Grundfos SP Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24
At a glance
Powered by AI
The document provides installation and operating instructions for Grundfos submersible pumps. It details delivery, storage, applications, preparations, electrical connection, installation, startup, operation, maintenance and addresses for customer support worldwide.

Submersible pumps are used to pump water and other liquids from boreholes, wells or storage tanks. They are suitable for pumping clean or dirty water with solid content.

The main components of a submersible pump system are the submersible pump, electric motor, power cable and riser pipe. The motor is directly connected to the pump housing and lowers the entire unit into the liquid to be pumped.

GRUNDFOS INSTRUCTIONS

SP
Installation and operating instructions

Other languages

http://net.grundfos.com/qr/i/98074911
English (GB) Installation and operating instructions
English (GB)

Original installation and operating instructions. 2. Introduction


These instructions apply to Grundfos submersible pumps,
CONTENTS type SP, with submersible motors, types Grundfos MS/MMS or
Page Franklin 4"-8".
1. Symbols used in this document 2 If the pump is fitted with a motor of another motor make than
Grundfos MS or MMS, note that the motor data may differ from
2. Introduction 2
the data stated in these instructions.
3. Delivery and storage 2
3.1 Delivery 2 The USB stick supplied with the product contains
3.2 Storage 2 Note installation and operating instructions in various
4. Applications 3 languages.
4.1 Pumped liquids 3
4.2 Sound pressure level 3 3. Delivery and storage
5. Preparations before installation 3
5.1 Checking the motor liquid 3 3.1 Delivery
5.2 Positional requirements 5
The pump should remain in the packing until it is
5.3 Pump/motor diameter 5
Caution placed in vertical position during installation.
5.4 Liquid temperatures/cooling 5
Handle the pump with care.
5.5 Pipe connection 6
6. Electrical connection 6 When the pump part and motor are supplied as separate units
6.1 Frequency converter operation 7 (long pumps), fit the motor to the pump as described in section
6.2 Motor protection 7 7.1 Fitting the motor to the pump.
6.3 Lightning protection 8 The extra nameplate supplied with the pump should
6.4 Cable sizing 8 Note
be fixed at the installation site.
6.5 Control of single-phase MS 402 motors 9
Do not expose the pump to unnecessary impact and shocks.
6.6 Connection of single-phase motors 9
6.7 Connection of three-phase motors 10 3.2 Storage
7. Installation 11
Storage temperature
7.1 Fitting the motor to the pump 11
7.2 Removing and fitting the cable guard 12 Pump: -20 °C to +60 °C.
7.3 Connecting the submersible drop cable 12 Motor: -20 °C to +70 °C.
7.4 Riser pipe 12 The motors must be stored in a closed, dry and well ventilated
7.5 Maximum installation depth below water level [m] 12 room.
7.6 Cable clips 13
If MMS motors are stored, the shaft must be turned
7.7 Lowering the pump 13
by hand at least once a month. If a motor has been
7.8 Installation depth 13
Caution stored for more than one year before installation, the
8. Startup and operation 13 rotating parts of the motor must be dismantled and
8.1 Startup 13 checked before use.
8.2 Operation 14
The pump should not be exposed to direct sunlight.
9. Maintenance and service 14
If the pump has been unpacked, it should be stored horizontally,
10. Fault finding 15 adequately supported, or vertically to prevent misalignment of the
11. Checking motor and cable 16 pump. Make sure that the pump cannot roll or fall over.
12. Disposal 16 During storage, the pump can be supported as shown in fig. 1.

Warning
Prior to installation, read these installation and TM00 1349 2495
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
Fig. 1 Pump position during storage
1. Symbols used in this document
3.2.1 Frost protection
Warning If the pump has to be stored after use, it must be stored on a
If these safety instructions are not observed, it may frost-free location, or the motor liquid must be frost-proof.
result in personal injury.

Warning
If these instructions are not observed, it may lead to
electric shock with consequent risk of serious
personal injury or death.

If these safety instructions are not observed, it may


Caution
result in malfunction or damage to the equipment.

Notes or instructions that make the job easier and


Note
ensure safe operation.

2
4. Applications 5. Preparations before installation

English (GB)
Grundfos SP submersible pumps are designed for a wide range
Warning
of water supply and liquid transfer applications, such as the
supply of fresh water to private homes or waterworks, water Before starting work on the product, switch off the
supply in horticulture and agriculture, drawdown of groundwater power supply. Make sure that the power supply
and pressure boosting, and various industrial jobs. cannot be accidentally switched on.
The pump must be installed so that the suction interconnector is 5.1 Checking the motor liquid
completely submerged in the liquid. The pump can be installed
horizontally or vertically. See section 5.2 Positional requirements. The motors are factory-filled with a special non-poisonous liquid
which is frost-proof down to -20 °C.
4.1 Pumped liquids
Check the level of motor liquid and refill if required.
Clean, thin, non-explosive liquids without solid particles or fibres. Note
Use clean water.
The maximum sand content of the water must not exceed
50 g/m3. A larger sand content will reduce the life of the pump If frost protection is required, special Grundfos liquid
and increase the risk of blockage. must be used to refill the motor. Otherwise clean
Caution
water may be used for refilling (however, never use
When pumping liquids with a density higher than that distilled water).
Caution of water, motors with correspondingly higher outputs
Refill liquid as described below.
must be used.
5.1.1 Grundfos MS 4000 and MS 402 motors
If liquids with a viscosity higher than that of water are to be
pumped, contact Grundfos. The filling hole for motor liquid is placed in the following positions:
The pump versions SP A N, SP A R, SP N, SP R and SPE are • MS 4000: in the top of the motor.
designed for liquids with higher aggressiveness than drinking • MS 402: in the bottom of the motor.
water. 1. Position the submersible pump as shown in fig. 2.
The maximum liquid temperature appears from section 5.4 Liquid The filling screw must be at the highest point of the motor.
temperatures/cooling. 2. Remove the screw from the filling hole.
4.2 Sound pressure level 3. Inject liquid into the motor with the filling syringe until the
liquid runs back out of the filling hole. See fig. 2.
The sound pressure level has been measured in accordance with
4. Replace the screw in the filling hole and tighten securely
the rules laid down in the EC machinery directive 2006/42/EC.
before changing the position of the pump.
Sound pressure level of pumps
Torques
The values apply to pumps submerged in water, without external
• MS 4000: 3.0 Nm.
regulating valve.
• MS 402: 2.0 Nm.
Pump type LpA [dB(A)] The submersible pump is now ready for installation.

SP 1A < 70 MS 4000 MS 402


SP 2A < 70
SP 3A < 70
SP 5A < 70
SP 7 < 70
SP 9 < 70
SP 11 < 70
SP 14 < 70
SP 17 < 70
SP 30 < 70
SP 46 < 70 TM00 6423 0606

SP 60 < 70
SP 77 < 70
SP 95 < 70 Fig. 2 Motor position during filling - MS 4000 and MS 402
SP 125 79
SP 160 79
SP 215 82

Sound pressure level of motors


The sound pressure level of Grundfos MS and MMS motors is
lower than 70 dB(A).
Other motor makes: See installation and operating instructions
for these motors.

3
5.1.2 Grundfos MS 6000 motors rule or a small rod through the hole until it touches the diaphragm.
See fig. 5.
English (GB)

• If the motor is delivered from stock, check the level of motor


liquid before fitting the motor to the pump. See fig. 3.
Caution Take care not to damage the diaphragm.
• When pumps are delivered direct from Grundfos, the level has
already been checked.
• Check the level in connection with service. See fig. 3.
The filling hole for motor liquid is placed at the top of the motor.

TM00 1353 5092


1. Position the submersible pump as shown in fig. 3. The filling
screw must be at the highest point of the motor.
2. Remove the screw from the filling hole.
3. Inject liquid into the motor with the filling syringe until the
liquid runs back out of the filling hole. See fig. 3.
Fig. 5 Measuring the distance from bottom plate to
4. Replace the screw in the filling hole and tighten securely diaphragm
before changing the position of the pump.
Torque: 3.0 Nm. The table below shows the correct distance from the outside of
The submersible pump is now ready for installation. the bottom plate to the diaphragm:

Distance
Motor Dimension
[mm]
Franklin 4", 0.25 - 3 kW
A 8
(fig. 6a)
Franklin 4", 3 - 7.5 kW
B 16
(fig. 6b)
Franklin 6", 4-45 kW
C1 35
(fig. 6c)
Franklin 6", 4-22 kW
45° (fig. 6d)
C2 59
TM03 8129 0507

6a 6b

Fig. 3 Motor position during filling - MS 6000

5.1.3 Grundfos MMS 6, MMS 8000, MMS 10000 and


MMS 12000 motors
1. Place the motor at a 45 ° angle with the top of the motor
6c 6d
upwards. See fig. 4.
2. Unscrew the plug A and place a funnel in the hole.
3. Pour tap water into the motor until the motor liquid inside the
motor starts running out of A.

TM00 6422 3695


Caution Do not use motor liquid as it contains oil.

4. Remove the funnel and refit the plug A.

Before fitting the motor to a pump after a long period Fig. 6 Franklin motors
Caution of storage, lubricate the shaft seal by adding a few
drops of water and turning the shaft. If the distance is not correct, carry out an adjustment as
The submersible pump is now ready for installation. described in section 5.1.5 Franklin motors.

45°
TM03 0265 3605

Fig. 4 Motor position during filling - MMS

5.1.4 Franklin motors from 3 kW and up


Check the level of motor liquid in Franklin 4" and 6" motors by
measuring the distance from the bottom plate to the built-in
rubber diaphragm. The distance can be measured by inserting a

4
5.1.5 Franklin motors 5.2.1 Motors suitable for horizontal installation

English (GB)
Check the level of motor liquid in Franklin 8" motors as follows:
1. Press out the filter in front of the valve at the top of the motor Output power Output power
50 Hz 60 Hz
using a screwdriver. If the filter is slotted, unscrew. Figure 7 Motor
shows the position of the filling valve. [kW] [kW]
2. Press the filling syringe against the valve and inject the liquid.
See fig. 7. If the valve cone is depressed too far, it may be MS All All
damaged thus causing the valve to leak. MMS 6 5.5 - 37 5.5 - 37
3. Remove any air in the motor by pressing the point of the filling MMS 8000 22-110 22-110
syringe lightly against the valve. MMS 10000 75-190 75-190
4. Repeat the process of injecting liquid and releasing air until MMS 12000 147-250 147-250
the liquid starts running out or the diaphragm is in its correct
position (Franklin 4" and 6"). When Franklin 4" motors up to and including 2.2 kW are started
5. Refit the filter. more than 10 times a day, we recommend that you incline the
motor at least 15 ° above the horizontal plane in order to minimise
The submersible pump is now ready for installation.
wearing of the upthrust disc.

During operation, the suction interconnector of the


Caution pump must always be completely submerged in the
liquid. Make sure that the NPSH values are fulfilled.

Warning

TM00 1354 5092


If the pump is used for pumping hot liquids (40 to 60
°C), make sure that persons cannot come into
contact with the pump and the installation, e.g. by
installing a guard.

Fig. 7 Position of filling valve 5.3 Pump/motor diameter


We recommend that you check the borehole with an inside
5.2 Positional requirements calliper to ensure unobstructed passage.

Warning 5.4 Liquid temperatures/cooling


If the pump is to be installed in a position where it is The maximum liquid temperature and the minimum flow velocity
accessible, the coupling must be suitably isolated past the motor appear from the table below.
from human touch. The pump can for instance be
We recommend that you install the motor above the well screen
built into a flow sleeve.
in order to achieve proper motor cooling.
Depending on motor type, the pump can be installed either
vertically or horizontally. A complete list of motor types suitable In cases where the stated flow velocity cannot be
Caution
for horizontal installation is shown in section 5.2.1 Motors suitable achieved, a flow sleeve must be installed.
for horizontal installation. If there is a risk of sediment build-up, such as sand, around the
If the pump is installed horizontally, the discharge port should motor, use a flow sleeve in order to ensure proper cooling of the
never fall below the horizontal plane. See fig. 8. motor.

Allowed
TM00 1355 5092

Not allowed

Fig. 8 Positional requirements

If the pump is installed horizontally, e.g. in a tank, we recommend


that you fit it in a flow sleeve.

5
5.4.1 Maximum liquid temperature The supply voltage, rated maximum current and cos φ appear
from the loose data plate which must be fitted close to the
English (GB)

Out of consideration for the rubber parts in pump and motor, the
liquid temperature must not exceed 40 °C (~ 105 °F). See also installation site.
the table below. The required voltage quality for MS and MMS motors, measured
The pump can operate at liquid temperatures between 40 °C and at the motor terminals, is - 10 %/+ 6 % of the nominal voltage
60 °C (~ 105 °F and 140 °F) provided that all rubber parts are during continuous operation (including variation in the supply
replaced every third year. voltage and losses in cables).
Check also that there is voltage symmetry in the power supply
Installation lines, i.e. same difference of voltage between the individual
phases. See section 11. Checking motor and cable, item 2.
Motor Flow past
Vertical Horizontal
the motor Warning
Grundfos The pump must be earthed.
MS 402 40 °C 40 °C The pump must be connected to an external mains
0.15 m/s switch with a minimum contact gap of
MS 4000 (~ 105 °F) (~ 105 °F)
MS 6000 3 mm in all poles.
Grundfos 60 °C 60 °C If MS motors with a built-in temperature transmitter (Tempcon)
0,15 m/s are not installed together with a MP 204 or similar Grundfos
MS 4000I* (~ 140 °F) (~ 140 °F)
Flow sleeve Flow sleeve motor protection, they must be connected to a 0.47 μF capacitor
Grundfos
1.00 m/s recommended recommended approved for phase-phase operation (IEC 384-14) to meet the EC
MS 6000I*
EMC directive (2004/108/EC). The capacitor must be connected
25 °C 25 °C to the two phases to which the temperature transmitter is
0.15 m/s
Grundfos (~ 77 °F) (~ 77 °F) connected. See fig. 9.
MMS 30 °C 30 °C
0.50 m/s
(~ 86 °F) (~ 86 °F)
Franklin 30 °C 30 °C
0.08 m/s
4" (~ 85 °F) (~ 85 °F)
Franklin 30 °C 30 °C
0.16 m/s
6" and 8" (~ 85 °F) (~ 85 °F)
* At an ambient pressure of minimum 1 bar (1 MPa).

37 kW MMS 6, 110 kW MMS 8000 and 170 kW


MMS 10000: The maximum operational liquid
Note temperature is 5 °C lower than the values stated in
the above table.
190 kW MMS 10000: The temperature is 10 °C lower.

5.5 Pipe connection


If noise may be transmitted to the building through the pipework,
we recommend that you use plastic pipes.

Note We recommend plastic pipes for 4" pumps only.


When using plastic pipes, secure the pump by an unloaded
straining wire.

TM00 7100 0696


Warning
Make sure that the plastic pipes are suitable for the
actual liquid temperature and the pump pressure.

When connecting plastic pipes, use a compression coupling


between the pump and the first pipe section. Fig. 9 Connection of capacitor

6. Electrical connection Colours of the leads

Lead Flat cable Single leads


Warning
During electrical installation, make sure that the 1 = L1 Brown Black
power supply cannot be accidentally switched on. 2 = L2 Black Yellow
3 = L3 Grey Red
Warning
4 = PE Yellow/green Green
The electrical installation should be carried out by an
authorised person in accordance with local The motors are wound for direct-on-line starting or star-delta
regulations. starting, and the starting current is between four and six times the
rated current of the motor.
The run-up time of the pump is only about 0.1 second.
Direct-on-line starting is therefore normally approved by the
power supply company.

6
6.1 Frequency converter operation 6.2 Motor protection

English (GB)
6.1.1 Grundfos motors 6.2.1 Single-phase motors
Three-phase Grundfos motors can be connected to a frequency Single-phase MS 402 motors incorporate a thermal switch and
converter. require no additional motor protection.

If an MS motor with temperature transmitter is Warning


connected to a frequency converter, a fuse When the motor has been thermally switched off, the
incorporated in the transmitter will melt and the motor terminals are still live. When the motor has
Caution
transmitter will be inactive. The transmitter cannot be cooled sufficiently, it will restart automatically.
reactivated. This means that the motor will operate
Single-phase MS 4000 motors must be protected. A protective
like a motor without a temperature transmitter.
device can either be incorporated in a control box or be separate.
If a temperature transmitter is required, Grundfos offers a Pt100 Franklin 4" PSC motors must be connected to a motor-protective
or Pt1000 sensor for the submersible motor.
circuit breaker.
The motor should not run at a frequency higher than 6.2.2 Three-phase motors
the rated frequency (50 or 60 Hz) during frequency
MS motors are available with or without a built-in temperature
converter operation. In connection with pump
transmitter.
Caution operation, never reduce the frequency (and
consequently the speed) to such a level that the The following motors must be protected by a motor-protective
necessary flow of cooling liquid past the motor is no circuit breaker with thermal relay, or a MP 204 and contactor(s):
longer ensured. • motors with a built-in and intact temperature transmitter
To avoid damage to the pump part, the motor must stop when the • motors with or without a defective temperature transmitter
pump flow falls below 0.1 x nominal flow. • motors with or without a Pt100 sensor.
Depending on the frequency converter type, it may expose the MMS motors have no built-in temperature transmitter.
motor to detrimental voltage peaks. The Pt100 and the Pt1000 sensor are available as an accessory.

Warning 6.2.3 Required settings of motor-protective circuit breaker


MS 402 motors for supply voltages up to and For cold motors, the tripping time of the motor-protective circuit
including 440 V (see motor nameplate) must be breaker must be less than 10 seconds at 5 times the rated
protected against voltage peaks higher than maximum current of the motor. During normal operating
650 V (peak value) between the supply terminals. conditions the motor must be running at full speed in less than
3 seconds.
We recommend that you protect other motors against voltage
peaks higher than 850 V. If this requirement is not met, the motor warranty will
Caution
The above disturbance can be abated by installing an RC filter be invalidated.
between the frequency converter and the motor. In order to ensure optimum motor protection, the motor-protective
Possible increased acoustic noise from the motor can be abated circuit breaker should be set as follows:
by installing an LC filter which will also eliminate voltage peaks 1. Set the motor-protective circuit breaker to the rated maximum
from the frequency converter. current of the motor.
We recommend that you install an LC filter when using a 2. Start the pump and let it run for half an hour at normal
frequency converter. See section 6.7.6 Frequency converter performance.
operation.
3. Slowly grade down the scale indicator until the motor trip point
For further details, contact your frequency converter supplier or is reached.
Grundfos.
4. Increase the setting by 5 %.
6.1.2 Other motor makes than Grundfos The highest permissible setting is the rated maximum current of
Contact Grundfos or the motor manufacturer. the motor.
For motors wound for star-delta starting, the motor-protective
circuit breaker should be set as above, but the maximum setting
should be rated maximum current x 0.58.
The highest permissible startup time for star-delta starting or
autotransformer starting is 2 seconds.

7
6.3 Lightning protection The sizing tool provides an accurate calculation of the voltage
drop at a given cross-section on the basis of the following
English (GB)

The installation can be fitted with a special overvoltage protective


parameters:
device to protect the motor from voltage surges in the power
supply lines when lightning strikes somewhere in the area. • cable length
See fig. 10. • operating voltage
• full-load current
L1
L2 L • power factor
L3 N
PE PE
• ambient temperature.
You can calculate the voltage drop both for direct-on-line and
star-delta starting.
In order to minimise operating losses, the cable cross-section

TM00 1357 3605


825045 825017 may be increased. This is only cost-efficient if the borehole
provides the necessary space, and if the operating time of the
pump is long. The cable sizing tool also provides a power loss
Three-phase Single-phase calculator that shows the potential savings of an increased
cross-section.
Fig. 10 Fitting an overvoltage protective device
As an alternative to the cable sizing tool, select the cross-section
The overvoltage protective device will not, however, protect the on the basis of the current values of the given cables.
motor against a direct stroke of lightning. The cross-section of the submersible drop cable must be large
The overvoltage protective device should be connected to the enough to meet the voltage quality requirements specified in
installation as close as possible to the motor and always in section 6. Electrical connection.
accordance with local regulations. Ask Grundfos for lightning Determine the voltage drop for the cross-section of the
protective devices. submersible drop cable by means of the diagrams on pages 17 to
MS 402 motors, however, require no further lightning protection 20.
as they are highly insulated. Use the following formula:
A special cable termination kit with a built-in overvoltage I = Rated maximum current of the motor.
protective device is available for Grundfos 4" motors For star-delta starting, I = rated maximum current of the motor x
(product No 799911 or 799912). 0.58.
6.4 Cable sizing Lx = Length of cable converted to a voltage drop of 1 % of the
nominal voltage.
Submersible motor cables are dimensioned for
Caution
length of drop cable
submersion in liquid, and will not necessarily have Lx =
sufficient cross-section to be in free air. permissible voltage drop in %
Make sure that the submersible drop cable can withstand q = Cross-section of submersible drop cable.
permanent submersion in the actual liquid and at the actual Draw a straight line between the actual I-value and the Lx-value.
temperature. Where the line intersects the q-axis, select the cross-section that
The cross-section (q) of the cable must meet the following lies right above the intersection.
requirements: The diagrams are made on the basis of the formulas:
The submersible drop cable must be sized to the rated maximum
Single-phase submersible motor
current (In) of the motor.
The cross-section must be sufficient to make a voltage drop over U × ΔU
L=
the cable acceptable.   
I × 2 × 100 ×  cos   --q- + sin   XI
Grundfos supplies submersible drop cables for a wide range of
installations. For correct cable sizing, Grundfos offers a cable Three-phase submersible motor
sizing tool on the USB stick supplied with the motor.
U × ΔU
L=
  
I × 1.73 × 100 ×  cos   --q- + sin   XI

L = Length of submersible drop cable [m]


U = Rated voltage [V]
ΔU = Voltage drop [%]
I = Rated maximum current of the motor [A]
cos φ = 0.9
ρ = Specific resistance: 0.02 [Ωmm2/m]
q = Cross-section of submersible drop cable [mm2]
sin φ = 0.436
TM05 8770 2613

Xl = Inductive resistance: 0.078 x 10-3 [Ω/m].

Fig. 11 Cable sizing tool

8
6.5 Control of single-phase MS 402 motors MS 402 PSC motors incorporate motor protection and should be
connected to the mains as shown in fig. 13.

English (GB)
Warning
The single-phase MS 402 motor incorporates motor
protection which cuts out the motor in case of
excessive winding temperatures while the motor is
still supplied with voltage. Allow for this, when the
motor forms part of a control system.
If a compressor is included in a control system together with an
ochre filter, the compressor will run continuously once the motor
protection has cut out the motor, unless other special precautions

Yellow/green
have been taken.

Brown

Black
6.6 Connection of single-phase motors

Grey
6.6.1 2-wire motors

TM00 1359 5092


MS 402 2-wire motors incorporate motor protection and a starter
device and can therefore be connected direct to the mains.
See fig. 12.

Fig. 13 PSC motors

See www.franklin-electric.com and fig. 14.

L N
Yellow/green

Black

Black

TM00 1358 5092

Yellow/green
C

Brown
Black

Grey

TM00 1361 1200


Fig. 12 2-wire motors

6.6.2 PSC motors M


1
The PSC motors are connected to the mains via a run capacitor
which should be sized for continuous operation.
Fig. 14 Franklin motors
Select the correct capacitor size from the table below:
6.6.3 3-wire motors
Motor Capacitor MS 4000 3-wire motors must be connected to the mains via a
[kW] [μF] 400 V, 50 Hz Grundfos SA-SPM 5 (60 Hz), 7 or 8 (50 Hz) control box
0.25 12.5 incorporating motor protection.
0.37 16 MS 402 3-wire motors incorporate motor protection and should be
connected to the mains via a Grundfos control box SA-SPM 2, 3
0.55 20
or 5 (60 Hz), 7 or 8 (50 Hz) without motor protection.
0.75 30
1.10 40
1.50 50
2.20 75

9
6.7 Connection of three-phase motors 6.7.3 Grundfos motors - star-delta starting
English (GB)

Three-phase motors must be protected. The connection of Grundfos motors wound for star-delta starting
See section 6.2.2 Three-phase motors. appears from the table below and fig. 16.
For electrical connection via the MP 204, see the separate
installation and operating instructions for this unit. Connection Grundfos 6" motors
When a conventional motor-protective circuit breaker is being PE Yellow/green
used, the electrical connection should be carried out as described U1 Brown
below.
V1 Black
6.7.1 Checking the direction of rotation
W1 Grey
The pump must not be started until the suction W2 Brown
Caution interconnector has been completely submerged in U2 Black
the liquid.
V2 Grey
When the pump has been connected to the power supply, check
the direction of rotation: Check the direction of rotation as described in section
1. Start the pump and measure quantity of water and head. 6.7.1 Checking the direction of rotation.
2. Stop the pump and interchange two phases. PE L1 L2 L3
3. Start the pump and measure quantity of water and head.
4. Stop the pump.
5. Compare the two results. The connection giving the larger
quantity of water and the higher head is the correct one.
6.7.2 Grundfos motors - direct-on-line starting
The connection of Grundfos motors wound for direct-on-line
starting appears from the table below and fig. 15. W2 U2 V2

TM03 2100 3705


PE U1 V1 W1
Cable/connection
Mains
Grundfos 4" and 6" motors
M
3
PE PE (yellow/green)
L1 U (brown) Fig. 16 Grundfos motors wound for star-delta starting
L2 V (black)
If direct-on-line starting is required, the motors should be
L3 W (grey) connected as shown in fig. 17.
Check the direction of rotation as described in section
PE L1 L2 L3
6.7.1 Checking the direction of rotation.

PE L1 L2 L3

W2 U2 V2

TM03 2101 3705


PE U1 V1 W1

PE U V W M
TM03 2099 3705

3
M Fig. 17 Grundfos motors wound for star-delta starting -
3 direct-on-line starting

Fig. 15 Grundfos motors - direct-on-line starting

10
6.7.4 Connection in the case of unidentified cable 7. Installation

English (GB)
marking/connection (Franklin motors)
We recommend that you first fit a 50 cm long pipe to the pump to
If you do not know where the individual leads are to be connected facilitate handling of the pump during installation.
to the mains in order to ensure the correct direction of rotation,
proceed as follows: Lift the pump to vertical position before removing it
Caution
from the wooden box.
Motors wound for direct-on-line starting
Connect the pump to the mains as is expected to be right.
Then check the direction of rotation as described in section
6.7.1 Checking the direction of rotation.
Motors wound for star-delta starting
Determine the windings of the motor by means of an ohmmeter
and name the lead sets for the individual windings accordingly:
U1-U2, V1-V2, W1-W2. See fig. 18.

TM05 1617 3311


Fig. 19 Lifting the pump into vertical position

TM00 1367 5092 7.1 Fitting the motor to the pump


When the pump part and the motor are supplied as separate units
(long pumps), fit the motor to the pump as follows:
1. Use pipe clamps when handling the motor.
Fig. 18 Unidentified cable marking/connection - motors wound
2. Place the motor in vertical position at the borehole seal.
for star-delta starting
See fig. 20.
If star-delta starting is required, connect the leads as shown in
fig. 16.
If direct-on-line starting is required, connect the leads as shown
in fig. 17.
Then check the direction of rotation as described in section
6.7.1 Checking the direction of rotation.
6.7.5 Soft starter
We only recommend the use of soft starters which control the
voltage on all three phases and which are provided with a bypass
switch.
Ramp times: Maximum 3 seconds.
For further details, contact your soft starter supplier or Grundfos.

TM00 5259 2402


6.7.6 Frequency converter operation
Three-phase MS motors can be connected to a frequency
converter.

To enable the monitoring of the motor temperature,


Note we recommend that you install a Pt100/Pt1000 Fig. 20 Motor in vertical position
sensor together with a PR5714 or CU 220 (50 Hz).
Permissible frequency ranges: 30-50 Hz and 30-60 Hz.
Ramp times: Maximum 3 seconds for start and stop.
Depending on the type, the frequency converter may cause
increased acoustic noise from the motor. Furthermore, it may
expose the motor to detrimental voltage peaks. This can be
abated by installing an LC filter between the frequency converter
and the motor.
For further details, contact your frequency converter supplier or
Grundfos.

11
3. Lift the pump part by means of pipe clamps fitted to the 7.3 Connecting the submersible drop cable
extension pipe. See fig. 21.
English (GB)

7.3.1 Grundfos motors


Before connecting the submersible drop cable to the motor, make
sure that the cable socket is clean and dry.
To facilitate the connection of the cable, lubricate the rubber parts
of the cable plug with non-conducting silicone paste.
Tighten the screws holding the cable to these torques [Nm]:
MS 402: 2.0
MS 4000: 3.0
MS 6000: 4.5
MMS 6: 20
MMS 8000: 18
MMS 10000: 18
MMS 12000: 15

7.4 Riser pipe


If a tool, e.g. a chain pipe wrench, is used when the riser pipe is
fitted to the pump, the pump must only be gripped by the pump

TM02 5263 2502


discharge chamber.
The threaded joints on the riser pipe must all be well cut and fit
together to ensure that they do not work loose when subjected to
torque reaction caused by the starting and stopping of the pump.

Fig. 21 Lifting the pump into position The thread on the first section of the riser pipe which is to be
screwed into the pump should not be longer than the threads in
4. Place the pump part on top of the motor. the pump.
5. Fit and tighten the nuts. See table below. If noise may be transmitted to the building through the pipework,
we recommend that you use plastic pipes.
Make sure that the coupling between the pump and
Caution
motor engages properly. Note We recommend plastic pipes for 4" pumps only.
The bolts and nuts securing the straps to the pump must be When plastic pipes are used, secure the pump by an unloaded
cross-tightened to the following torques: straining wire to be fastened to the discharge chamber of the
pump. See fig. 22.
Torque
Bolt/nut
[Nm]
M8 18
M10 35
M12 45
M16 120
SP 215, 50 Hz, with more than 8 stages
150

TM00 1368 2298


SP 215, 60 Hz, with more than 5 stages

When fitting the motor to the pump part, cross-tighten the nuts to
the following torques:

Torque Fig. 22 Fixing the straining wire


Staybolt diameter
[Nm]
When connecting plastic pipes, use a compression coupling
5/16 UNF 18
between the pump and the first pipe section.
1/2 UNF 50
Where flanged pipes are used, the flanges should be slotted to
M8 18 take the submersible drop cable and a water indicator hose, if
M12 70 fitted.
M16 150 7.5 Maximum installation depth below water level [m]
M20 280 Grundfos MS 402: 150
Grundfos MS 4000: 600
Make sure that the pump chambers are aligned when
Caution Grundfos MS 6000: 600
assembly has been completed.
Grundfos MMS: 600
7.2 Removing and fitting the cable guard Franklin motors: 350
If the cable guard is screwed on to the pump, it should be
removed and fitted by means of screws.

Make sure that the pump chambers are aligned when


Caution
the cable guard has been fitted.

12
7.6 Cable clips 8. Startup and operation

English (GB)
Fit cable clips every 3 metres to fix the submersible drop cable
and the straining wire, if fitted, to the riser pipe of the pump. 8.1 Startup
Grundfos supplies cable clip sets on request. When the pump has been connected correctly and it is
submerged in the liquid to be pumped, it should be started with
1. Cut off the rubber band so that the piece with no slit becomes
the discharge valve closed off to approximately 1/3 of its
as long as possible.
maximum volume of water.
2. Insert a button in the first slit.
Check the direction of rotation as described in section
3. Position the wire alongside the submersible drop cable as 6.7.1 Checking the direction of rotation.
shown in fig. 23.
If there are impurities in the water, open the valve gradually as
the water becomes clearer. Do not stop the pump until the water
is completely clean, as otherwise the pump parts and the
non-return valve may become blocked.
As the valve is being opened, check the drawdown of the water
level to ensure that the pump always remains submerged.
The dynamic water level should always be above the suction
interconnector of the pump. See section 5.2 Positional
requirements and fig. 24.

TM00 1369 5092 L3


L2

Fig. 23 Fitting the cable clips


L4
4. Wind the band once around the wire and the cable. Then wind
it tightly at least twice around the pipe, wire and the cable.
5. Push the slit over the button and cut off the band. L5
Where large cable cross-sections are used, it will be necessary to
wind the band several times.
L1
Where plastic pipes are used, some slackness must be left
between each cable clip as plastic pipes expand when loaded.
When flanged pipes are used, the cable clips should be fitted
above and below each joint.

7.7 Lowering the pump


We recommend that you check the borehole by means of an

TM00 1041 3695


inside calliper before lowering the pump to ensure unobstructed
passage.
Lower the pump carefully into the borehole, taking care not to
damage the motor cable and the submersible drop cable.
Fig. 24 Comparison of various water levels
Do not lower or lift the pump by means of the motor
Caution
cable. L1: Minimum installation depth below dynamic water level.
We recommend minimum 1 metre.
7.8 Installation depth
L2: Depth to dynamic water level.
The dynamic water level should always be above the suction
L3: Depth to static water level.
interconnector of the pump. See section 5.2 Positional
requirements and fig. 24. L4: Drawdown. This is the difference between the dynamic and
the static water levels.
Minimum inlet pressure is indicated in the NPSH curve for the
pump. The minimum safety margin should be 1 metre head. L5: Installation depth.
We recommend that you install the pump so that the motor part is If the pump can pump more than yielded by the well, we
above the well screen in order to ensure optimum cooling. recommend that you install the Grundfos MP 204 motor protector
See section 5.4 Liquid temperatures/cooling. or some other type of dry-running protection.
When the pump has been installed to the required depth, the If no water level electrodes or level switches are installed, the
installation should be finished by means of a borehole seal. water level may be drawn down to the suction interconnector of
the pump and the pump will then draw in air.
Slacken the straining wire so that it becomes unloaded and lock it
to the borehole seal by means of wire locks. Long time of operation with water containing air may
Caution damage the pump and cause insufficient cooling of
For pumps fitted with plastic pipes, the expansion of
the motor.
the pipes when loaded should be taken into
Note
consideration, when deciding on the installation
depth of the pump.

13
8.2 Operation
English (GB)

8.2.1 Minimum flow rate


To ensure the necessary cooling of the motor, the pump flow rate
should never be set so low that the cooling requirements in
section 5.4 Liquid temperatures/cooling cannot be met.
8.2.2 Frequency of starts and stops

Motor type Number of starts

• Minimum 1 per year is


recommended.
MS 402
• Maximum 100 per hour.
• Maximum 300 per day.
• Minimum 1 per year is
recommended.
MS 4000
• Maximum 100 per hour.
• Maximum 300 per day.
• Minimum 1 per year is
recommended.
MS 6000
• Maximum 30 per hour.
• Maximum 300 per day.
• Minimum 1 per year is
recommended.
PVC windings
• Maximum 3 per hour.
• Maximum 40 per day.
MMS6
• Minimum 1 per year is
recommended.
PE/PA windings
• Maximum 10 per hour.
• Maximum 70 per day.
• Minimum 1 per year is
recommended.
PVC windings
• Maximum 3 per hour.
• Maximum 30 per day.
MMS 8000
• Minimum 1 per year is
recommended.
PE/PA windings
• Maximum 8 per hour.
• Maximum 60 per day.
• Minimum 1 per year is
recommended.
PVC windings
• Maximum 2 per hour.
• Maximum 20 per day.
MMS 10000
• Minimum 1 per year is
recommended.
PE/PA windings
• Maximum 6 per hour.
• Maximum 50 per day.
• Minimum 1 per year is
recommended.
PVC windings
• Maximum 2 per hour.
• Maximum 15 per day.
MMS 12000
• Minimum 1 per year is
recommended.
PE/PA windings
• Maximum 5 per hour.
• Maximum 40 per day.

9. Maintenance and service


All pumps are easy to service.
Service kits and service tools are available from Grundfos.
The pumps can be serviced at a Grundfos service centre.

Warning
If a pump has been used for a liquid which is
injurious to health or toxic, the pump will be classified
as contaminated.
If Grundfos is requested to service the pump, Grundfos must be
contacted with details about the pumped liquid, etc. before the
pump is returned for service. Otherwise Grundfos can refuse to
accept the pump for service.
Possible costs of returning the pump are paid by the customer.

14
10. Fault finding

English (GB)
Fault Cause Remedy
1. The pump does not run. a) The fuses are blown. Replace the blown fuses. If the new ones blow too,
check the electric installation and the submersible drop
cable.
b) The ELCB or the voltage-operated ELCB
Cut in the circuit breaker.
has tripped.
c) No power supply. Contact the power supply company.
d) The motor-protective circuit breaker has Reset the motor-protective circuit breaker
tripped. (automatically or possibly manually).
Check the voltage if it trips again. If the voltage is okay,
see items 1e to 1h.
e) The motor-protective circuit
Replace the motor-protective circuit breaker/contactor.
breaker/contactor is defective.
f) Starter device is defective. Repair or replace the starter device.
g) The control circuit has been interrupted or is
Check the electric installation.
defective.
h) The dry-running protection has cut off the
Check the water level. If it is okay, check the water
power supply to the pump due to low water
level electrodes/level switch.
level.
i) The pump/submersible drop cable is
Repair or replace the pump/cable.
defective.
2. The pump runs but gives a) The discharge valve is closed. Open the valve.
no water. b) No water or too low water level in borehole. See item 3a.
c) The non-return valve is stuck in closed
Pull out the pump and clean or replace the valve.
position.
d) The suction strainer is blocked. Pull out the pump and clean the strainer.
e) The pump is defective. Repair or replace the pump.
3. The pump runs at a) The drawdown is larger than anticipated. Increase the installation depth of the pump, throttle the
reduced performance. pump or install a pump with a smaller performance.
b) Wrong direction of rotation. See section 6.7.1 Checking the direction of rotation.
c) The valves in the discharge pipe are partly
Clean or replace the valves.
closed/blocked.
d) The discharge pipe is partly blocked by
Clean or replace the pipe.
impurities (ochre).
e) The non-return valve of the pump is partly
Pull out the pump and clean or replace the valve.
blocked.
f) The pump and the riser pipe are partly Pull out the pump and clean or replace it.
blocked by impurities (ochre). Clean the pipes.
g) The pump is defective. Repair or replace the pump.
h) Leakage in the pipework. Check and repair the pipework.
i) The riser pipe is defective. Replace the pipe.
4. Frequent starts and a) The differential of the pressure switch Increase the differential. The stop pressure must not
stops. between the start and stop pressures is too exceed the operating pressure of the pressure tank,
small. and the start pressure should be high enough to
ensure sufficient water supply.
b) The water level electrodes or level switches Adjust the intervals of the electrodes/level switches to
in the reservoir have not been installed ensure suitable time between the cutting-in and
correctly. cutting-out of the pump. See installation and operating
instructions for the electrodes/level switches. If the
intervals between stop/start cannot be changed via the
automatics, the pump performance may be reduced by
throttling the discharge valve.
c) The non-return valve is leaking or stuck
Pull out the pump and clean or replace the valve.
half-open.
d) The tank precharge pressure is too small. Adjust the tank precharge pressure in accordance with
its installation and operating instructions.
e) The tank is too small. Increase the capacity of the tank by replacing or
supplementing with another tank.
f) The diaphragm of the tank is defective. Check the diaphragm tank.

15
11. Checking motor and cable
English (GB)

1. Supply voltage

Measure the voltage between the phases


by means of a voltmeter. The voltage should, when the motor is loaded, be within the
On single-phase motors, measure range specified in section 6. Electrical connection.
between phase and neutral or between The motor may burn if there are larger variations in voltage.
two phases, depending on the type of Large variations in voltage indicate poor power supply, and

TM00 1371 5092


supply. Connect the voltmeter to the the pump should be stopped until the defect has been
terminals in the motor-protective circuit remedied.
breaker.

2. Current consumption On three-phase motors, the difference between the current in


the phase with the highest consumption and the current in the
phase with the lowest consumption should not exceed 5 %.
If so, or if the current exceeds the rated current, there are the
following possible faults:
• The contacts of the motor-protective circuit breaker are
burnt.
Measure the amps of each phase while Replace the contacts or the control box for single-phase
the pump is operating at a constant operation.
discharge head (if possible, at the
• Poor connection in leads, possibly in the cable joint.
performance where the motor is most
See item 3.
heavily loaded). For maximum operating
• Too high or too low supply voltage. See item 1.
current, see nameplate.
• The motor windings are short-circuited or partly disjointed.
See item 3.
• Damaged pump is causing the motor to be overloaded.
TM00 1372 5092

Pull out the pump for overhaul.


• The resistance value of the motor windings deviates too
much (three-phase). Move the phases in phase order to a
more uniform load. If this does not help, see item 3.
Items 3 and 4: Measurement is not necessary when the supply voltage and the current consumption are normal.
3. Winding resistance

For three-phase motors, the deviation between the highest


Disconnect the submersible drop cable and the lowest value should not exceed 10 %. If the deviation
from the motor-protective circuit breaker. is higher, pull out the pump. Measure motor, motor cable and
Measure the winding resistance between drop cable separately, and repair or replace defective parts.
TM00 1373 5092

the leads of the drop cable. Note: The operating winding of single-phase 3-wire motors
will assume the lowest resistance value.

4. Insulation resistance

Disconnect the submersible drop cable


from the motor-protective circuit breaker. If the insulation resistance is less than 0.5 MΩ, the pump
Measure the insulation resistance from should be pulled out for motor or cable repair.
TM00 1374 5092

each phase to earth (frame). Make sure Local regulations may specify other values for the insulation
that the earth connection was made resistance.
carefully.

12. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.

Subject to alterations.

16
Appendix 1

Appendix
TM00 1346 5092
U = 3 x 400 V
Example: I = 40 A
U = 3 x 400 V U = 2
I = 40 A L = 140 m %
L = 140 m
U = 2%

140- = 70 m = q  25 mm2
L - = ---------
Lx = -------
U 2%

17
Appendix

TM00 1345 5092


U = 3 x 380 V
Example: I = 10 A
U = 3 x 380 V U = 2
I = 10 A L = 120 m %
L = 120 m
U = 2%

L - = ---------
Lx = ------- 120- = 60 m = q  6 mm2
U 2%

18
Appendix
TM00 1348 5092
U = 3 x 220 V
Example: I=5A
U = 3 x 220 V U = 3
I = 5A L = 105 m %
L = 105 m
U = 3%

105
L - = ---------
Lx = ------- - = 35 m = q  2,5 mm2
U 3%

19
Appendix

TM00 1347 5092


U = 3 x 415 V
Example: I = 100 A
U = 3 x 415 V U = 3
I = 100 A L = 150 m %
L = 150 m
U = 3%

150
L - = ---------
Lx = ------- - = 50 m = q  50 mm2
U 3%

20
Appendix 1

Appendix
SP1 - SP 2 - SP 3 - SP 5

Fig. 1 Fig. 2 Fig. 3

TM00 1323 5092


Fig. 1 Fig. 2 Fig. 3

SP 7 - SP 9 - SP 11 - SP 14 - SP 17 - SP 30 - SP 46 - SP 60

Fig. 1 Fig. 2
TM06 0693 0814

Fig. 1 Fig. 2

21
Appendix

SP 77 - SP 95 - SP 125 - SP 160 - SP 215

Fig. 1 Fig. 2 Fig. 3

TM00 1326 5092


Fig. 1 Fig. 2 Fig. 3

22
Argentina Finland Malaysia Spain

Grundfos companies
Bombas GRUNDFOS de Argentina S.A. OY GRUNDFOS Pumput AB GRUNDFOS Pumps Sdn. Bhd. Bombas GRUNDFOS España S.A.
Ruta Panamericana km. 37.500 Centro Trukkikuja 1 7 Jalan Peguam U1/25 Camino de la Fuentecilla, s/n
Industrial Garin FI-01360 Vantaa Glenmarie Industrial Park E-28110 Algete (Madrid)
1619 Garín Pcia. de B.A. Phone: +358-(0) 207 889 500 40150 Shah Alam Tel.: +34-91-848 8800
Phone: +54-3327 414 444 Telefax: +358-(0) 207 889 550 Selangor Telefax: +34-91-628 0465
Telefax: +54-3327 45 3190 Phone: +60-3-5569 2922
France Telefax: +60-3-5569 2866 Sweden
Australia Pompes GRUNDFOS Distribution S.A. GRUNDFOS AB
GRUNDFOS Pumps Pty. Ltd. Parc d’Activités de Chesnes Mexico Box 333 (Lunnagårdsgatan 6)
P.O. Box 2040 57, rue de Malacombe Bombas GRUNDFOS de México S.A. de 431 24 Mölndal
Regency Park F-38290 St. Quentin Fallavier (Lyon) C.V. Tel.: +46 31 332 23 000
South Australia 5942 Tél.: +33-4 74 82 15 15 Boulevard TLC No. 15 Telefax: +46 31 331 94 60
Phone: +61-8-8461-4611 Télécopie: +33-4 74 94 10 51 Parque Industrial Stiva Aeropuerto
Telefax: +61-8-8340 0155 Apodaca, N.L. 66600 Switzerland
Germany Phone: +52-81-8144 4000 GRUNDFOS Pumpen AG
Austria GRUNDFOS GMBH Telefax: +52-81-8144 4010 Bruggacherstrasse 10
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Schlüterstr. 33 CH-8117 Fällanden/ZH
Grundfosstraße 2 40699 Erkrath Netherlands Tel.: +41-44-806 8111
A-5082 Grödig/Salzburg Tel.: +49-(0) 211 929 69-0 GRUNDFOS Netherlands Telefax: +41-44-806 8115
Tel.: +43-6246-883-0 Telefax: +49-(0) 211 929 69-3799 Veluwezoom 35
Telefax: +43-6246-883-30 e-mail: [email protected] 1326 AE Almere Taiwan
Service in Deutschland: Postbus 22015 GRUNDFOS Pumps (Taiwan) Ltd.
Belgium e-mail: [email protected] 1302 CA ALMERE 7 Floor, 219 Min-Chuan Road
N.V. GRUNDFOS Bellux S.A. Tel.: +31-88-478 6336 Taichung, Taiwan, R.O.C.
Boomsesteenweg 81-83 Greece Telefax: +31-88-478 6332 Phone: +886-4-2305 0868
B-2630 Aartselaar GRUNDFOS Hellas A.E.B.E. E-mail: [email protected] Telefax: +886-4-2305 0878
Tél.: +32-3-870 7300 20th km. Athinon-Markopoulou Av.
Télécopie: +32-3-870 7301 P.O. Box 71 New Zealand Thailand
GR-19002 Peania GRUNDFOS Pumps NZ Ltd. GRUNDFOS (Thailand) Ltd.
Belarus Phone: +0030-210-66 83 400 17 Beatrice Tinsley Crescent 92 Chaloem Phrakiat Rama 9 Road,
Представительство ГРУНДФОС в Telefax: +0030-210-66 46 273 North Harbour Industrial Estate Dokmai, Pravej, Bangkok 10250
Минске Albany, Auckland Phone: +66-2-725 8999
220125, Минск Hong Kong Phone: +64-9-415 3240 Telefax: +66-2-725 8998
ул. Шафарнянская, 11, оф. 56, БЦ GRUNDFOS Pumps (Hong Kong) Ltd. Telefax: +64-9-415 3250
«Порт» Unit 1, Ground floor Turkey
Тел.: +7 (375 17) 286 39 72/73 Siu Wai Industrial Centre Norway GRUNDFOS POMPA San. ve Tic. Ltd. Sti.
Факс: +7 (375 17) 286 39 71 29-33 Wing Hong Street & GRUNDFOS Pumper A/S Gebze Organize Sanayi Bölgesi
E-mail: [email protected] 68 King Lam Street, Cheung Sha Wan Strømsveien 344 Ihsan dede Caddesi,
Kowloon Postboks 235, Leirdal 2. yol 200. Sokak No. 204
Bosna and Herzegovina Phone: +852-27861706 / 27861741 N-1011 Oslo 41490 Gebze/ Kocaeli
GRUNDFOS Sarajevo Telefax: +852-27858664 Tlf.: +47-22 90 47 00 Phone: +90 - 262-679 7979
Zmaja od Bosne 7-7A, Telefax: +47-22 32 21 50 Telefax: +90 - 262-679 7905
BH-71000 Sarajevo Hungary E-mail: [email protected]
Phone: +387 33 592 480 GRUNDFOS Hungária Kft. Poland
Telefax: +387 33 590 465 Park u. 8 GRUNDFOS Pompy Sp. z o.o. Ukraine
www.ba.grundfos.com H-2045 Törökbálint, ul. Klonowa 23 Бізнес Центр Європа
e-mail: [email protected] Phone: +36-23 511 110 Baranowo k. Poznania Столичне шосе, 103
Telefax: +36-23 511 111 PL-62-081 Przeźmierowo м. Київ, 03131, Україна
Brazil Tel: (+48-61) 650 13 00 Телефон: (+38 044) 237 04 00
BOMBAS GRUNDFOS DO BRASIL India Fax: (+48-61) 650 13 50 Факс.: (+38 044) 237 04 01
Av. Humberto de Alencar Castelo Branco, GRUNDFOS Pumps India Private Limited E-mail: [email protected]
630 118 Old Mahabalipuram Road Portugal
CEP 09850 - 300 Thoraipakkam Bombas GRUNDFOS Portugal, S.A. United Arab Emirates
São Bernardo do Campo - SP Chennai 600 096 Rua Calvet de Magalhães, 241 GRUNDFOS Gulf Distribution
Phone: +55-11 4393 5533 Phone: +91-44 2496 6800 Apartado 1079 P.O. Box 16768
Telefax: +55-11 4343 5015 P-2770-153 Paço de Arcos Jebel Ali Free Zone
Indonesia Tel.: +351-21-440 76 00 Dubai
Bulgaria PT. GRUNDFOS POMPA Telefax: +351-21-440 76 90 Phone: +971 4 8815 166
Grundfos Bulgaria EOOD Graha Intirub Lt. 2 & 3 Telefax: +971 4 8815 136
Slatina District Jln. Cililitan Besar No.454. Makasar, Romania
Iztochna Tangenta street no. 100 Jakarta Timur GRUNDFOS Pompe România SRL United Kingdom
BG - 1592 Sofia ID-Jakarta 13650 Bd. Biruintei, nr 103 GRUNDFOS Pumps Ltd.
Tel. +359 2 49 22 200 Phone: +62 21-469-51900 Pantelimon county Ilfov Grovebury Road
Fax. +359 2 49 22 201 Telefax: +62 21-460 6910 / 460 6901 Phone: +40 21 200 4100 Leighton Buzzard/Beds. LU7 4TL
email: [email protected] Telefax: +40 21 200 4101 Phone: +44-1525-850000
Ireland E-mail: [email protected] Telefax: +44-1525-850011
Canada GRUNDFOS (Ireland) Ltd.
GRUNDFOS Canada Inc. Unit A, Merrywell Business Park Russia U.S.A.
2941 Brighton Road Ballymount Road Lower ООО Грундфос Россия GRUNDFOS Pumps Corporation
Oakville, Ontario Dublin 12 109544, г. Москва, ул. Школьная, 39-41, 17100 West 118th Terrace
L6H 6C9 Phone: +353-1-4089 800 стр. 1 Olathe, Kansas 66061
Phone: +1-905 829 9533 Telefax: +353-1-4089 830 Тел. (+7) 495 564-88-00 (495) 737-30-00 Phone: +1-913-227-3400
Telefax: +1-905 829 9512 Факс (+7) 495 564 88 11 Telefax: +1-913-227-3500
Italy E-mail [email protected]
China GRUNDFOS Pompe Italia S.r.l. Uzbekistan
GRUNDFOS Pumps (Shanghai) Co. Ltd. Via Gran Sasso 4 Serbia Grundfos Tashkent, Uzbekistan The Repre-
10F The Hub, No. 33 Suhong Road I-20060 Truccazzano (Milano) Grundfos Srbija d.o.o. sentative Office of Grundfos Kazakhstan in
Minhang District Tel.: +39-02-95838112 Omladinskih brigada 90b Uzbekistan
Shanghai 201106 Telefax: +39-02-95309290 / 95838461 11070 Novi Beograd 38a, Oybek street, Tashkent
PRC Phone: +381 11 2258 740 Телефон: (+998) 71 150 3290 / 71 150
Phone: +86 21 612 252 22 Japan Telefax: +381 11 2281 769 3291
Telefax: +86 21 612 253 33 GRUNDFOS Pumps K.K. www.rs.grundfos.com Факс: (+998) 71 150 3292
Gotanda Metalion Bldg., 5F,
Croatia 5-21-15, Higashi-gotanda Singapore Addresses Revised 25.01.2016
GRUNDFOS CROATIA d.o.o. Shiagawa-ku, Tokyo GRUNDFOS (Singapore) Pte. Ltd.
Buzinski prilaz 38, Buzin 141-0022 Japan 25 Jalan Tukang
HR-10010 Zagreb Phone: +81 35 448 1391 Singapore 619264
Phone: +385 1 6595 400 Telefax: +81 35 448 9619 Phone: +65-6681 9688
Telefax: +385 1 6595 499 Telefax: +65-6681 9689
www.hr.grundfos.com Korea
GRUNDFOS Pumps Korea Ltd. Slovakia
Czech Republic 6th Floor, Aju Building 679-5 GRUNDFOS s.r.o.
GRUNDFOS s.r.o. Yeoksam-dong, Kangnam-ku, 135-916 Prievozská 4D
Čajkovského 21 Seoul, Korea 821 09 BRATISLAVA
779 00 Olomouc Phone: +82-2-5317 600 Phona: +421 2 5020 1426
Phone: +420-585-716 111 Telefax: +82-2-5633 725 sk.grundfos.com
Telefax: +420-585-716 299
Latvia Slovenia
Denmark SIA GRUNDFOS Pumps Latvia GRUNDFOS LJUBLJANA, d.o.o.
GRUNDFOS DK A/S Deglava biznesa centrs Leskoškova 9e, 1122 Ljubljana
Martin Bachs Vej 3 Augusta Deglava ielā 60, LV-1035, Rīga, Phone: +386 (0) 1 568 06 10
DK-8850 Bjerringbro Tālr.: + 371 714 9640, 7 149 641 Telefax: +386 (0)1 568 06 19
Tlf.: +45-87 50 50 50 Fakss: + 371 914 9646 E-mail: [email protected]
Telefax: +45-87 50 51 51
E-mail: [email protected] Lithuania South Africa
www.grundfos.com/DK GRUNDFOS Pumps UAB GRUNDFOS (PTY) LTD
Smolensko g. 6 Corner Mountjoy and George Allen Roads
Estonia LT-03201 Vilnius Wilbart Ext. 2
GRUNDFOS Pumps Eesti OÜ Tel: + 370 52 395 430 Bedfordview 2008
Peterburi tee 92G Fax: + 370 52 395 431 Phone: (+27) 11 579 4800
11415 Tallinn Fax: (+27) 11 455 6066
Tel: + 372 606 1690 E-mail: [email protected]
Fax: + 372 606 1691
ECM: 1157986
98074911 0616

www.grundfos.com
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S

You might also like