
Trip Prevention Selection Deceleration
9-02 (Trip DEC Sel) 0000
During Deceleration 0001: Disable Trip Prevention
During Deceleration
4-16
Chapter 4 Software Index
Trip Prevention Level During
9-03 (Trip DEC Level) 50 - 300 200
Deceleration (%)
0000: Enable Trip Prevention in Run
Trip Prevention Selection in Mode
9-04 (Trip RUN Sel) 0000
Run Mode 0001: Disable Trip Prevention in
Run Mode
Trip Prevention Level In Run
9-05 (Trip Run Level) 50 - 300 200
Mode (%)
0000: Trip Prevention Deceleration
Trip Prevention Deceleration Time Set by 3-03
9-06 (Dec Sel Trip RUN) 0000
Time Selection in Run Mode 0001: Trip Prevention Deceleration
Time Set by 9-07
(Dec Time Trip Deceleration Time In Trip
9-07 0.1 – 3600.0 3.0
RUN) Prevention Mode (Seconds)
0000: Enable Electronic Motor
Electronic Motor Overload Overload Protection
9-08 (Motor OL1 Sel) 0000
Protection Operation Mode 0001: Disable Electronic Motor
Overload Protection
0000: Electronic Motor Overload
Protection Set for
Non-Inverter Duty Motor
9-09 (Motor Type) Motor type Selection 0000
0001: Electronic Motor Overload
Protection Set for Inverter
Duty Motor
0000: Constant Torque (OL =103 %)
Motor Overload Protection (150 % for 1 Minute)
9-10 (Motor OL1 Curve) 0000
Curve Selection 0001: Variable Torque (OL = 113 %)
(123 % for 1 Minute)
0000: Coast-to-Stop After Overload
Protection is Activated
Operation After Overload
9-11 (Motor OL1 Operat) 0001: Drive Will Not Trip when 0000
Protection is Activated
Overload Protection is
Activated (OL1)
0000: Disable Over torque Operation
0001: Enable Over torque Operation
Only if at Set Frequency
9-12 (Torq Det Sel) Over torque Detection Selection 0000
0002: Enable Over torque Operation
while the Drive is in Run
Mode
0000: Drive will Continue to
Operate After Over torque is
Operation After Over torque
9-13 (Torq Det Operat) Activated 0000
Detection is Activated
0001: Coast-to-Stop After Over
torque is Activated
Over torque Threshold Level
9-14 (Torq Det Level) 30 - 200 160
(%)
Over torque Activation Delay
9-15 (Torq Det Delay) 0.0 - 25.0 0.1
Time (Seconds)
4-17
Chapter 4 Software Index
4-19
Chapter 4 Software Index
4-20
Chapter 4 Software Index
4.4 Parameter Function Description
Parameter Group 0: Drive Operation Mode
0-00:Control Mode
0000:Vector mode (General Mode)
0001:Vector mode (VT Mode)
0002:V/F mode
To select the most suitable vector control mode or V/F mode according to the load characteristics.
1. Vector (general mode) is inclined to control the general load or rapidly-changed torque load.
2. Vector (VT mode) is suitable for Blower/ Pump and HVAC load. The magnetic current of
motor will be variable with the torque, which will reduce the current to save the energy.
3. As V/F mode is selected, please set the parameter group10 comply with the load features.
0-01:Motor Rated Voltage(Vac)
0-02:Motor Rated Current(A)
0-03:Motor Rated Power (kW)
0-04:Motor Rated Speed (RPM)
0-05:Motor Rated Frequency (Hz)
0-06:Motor Parameter Auto Tuning
0000: Disabled 0001: Enabled
It is necessary to input the data on nameplate and auto tuning as long as changing the motor as
vector mode is selected.
Auto tuning: firstly input the data to 0-01~0-05 according to the nameplate after power off, then set
0-06=0001and perform auto tuning; the motor will run. It will stop as the inverter finishes auto
tuning. The detected internal data will auto be written to parameter group 14.
ex. If the motor rated speed is 1700 rpm, please set 0-04 to 17.0
Precaution
1. The motor parameter auto tuning is the stationary auto tuning. During motor auto tuning, the motor
does not rotate, and the keypad display -AT-.
2. During motor parameter auto tuning, the input signal in control circuit is invalid.
3. Before motor parameter auto tuning, please confirm the stop state of the motor.
4. The motor parameter auto tuning is only available for vector control mode (0-00=0000or 0-00=0001).
220V series:170.0~264.0
440V series:323.0~528.0
To make sure the voltage level of inverter, please input the actual on-site voltage value.
0-08 Language Selection
0000: English
0001: German
0002: French
0003: Italian
0004: Spanish
4-21
Chapter 4 Software Index
The function is only available for the products with LCD operation keypad. The operation is not
necessary for the one with LED.
4-22
Chapter 4 Software Index
S1 (forward) S1 (forward)
S2 (reverse) S2 (reverse)
COM (0V common) 24V (common)
轉
4-23
Chapter 4 Software Index
1-01 = 0002, Control mode is as below:
(1). Input signal is NPN: (2). Input signal is PNP:
S1 (run) S1 (run)
S2 (stop) S2 (stop)
S3 (FWD/REV) S3 (FWD/REV)
COM 24V(common)
※Note: As 3 wire control mode is selected, the terminal S3 is not controlled by 5-02.
1.) 1-04=0000:As starting, the inverter accelerates from 0 to target frequency in the set time.
2.) 1-04=0001:As starting, the inverter accelerates to target frequency from the detected speed of
motor.
1-05 : Stopping Method 0000: Controlled Deceleration-to- Stop with DC Injection Braking
4-24
Chapter 4 Software Index
(Rapid Stop)
0001: Free run stop
1.) 1-05=0000: the inverter will decelerate to 0Hz in preset deceleration time after receiving the stop
command.
2.) 1-05=0001: the inverter will stop output as receiving the stop command. The motor will inertia
free run to stop.
1-06 : Frequency Command Source Selection
0000: Set the Frequency with Keypad
0001: Potentiometer on Keypad
0002: External Analog Signal Input or Remote Potentiometer
0003: Up/Down Frequency Control Using MFIT (S1 - S6)
0004: Communication Setting Frequency
0005: Impulse frequency (S5) setting frequency (ver2.3)
1.) 1-06=0001,as one of the parameter in group 5-00~ 5-06is set 16 and multifunction terminal is
OFF, the frequency is set by the KNOB(VR for principal speed) on keypad. While the
multifunction is ON, the frequency is set by analog signal (auxiliary speed) on terminal block
(TM2).
2.) 1-06=0002,as one of the parameter in group 5-00~ 5-06 is set 16 and the multifunction terminal
is OFF, he frequency is set by analog signal (principal speed) on terminal block (TM2), While
the multifunction is ON, the frequency is set by the KNOB(VR for auxiliary speed) on keypad.
3.) Please refer to description of parameter group 5-00~ 5-06 (multifunction input terminals) for the
function Up/Down terminal.
4.) The priority in reading frequency is PLC frequency control >traverse run >Jog> preset
speed>▲▼ on keypad or Up / Down or communication control.
5.) Impulse frequency command input source should be setting as S5 terminal and need to
coordinate with 5-10 frequency exchange times ratio. For example, the input value S5 is 4KHZ,
5-10 is 1.500 times, and output frequency is 40.00*1.5=60.00HZ. 5-04(S5) should be setting as
19.
1-07:Keypad Operation with Up/Down Keys in Run Mode
0000: ‘Enter’ must be pressed after frequency change with Up/Down Keys on keypad.
0001: Frequency will be changed directly when Up/Down Keys are Pressed
4-25
Chapter 4 Software Index
※Note: 1-00=0001, 2-04=0000, 2-00=0001or 0002 after power lost for a long time, please OFF the
power and power switches in case of injury to person and machine by the resupplied power.
1.) 2-03=0:the inverter will not auto restart as trip for accident.
2.) 2-03>0,2-02= 0:
The inverter will conduct SPIN START in 0.5 second after trip for accident. The motor will
inertia run to frequency at the trip stop, then according to setting accelerate or decelerate time to
target frequency.
3.) 2-03>0,2-02>0:
The output will be stopped for a period which is determined by the 2-02 after accident trip. Then,
spin start to present target frequency.
4.) As the inverter is set in braking deceleration or DC braking, it will not perform restart after accident.
1.) 2-04=0000:the inverter will detect motor speed and accelerated the setting frequency as speed
4-26
Chapter 4 Software Index
search enable.
2.) 2-04=0001:the inverter will accelerated the motor speed from stop (zero speed) to setting
frequency.
2-05 :Direct running after power up:
0000: Enable Direct Running After Power Up
0001: Disable Direct Running After Power Up
Danger:
1.) 2-05=0000 and the inverter is set external terminal controlled(1-00=0001), if the run switch is
ON as power is supplied, the inverter will auto start. It is recommend that to cut off the power
switch and run switch in case of injury to persons or machine as power is supplied again.
2.) 2-05=0001and the inverter is set external terminal controlled(1-00=0001), if the run switch is
ON as power is supplied, the inverter will not auto start and flash STP1. It is necessary to
OFF the run switch and then ON to normally start.
4-27
Chapter 4 Software Index
※NOTE:
1.When 2-08≠0,the momentary power loss and Restart is disabled,the inverter will do KEB
Function.
2.When power off,CPU detect the DC Voltage. KEB function enable when DC Voltage below than
190V(220V system)or 380V(440V system).
3.When KEB function enabled,the inverter decelerate to zero by 2-08,and the inverter stop.
4.IF the power on signal enabled during the KEB function ,the inverter accelerate to original
frequency.
2.)When 5-00 – 5-06 is set 06 (the second acceleration and deceleration time),the first
acceleration/ deceleration/ S curve or the second acceleration/ deceleration/ S curve will be set
by ON the external input terminal.
3.) When 5-00 – 5-06 is set 05 (Jog),Jog run is controlled by external terminals. The acceleration
/ deceleration time + S curve time. For example: acceleration time = 3-03+ 3-04。
4-29
Chapter 4 Software Index
8.)During acceleration and deceleration process, there might be residual error in acceleration and
deceleration toggling. Please set the S curve time as 0 (3-04/3-05), if you need to toggle acceleration
and deceleration time in acceleration / deceleration process.
SC ti
Output frequency
Time
3-10 : DC Injection Brake Start Frequency (Hz) : 0.1 – 10.0
3-11 : DC Injection Brake Level (%) : 0.0 – 20.0
3-12 : DC Injection Brake Time(second) : 0.0 – 25.5
3-12 / 3-10 is the action time and start frequency of DC braking, as graph below:
HZ
3-10
t
3-12
The upper setting of 3-11 will be corrected 20.0 after manual V2.3.
3-13 : Skip Frequency #1 (Hz) : 0.00 –650.00
3-14 : Skip Frequency #2 (Hz) : 0.00 –650.00
3-15 : Skip Frequency #3 (Hz) : 0.00 –650.00
3-16 : Skip Frequency Bandwidth (± Hz) : 0.00 –30.00
Example: as 3-13is set as 10.0Hz / 3-14 as 20.0 Hz / 3-15a s 30.0 Hz / 3-16 as 2.0Hz
10Hz ±2Hz=8-12Hz
20Hz ±2Hz=18-22Hz skip frequency
30Hz ±2Hz=28-32Hz
3-16
3-15
3-14
3-13
4-30
Chapter 4 Software Index
4.) 3-18=0003:Copy the parameters to inverter or module to mutually verify the parameters.
※Note: The copy function is available for the models with same capacity.
1.) 3-19=0000:The fan run as the inverter senses temperature rises. Thusly, extend the service
period.
3.) 3-19=0002:The fan is continuously running regardless of the action of the inverter.
4.) 3-19=0003:The fan is always stopping regardless of the action of the inverter.
※Note: Depend on the hardware, the function is disable at 15HP above of 220V class and 20HP
above of 440V class. The fan is running after the inverter power on.
3-20: Energy Saving Mode Operation 0000: Disabled
0001: Controlled by MFIT at Set Frequency
3-21: Energy saving operation gain (%): 0-100
1.) In terms of FAN, PUMP or other heavy inertia loads which need greater start torsion, while in
operation they need not so high torsion. Consequently, to decline the output voltage to saving
energy by setting 3-20 is necessary.
2.) 5-00 ~5-06(Multifunction input terminal) set as10 to saving energy.
4-31
Chapter 4 Software Index
3.) 3-20=0001, If the multifunction terminal is set as 10(energy saving control terminal) ,the output
voltage will gradually decline to ‘original voltage’ב3-21’ preset value as the terminal’ is ON.
The output voltage will rise to original voltage as the terminal is OFF.
※Note:1.The declining and rising speeds of voltage for energy saving is same as the ones for
SPEED SEARCH.
2. Energy saving mode is only available under V/F mode. (0-00 = 0002)。
4-32
Chapter 4 Software Index
4-02:DC Bus Voltage Display Selection: 0000: Disable Bus Voltage Display
0001:Enable
Keypad displays PID feedback value :
Parameter 5-05=20 (That is, S6 is set as the PID feedback analog terminal, refer to PID),
11-0=1(PID is enabled), and 4-06=1(Display S6 as PID analog feedback value 0~100, the formula as
follow:)
4-33
Chapter 4 Software Index
If feedback signal is 0~10V, (12-6=0000), keypad display value = (S6/10V)*100
If feedback Signal is 4~20mA, (12-6=0001), keypad display value = (S6/20mA)*100
※Note: Please press DSP Key to switch between the output frequency and PID feedback value.
4-34
Chapter 4 Software Index
The inverter will decelerate to stop and Flash E.S as the emergency stop signal received
regardless of 1-05 setting. After such signal released, OFF the operation switch then ON or Press
Operation Key, the inverter will restart from the start frequency. If the emergency signal was
released before the inverter stop completely, the inverter still carries out emergency stop. The
8-02/03 determines the action of the error terminal. As 8-02/0=0: the error terminal does not act
when the external emergency signal input. While 8-02/03=9, the error terminal does act when
emergency signal input.
6. 5-00~06=8:Base Block
The inverter stop output as receiving STOP command, and the motor Free-Run stops.
When starting, the inverter detects the present speed of the motor firstly, then, the inverter
accelerates from the present speed to preset speed.
8. 5-00~06=10:Energy-saving operation
In terms of FAN, PUMP or other heavy inertia loads which need greater start torque, while in
operation they need not so high torsion. Thusly, to decline the output voltage is to saving energy.
The output voltage gradually declines as the multifunction terminal is ON. It will gradually
increase (to the original voltage) as the Multifunction terminal is OFF.
※Note:The acceleration and deceleration speed of energy saving operation is the same as the speed of
SPEED SEARCH.
4-36
Chapter 4 Software Index
External switch terminal is OFF:1-00/01 determines the operation signal and frequency signal.
External switch terminal is ON:Keypad controls the operation signal and frequency signal but not
controlled by 1-00/01.
External switch terminal is OFF:in communication, the master (PC or PLC) can control the
inverter operation and frequency signal and allowably modify the parameters, and the operation
signals from Keypad and TM2 are idle. Furthermore, the keypad can only display the voltage,
current and frequency, the parameters are readable and not writable, and Emergency Stop is
valid.
External switch terminal is ON:in communication, the inverter is controlled by the keypad
regardless of the setting of 1-00/1-06 and master. Under such circumstance, the master still can
read and write the inverter parameters.
The acceleration and deceleration action is unavailable till the forbid acceleration and
deceleration signals are released. The action is illustrated in the graph below:
Operation
Signal
Disable
ACC/DEC
12. 5-00~06=14,15:UP / DOWN Function (Actual ACC/DEC time is base on the setting):
(1)Please set 1-06 = 3 if you want to use the UP/DOWN Function, and the other frequency signals
are useless.
(2)Set 5-08 = 0 and 5-09 = 0, the inverter accelerates to the preset value of 6-00 when the
operation terminal is ON. Then, it maintains the certain speed. As the inverter receives the
UP/DOWN command, it will accelerate / decelerate till the command is released. The
inverter runs at the certain speed. The inverter will ramp stop or Free-Fun stop which is
determined by the 1-05 as long as the inverter receives the STOP command. And the
frequency of Stopping will be stored in 6-00. The UP/DOWN KEY is invalid as the inverter
stops. It is necessary to use the Keypad to modify the preset parameter.
4-37
Chapter 4 Software Index
(3)Set 5-08 = 1, the inverter will operate from 0Hz when the operation terminal is ON. The
action of UP/DOWN is as above description. The inverter will ramp stop or free-run stop
which determined by1-05 setting when as it receiving the Stop Command and back to 0Hz.
The next operation will start at 0 Hz.
(4) That UP/Down Signal Simultaneously act are invalid
(5) 5-09≠ 0, the inverter will accelerate to the setting of 6-00 and maintain at the speed. When
the UP/Down terminal is On, setting frequency is present value 6-00±5-09, and the inverter
will accelerate/ decelerate to frequency 6-00. The upper frequency limit and lower frequency
limit also restrict the operation. If the signal of UP/ DOWN is maintained over 2 seconds, the
inverter will begin to accelerate/ decelerate. If 5-09=0, the operation is the same, till the UP/
DOWN signal stops. Please refer to the time diagram of 5-09.
Operation
UP
DOWN
Output 6-00
Frequency
13. 5-00~06=16 Principal/Auxiliary speed toggle
Multifunction terminal = OFF, the frequency is set by the VR (Master Speed) on the
Keypad. Whereas, Multifunction terminal = ON, the frequency is set by the analog signal
terminal (Auxiliary Speed) on the TM2 on terminal Block.
14. 5-00~06=17(PID Function Disable)
The PID Function Disable is ON. PID is not controlled by 11-0, while OFF, it is controlled
by 11-0.
15. 5-00~06=18(Reset Command)
The Reset command is same as Reset Key on the panel is ON. The command is OFF, and the
inverter does not response. The factory set of 5-05 is Reset command.
16. 5-04=19 (Encoder Input terminal)
The multifunction terminal S5 is set 19 means it is the input terminal for PLC program
Encoder.
17. 5-05=20 (PID feedback input terminal)
The multifunction terminal S6=20 means the PID feedback input terminal and 0~10V (0~
20 mA) or 2~10V (4~20mA) is available by the setting of 11-0.
18. 5-05=21 /22(Bias signal 1/2 input)
To regulate the Offset of the Keypad VR or AIN analog input, only the signal of 0~10V (0~ 20 mA)
or 2~10V (4~20mA) is available.
5-05=21 Function 5-05=22Function * The value is 0 when AIN+(S6-5V)<0
Hz Hz
4-38 Upper Frequency
Upper Frequency Limit 3-00
Limit 3-00
V V
0 10 0 5
Chapter 4 Software Index
(1) Set 5-08=0, the inverter will accelerate to the speed of 6-00 as receiving the Run command and
run at such certain speed. The inverter begins to accelerate (decelerate) as the UP (Down) terminal
is energized. The inverter will hold the speed as the UP/DOWN command released. When the Run
Signal releases, the inverter will ramp stop or stop output (determined by the 1-05). It will store the
frequency when the operation signal disappeared. UP/DOWN keys are idle when the inverter is
stop. The keypad is available for you modify the preset frequency (6-00). If 5-08=0002, the
UP/Down is available as the inverter stops.
4-39
Chapter 4 Software Index
(2)Set 5-08=1, as the Run terminal is energized, the inverter operates from 0 Hz, the Function of
UP/DOWN is same as the above description. When the Run Signal released, the inverter will
ramp stop or stop output (determined by 1-05) .And back to 0 Hz. The following operation will
always begin from 0 Hz.
(2) 5-09 = 0.01 to 5.00, UP/ DOWN terminal ON, that equivalent to increase/ decrease the
frequency of 5-09. If the pressing is over 2second, revive the original UP/DOWN mode (Please
refer to the following diagram)
For example, when S5 impulse is 1KZ(1000), and 5-10 be setting as 1.50 times. The inverter
4-40
Chapter 4 Software Index
frequency command is 1000*1.5=1500=15.00HZ. The frequency accuracy of S5 is by base
of 100, 1K(1000) present 10.00 HZ.
Reference Source 2:
4-41
Chapter 4 Software Index
Parameter Group 6- Jog and Preset (MFIT) Speed Setting on Keypad
Priority in reading the frequency: Jog > Preset speed > Keypad frequency or external frequency signal
Multifunction Multifunction Multifunction Jog Command Output
terminal3 terminal 2 terminal 1 terminal frequency preset
Preset value=04 Preset value =03 Preset value =02 Preset value =05 value
0 0 0 0 6-00
X X X 1 6-01
0 0 1 0 6-02
0 1 0 0 6-03
0 1 1 0 6-04
1 0 0 0 6-05
1 0 1 0 6-06
1 1 0 0 6-07
1 1 1 0 6-08
4-42
Chapter 4 Software Index
0Hz B V D
0V 5V 10V 0Hz V
0V 5V 10V
(0mA) (20mA)
(0mA) (20mA)
The setting of figure 3: The setting of figure 4:
7-00 7-01 7-02 7-03 7-05 7-00 7-01 7-02 7-03 7-05
E 100﹪ 20% 1 0 100% F 100﹪ 50% 1 1 100%
Hz Figure 3 Hz Figure 4
60Hz Upper Frequency Limit 60Hz
Upper Frequency Limit
(3-00=60) (3-00=60)
30Hz 30Hz
Bias Bias F
0% E
0Hz V -0% 0Hz V
-50% 2V 5V 10V
10V -50%
(4mA) (20mA) (20mA)
-100% -100%
4-43
Chapter 4 Software Index
3. The inverter reads the average value of A/D signals once per (7-04×4ms). Users can determine scan
intervals according to noise in the environment. Increase 7-04 in noisy environment, but the respond
time will increase accordingly.
4-44
Chapter 4 Software Index
Parameter Group 8 - Multifunction output terminal and output signal
operation mode
Multifunction analog output control:
8-00:Analog Output Voltage Mode:
0000: Output frequency
0001: Frequency Setting
0002: Output voltage
0003: DC Bus Voltage
0004: Motor current
0005: FEEDBACK Signal of PID
8-01:Analog Output Gain = 0 ~ 200%
The multifunction analog output terminal of the terminal block (TM2), is 0~10Vdc analog output. The
output type is determined by the 8-01. The function of 8-01 is: when there is tolerance for the external
voltage meter and peripheral equipment, please regulate 8-00.
The FEEDBACK value of PID (That is the input voltage and current of S6) outputs analog value from
FM+ terminal. ( decide to parameter 4-06) The value is corresponding to the input signal 0~10V(0 ~ 20
mA) or 2~10V (4~20mA).
※Note: The max output voltage is 10V due to the circuit, even the output voltage should be higher than
10V.
0000: Run
0001: Frequency Reached (Target Frequency) (Set Frequency ± 8-05)
0002: Set Frequency (8-04 ± 8-05)
0003: Frequency Threshold Level (> 8-04) - Frequency Reached
0004: Frequency Threshold Level (< 8-04) - Frequency Reached
0005: Over torque Threshold Level
0006: Fault
0007: Auto-restart
0008: Momentary AC Power Loss
0009: Rapid Stop Mode
0010: Coast-to-Stop Mode
0011: Motor Overload Protection
0012: Drive Overload Protection
0013: PID Feedback Signal Break
0014: PLC Operation
0015: Power On
4-45
Chapter 4 Software Index
4-46
Chapter 4 Software Index
8-02/03= 01:
The preset frequency is reached ( ± 8-05)
8-02/3= 02:
Arbitrary frequency consistency Fout = 8-04 ± 8-05
4-47
Chapter 4 Software Index
4-48
Chapter 4 Software Index
4-49
Chapter 4 Software Index
The over torque is defined as: the output torque is inside parameter 9-15, the voltage level(the inverter
rated torque is 100%) is over 9-14 parameter.
9-13 = 0000:If there is over torque, the inverter can continue to run and flashes OL3 till the output
torque is less than the 9-14 setting value.
= 0001:If there is over torque, the inverter coasts to stop and flashes OL3. it is necessary to press
‘RESET’ or external terminal to continue to run.
Parameter8-02,03(Multifunction output terminal ) = 05, the output terminal is output over torque signal.
※Note: Over torque output signal will be output as the parameter 9-12=0001or 0002 when the level and
time are over the range.
4-52
Chapter 4 Software Index
1. 10-0=18, set the V/F pattern freely complying with 10-4~10-9 (Refer to following diagram)
(V)
10-5
(Vmax)
10-7
(Vmid)
10-9
(Vmin)
Hz
10-8 10-6 10-4 650
4-53
Chapter 4 Software Index
Netz- Netz-fr
10-0 V/f-Modell 10-0 V/f-Modell
freq. eq.
V(%) V(%)
Standardanwendung
Standardanwendung
100 100
0 9
0.1 3 0.1 3
V(%) V(%)
Hohes Anzugsdrehmoment
Hohes Anzugsdrehmoment
10
1 100 100
11
2
0.1 3 12 0.1 3
3
50Hz 60Hz
V(%) V(%)
Variables Drehmoment
Variables Drehmoment
4 100 13 100
5 14
0.1 25 0.1 30
V(%) V(%)
Konstantes Drehmoment
Konstantes Drehmoment
6 15
100 100
7 16
8 17
0.1 5 0.1 6
4-54
Chapter 4 Software Index
10-0 B C
0/9 50.0% 1.0%
1 / 10 60.0% 1.0%
2 / 11 65.0% 1.0%
3 / 12 70.0% 1.0%
4 / 13 40.0% 1.0%
5 / 14 35.0% 1.0%
6 / 15 45.0% 1.0%
7 / 16 55.0% 1.0%
8 / 17 65.0% 1.0%
3. The inverter will output the value that B, C voltage (refer to 10-0) plus 10-1 V/F pattern setting.
And the start torque will be raised.
Voltag
100%
10-1=
Hz
1 50/6
2 5/3
※Note: 10-1=0, Torque boost function is invalid
4. When the induction motor is in running, there must be slip due to the load. It is necessary to boost to
improve the precision of the speed.
Output Current-(10-2) Note : 0-02=motor rated current
Slip frequency boost = × (10-3)
(0-02)-(10-2) 10-2=motor no load current
10-3 rough value= (Motor synchronization speed– Rated speed) / Motor synchronization speed
120
eg: 4 Poles,60Hzinduction motor synchronization speed = × 60=1800 RPM
4
※Note: Motor no load current(10-2) differs with the inverter capacities(15-0)(Refer to 0-02 note),
It should be regulated according to the actual condition.
4-55
Chapter 4 Software Index
11-1 is the calibration gain. Deviation = (target value – detected value) × 11-1
4-56
Chapter 4 Software Index
11-5: PID Offset : 0000 : Positive Direction
0001 :Negative Direction
11-6: PID Offset Adjust (%) : -109% ~ +109%
11-5/11-6:PID the calculated result pluses 11-6 (the sign of 11-6 is determined by 11-5).
※Note: PID Function is available for controlling the output flow, external fan flow and temperature.
The controlling flow is as follow:
1. Performing PID control, set 5-05=23, AI2 (S6) on TM2 as PID feedback signal.
2. The target value of above diagram is the 1-06 input frequency.
3. There are two ways to see the PID feedback signal, one is using the Keypad switch display (4-06
must be setting as 1), the other is using analog output FM+ (8-00 must be setting as 5).
4-57
Chapter 4 Software Index
12-1is the level for signal loss. Deviation = Command value – Feedback value. While the deviation
is larger than the loss level, the feedback signal is lost.
0000:Disable
0001:1 second
0030: 30 seconds
12-4=0:As PID feedback value reaches the command value, the integrator will not be reset to 0.
12-4=1~30:As PID feedback value reaches the target value, reset to 0 in 1~30 seconds and inverter
stops output. The inverter will output again as the feedback value differs from the target
value.
12-5=0 ~ 100% unit value:restart the tolerance after the integrator reset to 0.
13-0: to set the communication station codes which are suitable for driving more than one inverters
situations.
4-59
Chapter 4 Software Index
0001: 9600
0002: 19200
0003: 38400
4-60
Chapter 4 Software Index
1. If 0-00=0 or 1(vector mode ) is selected, as power ON, set 0-06=1, the motor will run as the
inverter performs auto tuning. As the motor stop, it means that auto tuning finished. The inverter
will write the internal parameter of the motor to 14-0~ 14-4, and auto reset the 0-06 as 0.
2. Auto tuning must be carried out as long as the motor changed. If the internal parameters is known
already, they can be input to 14-0~14-4 directly.
3. 0-06=1,to perform auto tuning, after finished, 0-06 auto reset to 0, the Keypad displays END.
4.The parameter group only affect the current vector.
15-1:Software Version
1. When the inverter doesn’t work normally, the former fault log stored in2.xxxx will be transferred
to 3.xxxx, then, the one in 1.xxxx to 2.xxxx. The present fault will be stored in the blank 1.xxxx.
Thusly, the fault stored in 3.xxxx is the earliest one of the three, while the one 1.xxxx is the latest.
2. Enter 15-2, the fault 1.xxxx will be displayed firstly, press▲, you can read 2.xxx→3.xxx→1.xxx,
whereas▼, the order is 3.xxx→2.xxx→1.xxx→3.xxx.
3. Enter 15-2, the three fault log will be cleared as the reset key is pressed. The log content will
changed to 1.---,2.---,3.---.
4-61
Chapter 4 Software Index
4. E.g. if the fault log content is ‘1.OCC’ which indicates the latest fault is OC-C, and so on.
15-6:Reset the factory setting: 1110: Reset the 50Hz factory setting
※Note:
Motor parameters (14-0~14-4) will be modified under V/F control mode when reset factory setting.
On the contrary, motor parameters (14-0~14-4) will not be modified under vector control mode
when reset factory setting.
4-62
Chapter 4 Software Index
¿ À P NO / NC
4-63
Chapter 4 Software Index
4.5.2 Function of Basic Instruction
Function D (d) Command
Sample 1: I1─D ──[ Q1
I1 OFF ON OFF
D OFF ON OFF
One complete scan period
Q1 OFF ON OFF
Sample 2: i1─d ──[Q1
I1 OFF ON OFF
I1 is the reverse phase of i1.
i1 ON OFF ON
d1 OFF ON OFF
One complete scan period
Q1 OFF ON OFF
NORMAL ( - [ ) Output
I1 ── [Q1
I1 OFF ON OFF
Q1 OFF ON OFF
I1 ── ¿Q1
I1 OFF ON OFF
Q1 OFF ON
I1 ── ÀQ1
I1 OFF ON OFF
Q1 ON OFF
P Output
i1 ──PQ1
I1 OFF ON OFF ON OFF ON OFF
I1 is the reverse
phase of i1.
i1
Q1 ON OFF ON OFF
4-64
Chapter 4 Software Index
4-65
Chapter 4 Software Index
Sample:
m1 ┬ -- ─ q1 ─﹝M2
M2 ┴
1 ┐
When the target value is reached, C3 =ON.
M2 │
0000
The input point C3 in the ladder program should be
│─
0020 C3
I3 ON.
┘
4-66
Chapter 4 Software Index
(2) Counter Mode 2
※Note:
Under this Mode, the counting preset value appeared will be greater than 20, unlike the Mode
1 in which the value is locked at 20.
(3) The counter Mode 3 is similar to the counter Mode 1 except that the former can memory the
recorded value after the power is cut off and continued counting when the power is turned on at
the next time.
(4) The counter Mode 4 is similar to the counter Mode 2 except that the former can memory the
recorded value after the power is cut off and continued counting when the power is turned on at
the next time.
4-67
Chapter 4 Software Index
Timer
Symbol Description
1
c Timing Mode (1-7)
d Timing unit
2 4 1: 0.0 – 999.9 sec
2: 0 – 9999 sec
5 6 3: 0 – 9999 min
3 e Use (I1 ~ f8) to RESET the timing value.
ON: the counter is reset to zero and h OFF
OFF: the counter continues to count
f Preset Timing Value
g Target (setting) Timing Values
h The code of the Timer (T1 ~T8 total: 8 groups).
4-68
Chapter 4 Software Index
Sample:
T5 ─ -- ─ -- ─﹝Q1
1 ┐
1 │
000.0
│─
When the time reaches to the target value
010.0 T5
10.0 sec, T5 is ON
┘
4-69
Chapter 4 Software Index
4-70
Chapter 4 Software Index
(5) Timer Mode 5 (Flash A Mode)
4-71
Chapter 4 Software Index
Analog comparator
1 Symbol Description
4-72
Chapter 4 Software Index
Symbol Description
1
c Encoder control mode (1-2)
2 4 Use (I1 ~ f8) to set counting up or counting down
d OFF: counting up (0, 1, 2, 3, 4….)
5 7 ON: counting down ( ….3, 2, 1, 0)
3
e Use (I1~f8) to Reset counting value.
6
f A1, Encoder Input Value/Encoder dividing ratio(h)
g A2, Setting comparing value
h C, Encoder dividing ratio
i Encoder comparing output terminal, H1~H4
※Comparison Enable/ Disable of the Encoder input value is determined by the Ladder Program ON/OFF.
Running Instruction
4-73
Chapter 4 Software Index
Symbol Description
F1 ─ -- ─ -- ─﹝Q1
10.0
M1 ┐ When Inverter operating, F1=ON.
M2 10.0
n The input terminal of F1 in the ladder program
│
60.00 F1
n mode should be ON.
30.00
│─
4-74
Chapter 5 Troubleshooting and maintenance
CTER Current Sensor Current sensor error or circuit Send the inverter back
detecting error malfunctions for repairing
5-1
Chapter 5 Troubleshooting and maintenance
5-2
Chapter 5 Troubleshooting and maintenance
5.1.3 Errors which can be recovered manually but not auto matically
Display Error Cause Remedy
1. Detection circuit
1.Check the noise between Power
Over-current during malfunctions
OC line and motor line
stop 2. Bad connection for CT
2.Send the inverter back for
signal cable
repairing
5-3
Chapter 5 Troubleshooting and maintenance
The inverter will ramp stop and then flash E.S., when input external
External
E.S. emergency stop signal via the multifunctional input terminal (refer to
emergency stop
descriptions of 5-00~5-06).
The inverter stops immediately and then flashes b.b., when external
b.b. External base
base block is input through the multifunctional input terminal (refer
block
to descriptions of 5-00~5-06).
5-4
Chapter 5 Troubleshooting and maintenance
EPr2
Parameter not Copy the parameter to inverter to 1.Rewrite again
match verify the parameter is not match. 2.Replace copy unit
5-5
Chapter 5 Troubleshooting and maintenance
Is power applied to L1(L), L2, and L3(N) ‧Is the power applied?
terminals (is the charging indicator lit)? ‧Turn the power OFF and then ON again.
‧Make sure the power voltage is correct.
‧Make sure screws are secured firmly.
Are there voltage across the output terminal
‧Turn the power OFF and then ON again.
T1, T2, and T3?
Is overload causing the motor blocked? ‧Reduce the load to let the motor running.
Motor can
Are there any abnormalities in the inverter?
not run ‧See error descriptions to check wiring and
Is forward or reverse running command issued? correct if necessary.
Are wiring for output terminals T1, T2, and T3 ‧Wiring must match U, V, and W terminals
correct? of the motor.
Motor runs
inversely
Are wiring for forward and reverse signals ‧Check wiring are correct if necessary.
correct?
Are wiring for analog frequency inputs correct? ‧Check wiring are correct if necessary.
The motor
speed can
not be
Is the setting of operation mode correct? ‧Check the operation mode of the operator.
regulated.
Is the load too heavy? ‧Reduce the load.
5-6
Chapter 5 Troubleshooting and maintenance
5-7
Chapter 5 Troubleshooting and maintenance
Is fault fully NO
understood?
YES
Any
Symptoms other than burn NO symptoms of burn YES Check burnt and damaged
out, damage, or fuse meltdown in parts
the inverter?
out and damage?
YES
Abnormal NO
signal? Is the main circuit NO Replace DM
DM intact?
YES
YES
Any abnormalities in 有 Replace the abnormal boards
appearances?
5-8
Chapter 5 Troubleshooting and maintenance
Perform parameter
initializations
YES
YES
Are there NO
voltage outputs in output Replace the control board
terminals U, V and W
YES
Connect the motor to run Is the control NO
board working well after
replacement
YES
NO
Are output NO
current of each phase
even?
5-9
Chapter 5 Troubleshooting and maintenance
YES
YES
Any abnormal NO
Is the current detector
indications?
OK?
YES
Input operation command Replace control board Replace the current controller
YES
Are there NO
voltage output at U,V and W output Replace control board
terminals?
YES
Is the inverter
NO
Connect the motor to run working well after
replacement
NO
5-10
Chapter 5 Troubleshooting and maintenance
NO
Apply the power
NO
Input operation command
YES
Are there NO
voltage output at T1,T2,T3 Replace the control board
output terminals?
Is the inverter NO
YES working well after
Connect the motor to run replacement
YES
YES
Any abnormal value?
NO
5-11
Chapter 5 Troubleshooting and maintenance
YES Is MCCB
applied?
NO
Can MCCB be NO
applied? Short circuited wiring
Is LED 101lit? NO
7300CV fault
YES
5-12
Chapter 5 Troubleshooting and maintenance
NO
NO
Bad connection between YES Correct the bad connection
7300CV and the motor
NO
5-13
Chapter 5 Troubleshooting and maintenance
5-14
Chapter 5 Troubleshooting and maintenance
L1(L) T1(V)
Power source Hookup of insulation test
L2 T-VERTER T2(V)
Motor
L3(N) T3(V)
Ground terminal
Ground terminal
5-15
Chapter 6 Peripherals Components
6-1
Chapter 6 Peripherals Components
0060-BE JNVPHV-0060 1*5 JNBR-4R8KW27R2 60 45 4800 27.2 10 117 535*50*110 (*4 pcs)
6-2
Chapter 6 Peripherals Components
B. Content
c Inverter
d LED (JNSDOP-LED) or LCD (JNSDOP-LCD) Keypad
eREMOTE Cable for Keypad
C. Operation procedure:
Warning: Turn OFF the power supply. The following procedures should be performed after
there is no display on the keypad.
1. Remove the keypad from the Inverter.
2. Please refer to Diagram before mounting the keypad to your machine or Panel.
3. Connect the inverter and the keypad with the remote cable in accordance with the above
Diagram.
Supply the power to operate ONLY after all elements are securely fixed.
6-3
Chapter 6 Peripherals Components
6-4
Chapter 6 Peripherals Components
6. 5 EMC Filter
The inverter adopts rapid switching components to improve the efficiency of the motor and to
reduce the motor noise. Using the EMC Filter allows the EMI (Electromagnetic Interference) and
RFI (Radio Frequency interference) to be controlled within certain range.
EMC Directives
The inverter with optional filter complies with the EMC directives 89/336/EEC, limiting the
environmental EMI and RFI. Independent tests have demonstrated compliance to the following
standards when the optional filters are used.
EMI radio standard、EMS immunity standard
EN 61800-3 1996/A11: 2000:First Environment Unrestricted Distribution (Class B).
EN 61800-3 1996/A11: 2000:First Environment Restricted Distribution
Filter Selection
Filter Model
Inverter Model Rating (INPUT) First Environment First Environment
Restricted Distribution Unrestricted Distribution
R500AC-UF 1 φ 170 ~264V Built in FS 6146-11-07
0001AC-UF 1 φ 170~264V Built in FS 6146-11-07
0002AC-UF 1 φ 170~264V Built in FS 6146-27-07
0003AC-UF 1 φ 170 ~264V Built in FS 6146-27-07
R500AC-U 1 φ 170 ~264V FS 6146-11-07 --
0001AC-U 1 φ 170~264V FS 6146-11-07 --
0002AC-U 1 φ 170~264V FS 6146-27-07 --
0003AC-U 1 φ 170 ~264V FS 6146-27-07 --
R500BC-U 3 φ 170 ~264V FS 6147-8.9-07 --
0001BC-U 3 φ 170 ~264V FS 6147-8.9-07 --
0002BC-U 3 φ 170 ~264V FS 6147-8.9-07 --
0003BC-U 3 φ 170 ~264V FS 6147-19-07 --
0005BC-U 3 φ 170 ~264V FS 6147-19-07 --
7R50BC-U 3 φ 170 ~264V FS 6147-39-07 --
0010BC-U 3 φ 170 ~264V FS 6147-39-07 --
0001BE-UF 3 φ 323~528 V Built in FS 6149-4.6-07
0002BE-UF 3 φ 323~528 V Built in FS 6149-4.6-07
0003BE-UF 3 φ 323~528 V Built in FS 6149-10-07
JNTHBCBA
0005BE-UF 3 φ 323~528 V Built in FS 6149-10-07
7R50BE-UF 3 φ 323~528 V Built in FS 6149-28-07
0010BE-UF 3 φ 323~528 V Built in FS 6149-28-07
0015BE-UF 3 φ 323~528 V Built in FS 6149-28-07
0001BE-U 3 φ 323~528 V FS 6149-4.6-07 --
0002BE-U 3 φ 323~528 V FS 6149-4.6-07 --
0003BE-U 3 φ 323~528 V FS 6149-10-07 --
0005BE-U 3 φ 323~528 V FS 6149-10-07 --
7R50BE-U 3 φ 323~528 V FS 6149-28-07 --
0010BE-U 3 φ 323~528 V FS 6149-28-07 --
0015BE-U 3 φ 323~528 V FS 6149-28-07 --
0020BE-U 3 φ 323~528 V JUNF34048S-MA --
0025BE-U 3 φ 323~528 V KMF370A --
0030BE-U 3 φ 323~528 V KMF370A --
0040BE-U 3 φ 323~528 V KMF3100A --
0050BE-U 3 φ 323~528 V KMF3100A --
0060BE-U 3 φ 323~528 V KMF3150A --
0075BE-U 3 φ 323~528 V KMF3180A --
6-5
Chapter 6 Peripherals Components
Dimensions (mm)
Model
W W1 H H1 D d M
KMF370A 93 79 312 298 190 7 M6
KMF3100A 93 79 312 298 190 7 M6
JUNF34048S-MA KMF3150A 126 112 312 298 224 7 M6
KMF3180A 126 112 312 298 224 7 M6
250
225
L3
L3
LOAD
LINE
L2
100 50
L2
4 − φ 6.5
L1
L1
PE
PE
70
6-6
Chapter 6 Peripherals Components
Note:
Please put on the cover of inverter to avoid the Interface Card disturbed by outside
static electricity.
Please using isolated RS232 / RS485 converter to link PC and interface card to avoid damage
equipment.
6-7
Chapter 6 Peripherals Components
JNSIF-232Wiring Diagram:
L1(L) T1
THREE-PHASE L2 T2
M
POWER SUPPLY L3(N) T3
7300CV
SERIES
RS-232 INVERTER
CON2 (12P)
JNSIF-232
1.8m
6-8
Chapter 6 Peripherals Components
L1(L) T1
THREE-PHASE
L2 T2 M
POWER SUPPLY
L3(N) T3
7300CV
SERIES
INVERTER
CON2 (12P)
JNSIF-MP
1
55m
6-9
Appendix
App 1
Appendix
2. The motor parameters (14-0~14-4) are not be modified when factory setting
under vector mode. The internal parameters will be maintained at the ones
after auto tuning (refer to Auto Tuning and Description on motor Internal
Parameter).
3: The motor parameters (14-0~14-4) will be modified to factory setting
completely under whatever operation mode.
App 2
Appendix
App 3