THE COMPANY
www.fermacell.co.uk FERMACELL SETTING STANDARDS
COMPOSITION
For partitions, this is most apparent when the Slimmer Party Wall
Solutions
Easier to achieve acoustic
ratings
Potential time & cost
saving
properties required of the finished wall call for Moisture Resistant Can be installed before Potential cost saving
envelope complete
more than one type of building board to be used
F60 from a Single Layer, Less sheets required to Potential cost saving
in the construction. Hotel bathrooms, for example, Class 0 Certified achieve desired fire
resistance
often require Moisture Resistance with Acoustic Holds 30 kg on a Screw, Minimal service ply/patress Potential cost saving
Insulation and Fire Protection. Hospitals will add 50Kg with Toggle Bolt or noggings required
Multi Purpose Board Results in rationalisation Saving through quality
Impact Resistance and flexibility in accepting of boards control
wall mounted fittings to this. These criteria Ecologically Certified Important contribution to Comfort
overall health & wellbeing
almost always demand compromise solutions Easily applied Fine Surface No need for plastering Time and co-ordination
involving specialist board selection and composite Treatment (FST) trades or water ingress
into the building
savings
sizes as well as custom formats For factory based modular construction and
timber frame housing applications, boards up
up to 6000 mm x 2540 mm. to 6000 x 2540 mm can be supplied reducing
the need of jointing.
Wallboard thicknesses range from
VENTED AND INSULATED RAINSCREEN
10 mm to 18 mm. This choice gives both
specifier and installer the ability to select Fermacell Gypsum Fibreboard has been tested
independently for use as a backer board in vented
the most appropriate product to speed and insulated rainscreen applications. Testing has
installation and eliminate waste. shown it to be weather resistant, and that it does
not degrade with permanent exposure.
ONE-MAN BOARD
One-man boards are available in 1200 x 800, Discolouration may occur due to moisture
1200 x 1200 and 1500 x 1000 mm. absorption in the board surface. A surface
treatment or other protection is recommended
STANDARD SIzE BOARDS for prolonged exposure prior to the installation
of the cladding system.
Standard size boards in thicknesses from 10 mm
to 18 mm are available. Special sizes to eliminate
Test in accordance with CWCT Standard Test
waste and reduce jointing are available to order.
Methods at a UKAS accredited facility.
TAPERED EDGE BOARDS
FLOORING SYSTEMS
Tapered edge boards are available with 2 or 4
Fermacell Flooring Systems are a dry alternative to
sided Tapered edges for conventional Dry Lining
conventional wet screed systems and are designed
installation techniques.
for upgrading both impact and airborne sound
insulation in floors, or for increasing thermal
H2O BOARDS
performance. They are also particularly suitable for
Powerpanel H2O is a cement bonded light-concrete use with warm water underfloor heating systems
board with a laminated structure, reinforced both and can be used for upgrading the fire protection
sides with an alkali-resistance glass fibre mesh. H2O to the upper surface of a floor construction.
is a water resistant board for wet areas and semi
exposed applications ACCESSORIES
A full range of accessories is available including
HD BOARDS
Fermacell Screws, Jointstik, Joint Filler and Fine
Powerpanel HD Board is a cement bonded glass Surface Treatment ensuring perfect results whatever
fibre board reinforced with an aggregate of aerated the applications.
clay and recycled foamed glass granules. HD Boards
are especially practical because they are light-
weight and easy to use with a high strength. The
water repellent properties of the boards prevents
moisture ingress whilst allowing vapour to be
retained. HD Boards can be used in semi and fully
exposed applications, and as a render carrier board.
Width ± 1 mm
Diagonal difference ≤ 2 mm
Additional data
Moisture content at 65% relative air humidity and 20°C air temperature 1.3%
pH value 7-8
Characteristic strength and stiffness values of Fermacell Thickness of 12.5 MM FERMACELL GIVES
Gypsum Fibreboard in N/mm2 for design calculation according board in mm
CATEGORY 1 RACKING RESISTANCE,
to DIN 1052 (Test report No: z-9.1-434/ETA-03/0050) 10 12.5 15 18 ELIMINATING THE NEED FOR A
Perpendicular to the plane of the board PLYWOOD AND A PLASTERBOARD.
Bending fm,k 4.6 4.3 4.0 3.6
Bending fm,k 4.3 4.2 4.1 4.0 STRENGTH AND STIFFNESS VALUES
Tension ft,k 2.5 2.4 2.4 2.3 FOR EUROCODE 5 STRUCTURAL DESIGN.
Compression fc,k 8.5 8.5 8.5 8.5
TraINING
Our technical support Fermacell is an innovative, high performance product
staff are fully qualified to and installation techniques, whilst not difficult,
are different to standard Dry Lining practice. For
provide detailed technical this reason we recommend that first time users of
solutions – usually at the Fermacell – either specifiers or installers – contact
us for a brief explanation of the main differences in
time of your enquiry. the use of the board. Although this can be usually
accomplished by telephone, we always encourage
Where special detailing or a training, and offer on-site training as required.
non-standard solution is required
RECOMMENDED CONTRACTOR TRAINING
we shall undertake to have given
At Fermacell we have an Recommended Contractor
a preliminary answer within
training scheme. The purpose of the scheme
24 hours. is to enable contractors who want to install
Fermacell to be trained and certified by us in the
Visits either to your premises or site correct installation techniques and practices. The
may be arranged according to your Recommended Contractor training also consists of
requirements. Please call us for further Technical training for the contractors, surveying and
assistance. management staff.
INTERNATIONAL CERTIFICATION
Fermacell is produced to the highest international
quality standards – our reputation depends upon it.
In addition to the accreditation of our factories to ISO
9001 to ensure consistent product quality, Fermacell
itself has been certified by various leading authorities,
as well as international equivalent bodies throughout
Europe.
Fire
The result is the decibel scale, which starts at
sound: its generation, 0 dB – the point at which humans begin to hear
sound – and progresses to 140 dB, the point at
spread, reduction and which a single short noise is likely to irreparably
reception in the spoken damage hearing. The scale enables sound levels
picked up by the ear to be easily and meaningfully
word, music and all other
Acoustics
analysed – even a 3 dB change in sound pressure
forms of audio. level is considered significant.
Impact
• radio and television human ear, which picks up sound from 20 Hz to
• loudspeakers 20,000 Hz, has varying sensitivities to different
frequencies although the optimum range is
An Introduction to Sound
• musical instruments between 1,000 Hz to 4,000 Hz.
• machinery
WHAT IS PITCH?
Unwanted or intrusive sound is normally Pitch is another term for frequency.
Moisture
referred to as “noise”.
EFFECTS OF SOUND REDUCTION VALUES
ON AUDIBILITY
Rw Noise level
Environmental
35 dB Loud conversation can be distinguished
60 dB
and television
Health & Safety
COSHH
walls and floors, builders will need to prove, by reverberation and indoor ambient noise levels
site testing, that the sound insulation meets the are contained in Building Bulletin 93.
requirements of the new regulations.
Moisture
Fire
assessed on a sound reduction index by relating the dropping, in turn, five similar hammer heads that
sound power reduction through the material itself. comprise a standard tapping machine onto a floor
at a rate of ten impacts per second. The resultant
Purpose built laboratories consist of two rooms impact sound is measured in the room below in
with an opening between them, into which a test terms of sound pressure levels.
sample is inserted, thus allowing an evaluation of
Acoustics
partitioning and other insulation structures. The use of a resilient layer during testing is
not allowed.
Similarly, testing on site also involves establishing
the values relating to the sound pressure level SOUND INSULATION DESIGN
reductions between two rooms. Then reverberation
time of the receiving room indicates the By plotting surface mass against “mean” sound
Standardised Level Difference (DnT). insulation, it has been demonstrated by The
Empirical Mass Law that the insulation increases
Impact
While a graph of sound insulation v. frequency by 4 dB to 5 dB with every doubling of the
may be plotted from one third octave band surface mass.
Moisture
figure may be calculated from the sound insulation • The use of a single light gauge metal stud frame,
spectrum. This single figure, when achieved in lined with a layer of board, to produce separation
lab tests, is the Weighted Sound Reduction Index and discontinuity. Even though the air in the
(Rw) and is called the Weighted Standardised Level cavity can act as a “spring” connection between
Difference (DnT,w ) following site tests. the boards, this method gives insulation at least
5 dB greater than the empirical prediction.
Environmental
100
• The use of glass or rock infill to effectively
90 dampen the air spring in the cavity to produce
a 5 dB improvement to the value.
80
• Double layers of wallboard operating as semi
Sound Reduction Index R(dB)
Frequency (Hz)
SEPARATING WALLS, FLOORS AND STAIRS Fermacell Board totally satisfies the requirements of
Part E. It must be remembered that pre-completion
The airborne sound insulation standard for
tests must be carried out on site by an accredited
separating walls, floors and stairs in purpose built
third party test body on 10% of all different types
dwelling houses and flats is 45 dB, expressed as
Fire
of new dwellings.
DnT,w + Ctr. This target, with the addition of Ctr,
will ensure substantial sound insulation. Floors
An alternative to pre-completion testing is the
and stairs should have maximum values of impact
approval of separating (party) walls and floors
sound insulation of 62 dB LnT,w.
for new builds only, as Robust Details (RDs). They
will be deemed to satisfy Part E if they are built
Acoustics
FERMACELL SOLUTIONS
Environmental
* RD solutions must be read in conjunction with information supplied by Robust Details Limited.
Fermacell provides dry floor and ceiling solutions to help meet Part E and Robust Detail requirements.
Health & Safety
COSHH
Building Bulletin 93 associated with Document E The table below shows the performance
deals specifically with acoustics in new school requirements for airborne sound insulation
buildings, covering airborne insulation between between rooms expressed in DnT (tmf,max)W
teaching and learning spaces, and impact sound and impact sound insulation of floors maximum
Fire
insulation of their floors. It does not cover weighted BB93 standardised impact sound
administration and ancillary areas. pressure level LnT (tmf.max)W.
Acoustics
Music performance room / recording studio
Science laboratory
Music classroom
Impact
Assembly hall
Drama studio
Dining room
Gymnasium
Library
Moisture
Primary / secondary classroom 55 45 45 60
Open plan teaching / resource 50 45 45 40 60
Music classroom 55 55 55 55 55 55
Environmental
Lecture room (more than 50) 55 45 50 50 60 60 50 50 55
Library 55 40 45 45 55 55 45 50 45 60
Science laboratory 50 45 45 40 55 55 45 50 45 40 65
Drama studio 55 55 55 50 60 60 55 55 55 50 55 55
Assembly hall 55 55 55 50 55 55 55 55 55 50 55 55 55 60
Gymnasium 55 55 55 50 55 55 55 55 55 50 55 50 55 50 65
Product Use
Dining room 55 55 55 50 55 55 55 55 55 50 55 50 55 50 45 65
Performance requirements for airborne sound building regulations, state that partition walls
insulation set out in the table below, range and floors between rooms must be provided with
from 43 dB Rw to 53 dB Rw depending on the appropriate levels of fire resistance as well as
location of the rooms within the building. acoustic insulation.
Designers seeking to achieve these values should
also consider the potential for eliminating or Robust Fermacell Boards meet the acoustic and
Acoustics
minimising flanking sound transmission (sound fire requirements for walls and floors in hospitals,
that might be transferred through surrounding offering superior strength, resistance to impact
structures, such as plant and mechanical services). damage and pull-out for fixings.
PERFORMANCE REqUIREMENT FOR AIRBORNE SOUND INSULATION BETWEEN ROOMS IN dB(Rw) for HTM56
Impact
Examination rooms
Multi-bed wards
Seminar rooms
Ward pantries
Utility rooms
Day rooms
Nurseries
Offices
Moisture
Consulting room 43
Examination rooms 43 43
Treatment rooms • 53 43
Speech therapy rooms 48 48 • 48
Environmental
Offices 43 43 53 48 48
Seminar rooms 48 43 48 53 43 38
Single-bed wards 43 43 • 48 43 48 43
Multi-bed wards 53 53 48 • 48 43 53 43
Day rooms 53 53 43 • 48 43 53 43 48
Nurseries • • 43 • 53 48 • 48 43 43
Utility rooms • • 43 • 53 48 • 48 43 43 48 43
Ward pantries 48 48 48 53 43 38 48 43 43 48 43 48 38
90 1H31 1S31 –
Fire
30 1H23 or 1H31 1S11 or 1S16 3S11
90 1H31 1S31 –
Acoustics
90 1H32 or 1H31 1S31 –
90 1H32 1S31 –
HTM08-01 has recently been introduced and offers simpler guidance on performance of partitions
within Hospitals. These areas include:
Impact
(1) The performance requirements are shown as on-site figures.
(2) Guidance is given on designing from Laboratory (Rw) performance to on-site performance
Moisture
(4) An additional allowance must be made for the area of the separating element and the volume
of the room.
(5) Fermacell systems can provide simple solutions for all these criteria, Tables 3, 4, 5 and appendix
a should be referenced for design.
Environmental
Product Use
Health & Safety
COSHH
for greater wall heights with different Partition 4.50 m long by 3.0 m high
board configurations, stud profiles and Fermacell
with overall thickness of 100 mm;
comprising 1 layer each side of Severe
centres. This allows Fermacell to provide 1S15 H2O 3m
12.5 mm Powerpanel H2O Board Duty
(4)
a comprehensive range of rated build fixed to 0.6 mm 75 mm x 50 mm
Moisture
heights. This includes soft and hard body steel studs at 600 mm centres
The certificate for soft impact is based on an The resistance to hard impact is determined by a
assessment of the ability of the whole partition drop ball test. A steel ball 63.5 mm in diameter
to withstand a semi static load. A soft impact on weighing 1030 g is released in free fall on to the
Fire
light-weight partitions can result from, for example, face of a 12.5 mm Fermacell Board. The drop ball
the impact of a human body or in the case of panic tests are carried out on 1200 mm wide pieces of
caused by fire as a result of the crowd pressure in board, spanned between two supports at 625 mm.
corridors that line an escape route. The impact points are in the middle of the board
and near the edge of the board.
Acoustics
TYPICAL PARTITION TESTING TYPICAL PARTITION TESTING
Impact
Fermacell Hard Impact Test to DIN 4103
Moisture
Environmental
KEY
(1) Fermacell Board 12.5 mm
(2) C Stud 100 mm x 0.6 mm
(h) (Height of partition) = 3000 mm
(a) Deflection of the partition
(F) Location of force applied with 50 mm diameter ram
Product Use
FIxINGS TO WALLBOARDS
Picture hooks fixed by nails Screw Toggle
Fire
10 mm 15 25 35 20 40
• The loadbearing capability refers to static
(dead) loads only. 12.5 mm 17 27 37 30 50
12.5 + 10 mm 20 30 40 35 60
• For live loads which are subject to increase
(eg washbasins or stair-rails), the maximum 15 mm 18 28 38 30 55
load should be calculated and patresses of 18 mm 20 30 40 35 60
plywood or reinforcing pads of Fermacell 12.5 mm H2O N/A N/A N/A N/A 40
added behind the wall.
2 x 12.5 mm H2O N/A N/A N/A N/A 50
Impact
by 50%. If a stud support separates the fixings, then use the full loadbearing
MAxIMUM WALL LOADING strength shown above.
(2) Safety factor: 2 (Static load with relative humidity of up to 85%).
• With single stud walls a maximum of (3) Depth of cupboard or shelves: max. 350 mm.
(4) Standard toggle bolt with > 4 mm dia. screw.
150 kg/lm is recommended. (The toggle bolt manufacturer’s instruction should be observed.)
Moisture
• For separated stud walls and independent wall The stated load values can be added up, if the fixing centres are ≥ 500 mm.
For lesser fixing centres, 50% of the relevant permissible load per fixing should
linings, a maximum of 40 kg/lm is recommended. be used. The total single loads for walls should not exceed 1.5 kN/m and for
This figure is increased when the studs are braced. free-standing Dry Lining and double studwalls not physically connected to
one another, 0.4 kN/m. The stability of the wall or casing should be verified
as described above according to DIN 4103 Part 1 and BS 5234.
FIxINGS TO CEILINGS
CEILING LOADING
ceilings. Special steel cavity fixings and steel Maximum allowable load in kg (1)
spring fixings can be used. per Fermacell Board thickness in mm (2)
• Smaller loads may be fixed directly with fully Fermacell Board thickness (mm) kg (3)
threaded screws. 10 mm 20
12.5 mm 22
15 mm 23
10 + 10 mm 24
Product Use
12.5 + 12.5 mm 25
12.5 mm H2O 20
Fire
laundries, kitchens and shower rooms and as a
liner for plant rooms. The board also plays a key
confirmed by a series of role lining bathroom pods manufactured off site.**
the most uncompromising
Furthermore, Fermacell Board can make a significant
tests developed specifically
contribution to improved BREEAM ratings of new and
Acoustics
for rainscreen evaluation.* refurbished commercial and residential buildings.
Simulated cascading rain, 600 kpa wind The moisture resistance qualities of Fermacell are
speeds and intense humidity, far in accompanied by a host of additional advantages
excess of normal weather conditions that including: substantial financial benefits (Fermacell
would hit a building in its entire lifetime, can save up to 50% per m² when compared to other
have demonstrated that the 12.5 mm boards); its excellent fire and acoustic properties; its
Fermacell as a backerboard product is ease of fixing, cutting, jointing and general handling;
Impact
ideal for external use. and considerably less remedial problems.
Moisture
trusses used as separating wall frames.
Fermacell’s nominal density is 1,150 ± 50 kg/m² and
its bending strength value after drying at 40°C is ≥5.8
N/mm² with a transverse strength
of ≥0.3 N/mm².
Environmental
Bending, pressure and shearing tensile values
perpendicular to the board surface are
1.2 N/mm², 2.5 N/mm² and 0.6 N/mm² respectively
and bending, pressure and shearing in the board
surface are certified as 1.1 N/mm², 2.0 N/mm² and
0.3 N/mm² respectively. The tension in the board
surface is recorded at 0.5 N/mm².
Product Use
*The tests were conducted in accordance with guidelines set down by the
Centre for Windows and Cladding Technology and embraced air permeability,
static and dynamic watertightness, and wind resistance from both serviceability
and safety points of view.
COSHH
**Tiled Areas - We recommend reducing stud centres to 400mm for tiled areas
to ensure a solid and stable background.
qualities and superb All by products are fed back into the production
resistance to impact cycle and Fermacell have even instigated a
scheme for the collection and recycling of off
and moisture, brings
cuts and waste created on construction sites,
Acoustics
materials, making it a totally The product, and its manufacturing process, have
been awarded the coveted Rosenheim Institute
sustainable product that is ideal of Construction Biology and Ecology Certificate
for walls, ceilings or floors. and the Low Emissions Product Eco Certificate.
Moisture
Ecology Certificate
• eco INSTITUT – Quality Assurance
• WRAP – Recycled Content – Fermacell 91.5%
• LONDON Remade – Green Procurement –
Fermacell 100%
• Greenspec – Material Details
Health & Safety
• GreenGuide –
England
Wales
COSHH
Scotland
Fire
quality finish that eliminates the wet trades such
as plastering.
the case that no matter
what the final use of a eDUCaTION aND healThCare
building, there are common
This sector is probably the most demanding of any
Acoustics
partitioning needs. element of construction today.
Impact
development, partitioning with a
objects. In fact impact resistance is as critical as the
demonstrable pedigree such as Fermacell
acoustic properties of Fermacell.
is no longer an option. It is an essential.
Note: For further guidance please refer to:
EDUCATION
Moisture
www.partnershipsforschools.org.uk
‘Standard Specifications, Design & Guidance:
Partitions In Schools’ Fermacell Referenced as
Gypsum Fibreboard ISBN: 978-1-88478-923-8
HOSPITALS
Environmental
Note: For further guidance on wall requirements
to meet radiation protection, please contact our
Technical Department on +44 (0) 870 6090 306.
Product Use
Health & Safety
COSHH
reTaIl reSIDeNTIal
Loadbearing comes high on the list of essentials The single board solution with fewer layers and less
in retail developments, although an ability to cope insulation than plasterboard is one of the many
with impact is equally as important. An enviable attractions that Fermacell holds for the house builder,
loadbearing performance enables retailers using particularly those operating in the high end of the
Fire
Fermacell to install most of the fixtures and fittings market and self builders seeking the best for their
directly to the Fermacell Board reducing the property. The Fermacell package of superior acoustic
amount of reinforcement. performance, strength, speed, quality, ease of finish,
and moisture resistance have made it a firm favourite
SPOrTS, reCreaTION aND The arTS in this market – and even more so with builders of
timber frame properties seeking a strong breathing
Acoustics
The smooth finish of Fermacell, enhanced by wall construction that eliminates the need for
the use of Fine Surface Treatment and the even plywood as a racking board at the same time.
smoother double sanded version, is ideal for arts
and cultural centres where large, heavy pictures PrISONS aND DeTeNTION CeNTreS
and paintings are hung and regularly rehung in a
quality environment. There is no environment more demanding than
the HM Prison and Magistrates Court facilities.
These needs for strong partitioning are Fermacell provides an accepted solution with a
Impact
accompanied by a requirement for high impact range of historical and current projects throughout
resistance, but probably not quite as high as sports England, Wales & Scotland. Drawing on this expertise
and recreation centres where hard ball sports and Fermacell can provide tailored design and accepted
hefty human impact resistance is paramount. Not systems to suit all requirements demanded by Home
only does Fermacell meet all these criteria – it can Office or HM Prison Services.
be supplied in standard size sheets up to 3 m high
(special longer boards available) making it ideal for
Moisture
installations of this type.
Environmental
developing & designing spaces & services for
temporary exhibitions’ Author: Mike Sixsmith
ISBN: 0728707802 - Fermacell reference section
‘Wall-Lining Material’.
Product Use
Health & Safety
COSHH
COSHH Data Sheets for all Fermacell products that occupational exposure is minimised. When
including accessories are available, please installing Fermacell Boards these include:
contact our Technical Department on
+44 (0) 870 6090 306 or • Ensure good ventilation when cutting Fermacell
email [email protected] • Use dust extractors where possible to minimise
Impact
Fire
Use a dust mask that meets EN 149 specifications.
Skin contact: Flush and wash with water
and soap.
Eye Contact: Rinse eyes immediately with
clean water.
Acoustics
Ingestion: Drink plenty of milk or water.
Control of Substances Hazardous to Health (Coshh) and Health & Safety Information
range of Fermacell products please contact
+44 (0) 870 6090 306.
Impact
should be undertaken in the correct manner
using mechanical handling equipment where
appropriate); cutting and handling of metal
components (the wearing of gloves to avoid cuts
and abrasions is recommended); and the avoidance
of contact between the eyes and liquid products.
Moisture
Please see the diagrams opposite for handling and
storage guidance.
Environmental
moisture; wet boards should be allowed to dry out
completely on a level surface before use. The
stacking of boards on their edges can lead to
deformation of the boards and damage to the
edges. Boards should generally be carried upright
and the use of board lifters is advised when fitting
boards to ceilings.
Introduction 29
Detailed Overview 33
Component Details 34
Installation Overview 39
Performance Details 40
PARTITIONS
www.fermacell.co.uk INTRODUCTION
Partitions
Education with solid masonry with the
Introduction
flexibility and speed of drywall,
Residential
in a construction that is often
Healthcare thinner, quicker and cheaper to
Linings
Recreation
This is largely achievable due to the all
Industrial/Office
round performance of the Fermacell
Boards that provide superior Fire, Acoustic
Prisons
& Ceilings
and Impact performance that eliminates
Floorings
wet trades making practical, technical and
PERFORMANCE RATINGS commercial sense.
Detailed Overview
41 71 MeTal STUD ParTITIONS
Fire Protection
dB dB
Timber Frames
FERMACELL PERFORMANCE
and Impact resistance over drywall construction.
The excellent screw retention properties of Fermacell
Component Details
Impact – Severe duty, able to
means that significantly fewer noggings or plywood
withstand impact from people as
well as objects (door handles etc). is needed for dead load fixtures and fittings; this
also allows junctions to be started from any point.
Acoustics – Greater acoustic
performance often with less layers
than plasterboard constructions TIMBer STUD ParTITIONS
Rainscreens
providing slimmer partitions.
These are more commonly used in domestic
Loadbearing – The composition
Installation Overview
applications. Timber partitions provide versatility
of Fermacell allows up 50 kg per
fixing to be hung from Fermacell and performance including racking strength for
using a toggle bolt and 30 kg from timber framed properties. The ability of Fermacell
a single screw. to be stapled to timber studs means increased
speed of fixing.
Fix & Finish
University of Manchester
is the Fermacell Dry Lining
board.
Components & Accessories
Linings
Partitions
Introduction
Components & Accessories
Linings
& Ceilings
Floorings
Detailed Overview
Fire Protection
Timber Frames
Fermacell recommended contractor Cheshire-based article which has a ‘wow factor’ with a minimalist
Component Details
Total Fire Stopping Systems, worked alongside concept.
the Architect to develop the use of Fermacell for
the scheme. Director Clare Church commented: The Fermacell Board was selected for a number
“Because of the composition of Fermacell we have of reasons including quicker installation and
been able to commence on site 6 months before subsequent Client alterations are easily managed,
the building envelope was watertight and thereby its environmentally friendly properties, 100%
Rainscreens
accelerate the programme. recyclable, water and impact resistance together
with the inherent strength for direct fixing of heavy Installation Overview
We have completed a range of installations, loads i.e. cupboards and shelving without the need
standard partition types 1S21 and 1S31, Shaftwall, for noggings or plywood.”
Security walls and wall linings to a height of
26 metres integrating large slot windows and Fermacell offers a range of systems of varying
link bridges. thicknesses and performances. “The versatility
Fix & Finish
risk of incorrect board selection. Firestopping Systems have given the Client,
Architect and Main Contractor confidence tackling
My colleague Neil Fairhurst managed the Partitions difficult aspects such as the Atrium wall, lining
Wet Areas
& Ceiling packages and it’s great to see a large 26 metre columns and the gable ends.”
project from a bare concrete frame to the finished
aCCeSSOrIeS
COMPONENTS ACCESSORIES
Partitions
Fermacell Board
Introduction
Size
Detailed Overview
5 m2 per kg for filling Tapered edge Nominal 0.6 gauge 50 mm fixing face
Fire Protection
Fermacell Primer/Sealer
Installation Overview
Fermacell Waterproofing
Fermacell Powerpanel H2O Application
12.5 mm thickness. For sealing all splashback areas prior
to tiling.
Partitions
(Fine Surface Treatment) is used as an alternative to plastering.
Refer to finishing section of manual for guidelines on FST,
Introduction
plastering, tiling or wall papering.
Linings
Fermacell screws @ 250 mm c/c
Twin stud construction
DIN standard stud
& Ceilings
Mineral insulation
Floorings
Acoustic strip to all head
and foot track and abutments
Detailed Overview
Fire Protection
Timber grounds to
full stud height and
fill stud profile
Timber Frames
Door header
formed with the
Component Details
track 200mm folded
over and secured to
studs each end
Min. 200 mm
overlap at door
head stud/track
junctions
Rainscreens
Installation Overview
Acoustic isolation
strip to all floor and
Performance Details
wall intersections,
fire rated and
Wet Areas
Fermacell Board should be fixed at max 250 mm centres for partitions applications.
20
≤≤ 20
is expected to exceed 10 mm.
A
There are three sections which must have the same
Min. board
≥ 20
Timber Frames
A
to the Soffit.
2. The distance from the top of the stud to
A
Deflection Head Detail Deflection Head constructions will give a reduction in overall acoustic performance unless special detailing is used.
A
≤ 20
≤ 20
≤≤≤ 20
A
A
A
A
A
overlap 10 mm
≥ 20
≤ 20 ≤A 20 ≤ 20
A = Expansion in mm A A = Expansion in mm
≤≤≤ 20
20
≤ 20
AA
A
20
A
AA
≤ 20
≤≤ 20
≤ 20
20
50 mm wide.
A
A
A
AA
≤ 20≤ 20 ≤
20
≤20
A
≤≤ 20
A
AA
A
A
A
A
Technical Department.
Wet Areas
≤ 20
≤ 20 ≤ 20 ≤ 20
≤ 20 ≤ 20 ≤ 20
A
A
A
A
A
≤≤ 20
AA
A
A
A = Deflection in ≤ 20 mm
Partitions
T-junctions with single or double-layer
boarding, with C stud fixed to Fermacell [1]
Introduction
Board. [2]
[5]
Linings
(8) Staples, galvanised, for fixing Fermacell
in Fermacell
(9) Fermacell Joint Filler
T-junctions with single or double-layer boarding, with Protektor C stud fixed to FERMACELL board.
& Ceilings
Floorings
CORNER & T-JUNCTIONS
Detailed Overview
(2) Insulating material 5) Protektor Header or
Fire Protection
(4) Stud profile [4]
[1] 6) Inner corner profile
(5) Header or footer track [5] [7] [2]
7) FERMACELL screws
(6) Inner corner profile [5] 1) FERMACELL boards 12.5 or 1
A = screws
(7) Fermacell Expansion
3.9 x 30in
mm mm [9]
[5] [9]
[8] 8) Staples,
2) Insulating galvanised,
material
[6]
(8) Staples, galvanised, for fixing Fermacell FERMACELL
3) Edge insulating stripsin FER
in Fermacell 9) FERMACELL
4) Protektor Stud profileJoint F
(9) Fermacell Joint Filler
≤ 20
Timber Frames
[7] 8) Staples, galvanised, for fixing
Component Details
FERMACELL in FERMACELL
≤ 20 ≤ 20 ≤ 20
Rainscreens
[8] [8]
(1) Fermacell Boards 12.5 or 10 mm
FERMACELL separated stud partition,
(2) Insulating material [5] Installation Overview
90-A, (5) Header or footerdouble-layer
track boarding, F 90-A, [6]
(6) Header or footerDeflection
track Head Detail [7] [9] [5]
(7) Fermacell screws 3.9 x 30 mm
(8) Staples, galvanised, for fixing Fermacell
in Fermacell
(9) Fermacell Joint Filler
Fix & Finish
A = Expansion in mm
Performance Details
≤ 20
A
≥ 20
Fermacell stud partition wall, single-layered boarding F 30-A/F 60-A. Expansion joint
The spacing of movement control joints is
Components & Accessories
Fermacell separated stud partition wall, double-layer boarding, F 90-A. Expansion joint
Timber Frames
Component Details
CURVED PARTITIONS
Bending Fermacell
Gypsum Fibreboards
When preparing curved wall and ceiling
structures using standard size 10 mm and
12.5 mm Fermacell Boards, there are three
Rainscreens
REDUCTION JUNCTIONS
Partitions
Wall movement joints and façade ≥ 20
junctions. A A
Introduction
Exterior facades, principally curtain walls,
can be subject through wind loads, causing
pressure and suction movements, and must
be designed accordingly. Ensure that no
structural forces affect the Fermacell Boards
and that the required sound-reduction and
fire resistance characteristics are met.
Linings
F 30-A /F 60-A. Wall movement joint and/or
façade junction with a steel stud and strips
of board.
A= Expansion in mm
& Ceilings
Floorings
REDUCTION JUNCTIONS
Detailed Overview
thickness of the partition must be reduced
Fire Protection
to match the size of the junction section.
To compensate acoustically, a lead sheet
can be fitted in the reduced wall section
on one or both sides.
Timber Frames
Component Details
SKIRTING
Rainscreens
to meet function and design requirements.
• Conventional skirting Installation Overview
• Recessed skirting
• Recessed skirting partition with double-
layer boarding – to maintain the sound
reduction and fire resistance, additional
layers of board material should be built
into the wall cavity.
Fix & Finish
≥25
Wet Areas
12.5 12.5
max.
Fire Protection
Installation method for frames with Protektor reinforcing sub-structure (dimensions in mm) [2]
timber support.
50 kg – 60 kg doors – Timber inserts are
required to the full partition height. An L
Installation Overview
STeel STUDS
Partitions
Ensure the floor is clean Fix the base track to the
and flat; mark out the floor at 600 mm centres
Introduction
line of the partition using suitable fixings.
allowing for the width of Isolating strips must
the Fermacell Boards. be used to ensure the
correct Acoustic and Fire
performance.
Linings
STEP THREE STEP FOUR
& Ceilings
Floorings
fixed, plumb the top should be cut no more
track in to position that 10 mm shorter than
and fix with Fermacell the floor to ceiling height
screws or proprietary and not mechanically
fixings. Fix end studs to fixed. They should be
the substrates ensuring installed facing the same
adequate acoustic direction.
Detailed Overview
insulation at 600 mm
Fire Protection
Door openings should
centres. be marked and the studs
either side of the door
opening fixed.
Installation method for frames with Protektor reinforcin
Timber Frames
Install insulation (if Screw fix the boards as
required) making sure per the fixing sequence
that there is a cavity (7 & 8) at 250 maximum
Component Details
between the insulation centers using Fermacell
and one face of the screws. The vertical
Fermacell Boards. Cut the joints can be “mirrored“
Fermacell Boards 10 mm through the partition
less than the room height when using Fermacell
and install tight to the Jointstik. Do not fix the
ceiling line. boards to the top and
bottom tracks.
Rainscreens
Installation Overview
1.8
1.7
≤ 250 mm
1.5
1.6
7 6 5 4 3 2 1
Wet Areas
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1S15
Components & Accessories
Severe
Linings
31 3 3 75 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
Severe
32 4.5 4.5 100 30 43
Facings 1 layer 12.5 mm Fermacell Board each side
Severe
33 6 5 125 30 43
Facings 1 layer 12.5 mm Fermacell Board each side
& Ceilings
Floorings
Severe
34 7.9 5.5 150 30 43
Facings 1 layer 12.5 mm Fermacell Board each side
1S15/2
Detailed Overview
Severe
Fire Protection
1S16
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
Timber Frames
1 layer 12.5 mm Fermacell Board each side plus 44 4.85 4.5 110 30 46
Facings
1 layer 10 mm Fermacell Board outer side
Component Details
Severe
1 layer 12.5 mm Fermacell Board each side plus 45 6.65 5 135 30 48
Facings
1 layer 10 mm Fermacell Board outer side
Studs 125 mm DIN standard studs @ 600 mm centres Severe
1 layer 12.5 mm Fermacell Board each side plus 46 8.35 5.5 160 30 48
Facings
1 layer 10 mm Fermacell Board outer side
Rainscreens
1S22
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
Installation Overview
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
(With Fire Rating)
Wall Weight
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m m mm mins Rw Grade
1S23
Severe
Linings
1 layer 12.5 mm plus 10 mm Fermacell Board each 67 7.65 5.5 130 60 57
Facings
side plus 1 layer 10 mm Fermacell Board outer side
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm plus 10 mm Fermacell Board each 68 9.7 6.5 155 60 59
Facings
side plus 1 layer 10 mm Fermacell Board outer side
Studs 125 mm DIN standard studs @ 600 mm centres
Severe
& Ceilings
Floorings
1 layer 12.5 mm plus 10 mm Fermacell Board each 69 11.25 7.5 180 60 59
Facings
side plus 1 layer 10 mm Fermacell Board outer side
1S35
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
79 9.35 6.5 140 90 60
Detailed Overview
1 layer 12.5 mm Fermacell Board each side plus
Fire Protection
Facings
2 layers 10 mm Fermacell Board each outer side
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus 80 11.25 7.5 165 90 62
Facings
2 layers 10 mm Fermacell Board each outer side
Studs 125 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus 81 12 8.5 190 90 62
Facings
2 layers 10 mm Fermacell Board each outer side
Timber Frames
Component Details
Rainscreens
Installation Overview
Wet Areas
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1S11
Components & Accessories
Heavy
Facings 1 layer 10 mm Fermacell Board each side 27 4 3 70 30 48
Heavy
Facings 1 layer 10 mm Fermacell Board each side 28 4.55 4.5 95 30 48
Heavy
Facings 1 layer 10 mm Fermacell Board each side 28 6.3 5 120 30 48
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 34 3.7 3 75 30 48
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 34 4.5 4.5 100 30 52
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 35 5.7 5 125 30 52
Component Details
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 37 7.6 5 150 30 54
1S14
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
1S21
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
Performance Details
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
(With Fire Rating)
Wall Weight
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m m mm mins Rw Grade
1S21 (CONTINUED)
Linings
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 35 5 4.5 100 60 54
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 35 6 5 125 60 52
& Ceilings
Floorings
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 35 6 5 125 60 54
Detailed Overview
1S24
Fire Protection
Studs 50 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus 58 4 4 95 60 59
Facings
1 layer 10 mm Fermacell Board each outer side
Insulation 40 mm mineral stone wool density 20 kg/m3
1S25
Timber Frames
Studs 2 x 75 mm DIN standard studs @ 600 mm centres 3.5 3.5
Component Details
Severe
(10)
, (10),
Facings 1 layer 12.5 mm Fermacell Board each side 38 ≥185 60 60
4 (9), 4 (9),
Insulation 70 mm mineral stone wool density 30 kg/m 3
5 (11) 5 (11)
Studs 2 x 75 mm DIN standard studs @ 600 mm centres 3.5 3.5
Severe
(10)
, (10),
Facings 1 layer 12.5 mm Fermacell Board each side 38 ≥185 60 57
5 (9), 5 (9),
Insulation 40 mm mineral stone wool density 45 kg/m 3
6 (11)
6 (11)
Rainscreens
1S29
Studs 50 mm DIN standard studs @ 600 mm centres
Installation Overview
Severe
Facings 46 5 5 110 60 56
1 layer 10 mm Fermacell Board outer side
70 mm mineral stone wool density 30 kg/m3 or
Insulation
60 mm mineral stone wool density 35 kg/m3
Studs 100 mm DIN standard studs @ 600 mm centres
Performance Details
(9) Wall thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and jointed
with an isolation strip (for example a self adhesive insulation strip). No mechanical bracing across studs. (10) Wall thickness, heights and construction properties quoted
are for separated steel stud partitions with U channels and C studs fixed parallel to each other without any jointing between the two separated stud sections. (11) Wall
thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and connected to each
other at <1/3 height with a fillet of board or an off-cut of steel stud.
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1S31
Components & Accessories
Severe
Facings 2 layers 10 mm Fermacell Board each side 57 4.1 4 90 90 52
Severe
Facings 2 layers 10 mm Fermacell Board each side 57 6.4 4 115 90 60
Severe
Facings 2 layers 10 mm Fermacell Board each side 58 8.6 4 140 90 60
1S31
Fire Protection
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 58 4 4 90 90 59
1 layer 10 mm Fermacell Board each outer side
Insulation 50 mm mineral stone wool density 50 kg/m 3
Severe
Facings 2 layers 12.5 mm Fermacell Board each side 64 4 4 100 90 59
Timber Frames
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 58 6.1 5.5 120 90 62
1 layer 10 mm Fermacell Board each outer side
Insulation 60 mm mineral stone wool density 30 kg/m 3
Facings 2 layers 12.5 mm Fermacell Board each side 64 6.5 5.5 125 90 62
Severe
Facings 2 layers 12.5 mm Fermacell Board each side 65 8.95 6.5 150 90 62
120 minute solution Facings 2 layers 12.5 mm Fermacell Board each side 65 8.95 4.5 125 120 62
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
(With Fire Rating)
Wall Weight
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m m mm mins Rw Grade
1S31 (CONTINUED)
Linings
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 59 10.4 7.5 170 90 62
1 layer 10 mm Fermacell Board each outer side
Insulation 60 mm mineral stone wool density 30 kg/m 3
Severe
Facings 2 layers 12.5 mm Fermacell Board each side 65 10.8 7.5 175 90 62
& Ceilings
Floorings
Insulation 50 mm mineral stone wool density 50 kg/m 3
1S31W
75 mm acoustic DIN standard studs
Studs
@ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus
Detailed Overview
Facings 58 4 4 120 90 64
1 layer 10 mm Fermacell Board each outer side
Fire Protection
60 mm mineral stone wool density 50 kg/m or 3
Insulation
60 mm mineral stone wool density 35 kg/m3
75 mm acoustic DIN standard studs
Studs
@ 600 mm centres
Severe
Facings 2 layers 12.5 mm Fermacell Board each side 64 4 4 125 90 64
60 mm mineral stone wool density 50 kg/m3 or
Insulation
60 mm mineral stone wool density 35 kg/m3
Timber Frames
100 mm acoustic DIN standard studs
Studs
@ 600 mm centres
Component Details
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 59 4.5 4.5 145 90 64
1 layer 10 mm Fermacell Board each outer side
60 mm mineral stone wool density 50 kg/m or 3
Insulation
60 mm mineral stone wool density 35 kg/m3
100 mm acoustic DIN standard studs
Studs
@ 600 mm centres
Severe
Facings 2 layers 12.5 mm Fermacell Board each side 65 4.5 4.5 150 90 64
Rainscreens
60 mm mineral stone wool density 50 kg/m3 or
Insulation
60 mm mineral stone wool density 35 kg/m3 Installation Overview
When using Acoustic Studs, confirm the test data with the Stud manufacturer first Fix & Finish
Performance Details
Wet Areas
(9) Wall thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and jointed
with an isolation strip (for example a self adhesive insulation strip). No mechanical bracing across studs. (10) Wall thickness, heights and construction properties quoted
are for separated steel stud partitions with U channels and C studs fixed parallel to each other without any jointing between the two separated stud sections. (11) Wall
thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and connected to each
other at <1/3 height with a fillet of board or an off-cut of steel stud.
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1S32
Components & Accessories
Studs 2 x 50 mm DIN standard studs @ 600 mm centres 3.5 (9), 3.5 (9),
Linings
Severe
Facings 60 (10) , (10) , ≥150 90 64
1 layer 10 mm Fermacell Board each outer side
50 mm mineral stone wool density 50 kg/m3 or 4.5 4.5
Insulation (11) (11)
60 mm mineral stone wool density 35 kg/m3
Studs 2 x 50 mm DIN standard studs @ 600 mm centres 3.5 (9), 3.5 (9),
3.2 3.2
Severe
Facings 2 layers 12.5 mm Fermacell Board each side 68 (10) , (10) , ≥155 90 64
& Ceilings
Floorings
Severe
Facings 60 3.5 3.5 ≥200 90 64
1 layer 10 mm Fermacell Board each outer side (10)
, (10)
,
Detailed Overview
Fire Protection
Severe
Facings 2 layers 12.5 mm Fermacell Board each side 69 3.5 3.5 ≥205 90 64
(10)
, (10)
,
50 mm mineral stone wool density 50 kg/m3 or 6.5 5
Insulation
60 mm mineral stone wool density 35 kg/m3 (11) (11)
Timber Frames
1S32/2
Studs 2 x 75 mm DIN standard studs @ 500 mm centres
Component Details
Severe
Facings 2 layers 10 mm Fermacell Board each side 61 3.5 (10) 3.5 (11) ≥205 60 64
Performance Details
Wet Areas
(9) Wall thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and jointed
with an isolation strip (for example a self adhesive insulation strip). No mechanical bracing across studs. (10) Wall thickness, heights and construction properties quoted
are for separated steel stud partitions with U channels and C studs fixed parallel to each other without any jointing between the two separated stud sections. (11) Wall
thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and connected to each
other at <1/3 height with a fillet of board or an off-cut of steel stud.
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
(With Fire Rating)
Wall Weight
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m m mm mins Rw Grade
1S33
Linings
Severe
Facings 1 layer 18 mm Fermacell Board each side 50 4 4 111 90 57
Severe
Facings 1 layer 18 mm Fermacell Board each side 50 5.9 5 136 90 57
& Ceilings
Floorings
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
Facings 1 layer 18 mm Fermacell Board each side 50 5.9 4.5 136 120 57
Detailed Overview
1S34/1
Fire Protection
Studs 125 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm plus 10 mm Fermacell Board each
Facings 71 10.8 7 180 90 62
side plus 1 layer 10 mm Fermacell Board outer side
1S34/2
Timber Frames
Studs 125 mm DIN standard studs @ 600 mm centres
Component Details
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 81 12 9 190 90 63
2 layers 10 mm Fermacell Board each outer side
Insulation 40 mm mineral stone wool density 40 kg/m3
Rainscreens
Insulation 40 mm mineral stone wool density 40 kg/m3
Performance Details
(9) Wall thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and jointed
with an isolation strip (for example a self adhesive insulation strip). No mechanical bracing across studs. (10) Wall thickness, heights and construction properties quoted
are for separated steel stud partitions with U channels and C studs fixed parallel to each other without any jointing between the two separated stud sections. (11) Wall
thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and connected to each
other at <1/3 height with a fillet of board or an off-cut of steel stud.
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1S41
Components & Accessories
Severe
1 layer 15 mm Fermacell Board each side plus
Facings 76 5.5 5 135 120 62
1 layer 12.5 mm Fermacell Board each outer side
Insulation 50 mm mineral stone wool density 50 kg/m 3
Severe
1 layer 15 mm Fermacell Board each side plus
Facings 77 6.5 6 160 120 62
1 layer 12.5 mm Fermacell Board each outer side
& Ceilings
Floorings
Severe
1 layer 15 mm Fermacell Board each side plus
Facings 77 7 6.5 185 120 62
1 layer 12.5 mm Fermacell Board each outer side
Detailed Overview
1S42
Studs 2 x 75 mm DIN standard studs @ 600 mm centres
Severe
1 layer 15 mm Fermacell Board each side plus
Facings 72 6.5 6.5 ≥215 120 62
1 layer 12.5 mm Fermacell Board each outer side (11) (11)
Severe
Facings 2 layers 15 mm Fermacell Board each side 78 6.5 6.5 ≥220 120 62
Component Details
(11) (11)
Insulation 50 mm mineral stone wool density 50 kg/m 3
1S51
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
2 layers 12.5 mm Fermacell Board each side plus
Facings 89 6.5 6 170 180 64
1 layer 10 mm Fermacell Board each outer side
Insulation 80 mm mineral stone wool density 50 kg/m3
Rainscreens
1S52
Studs 75 mm DIN standard studs @ 600 mm centres
Fix & Finish
Severe
(9) Wall thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and jointed
with an isolation strip (for example a self adhesive insulation strip). No mechanical bracing across studs. (10) Wall thickness, heights and construction properties quoted
are for separated steel stud partitions with U channels and C studs fixed parallel to each other without any jointing between the two separated stud sections. (11) Wall
thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and connected to each
other at <1/3 height with a fillet of board or an off-cut of steel stud.
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
(With Fire Rating)
Wall Weight
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m m mm mins Rw Grade
1S15 H2O
Severe
Linings
1 layer 12.5 mm Powerpanel H2O inner side plus 29 3.05 3.05 75 30 41
Facings
1 layer 12.5 mm Fermacell Board outer side
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm Powerpanel H2O inner side plus 29 4 4 100 30 41
Facings
1 layer 12.5 mm Fermacell Board outer side
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
& Ceilings
Floorings
1 layer 12.5 mm Powerpanel H2O inner side plus 29 4.8 4.8 125 30 41
Facings
1 layer 12.5 mm Fermacell Board outer side
1S11 H2O
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
Detailed Overview
Facings 1 layer 12.5 mm Powerpanel H2O each side 30 4.5 4.5 100 30 49
Fire Protection
Insulation 60 mm mineral stone wool density 25 kg/m 3
Severe
Facings 1 layer 12.5 mm Powerpanel H2O each side 30 5 5 125 30 49
1S12 H2O
Timber Frames
Studs 50 mm DIN standard studs @ 600 mm centres
Component Details
Severe
1 layer 12.5 mm Powerpanel H2O inner side plus
Facings 33 3.7 3 75 30 49
1 layer 12.5 mm Fermacell Board outer side
Insulation 40 mm mineral stone wool density 50 kg/m3
Rainscreens
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
Installation Overview
1 layer 12.5 mm Powerpanel H2O inner side plus
Facings 33 6 5 125 30 51
1 layer 12.5 mm Fermacell Board outer side
Insulation 60 mm mineral stone wool density 25 kg/m3
1S13 H2O
Studs 50 mm DIN standard studs @ 600 mm centres
Fix & Finish
outer side
Insulation 60 mm mineral stone wool density 25 kg/m3
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1S31 H2O
Components & Accessories
Severe
Facings 2 layers 12.5 mm Powerpanel H2O on both sides 64 3.5 3 155 90 61
1S41 H2O
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
Facings 2 layers 12.5 mm Powerpanel H2O each side 55 4 4 125 120 57
Severe
Facings 2 layers 12.5 mm Powerpanel H2O each side 55 5.85 5.85 150 120 57
1S42 H2O
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus
Timber Frames
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 60 7.45 6.5 150 120 60
1 layer 12.5 mm Powerpanel H2O each outer side
Insulation 60 mm mineral stone wool density 25 kg/m3
1S43 H2O
Rainscreens
Severe
Facings 2 layers 12.5 mm Powerpanel H2O on both sides 65 4 3.5 205 120 63
Performance Details
Wet Areas
Sound Insulation
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m mm mins Rw Grade
1H11
Linings
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 38 3.1 85 30 44
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 40 4.1 105 30 44
& Ceilings
Floorings
Studs 75 mm x 50 mm @ 600 mm centres
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 41 4.1 100 30 47
Detailed Overview
Fire Protection
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 40 4.1 114 30 44
1H12
Studs 60 mm x 40 mm @ 500 mm centres
Heavy
Facings 1 layer 10 mm Fermacell Board each side 32 3.1 80 30 44
Timber Frames
Insulation 40 mm mineral stone wool density 30 kg/m3
Component Details
Heavy
Facings 1 layer 10 mm Fermacell Board each side 34 4.1 100 30 44
Rainscreens
Studs 89 mm x 38 mm @ 500 mm centres
Heavy
Installation Overview
Facings 1 layer 10 mm Fermacell Board each side 34 4.1 109 30 44
1H15
Studs 2 x 60 mm x 40 mm @ 600 mm centres with 30 mm air gap
Fix & Finish
Severe
Sound Insulation
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1H22
Components & Accessories
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 40 4.1 100 60 44
40 mm mineral stone wool density 45 kg/m3 or
Insulation
60 mm mineral stone wool density 30 kg/m3
Insulation 70 mm x 30 kg/m3 47
Severe
& Ceilings
Floorings
1H22RB
Detailed Overview
Fire Protection
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 40 4.1 100 60 52*
40 mm mineral stone wool density 45 kg/m3 or
Insulation
60 mm mineral stone wool density 30 kg/m3
Studs 89 mm x 38 @ 600 mm centres
Severe
Resilient Bar to inner side
Facings 1 layer 12.5 mm Fermacell Board each side 41 4.1 114 60 52*
Timber Frames
1H23
Studs 2 x 60 mm x 40 mm @ 600 mm centres with 30 mm air gap
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 42 3.1 175 60 57
Severe
1H29
Studs 75 mm x 50 mm @ 600 mm centres
Severe
* - Interpolated performance
Sound Insulation
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m mm mins Rw Grade
1H31
Linings
1 layer 12.5 mm Fermacell Board each side plus
Severe
Facings 62 3.1 105 90 51
1 layer 10 mm Fermacell Board each outer side
50 mm mineral stone wool density 50 kg/m3 or
Insulation
70 mm mineral stone wool density 30 kg/m3
Studs 80 mm x 40 mm @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 64 4.1 125 90 54
& Ceilings
1 layer 10 mm Fermacell Board each outer side
Floorings
Insulation 70 mm mineral stone wool density 30 kg/m3
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 64 4.1 120 90 54
1 layer 10 mm Fermacell Board each outer side
Detailed Overview
Fire Protection
Insulation 70 mm mineral stone wool density 30 kg/m3
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 64 4.1 134 90 54
1 layer 10 mm Fermacell Board each outer side
Insulation 70 mm mineral stone wool density 30 kg/m3
1H31RB
Timber Frames
Studs 75 mm x 50 mm @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus
Component Details
Facings 64 4.1 120 90 60*
1 layer 10 mm Fermacell Board each outer side
Insulation 70 mm mineral stone wool density 30 kg/m3
Resilient Bar to inner side 1 layer 12.5 mm Fermacell Board each side plus
Facings 64 4.1 134 90 60*
1 layer 10 mm Fermacell Board each outer side
Insulation 70 mm mineral stone wool density 30 kg/m3
Rainscreens
1H32
75 mm x 50 @ 600 mm centres (one-sided traverse
Installation Overview
Studs
30/50 timber without mineral stone wool strip)
Severe
Studs
30/50 timber with mineral stone wool strip)
Severe
* - Interpolated performance
Wet Areas
Sound Insulation
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1H35
Components & Accessories
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 65 3.1 175 90 66
1 layer 10 mm Fermacell Board each outer side
Insulation 50 mm mineral stone wool density 50 kg/m 3
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 69 4.1 205 90 66
1 layer 10 mm Fermacell Board each outer side
& Ceilings
Floorings
Severe
1 layer 12.5 mm Fermacell Board each side plus
Facings 70 4.1 233 90 66
1 layer 10 mm Fermacell Board each outer side
Detailed Overview
1H36
Studs 2 x 75 mm x 50 mm @ 500 mm centres with 30 mm air gap
Severe
Facings 2 layers 10 mm Fermacell Board each side 41 4.1 280 60 62
Severe
Timber Frames
1H37
Rainscreens
Sound Insulation
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m mm mins Rw Grade
1H13
Severe
Linings
37 3.1 85 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
Severe
39 4.1 105 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
Severe
40 4.1 100 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
& Ceilings
Floorings
Studs 89 mm x 38 mm @ 600 mm centres
Severe
40 4.1 114 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
Severe
46 4.1 100 60 41
Facings 1 layer 15 mm Fermacell Board each side
Detailed Overview
Fire Protection
1H14
Studs 75 mm x 50 mm @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus 52 4.1 110 30 43
Facings
1 layer 10 mm Fermacell Board outer side
Studs 89 mm x 38mm @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board each side plus 52 4.1 124 30 43
Facings
Timber Frames
1 layer 10 mm Fermacell Board outer side
Component Details
1H21
Studs 75 mm x 50 mm @ 500 mm centres
Severe
61 4.1 115 60 48
Facings 2 layers 10 mm Fermacell Board each side
Rainscreens
Studs 89 mm x 38 mm @ 500 mm centres
Severe
61 4.1 129 60 48
Facings 2 layers 10 mm Fermacell Board each side Installation Overview
Similar performance is achievable by using 40 mm x 60 mm studs, and 40 mm x 80 mm studs with the same boarding
and insulation configurations.
Fix & Finish
1H33
Studs 60 mm x 40 mm @ 600 mm centres
Severe
Sound Insulation
(Without Fire Rating)
Wall Thickness
Partitions
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1H13 H2O
Components & Accessories
Severe
1 layer 12.5 mm Fermacell Powerpanel H2O Board
Facings 33 3.1 3.1 85 60 40
each side
Insulation 60 mm mineral stone wool density 25 kg/m3
Severe
1 layer 12.5 mm Fermacell Powerpanel H2O Board
Facings 35 4.1 4.1 100 60 40
each side
& Ceilings
Floorings
Severe
1 layer 12.5 mm Fermacell Powerpanel H2O Board
Facings 36 4.1 4.1 114 60 40
each side
Detailed Overview
Component Details
Rainscreens
Installation Overview
Fix & Finish
Performance Details
Wet Areas
Sound Insulation
Wall Thickness
Partitions
Applied Load
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kN/stud kg/m2 m mm mins Rw Grade
1HT14
Severe
Linings
12 35 3 105 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
Severe
5.56 35 2.6 114 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
1HT15
& Ceilings
Floorings
Studs 80 mm x 40 mm @ 600 mm centres
Severe
6.4 39 3 110 30 41
Facings 1 layer 15 mm Fermacell Board each side
Severe
5.56 39 2.6 119 30 41
Facings 1 layer 15 mm Fermacell Board each side
Detailed Overview
Fire Protection
1HT21
Studs 80 mm x 50 mm @ 600 mm centres
Severe
10 64 2.6 130 60 47
Facings 2 layers 12.5 mm Fermacell Board each side
Timber Frames
Component Details
Rainscreens
Installation Overview
Wet Areas
Sound Insulation
Wall Thickness
Partitions
Applied Load
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1HT11
Components & Accessories
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 8 40 3 105 30 44
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 9.3 40 3 100 30 44
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 5.56 41 2.6 114 30 44
90 mm mineral stone wool density 10 kg/m3 or
Insulation
40 mm mineral stone wool density 30 kg/m3
Detailed Overview
Fire Protection
1HT22
Studs 89 mm x 38 mm @ 600 mm centres
Severe
Facings 1 layer 18 mm Fermacell Board each side A 58 3 125 60 ≥46
Severe
Facings 1 layer 15 mm Fermacell Board each side 10.8 48 3 150 60 ≥46
Timber Frames
Severe
Facings 1 layer 15 mm Fermacell Board each side 10 48 3 150 60 ≥46
1HT23
Studs 89 mm x 38 mm @ 600 mm centres
Rainscreens
Severe
(9) Wall thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and jointed
with an isolation strip (for example a self adhesive insulation strip). No mechanical bracing across studs. (10) Wall thickness, heights and construction properties quoted
are for separated steel stud partitions with U channels and C studs fixed parallel to each other without any jointing between the two separated stud sections. (11) Wall
thickness, heights and construction properties quoted are for separated steel stud partitions with U channels and C studs fixed parallel to each other and connected to each
other at <1/3 height with a fillet of board or an off-cut of steel stud.
Sound Insulation
Wall Thickness
Partitions
Applied Load
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kN/stud kg/m2 m mm mins Rw Grade
1HT 31-6
Linings
Severe
Facings 2 layers 15 mm Fermacell Board each side 15 84 3.5 160 90 ≥51
1HT 32-2RB
& Ceilings
Floorings
Studs 140 mm x 60 mm @ 600 mm centres
Severe
2 layers 12.5 mm Fermacell Board each side
Facings 16.8 78 3.5 ≈ 215 90 ≥60*
with a resilient bar to inner side
Insulation 140 mm mineral stone wool density 30 kg/m3
Detailed Overview
Fire Protection
Resilient Bar to inner side
1HT 32-12RB
Studs 140 mm x 60 mm @ 600 mm centres
Severe
2 layers 15 mm Fermacell Board each side
Facings 16.8 ≈ 94 3.5 ≈ 225 90 ≥60*
with a resilient bar to one side
Insulation 140 mm Homatherm
Timber Frames
Component Details
Resilient Bar to inner side
1HT 35-1
100 mm x 60 mm @ 600 mm centres plus
Studs
60 mm x 45 mm @ 600 mm centres
Severe
Rainscreens
Insulation 100 mm mineral stone wool density 30 kg/m3
N.B. Only 100 mm x 60 mm stud is loaded. Installation Overview
Wet Areas
Sound Insulation
Wall Thickness
Partitions
Applied Load
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
N/
SYSTEM SPECIFICATIONS mm2
kg/m2 m mm mins Rw Grade
1HG31-1
Components & Accessories
Severe
1 layer 12.5 mm Fermacell Board inner side plus 30/
Facings 2.5 63 3 142.5 68†
2 layers 15 mm Fermacell Board outer side 90**
Insulation 100 mm mineral stone wool density 30 kg/m3
Severe
1 layer 12.5 mm Fermacell Board inner side plus 30/
External protection sheeting Facings 2 62 3 142.5 68†
2 layers 15 mm Fermacell Board outer side 90**
& Ceilings
Floorings
Severe
1 layer 12.5 mm Fermacell Board inner side plus 30/
Facings 2 62 2.6 162.5 68†
2 layers 15 mm Fermacell Board outer side 90**
Detailed Overview
1HG31-8
Studs 140 mm x 60 mm @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board inner side plus 30/
Facings 2 ≈ 77 3 190 ≥68†
3 layers 12.5 mm Fermacell Board outer side 90**
Insulation 140 mm mineral stone wool density 20 kg/m3
Timber Frames
Component Details
1HG32
Studs 140 mm x 80 mm @ 600 mm centres
Rainscreens
30/
Facings 1 layer 15 mm Fermacell Powerpanel HD Board 2 ≈ 53 3 167.5 ≥66†
90**
outer side
Installation Overview
30/
Facings 1 layer 15 mm Fermacell Powerpanel HD Board 2 ≈ 53 3 167.5 ≥66†
90**
outer side
Fix & Finish
Sound Insulation
Wall Thickness
Partitions
Applied Load
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
N/
SYSTEM SPECIFICATIONS mm2
kg/m2 m mm mins Rw Grade
1HA11
Linings
1 layer 12.5 mm Fermacell Board plus vapour barrier
inner side plus 1 layer 12.5 mm Fermacell Board
Severe
Facings plus breather membrane, 60 mm PS15 rigid 2 54 3 ≈ 230 30 48
insulation, 3 mm reinforcement and 3 mm render
outer side
Insulation 140 mm mineral stone wool density 20 kg/m3
& Ceilings
Floorings
1HA31
Studs 140 mm x 60 mm @ 600 mm centres
2 layers 12.5 mm Fermacell Board inner side plus
Severe
Facings 2 layers 12.5 mm Fermacell Board outer side plus 2 ≈ 77‡ 3 190‡ 90 ≥51
Weatherboard
Detailed Overview
Insulation 140 mm mineral stone wool density 30 kg/m3
Fire Protection
Studs 100 mm x 60 mm @ 600 mm centres
2 layers 15 mm Fermacell Board inner side plus
Severe
Facings 2 layers 15 mm Fermacell Board outer side plus 2 ≈ 77‡ 3 165 90 ≥51
Weatherboard
Insulation 100 mm mineral stone wool density 20 kg/m3
Timber Frames
Component Details
Rainscreens
Installation Overview
Wet Areas
Introduction 63
Detailed Overview 67
Component Details 68
Installation Overview 70
Performance Details 71
LININgS
www.fermacell.co.uk INTRODUCTION
Partitions
Academic traditional timber frame as well
Introduction
as dot and dab fixing.
Residential
The use of Fermacell with wall lining
Healthcare
systems creates a quick and simple way to
Linings
Recreation
install systems that reduce the wet trades
required as the fast and simple jointing
Industrial systems for Fermacell Boards Fine Surface
Treatment (FST).
& Ceilings
Floorings
PERFORMANCE RATINGS
MeTal FraMe lINING SYSTeMS
20 60
dB dB
The use of Fermacell with metal frame Dry Lining
Detailed Overview
systems allows a dry system to be installed
Fire Protection
30 60 for lining walls where the background may be
mins mins
unsuitable for “dabbing”, where the existing wall
may be out of true or the surface may not allow the
adhesion of the Fermacell Bonding Compound.
FERMACELL PERFORMANCE
Metal frame systems allow the system to be fixed
Timber Frames
Impact – Able to withstand impact directly to the existing wall allowing different
from people as well as objects
cavity widths to be accommodated. This can be
Component Details
(door handles etc).
as little as 15 mm with a metal furring system.
Insulation and vapour barriers can be installed
Acoustics – Enhanced acoustic
insulation providing simple behind the Fermacell Boards. Where possible place
solutions to upgrade existing walls. the insulation between the battens and the wall
where there is a narrow cavity otherwise this will
Ease of construction – A variety reduce its overall effectiveness and may cause cold
Rainscreens
of Shaftwall and variable cavity bridging. We recommend that thermal calculations
lining systems allowing simple, are undertaken to eliminate cold bridging issues.
Installation Overview
Wet Areas
Introduction
Components & Accessories
Linings
& Ceilings
Floorings
Detailed Overview
Fire Protection
Timber Frames
Component Details
and may cause cold bridging. support the Fermacell Boards and these are set
generally at 400 mm centres for greater stability.
DIreCT BOND – “DOT aND DaB” Greater centres are allowable, please contact our
Technical department for further information. As
Performance Details
Fermacell can be installed using the dot and the C stud is not fixed to the background there is no
dab method; to do so Tapered edge boards restriction in the size of cavity and space is allowed
Wet Areas
Partitions
School.
Introduction
Designed by the Architects Co-Partnership, the school
maximizes the use of natural light and ventilation,
Environmentally friendly Fermacell offers excellent thermal insulation, as well as night
time cooling. Other environmental features include
Dry Lining is an integral part of
20% renewable energy and the overall carbon
many of the internal walls within
Linings
the new Sedgehill Secondary old one.
School in Lewisham which is
Sedgehill Secondary School opened at the beginning
aiming to achieve an “excellent”
of 2009 and accommodates 1,700 boys and girls
BREEAM rating. aged between 11 and 19 years. A Performing Arts
& Ceilings
Specialist School, it offers first class amenities
Floorings
Pupils continued their education including drama and dance facilities comprising four
studios as well as a central external performance
within the old school building
facility not only for use by the students, but also
during a phased demolition the local community.
Detailed Overview
process and the creation of, in
Fire Protection
effect, a five building campus Behrouz Shomali from Architects Co-Partnership,
commenting on the project said: “The design concept
surrounding a central courtyard.
is based around a sea shell – the idea being to deliver
an inclusive learning environment.”
A feature of the complex is a
circular series of six cantilevered A range of Fermacell partition and lining systems
Timber Frames
were used within the scheme and, in particular, the
barrel vault walkways around the
Component Details
3S11 and adjustable cavity wall lining systems.
main school courtyard.
There are a number of major benefits to using
the Fermacell 3S11 system. One of these is that it
provides a cavity when installed independently to
the Metsec structural steel framing allowing the
Rainscreens
contractor to overcome any protruding fixings and
provide a vapour barrier. Installation Overview
Wet Areas
COMPONENTS ACCESSORIES
Partitions
Fermacell Board
Introduction
Size
Detailed Overview
5 m2 per kg for filling Tapered edge Nominal 0.6 gauge 50 mm fixing face
Fire Protection
Pack Size 5 kg or 20 kg
Fermacell Jointstik
For edge glueing square edged
Fermacell Boards.
Timber Frames
20 lm / 310 ml tube
Coverage 37 lm / bulk applicator refill
Component Details
310 ml tubes or
Pack Size 580 ml bulk applicator refills
Partitions
Introduction
Compound at 400–600 mm
depending on board size
Linings
Fermacell Screws
Fermacell Bonding
@ 250 mm c/c
Compound continuous
(12.5 mm board)
50 mm from edge
& Ceilings
Floorings
Jointstik or taped
and jointed with
Fermacell
Fermacell Tape
Bonding
and Joint Filler,
Compound
dependent on
Detailed Overview
board type used
Fire Protection
Metal Furring
Lining system
Timber Frames
mechanically
fixed as required
Component Details
or DIN standard
independent
lining
Rainscreens
Tapered edge Fermacell Boards
Installation Overview
With Dot and dab fixing, Fermacell recommends two mechanical fixings
Fix & Finish
once bonding has set. Advisable where greater loads are to be fixed directly
to the boards.
Wet Areas
LININGS
Partitions
substrate
• Install the board as per fixing instructions in
the Fixing and Finishing section
* For double layer systems the second layer
can be screw fixed or stapled into place –
Detailed Overview
LININGS
systems.
• Mark horizontal lines at 800 mm centres
Component Details
Performance Details
Wet Areas
LININGS
Partitions
(3) Timber lining systems
• Allow a minimum cavity of 50 mm and a
Introduction
breather membrane to BS 4016 should be
installed for timber frame constructions
• Construct the timber lining as required
• Insulation can be inserted either between
the studs or in the cavity allowing adequate
clearance to the existing substrate
Linings
the Fixing and Finishing section. Fermacell
Boards can be screw fixed or stapled in
to place – please contact our technical
department for staple fixing details
& Ceilings
Floorings
(4) Dot and Dab (Direct Bond)
• Ensure the masonry background is dry
and dust free
• Direct bonding is not recommended for
solid exterior walls prone to moisture
Detailed Overview
ingress, an adjustable or independent
Fire Protection
lining system should be used instead
• The minimum finished dab thickness
should be no less than 10mm and not
greater than 25 mm
• Apply Fermacell Bonding Compound dabs
at 400 mm or 600 mm centres vertically to
suit the board width
• Each dab should be 50-75 mm wide
Timber Frames
x 250 mm long and 25 mm in from the
board edge at 30 mm vertical centres
Component Details
• A continuous ribbon of Fermacell Bonding
Compound should be applied around the
perimeter of the external walls and around
door/window frames and sockets
• The contact area of the dabs should be at
least 20% of the board surface
Rainscreens
Installation Overview
Wet Areas
Wall lININGS
STEP ONE
Partitions
Ensure the floor is clean and flat; mark out the Plumb the ceiling line with the floor track and
line of the wall lining allowing for the width of mark out.
Introduction
the Fermacell Boards and any desired cavity. Fix the base and ceiling tracks at 600 mm
If using an adjustable cavity metal system centres using suitable fixings and insert DIN
mark out the bracket centres along the standard studs into the tracks.
channel paths. If using an adjustable cavity system, fit the
brackets and then secure the channels to them.
Components & Accessories
Linings
butt the next board and the Joint Filler for Tapered
screw fix. edge boards once dry.
Tapered edge board:
Position and fix the next
board. Once bonding
is dry, apply Fermacell
Joint filler, embedding a
reinforcement tape, and
Rainscreens
STEP SIx
Surface Treatment to
the entire surface for a
smooth finish prior to
painting. See installation
manual for other
finishing options.
Performance Details
Wet Areas
Improved Sound
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
Insulation
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m mm mins ΔR1w Grade
3S01
Linings
Heavy
Facings 1 layer 12.5 mm Fermacell Board one side 20 3 62.5 N/A N/A
Insulation Optional
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 20 3.5 87.5 N/A N/A
Insulation Optional
& Ceilings
Floorings
Studs 100 mm DIN standard studs @ 600 mm centres
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 20 4.1 112.5 N/A N/A
Insulation Optional
Detailed Overview
3S11
Fire Protection
Studs 50 mm DIN standard studs @ 600 mm centres
Heavy
Facings 1 layer 15 mm Fermacell Board one side 23 3 65 30 20
Severe
Facings 1 layer 15 mm Fermacell Board one side 23 3.5 90 30 20
Timber Frames
Insulation 50 mm mineral stone wool density 40 kg/m3
Component Details
Severe
Facings 1 layer 15 mm Fermacell Board one side 23 4.1 115 30 20
3S12
Studs 50 mm DIN standard studs @ 600 mm centres
Severe
Rainscreens
Facings
1 layer 10 mm Fermacell Board one side
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
Installation Overview
3S21
Studs 50 mm DIN standard studs @ 600 mm centres
Severe
Improved Sound
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
Insulation
DIN 4103
BS 5234/
Introduction
3S31
Components & Accessories
Severe
1 layer 15 mm Fermacell Board plus
Facings 53 3.5 90 90 ‡ ≥22
2 layers 12.5 mm Fermacell Board outer side
Insulation 50 mm mineral stone wool density 40 kg/m3
Severe
1 layer 15 mm Fermacell Board plus
Facings 53 4 115 90 ‡ ≥22
& Ceilings
Severe
1 layer 15 mm Fermacell Board plus
Facings 53 4.5 140 90 ‡ ≥22
2 layers 12.5 mm Fermacell Board outer side
Detailed Overview
Fire Protection
Severe
1 layer 15 mm Fermacell Board plus
Facings 53 5 165 90 ‡ ≥22
2 layers 12.5 mm Fermacell Board outer side
Insulation 100 mm mineral stone wool density 30 kg/m3
Timber Frames
Component Details
DIreCT BOND
Wall Thickness
Performance
Wall Weight
Rainscreens
Thermal
Installation Overview
m2
SYSTEM SPECIFICATIONS kg/m2 mm
k/W
3TP01
Facings 1 layer 10 mm Tapered Edge Fermacell Board one side 12.5 10 0.03
Fix & Finish
Facings 1 layer 12.5 mm Tapered Edge Fermacell Board one side 15 12.5 0.03
Performance Details
Wet Areas
‡
Classification from both sides
72 FERMACELL +44 (0) 870 6090 306
LININgS
www.fermacell.co.uk PERFORMANCE DETAILS
Improved Sound
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
Insulation
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS kg/m2 m mm mins ΔR1w Grade
3S01 H2O
Heavy
Linings
1 layer 12.5 mm Fermacell Powerpanel H2O Board 19 2.55 62.5 N/A N/A
Facings
one side
Studs 75 mm @ 600 mm centres
Heavy
1 layer 12.5 mm Fermacell Powerpanel H2O Board 19 3.5 87.5 N/A N/A
Facings
one side
& Ceilings
Floorings
3S02 H2O
Studs 75 mm DIN standard studs @ 600 mm centres
Heavy
2 layers 12.5 mm Fermacell Powerpanel H2O Board 32 3.5 100 N/A N/A
Facings
Detailed Overview
one side
Fire Protection
3S11 H2O
Studs 75 mm DIN standard studs @ 600 mm centres
Timber Frames
Severe
2 layers 12.5 mm Fermacell Powerpanel H2O Board
Facings 37 3.5 100 30 ‡ 21
one side
Component Details
Insulation 60 mm mineral stone wool density 30 kg/m3
Rainscreens
Installation Overview
Wet Areas
‡
Classification from both sides
FERMACELL +44 (0) 870 6090 306 73
LININgS
PERFORMANCE DETAILS www.fermacell.co.uk
Flanking Sound
inc. blockwork
Wall Thickness
Partitions
Performance
Wall Weight
Wall Height
Fire Rating
Resistance
DIN 4103
BS 5234/
Thermal
Introduction
3WS01
Components & Accessories
DIN Std
Wall Liner System @ 600 mm centres
Linings
Studs
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 17 8 ≥42 n/a 57 0.53
DIN Std
Wall Liner System @ 600 mm centres
Studs
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 20 8 62.5 n/a 57 1.28
& Ceilings
Floorings
DIN Std
Wall Liner System @ 600 mm centres
Studs
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 20 8 87.5 n/a 57 1.28
Detailed Overview
3WS02
DIN Std
Wall Liner System @ 600 mm centres
Studs
Severe
Facings 2 layers 12.5 mm Fermacell Board one side 32 8 ≥55 30 62 0.57
DIN Std
Wall Liner System @ 600 mm centres
Timber Frames
Studs
Severe
Facings 2 layers 12.5 mm Fermacell Board one side 35 8 75 30 62 1.31
Component Details
DIN Std
Wall Liner System @ 600 mm centres
Studs
Facings 2 layers 12.5 mm Fermacell Board one side 35 8 100 30 62 1.31 Severe
3WS11
DIN Std
Wall Liner System @ 600 mm centres
Installation Overview
Studs
Severe
DIN Std
Wall Liner System @ 600 mm centres
Studs
Severe
Fix & Finish
3WS12
DIN Std Wall Liner System 50 mm DIN standard studs
Performance Details
DIN Std
Wall Liner System @ 600 mm centres
Studs
Severe
Flanking Sound
inc. blockwork
Wall Thickness
Partitions
Performance
Wall Weight
Wall Height
Fire Rating
Resistance
DIN 4103
BS 5234/
Thermal
Introduction
SYSTEM SPECIFICATIONS kg/m2 m mm mins RL,W k2 k/W Grade
3WH01
Linings
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 16 8 42.5 30 59 0.78
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 16 8 52.5 30 59 1.03
& Ceilings
Floorings
Battens 60 mm x 40 mm @ 600 mm centres
Severe
Facings 1 layer 12.5 mm Fermacell Board one side 17 8 72.5 30 59 1.53
Detailed Overview
3WH02
Fire Protection
Battens 30 mm x 50 mm @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board plus
Facings 26 8 52.5 60 63 0.81
1 layer 10 mm Fermacell Board one side
Insulation 30 mm mineral stone wool density 20 kg/m 3
Severe
1 layer 12.5 mm Fermacell Board plus
Facings 26 8 62.5 60 63 1.06
Timber Frames
1 layer 10 mm Fermacell Board one side
Insulation 40 mm mineral stone wool density 20 kg/m 3
Component Details
Battens 60 mm x 40 mm @ 600 mm centres
Facings
1 layer 12.5 mm Fermacell Board plus
27 8 82.5 60 63 1.56 Severe
1 layer 10 mm Fermacell Board one side
Insulation 60 mm mineral stone wool density 20 kg/m 3
Rainscreens
Facings 2 layers 12.5 mm Fermacell Board one side 29.5 8 55 60 63 0.82
Wet Areas
Introduction 77
Detailed Overview 81
Component Details 82
Installation Overview 84
Performance Details 86
FLOORINgS & CEILINgS
www.fermacell.co.uk INTRODUCTION
Partitions
requirements.
Introduction
Refurbishment
Linings
Timber Frame
The range of systems we produce not only increase
sound insulation but also give a dry screed solution
to overlay underfloor heating and levelling solutions
PERFORMANCE RATINGS
to uneven floors.
& Ceilings
Floorings
17 69
dB dB Fermacell’s ceiling systems provide superior acoustic
and fire performance to timber and concrete ceilings
by using either a resilient bar or a suspended
30 90
ceiling system, decreasing the airborne acoustic
Detailed Overview
mins mins
Fire Protection
transmission.
FERMACELL PERFORMANCE
Timber Frames
of cost effective, simple to install
solutions for improving the acoustic
Component Details
insulation of solid masonry floors
and timber floor constructions.
Rainscreens
enhance the airborne acoustic
performance. Installation Overview
the structure.
Underfloor heating
Introduction
solution.
Partitions
Introduction
Components & Accessories
Linings
& Ceilings
Floorings
Detailed Overview
Fire Protection
Pre-completion testing produced acoustic “Fermacell Flooring Elements have a much lower
performances which comfortably exceeded thermal resistance than chipboard, therefore
Part E requirements. The minimum airborne sound the response time of the heating system is much
result was 11 dB over the requirement, whilst quicker, and when you turn the heating down –
Timber Frames
the minimum impact sound result surpassed the or off – there is minimal delay.
Component Details
guidelines by 14 dB.
In addition, Fermacell is not an insulator, and so
Chris Smith, Managing Director of Jupiter can make UFH systems more efficient – the pipe
Underfloor Heating, commented: “On the face of temperature can be up to 5 degrees lower, saving
it our quote appeared to be more expensive than energy and money.”
that of the competitors. However, our proposal
Rainscreens
required only 55 mm depth compared to the Mark Swan commented: “Floor heating system
minimum 100 to 145 mm depth needed for the components need to be compatible in order to Installation Overview
Robust Detail construction. By saving a brick provide an efficient, integrated solution. We
course at each floor level, Swan Homes was able certainly achieved that through the joint initiative
to make substantial savings on build cost. put forward by Fermacell and Jupiter. Not only did
the Fermacell Gypsum Fibreboard enable us to save
“We worked very closely with Fermacell on this a brick course at each level of the building, but it
Fix & Finish
project in order to come up with an alternative enabled us to comfortably surpass the required
solution to the traditional tried and tested route.” acoustic sound test standards laid down by Part E
requirements.”
Andrew Richardson, Technical Manager with
Performance Details
FlOOrING eleMeNTS
COMPONENTS COMPONENTS
Partitions
Honeycomb sheets
For screeding, levelling and
insulating floors. 1500 mm x 1000 mm
A retaining sheet for honeycombing infill.
20 mm, 25 mm, 30 mm, 40 mm, 45 mm
Pack Size and 50 mm
Pack Size 30 mm – 30 sheets, 60 mm – 15 sheets
Coverage 1500 mm x 500 mm per sheet
Components & Accessories
Coverage
Floorings
Pack Size 5 kg or 20 kg
Fire Protection
19 mm or 22 mm Fermacell
Floor Screws Fermacell Self Levelling Compound
For securing flooring elements. To level uneven floors.
Timber Frames
Coverage 15 per m2
Coverage 5m2 per bag at 10 mm of levelling
Pack Size
30 lm for 100mm depth Pack Size Each 15 kg
Installation Overview
Coverage 75 m2
Coverage 20 m2
Partitions
Fermacell flooring solutions are designed for use
Introduction
as floating floors in a wide variety of applications.
Manufactured from Fermacell Gypsum Fibreboards,
they give a dry, robust and simple solution to your
flooring requirements.
Linings
the flooring elements give a wide variety of solutions
as a complete floor/ceiling specification.
& Ceilings
Floorings
share the same basic technology which produces
a continuous floating membrane capable of
installation and use in 24 hours, and which is
ready to accept a wide range of floor finishes.
Detailed Overview
Fire Protection
CEILING LOADS
1. Improving acoustic insulation:
Types 2E31 & 2E32
2. Over floor heating: Types 2E22 & 2E11
3. Levelling uneven floors: A range of solutions
from 0 – 2000 mm are available.
4. Improving thermal insulation:
Timber Frames
Types 2E13 & 2E14
Component Details
5. Wet-room floors: TE Powerpanel H2O
Flooring element.
Rainscreens
to timber, steel and concrete floors by providing
acoustic, fire, thermal mass and fixing performance.
Installation Overview
Due to the nature of the Fermacell Robust details Maximum allowable load in kg (1)
can be easily achieved as 2 layers of 10 mm board to per Fermacell Board thickness in mm (2)
the ceiling, giving the minimum mass requirement. Fermacell Board thickness (mm) kg (3)
This mass is used in multiple layers in thermal mass Toggle type fixings for
10 mm loaded ceiling
20 fittings
Fix & Finish
15 mm 23
Due to the screw holding ability, simple fittings can
be screwed directly into the ceiling board, or where 10 + 10 mm 24
12.5 + 12.5 mm 25
+44 (0) 870 6090 306. (1) Tested to DIN 4103, safety factor 2.
(2) Support spacing of the sub-structure ≤ 35 x board thickness.
Board fixed to the sub-structure with Fermacell screws.
(3) Observe the manufacturers operating and installation instructions.
MF CeIlING CONSTrUCTION
Partitions
Introduction
1200 1200 35
Linings
Edge Channel
Floorings
fixed at 600 mm
centres Soffit
Cleat
Detailed Overview
Fire Protection
Suitable Fixing
Structural Soffit
Rainscreens
Strap Hanger or
Angle Section
Installation Overview
Primary Channel
Fix & Finish
Note: Where ceiling weight exceeds 20 kg/m2 use Wafer Head Self Drilling Screws in lieu
of Connecting Clips. It is recommended that all double board systems are screw fixed.
25 mm flat strap may be used on ceiling drops up to 1 metre deep.
Partitions
Introduction
Fermacell Acoustic Fermacell Acoustic
Floor Element – Floor Element –
2E31 or 2E32 2E31 or 2E32
Linings
Concrete Rib Deck
Engineered 'I' Joist
MF Ceiling System
2 x 15 mm Fermacell
& Ceilings
Floorings
Detailed Overview
Fermacell Acoustic
Fire Protection
Fermacell Acoustic
Floor Element – Floor Element –
2E31 or 2E32 2E31 or 2E32
Timber Floor
Concrete Slab Timber Joist
Insulation
MF Ceiling System
Timber Frames
Resilient Bar
Component Details
10 mm Fermacell 2 x 10 mm Fermacell
Rainscreens
Fermacell Acoustic
Floor Element – Fermacell Acoustic
2E31 or 2E32 Floor Element –
2E31 or 2E32
Installation Overview
Screed
Fermacell 60 mm
Honeycomb Mass
Acoustic Flooring
Precast Concrete Floor
Fix & Finish
Thick Timber
MF Ceiling System Floorboards
Timber Joists
10 mm Fermacell
Performance Details
Wet Areas
FlOOrING SYSTeM
aCOUSTIC FlOOrING
Partitions
STEP THREE
& Ceilings
STEP FOUR
Floorings
STEP FIVE
Component Details
Installation Overview
Fix & Finish
Performance Details
Wet Areas
Partitions
STEP ONE STEP TWO
Introduction
Mark on the walls the Lay the Fermacell levelling
finished floor level. The compound to a minimum
thickness of the Floor of 10 mm deep a
Elements must be taken maximum of 60 mm.
into account when
calculating the finished
Linings
Repeat step 1 Acoustic
Flooring.
& Ceilings
STEP THREE STEP FOUR
Floorings
Level using the Fermacell Using pads of Fermacell
floor levelling set, strips to spread body weight
of graded timber may be lay the appropriate
used to set the height of Fermacell Flooring
the compound. element as steps 2–5
Detailed Overview
Acoustic Flooring.
Fire Protection
The Fermacell Trickle
Protection Sheet must
be used for timber floors
to avoid loss of the
granules.
Timber Frames
*when using Fermacell Self Levelling Compound the compound must be completely dry before installing the Fermacell Flooring Elements.
Component Details
aCOUSTIC hONeYCOMB FlOOrING
Rainscreens
Place an edging strip Lay the Honeycomb
along the walls to flooring element and
avoid flanking acoustic infill with the honeycomb Installation Overview
transmission, and to infill, level and repeat
allow for differential steps 2-5.
movement. The Fermacell
Trickle Protection Sheet
must be used for timber
floors to avoid loss of the
granules.
Fix & Finish
Performance Details
Wet Areas
Ceiling Weight
Partitions
Construction
Fire Rating
Introduction
Height
SYSTEM SPECIFICATIONS kg/m2 mm mins
2S11↑U
Components & Accessories
Type
Min 0.6 gauge. Confirm hanging and layout first
2S11↑U↓O
Channels 60 mm x 0.6 @ max 400 mm centres
28 130 30
Insulation 40 mm mineral stone wool density 30 kg/m3
Suspended steel ceiling system with fire protection from above
Type
and below. Min 0.6 gauge. Confirm hanging and layout first
Channels 60 mm x 0.6 @ max 500 mm centres
2S21↑U
Channels 60 mm x 0.6 @ max 400 mm centres
2S34↑U
Channels 60 mm x 0.6 @ max 500 mm centres
1 layer 15 mm Fermacell Board plus
Facings
2 layers 12.5 mm Fermacell Board one side
51 95 90
Insulation None
Performance Details
Ceiling Weight
Partitions
Construction
Fire Rating
Introduction
Height
SYSTEM SPECIFICATIONS kg/m2 mm mins
2S34↑U↓O
Linings
1 layer 15 mm Fermacell Board plus
Facings
2 layers 12.5 mm Fermacell Board one side
52 140 90
Insulation 40 mm mineral stone wool density 40 kg/m3
Suspended steel ceiling system with fire protection from above
Type
and below. Min 0.6 gauge. Confirm hanging and layout first
Channels 60 mm x 0.6 @ max 400 mm centres
& Ceilings
Floorings
Facings 4 layers 10 mm Fermacell Board one side
53 140 90
Insulation 40 mm mineral stone wool density 40 kg/m3
Suspended steel ceiling system with fire protection from above
Type
and below. Min 0.6 gauge. Confirm hanging and layout first
Detailed Overview
2H13↑U
Fire Protection
Min primary timber size 60 mm x 40 mm and min batten size 24 mm
Battens
x 48 mm at max 400 mm centres. Confirm support layout as required
Facings 2 layers 10 mm Fermacell Board one side
28 85 30
Insulation None
Type Suspended timber ceiling system with fire protection from below
Min primary timber size 60 mm x 40 mm and min batten size 24 mm
Battens
Timber Frames
x 48 mm at max 450 mm centres. Confirm support layout as required
Facings 2 layers 12.5 mm Fermacell Board one side
Component Details
37 90 30
Insulation None
Type Suspended timber ceiling system with fire protection from below
2H23↑U
Min primary timber size 60 mm x 40 mm and min batten size 24 mm
Battens
x 48 mm at max 400 mm centres. Confirm support layout as required
Rainscreens
Facings 3 layers 10 mm Fermacell Board one side
46 95 60
Insulation None Installation Overview
Type Suspended timber ceiling system with fire protection from below
Min primary timber size 60 mm x 40 mm and min batten size 24 mm
Battens
x 48 mm at max 500 mm centres. Confirm support layout as required
Facings 2 layers 15 mm Fermacell Board one side
40 95 60
Fix & Finish
Insulation None
Type Suspended timber ceiling system with fire protection from below
2H34↑U
Min primary timber size 60 mm x 40 mm and min batten size 24 mm
Battens
x 48 mm at max 500 mm centres. Confirm support layout as required
Performance Details
Insulation None
Type Suspended timber ceiling system with fire protection from below
Min primary timber size 60 mm x 40 mm and min batten size 24 mm
Battens
x 48 mm at max 400 mm centres. Confirm support layout as required
Facings 4 layers 10 mm Fermacell Board one side
63 105 90
Insulation None
Type Suspended timber ceiling system with fire protection from below
Ceiling Weight
Partitions
Construction
Fire Rating
Introduction
Depth
SYSTEM SPECIFICATIONS kg/m2 mm mins
2S01 H2O
Components & Accessories
2S11 H2O↑U
& Ceilings
Floorings
Type
Min 0.6 gauge. Confirm hanging and layout first
Fire Protection
2S11 H2O↑U↓O
Channels 60 mm x 0.6 @ max 500 mm centres
1 layer 12.5 mm Fermacell Board plus
Facings
1 layer 12.5 mm Powerpanel H2O one side
34 135 30
Insulation 40 mm mineral stone wool density 30 kg/m3
Suspended steel ceiling system with fire protection from above
Timber Frames
Type
and below. Min 0.6 gauge. Confirm hanging and layout first
Component Details
Sound Insulation
Ceiling Weight
Fire Rating
Rainscreens
2S14
Studs 225 mm Steel Joists set at 400 mm Centres with structural floorboard
Fix & Finish
Studs 225 mm Steel Joists set at 400 mm Centres with structural floorboard
Insulation None
2S16
Wet Areas
Studs 225 mm Steel Joists set at 400 mm Centres with structural floorboard
Sound Insulation
Ceiling Weight
Partitions
from below
Fire Rating
Introduction
SYSTEM SPECIFICATIONS kg/m2 Rw mins
2H12
Linings
MF suspended ceiling at max 400 mm centres
Facings 1 layer 10 mm Fermacell Board one side
16 >40 30
Insulation Optional - required for acoustic performance
Type Timber joisted ceiling systems with a layer of structural overlay board
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended Ceiling at max 500 mm centres
& Ceilings
Floorings
Facings 1 layer 12.5 mm Fermacell Board one side
19 40 30
Battens optional when joist
Insulation Optional
centres exceeds 400mm
Type Timber joisted ceiling systems with a layer of structural overlay board
2H15
Detailed Overview
Fire Protection
Engineered timber joists min 235 mm deep/without timber battens
Battens
minimum 50 mm x 30 mm at max 400 mm centres
min. 40 dB
Part E
Facings 1 layer 12.5 mm or 1 x 15 mm Fermacell Board one side
35 N/A*
Insulation Optional
Type Timber joisted ceiling systems with a layer of structural overlay board
Timber Frames
our Technical department on 0870 6090 306
Component Details
2H21
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 425 mm centres
min. 40 dB
Part E
Rainscreens
Type Timber joisted ceiling systems with a layer of structural overlay board
Installation Overview
Wet Areas
Sound Insulation
Ceiling Weight
Partitions
from below
Fire Rating
Introduction
2H23
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 400 mm centres
Facings 2 layers 10 mm Fermacell Board one side
29 45 60
50 mm mineral stone wool density 60 kg/m3 or
Insulation
100 mm mineral stone wool density 30 kg/m3
& Ceilings
Type Timber joisted ceiling systems with a layer of structural overlay board
Floorings
Type Timber joisted ceiling systems with a layer of structural overlay board
2H31
Timber joists with 2 sets of battens min 60 mm x 40 mm, or for lower
Battens
batten steel resilient bar or MF suspended Ceiling at max 350 mm centres
Facings 2 layers 10 mm Fermacell Board one side
38 N/A 90
50 mm mineral stone wool density 80 kg/m3 with wire netting
Insulation
Timber Frames
to hold up insulation
Type Timber joisted ceiling systems with a layer of structural overlay board
Component Details
Installation Overview
Fix & Finish
Performance Details
Wet Areas
Partitions
Construction
from below
Fire Rating
Introduction
SYSTEM SPECIFICATIONS kg/m2 mm mins
2H32
Linings
Facings 2 layers 15 mm Fermacell Board one side
46 ≥60 90
Insulation 2 layers 100 mm mineral stone wool density 30 kg/m3
Type Timber joisted ceiling systems with a layer of structural overlay board
& Ceilings
Floorings
2H33
Battens Timber battens (60/40) or steel acoustic hangers at 350 mm centres
Detailed Overview
Fire Protection
Insulation None
Timber Frames
2H34
Component Details
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 350 mm centres
1 layer 15 mm Fermacell Board plus
Facings
2 layers 12.5 mm Fermacell Board one side 54 ≥65 90
Insulation None
Rainscreens
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 425 mm centres
Facings 4 layers 10 mm Fermacell Board one side
≥65
Installation Overview
54 90
Insulation None
2H41
Timber joists with 2 sets of battens min 60 mm x 40 mm, or for lower
Fix & Finish
Battens
batten steel resilient bar or MF suspended Ceiling at max 350 mm centres
Facings 2 layers 10 mm Fermacell Board one side
38 110 120
50 mm mineral stone wool density 100 kg/m3 with wire netting
Insulation
to hold up insulation
Performance Details
Type Timber joisted ceiling systems with a layer of structural overlay board
Timber joists with 2 sets of battens min 60 mm x 40 mm, or for lower
Battens
batten steel resilient bar or MF suspended Ceiling at max 350 mm centres
Wet Areas
Ceiling Weight
Partitions
Construction
from below
Fire Rating
Introduction
Height
SYSTEM SPECIFICATIONS kg/m2 mm mins
2HD11
Components & Accessories
Type Timber joisted ceiling systems without a layer of structural overlay board
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 500 mm centres
& Ceilings
Floorings
Type Timber joisted ceiling systems without a layer of structural overlay board
2HD12
Detailed Overview
Fire Protection
Type Timber joisted ceiling systems without a layer of structural overlay board
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 500 mm centres
Timber Frames
Type Timber joisted ceiling systems without a layer of structural overlay board
2HD13
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 400 mm centres
Facings 1 layer 10 mm Fermacell Board one side
Rainscreens
16 35 30
Insulation Optional
Installation Overview
Type Timber joisted ceiling systems with a layer of structural overlay board
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 500 mm centres
Facings 1 layer 12.5 mm Fermacell Board one side
19 40 30
Insulation None Required
Fix & Finish
Type Timber joisted ceiling systems with a layer of structural overlay board
* Roofing Battens
Performance Details
Wet Areas
Ceiling Weight
Partitions
Construction
from below
Fire Rating
Introduction
Height
SYSTEM SPECIFICATIONS kg/m2 mm mins
2HD21
Linings
MF suspended ceiling at max 400 mm centres
Facings 2 layers 10 mm Fermacell Board one side
29 45 60
Insulation Optional
Type Timber joisted ceiling systems with a layer of structural overlay board
Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 500 mm centres
& Ceilings
Floorings
Facings 2 layers 12.5 mm Fermacell Board one side
35 50 60
Insulation Optional
Type Timber joisted ceiling systems with a layer of structural overlay board
Detailed Overview
2HD34
Fire Protection
* Timber battens min 48 mm x 24 mm, steel resilient bar or
Battens
MF suspended ceiling at max 500 mm centres
1 layer 15 mm Fermacell Board plus
Facings
2 layers 12.5 mm Fermacell Board one side 54 ≥65 90
Insulation None
Type Timber joisted ceiling systems without a layer of structural overlay board
Timber battens min 48 mm x 24 mm, steel resilient bar or
Timber Frames
Battens
MF suspended ceiling at max 3500 mm centres
Component Details
Facings 4 layers 10 mm Fermacell Board one side
54 ≥65 90
Insulation None
Type Timber joisted ceiling systems without a layer of structural overlay board
* Roofing Battens
Rainscreens
Installation Overview
Wet Areas
FerMaCell FlOOrING
Element Weight
Point Loading
Partitions
Performance
from above
Admissible
Fire Rating
Thickness
Thermal
Introduction
[1/Δ]
SYSTEM SPECIFICATIONS kN/m2 kN mm mins
m2K/W
2E11
Components & Accessories
0.23 2* 20 30 0.06
Areas of Application 1 + 2
2E22
Type 25 mm dry flooring element
& Ceilings
Floorings
0.29 3* 25 60 0.075
Areas of Application 1 + 2 + 3
Detailed Overview
2E13
Fire Protection
2E14
Timber Frames
2E31
20 mm element dry flooring elements +
Rainscreens
Type
10 mm wood fibre insulating slab 0.25 3 30 90 0.26
Areas of Application 1 + 2 + 3
Installation Overview
OPTION
Include 35 mm element - using 25 mm dry flooring
Type
2 layers 12.5 mm Fermacell Board 0.25 3 35 90 0.26
Areas of Application 1 + 2 + 3
Fix & Finish
2E32
20 mm dry flooring element +
Type
10 mm mineral wool insulating slab 0.25 1 30 90 0.31
Areas of Application 1
OPTION
Performance Details
Areas of Application 1
* Where the flooring elements are laid directly onto a concrete or stable base, then
the point loading increases as follows:
2E11 - 3.0kN
2E22 - 4.0kN
Point Loading
Partitions
Performance
from above
Admissible
Fire Rating
Thickness
Element
Thermal
Weight
Introduction
[1/Δ]
SYSTEM SPECIFICATIONS kN/m2 kN mm mins
m2K/W
H2O TE Flooring
Linings
for wet areas 0.25 3 25 90 0.15
Areas of Application 1 + 2 + 3
& Ceilings
Floorings
raNGeS OF USe aND aPPlICaTION
Detailed Overview
The addition of extra layers does not restrict the
Fire Protection
Premises and corridors in buildings for habitation, range of use and does not change the resistance
1 hotel bedrooms with bathrooms.
to concentrated loads. If the flooring elements
are laid on top of a concrete slab, the allowable
Offices and corridors, surgeries including wards
2 and waiting rooms and corridors ≤ 50 m2 adjacent concentrated load rating increases to 2.5 kN for
to an apartment, office or similar buildings. the 2E11 flooring elements and to 3.5 kN for the
2E22 flooring elements. The scope of use extends
Timber Frames
Corridors in hotels, retirement homes and boarding to field 3 for 2E11 and to field 4 for 2E22.
3 schools or similar buildings. Treatment and operating
Component Details
rooms not containing any heavy equipment.
Rainscreens
treatment rooms and operating rooms containing
heavy equipment.
Installation Overview
Areas intended for large gatherings of people,
for example: classrooms, auditoria, churches,
4 theatres, cinemas, conference rooms, waiting
rooms, concert halls.
Wet Areas
Overall Thickness
Airborne Sound
Impact Sound
Partitions
Performance
Fire Rating
Insulation
Introduction
DnTw
SYSTEM SPECIFICATIONS mm mins
+ Ctr
(L'n,w)
2FCH21
Components & Accessories
2FCH22
Facings 2 layers 15 mm Fermacell Board one side
Main Floor
with 22 mm chipboard overlay ≥320 60* ≥45 ≤62
Flooring
2E31 or 2E32 Fermacell acoustic flooring element
Solution
Ceiling MF or resilient bar system set at max 400 mm centres
Solution at 90° to joist
Robust Detail compliant * Expected performance
2FCS21
Timber Frames
2FCM21
Installation Overview
Insulation As required
As required
Insulation As required
Performance Details
As required
Overall Thickness
Airborne Sound
Impact Sound
Partitions
Performance
Fire Rating
Insulation
Introduction
DnTw
SYSTEM SPECIFICATIONS mm mins
+ Ctr
(L'n,w)
2FCM22
Linings
Insulation As required
As required
Main Floor Precast concrete floor 300 kg/m² min + 40 mm screed
60 ≥50 ≤62
Flooring
2E31 or 2E32 Fermacell acoustic flooring element
Solution
Ceiling 50 mm x 50 mm timber battens at 400 mm centres.
Solution Min 75 mm ceiling void
& Ceilings
Floorings
Robust Detail compliant Facings 1 layer 10 mm Fermacell Board one side
Insulation As required
As required
Main Floor Precast concrete floor 300 kg/m² min + 40 mm screed
60 ≥50 ≤62
Flooring
2E31 or 2E32 Fermacell acoustic flooring element
Detailed Overview
Solution
Fire Protection
Ceiling
MF ceiling system at 400 mm centres. Min 75 mm ceiling void
Solution
2FCM23
Facings 1 layer 10 mm Fermacell Board one side
Insulation As required
As required
Main Floor Mass concrete floor 300 kg/m² min
Timber Frames
60 ≥45 ≤62
Flooring 2E22 Fermacell flooring element with proprietary hot water floor
Component Details
Solution heating system
Ceiling 50 mm x 50 mm timber battens at 400 mm centres.
Solution Min 75 mm ceiling void
Facings 1 layer 10 mm Fermacell Board one side
Insulation As required
As required
Rainscreens
Flooring 2E22 Fermacell flooring element with proprietary hot water floor
Solution heating system
Ceiling
Installation Overview
MF ceiling system at 400 mm centres. Min 75 mm ceiling void
Solution
2FCM24
Facings 1 layer 10 mm Fermacell Board one side
Insulation As required
As required
Insulation As required
As required
Wet Areas
Introduction 99
Partitions
Education
Introduction
BeaM & COlUMN eNCaSeMeNT
Commercial property
A 30 minute construction is achieved using a single
layer of 10 mm Fermacell for beam and column
Recreation
encasement. Using only a single Hp/A rating,
Linings
Retail the unique composition of Fermacell Boards the
installation time of the encasement systems can
Prisons and detention be reduced by stapling the boards together or to
timber sections and beams.
& Ceilings
Floorings
PERFORMANCE RATINGS
ShaFTWall
20 52
dB dB From simple fire rated independent linings to full
Shaftwall solutions, Fermacell offers a range of
Fire Protection
30 240 performance systems from 30 minutes to 2 hours.
mins mins
Using simple stud systems and standard Fermacell
Boards, without the need for any specialist board,
the Fermacell Shaftwall system offers speed
FERMACELL PERFORMANCE of installation, whilst retaining our excellent
environmental credentials.
Timber Frames
Impact – Severe duty, able to
withstand impact from people as
Component Details
well as objects (door handles etc).
Rainscreens
Load bearing – The composition
of Fermacell allows up 50 kg per
fixing to be hung from Fermacell
using a toggle bolt and 30 kg from
a single screw.
designed by architects
Linings
RMJM.
Partitions
Introduction
Components & Accessories
Linings
& Ceilings
Floorings
Fire Protection
Timber Frames
Component Details
The centre pieces of the building are two art lecture Fermacell Technical Manager Andy Richardson
theatres – each able to accommodate 140 people. commented: "The level of fire protection will
Rainscreens
It also comprises an impressive reception area depend on a number of factors. These include
and restaurant, as well as two exhibition areas. whether the Fermacell Boards are integrated within
Throughout the building are a further three 80 a timber or steel structure, if there is insulation
seater and six 60 seater classrooms, with a host present and the height of the walls. We can react
of inter-changeable rooms available. very quickly to given design requirements and
provide solutions for walls up to 15 metres high.”
Fermacell was not only specified for the internal
Fix & Finish
walling because of its durability and robustness. Simple to install – although the technique is slightly
As with any public building, protection against fire different to plasterboard – Fermacell does not need
was a major consideration when designing a wet plaster skim to produce a suitable surface for
the partitions. Fermacell carries Class O painting. It is inherently stronger than conventional
Performance Details
classification as standard which means that it plasterboard and, as well as its strength and fire
achieves high levels of fire protection. Even with properties, it also provides acoustic, impact and
slim partitions it is possible to achieve up to moisture resistance.
Wet Areas
COMPONENTS ACCESSORIES
Partitions
Fermacell Board
Introduction
Pack Size 5 kg or 20 kg
Fermacell Jointstik
For edge glueing square edged
Fermacell Boards.
Timber Frames
20 lm / 310 ml tube
Coverage 37 lm / bulk applicator refill
Component Details
310 ml tubes or
Pack Size 580 ml bulk applicator refills
Performance Details
Wet Areas
Partitions
Using only a single Hp/A rating, Fermacell’s Steel Solution
Introduction
solution is easier to specify (see tables below).
BEAM ENCASEMENT
The following tables are valid for steel sections Fire resistance category
with a section factor of Hp/A ≤ 300m-1
F 30-A F 60-A F 90-A F 120-A
according to the formula: Hp/A = 2b – 2h – b2
Linings
10 10 + 10 15 + 12.5 18 + 18
Where Hp = Heated perimeter and
Minimum lining thickness for steel girders with Hp/A ≤ 300 m-1
A = Cross Sectional Area of Metal Element
COLUMN ENCASEMENT
Timber Solution
Fire resistance category
& Ceilings
Fire resistance category
Floorings
F 30-A F 60-A F 90-A F 120-A F 180-A
F 30-B F 60-B
Fermacell in mm
Fermacell in mm
2 x 15 +
10 10 + 10 10 2 x 10 4 x 15 5 x 15
1 x 12.5
Minimum lining thickness of timber beams and columns Minimum lining thickness for steel supports with Hp/A ≤ 300 m-1
Fire Protection
Classification to DIN 4102
TYPICAL LAYOUTS
Calculation of board dimensions must take into account the board thickness needed to achieve
Timber Frames
the required fire rating. Support frames must be set at maximum 400mm centres.
Component Details
Rainscreens
Proprietary steel encasement systems are suitable for use with Fermacell. Timber grounds may
be placed in the web as supports. These must be set at a maximum of 400 mm centres.
Fix & Finish
Performance Details
Wet Areas
Staggered joint
BeaM & COlUMN eNCaSeMeNT Encasement of a steel support
≥ 400 mm
for 4-sided exposure to fire
≥ 30 mm
≥ 30 mm
for 4-sided exposure to fire
3 layer steel beam encasement
for 4-sided exposure to fire
≥ 30 mm ≥ 30 mm
& Ceilings
Floorings
Multiple layers can be stapled board to board using proprietary diverging staples, refer to the
Fermacell Dry Lining Walls and Ceilings guide for further details, or contact our Technical Department
on +44 (0) 870 6090 306.
Fire Protection
Component Details
rated mastic. For multiple layer constructions, the outer layer should be jointed with Fermacell Joint
1 layer timber beam lining F 30-B
filler or Jointstik.
for 3-sided exposure to fire
Board Weight
Partitions
from below
Fire Rating
port
Introduction
e
BEAM ENCASEMENT
Linings
11.5 30
Facings 1 layer 10 mm Fermacell Board one side
& Ceilings
Facings
Floorings
1 layer 12.5 mm Fermacell Board one side
For Hp/A > 300m-1 SubFrame Steel clip system, timber grounds
42 120
Facings 2 layers 18 mm Fermacell Board one side
COLUMN ENCASEMENT
Fire Protection
SubFrame Steel clip system, timber grounds or frameless casing
11.5 30
Facings 1 layer 10 mm Fermacell Board one side
Timber Frames
1 layer 12.5 mm Fermacell Board one side
For Hp/A > 300m-1
Component Details
72 120
Facings 4 layers 15 mm Fermacell Board one side
Rainscreens
Fix & Finish
Performance Details
ng F 60-B
e
Wet Areas
Improved Sound
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
Insulation
DIN 4103
BS 5234/
Introduction
3S11
Components & Accessories
Heavy
Facings 1 layer 15 mm Fermacell Board one side 23 3 65 30 20
Severe
Facings 1 layer 15 mm Fermacell Board one side 23 3.5 90 30 20
Severe
Facings 1 layer 15 mm Fermacell Board one side 23 4.1 115 30 20
3S12
Fire Protection
Severe
1 layer 12.5 mm Fermacell Board plus 32 3 72.5 30 N/A
Facings
1 layer 10 mm Fermacell Board one side
Studs 75 mm DIN standard studs @ 600 mm centres
Severe
1 layer 12.5 mm Fermacell Board plus 32 3.5 97.5 30 N/A
Facings
1 layer 10 mm Fermacell Board one side
Studs 100 mm DIN standard studs @ 600 mm centres
Timber Frames
Severe
1 layer 12.5 mm Fermacell Board plus 32 4.5 122.5 30 N/A
Facings
Component Details
3S21
Studs 50 mm DIN standard studs @ 600 mm centres
Performance Details
Wet Areas
Sound Insulation
without Fire Rating
Wall Thickness
Partitions
with Fire Rating
Wall Height
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
SYSTEM SPECIFICATIONS m m mm mins Rw Grade
SHAFTWALL 1
Linings
at max 400 mm centres
Severe
1 layer 15 mm Fermacell Board plus 60/
Facings 6 4 112.5 47
1 layer 12.5 mm Fermacell Board one side 30
SHAFTWALL 2
& Ceilings
Floorings
Back to Back 100 mm x 0.7 mm Shaftwall profile stud
Studs
at max 400 mm centres
Severe
1 layer 15 mm Fermacell Board plus 120/
Facings 6 4 125 52
2 layers 12.5 mm Fermacell Board one side 60
Fire Protection
Fire performance for integrity only 120/120
Back to Back 100 mm x 0.7 mm Shaftwall profile stud
Studs
at max 400 mm centres
Severe
1 layer 15 mm Fermacell Board plus 120/
Facings 6 4 137.5 52
3 layers 12.5 mm Fermacell Board one side 120
Timber Frames
ShaFTWall
Component Details
From simple fire rated independent linings to full shaftwall solutions, Fermacell offers a range of
performance systems from 30 minutes to 2 hours. Using simple stud systems and standard Fermacell
Boards, without the need for any specialist board, the Fermacell Shaftwall system offers speed of
installation, whilst retaining our excellent environmental credentials.
Rainscreens
Fix & Finish
Performance Details
Wet Areas
Introduction 109
Self build
These are more commonly
Partitions
Factory built/Offsite used in domestic applications.
Introduction
Fermacell Timber stud
Education/Healthcare partitions provide versatility
Social housing and performance including
Category 1 racking strength
Linings
for Timber Framed properties.
PERFORMANCE RATINGS
& Ceilings
Floorings
significantly increased speed of fixing.
30 90
mins mins
Detailed Overview
FERMACELL PERFORMANCE Fermacell partitions achieve a number of
Fire Protection
advantages over masonry construction by reducing
the weight, build time and cost often associated
Impact – Severe duty, able to with masonry construction. Fermacell also meets
withstand impact from people as
Part E and a number of Robust Detail Compliant
well as objects (door handles etc).
systems as a gypsum based board.
Acoustics – Greater acoustic
Timber Frames
performance often with less layers raCkING STreNGTh
than plasterboard constructions
providing slimmer partitions.
Testing carried out at the CERAM testing centre
confirmed that Fermacell can replace timber sheet
Loadbearing – The composition
materials when used in timber frame constructions
of Fermacell allows up 50 kg per
fixing to be hung from Fermacell as the racking board adding lateral structural
using a toggle bolt and 30 kg from strength to the building. This means that Fermacell
Rainscreens
a single screw. can be used as a Dry Lining board giving fire and
acoustic properties, and a structural board also
Speed of construction – Fermacell saving time and money on fixing separate gypsum
Performance Details
allows the partitions to be installed and timber sheet materials. The table on page 8
before the building envelope shows the racking test data.
is complete. Due to the unique
finishing system (FST) the overall
installation of Fermacell is faster
Fix & Finish
than plasterboard.
Years of experience in
the European Timer
Partitions
Partitions
Simple single stud solutions with 12.5mm Fermacell to Fermacell offers simple acoustic solutions to
Introduction
each side exceed the Part E requirement of Rw 40dB, Part E, BB93 and HTM requirements. Fermacell
as well as providing a wall ready to accept tiles or a also meets and exceeds Robust Detail compliancy
simple FST and paint finish. This give a 30 minute fire as a gypsum based board due to exceeding
rating and can be fixed to directly for dead loading the mass requirements in thinner board layers.
such as Kitchen Cabinets, shelving, large TV’s etc.
Please refer to screw loading on page 6. BreaThING WallS
Linings
TWIN FraMe SYSTeMS Breathing walls rely on the racking board to be
positioned on the inside of the timber frame,
Fermacell partitions achieve a number of unlike traditional timber frame systems where
advantages over masonry construction by reducing it is normally positioned to the cold cavity side.
& Ceilings
Floorings
the weight, build time and often cost associated A vapour control layer is not needed in a breathing
with masonry construction. wall construction as the structure allows the free
passage of moisture. Such constructions can include
ClOSeD PaNelS aND OPeN PaNelS a natural fibre insulation board or a breather
Detailed Overview
membrane holding the thermal insulation in place.
IN OFFSITe MaNUFaCTUrING
Fire Protection
Using a natural fibre insulation board will add to the
air tightness of the building and will also add to the
Fermacell is produced in a panel size of 6000 mm thermal mass of the building.
x 2540 mm. This gives the flexibility of board sizing
and joint reduction in a factory environment where
exTerNal WallS aND raINSCreeN
processing time is key.
Timber Frames
The ability of Fermacell to withstand a degree of Fermacell has been independently tested as a
moisture lends it to reducing those programme Rainscreen backed board for Vented and Insulated
glitches on site where inclement weather can really systems. Thus the same board can be used on
slow things down. Prefabricated spandrel panels the inside and the outside of the frame. This gives
are already fitted into roof spaces where no weather an inherently greater fire performance at boundary
protection is in place, with no degradation of the conditions, especially where reduced distance
boards. We would always recommend that our between dwellings are now commonplace.
Rainscreens
advice is sought in these matters first as Fermacell
is moisture resistant, not waterproof. raCkING PerFOrMaNCe Performance Details
to timber frame buildings during and after the build, for the substitution of a traditional two layer system
finding a cost effective solution is easy with Fermacell. with a single layer to give structural performance as
Due to it’s moisture resistance, Fermacell can be well as fire, acoustic, hanging and moisture resistance.
installed before the building envelope is complete.
For the minimal risk, Fermacell gives an inherent fire SIPS PaNelS
protection to the timber frame during the build.
As well as then providing an internal lining board to Fermacell can provide additional fire protection to
Wet Areas
all areas for acoustic, hanging, racking and impact SIPS panels. A single layer of 18 mm Fermacell, with
protection. This can have a significant positive effect insulation, gives a loaded 89x38 mm timber frame a
on programme of works on any tightly controlled site. single layer solution, which can be factory fitted as
an added benefit.
Sound Insulation
Wall Thickness
Partitions
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
1H12
Studs 89 mm x 38 mm @ 500 mm centres
Linings
Heavy
Facings 1 layer 10 mm Fermacell Board each side 34 4.1 109 30 44
Heavy
Facings 1 layer 10 mm Fermacell Board each side 35 4.1 95 30 44
1H13
Studs 89 mm x 38 mm @ 600 mm centres
Severe
40 4.1 114 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
Detailed Overview
Severe
Fire Protection
40 4.1 100 30 41
Facings 1 layer 12.5 mm Fermacell Board each side
Severe
46 4.1 105 60 41
Facings 1 layer 15 mm Fermacell Board each side
1H22
Studs 89 mm x 38 @ 600 mm centres
Timber Frames
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 41 4.1 114 60 44
40 mm mineral stone wool density 45 kg/m3 or
Insulation
60 mm mineral stone wool density 30 kg/m3
Insulation 70 mm x 30 kg/m3 47
Insulation 70 mm x 30 kg/m3 47
* For a Fire Performance of a complete wall, please contact the Fermacell Technical Department.
** Up to ΔRw 20dB Sound Improvement as an independant lining.
Wet Areas
Sound Insulation
Wall Thickness
Partitions
Applied Load
Wall Weight
Wall Height
Fire Rating
DIN 4103
BS 5234/
Introduction
kN/
SYSTEM SPECIFICATIONS stud
kg/m2 m mm mins Rw Grade
1HT11
Studs 89 mm x 38 mm @ 600 mm centres
Linings
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 5.56 41 2.6 114 30 44
90 mm mineral stone wool density 10 kg/m3 or
Insulation
40 mm mineral stone wool density 30 kg/m3
Studs 75 mm x 50 mm @ 600 mm centres
Severe
Facings 1 layer 12.5 mm Fermacell Board each side 9.3 40 3 100 30 44
& Ceilings
Floorings
Insulation 40 mm mineral stone wool density 30 kg/m 3
1HT22
Studs 89 mm x 38 mm @ 600 mm centres
Severe
Facings 1 layer 18 mm Fermacell Board each side A 58 3 125 60 ≥46
Detailed Overview
Fire Protection
Insulation 90 mm mineral stone wool density 30 kg/m3
Severe
Facings 1 layer 15 mm Fermacell Board each side 10.8 48 3 150 60 ≥46
Severe
Facings 1 layer 15 mm Fermacell Board each side 10 48 3 150 60 ≥46
Timber Frames
Insulation 140 mm mineral stone wool density 30 kg/m3
Rainscreens
Insulation 2 x 90 mm mineral stone wool density 10 kg/m3
3HT22
Studs 89 mm x 38 mm @ 600 mm centres
1 layer 18 mm Fermacell Board inner side plus
Severe
Facings Timber Sheathing board to 9mm OSB, ply or similar A ≈ 31 3 116 60† ≈ 43
outer side
Insulation 90 mm mineral stone wool density 35 kg/m3
75 mm x 50 mm or 70 mm x 44 mm
Studs
@ 600 mm centres
Severe
A – Loading up to maximum for timber grade stress in accordance with EN 1995-1-1 and EN 1995-1-2
†
Fire rating from Fermacell side only
Introduction 115
Fermacell provides
outstanding performance
Partitions
in new gateway building.
Introduction
More than 20,000 m2 of Fermacell
Boards has been used in the
construction of the new
Linings
£5.6 million Gateway Building
at the University of Cumbria,
Lancaster Campus.
& Ceilings
Floorings
for the internal walls but has
also been utilised as an external
carrier board for the structure’s
Detailed Overview
rainscreen cladding.
Fire Protection
Timber Frames
Fermacell has been widely used in rainscreen
applications on timber frame constructions
throughout Europe for the past 20 years.
Rainscreens
The use of 12.5 mm Fermacell as an external
backer board proved very successful in this
application. It was exposed to the rain for nearly
three months before the rainscreen cladding was
installed and coped admirably with the conditions.
Fix & Finish
INSULATED
Introduction
4
Linings
7
2
6
& Ceilings
Floorings
1
Detailed Overview
3
Fire Protection
Timber Frames
VENTED
4
Rainscreens
7
2
6
Fix & Finish
3
Wet Areas
Fermacell Gypsum Fibreboard has been tested 1. 12.5 mm Fermacell Square edge board
independently for use as a backer board in vented 2. Dry Lining (Fermacell / Internal Lining Board) with
Partitions
rainscreen applications. Testing has shown it to be vapour control layer where required
weather resistant, and that it does not degrade
Introduction
3. Fermacell Jointstik adhesive to horizontal joints
with permanent exposure. Discolouration may and minimum 50 mm foil tape over all joints
occur due to moisture absorption in the board and screws.
surface. A surface treatment or other protection 4. Metal or Timber stud to suit loading requirements.
is recommended for prolonged exposure prior to
5. Head & Foot Track
the installation of the cladding system.
6. Insulation
Linings
Test in accordance with CWCT Standard Test 7. Screws wafer head zinc plated 4.2 mm gauge with
Methods at UKAS accredited facility. 10.5 mm Head. eg Hilti S-DD03Z 4.2 x 25 mm
Taylor Woodrow Technology @ 150 mm c/c.
Leighton Buzzard 8. Anchor Fixing
LU7 4OH
& Ceilings
Floorings
Shown is an indicative cladding system using
Test Sequence brackets and rails, and an insulated system. Suitable
(i) Water tightness : Static system to be specified by architect or specifier
(ii) Air Permeability : Pressure Cycling
Fermacell is not only an excellent Rainscreen backer
Detailed Overview
(iii) Wind Resistance : up to 1.5 kN (+Ve & -Ve)
Fire Protection
(iv) Air Permeability : Pressure Cycling material, Fermacell is also a high performance,
(v) Water tightness : Static multipurpose building board. It combines in a
(vi) Wind Resistance : Above 2.1 kN (+Ve & -Ve) single product exceptional fire, impact and moisture
(vii) Dynamic Water Test : 600 Kpa resistant properties with high levels of acoustic
insulation and weight carrying capacity.
Timber Frames
12.5 mm Fermacell
Fixing type Material condition Applied load
Rainscreens
6 mm Woodscrew Soaked 0.7 KN
15 mm Fermacell
Fixing type Material condition Applied load
Fix & Finish
Introduction 119
Partitions
slightly differently to problems associated with
Introduction
traditional plasterboard; traditional Dry Lining methods.
thus speeding up the The screw retention capabilities of
installation time by Fermacell allows most fixtures to be fitted
Linings
directly to the board (see table below).
and providing a more user
friendly finishing system BOarD FITTING
with our FST (Fine Surface Fermacell Boards are cut and fitted in a similar way
Treatment).
& Ceilings
to plasterboard eliminating the need for specialist
Floorings
tools and skills.
Detailed Overview
Fire Protection
Fermacell's Joint filler or Jointstik provides quicker
and more simple application versus traditional Dry
Lining methods; with Jointstik a stronger joint can be
achieved without the need for further reinforcement.
SUrFaCe FINISh
Timber Frames
With Fermacell’s FST (Fine Surface Treatment) a skim
plaster type finish can be achieved in a fraction of the
time without the need of specialist skills; allowing the
experienced tradesman, self builder or DIY enthusiast
to achieve a flawless finish.
Rainscreens
LOAD-CARRYING CAPACITY OF FERMACELL WALLS
Fermacell Loadbearing strength in kg (2)
Gypsum
Installation Overview
Fibreboards
(thickness) (1)
Picture hooks fixed by nails Screw Toggle
with cont. Bolt/
thread Cavity
5 mm Fixing (4)
Fix & Finish
dia. (3)
10 mm 15 25 35 20 40
12.5 mm 17 27 37 30 50
12.5 + 10 mm 20 30 40 35 60
Wet Areas
15 mm 18 28 38 30 55
18 mm 20 30 40 35 60
(1) Maximum stud centres = 50 x board thickness. N.B. Where fixings are less
than 500 mm apart, reduce the load per fixing by 50%. If a stud support
separates the fixings, then use the full loadbearing strength shown above.
(2) Safety factor: 2 (Static load with relative humidity of up to 85%).
(3) Depth of cupboard or shelves: max. 350 mm.
(4) Standard toggle bolt with > 4 mm dia. screw. (The toggle bolt
manufacturer’s instruction should be followed.)
COMPONENTS ACCESSORIES
Partitions
Fermacell Board
Introduction
Pack Size 5 kg or 20 kg
Fermacell Jointstik
For edge glueing square edged
Fermacell Boards.
Timber Frames
20 lm / 310 ml tube
Coverage 37 lm / bulk applicator refill
310 ml tubes or
Pack Size 580 ml bulk applicator refills
Partitions
Electric Screwdriver
directly bonded, or mounted on a SFS frame to
exterior walls.
Introduction
Electric screwdriver with a minimum speed
of 3500 rpm. A cordless screwdriver may
be used, but check the speed first. Slower
speed tools may cause lipping when
installing boards on steel studwork.
GeNeral SITe GUIDelINeS.
Linings
If using staples or nails, a pneumatic gun
and compressor operating at 7 bar will be
needed. (This equipment is available from Fermacell Boards should be fixed at a mean relative
many hire centers).
humidity of ≤80% and a room temperature of
+5° C. The temperature of the adhesive should
be +10° C.
& Ceilings
Floorings
Plumb Line
Plumb line or long spirit level. The boards must be acclimatised to the installation
area, and in the 12 hours after jointing the relative
room climate should not change significantly.
Lower temperatures prolong curing times.
Detailed Overview
Fire Protection
Mastic Gun Filling joints with Joint filler and the application
Mastic gun for Jointstik tubes. of FST should only be carried out at a mean
relative humidity of ≥70% (corresponding to a
board moisture content of ≤1.3%), and the room
temperature should be +5° C.
Timber Frames
Decorator’s Scraper
Decorator’s scraper or similar for removing Wet trades or wet screeding, or asphalting should
excess Fermacell Jointstik (after curing). be completed prior to joint filling.
The adhesive method of jointing can be used
prior to these applications, however, check
with the our Technical Department first on
Taping knife +44 (0) 870 6090 306.
Taping knife or plastering trowel for
applying Fermacell Joint filler to the joint.
Rainscreens
Gas burner heating can damage the boards due
to the risk condensation and thermal shock. This
applies particularly to cold interiors with poor
Installation Overview
Rigid Bladed Scoring Knife ventilation. Rapid heating, which can result in
Rigid bladed scoring knife, such as a thermal shock, must be avoided.
Fermacell knife, for scoring and snapping
the boards.
Fix & Finish
Steel Trowel
A steel trowel for applying Fermacell FST
(Fine Surface Treatment). Special Fermacell
applicators are available from selected
distributors.
FINIShING
Partitions
Introduction
Components & Accessories
Linings
& Ceilings
Floorings
Detailed Overview
Fire Protection
A plaster is not normally recommended as the Fermacell Boards can be painted directly. Refer to
same finish can be achieved using FST, which is our instruction manual for recommendations for
much faster and a fraction of the cost. Where joint treatment in this case. Fermacell FST gives
a skim is to be used, for whatever reason, our a smooth surface ready to accept a paint finish.
recommendation is that the boards should be Typically a mist coat and two undiluted top coats
sealed with a Board Sealer or High Suction Plaster are required. Where vinyl or oil based paints are
Primer, as recommended by the skim manufacturer. to be used without the prior application of FST,
Rainscreens
Fibre tape must be applied to all joints, and a we recommend the boards are sealed first.
test area of at least 1 m2 should be completed
Installation Overview
first, to confirm compatibility / suitability. We do not recommend the use of eggshell paint
finishes. However, where eggshell paints are used,
a minimum of two coats of FST must be applied
first, followed by a sealant. In all cases, refer to
Fix & Finish
FINIShING
Partitions
Introduction
Components & Accessories
Linings
& Ceilings
Floorings
Detailed Overview
Fire Protection
TIlING that require sealing must be protected against
the penetration of water to a height of 2000 mm
Timber Frames
above the bath floor, with adequate spacing above
Before tiling, all areas should be clean and free
the actual shower and bath areas. For showers,
from dust. If a priming coat is required, this should
waterproofing must extend to at least 300 mm
be allowed to dry for 24 hours before tiling work
above the shower head.
starts.
Rainscreens
recommended that all walls in any shower or
with a waterproofing system such as the Fermacell
bathroom are sealed against rising moisture
Waterproofing system. This is a paintable system Installation Overview
to a height of 150mm. In all cases refer to
suitable for use with cement based adhesives. Tile
manufacturers instructions. Fermacell recommends
adhesives with a low water content should be used
a maximum tile size of 300 mm x 300 mm.
and tiles fixed with a thin bead adhesive method,
For larger tiles please contact our Technical
without pre-wetting.
Department on +44 (0) 870 6090 306.
Fix & Finish
1. STUDWORK
Partitions
If you are using a steel subframe, a minimum Allow for full height stud every 500 mm of wall
50 mm fixing face and a 0.6 mm gauge stud length when using 1500 mm x 1000 mm one-
Introduction
must be used, with associated head and floor man boards, or every 600 mm of wall length
track to suit. when using other sizes in 12.5 mm thickness or
If you are using timber for the subframe, you every 400 mm of wall length when using
will need (75 mm x 50 mm) P.S.E. well seasoned 10 mm thickness, plus one extra stud for the
timber for both the vertical studwork and the final wall fix. Allow two times the wall length
head and floor track. An 89 mm x 38 mm studs for the head and floor tracks. In all cases ensure
may be used, but only with the adhesive or that studwork spacing is suitable for the size
Components & Accessories
2. FIxING
For the steel frame use ≥ 40 mm screws with For timber frame use ≥ 80 mm screws with wall
wall plugs (if appropriate) for fixing head and plugs (if appropriate) for fixing head and floor
floor tracks, and end studs to the existing tracks and end studs to the existing structure.
structure. Allow for fixing frame anchors at ≤ Allow for fixing frame anchors at ≤ 600 mm
& Ceilings
Floorings
600mm centres. Intermediate studs are not centres. Use 100 mm round headed nails for
fixed to the head and floor track. screw fixing the studs to the head and sole
plate (3 per fixing, 6 per stud).
Detailed Overview
Fire Protection
For most general applications we recommend This grade of insulation gives excellent all round
40 mm thick, 45 kg/m3 mineral fibre insulation thermal and acoustic properties and when used
in batt or roll form. The width of the insulation in conjunction with 12.5 mm board provides
should match the stud spacing (see note 1). F60 partitions (see Fermacell systems 1S21and
1H22).
Timber Frames
4. FERMACELL BOARDS
Fermacell Boards available in both Square and Our Tapered edge boards are designed to
Tapered edge (2 sides and 4). For board sizes accommodate a joint reinforcement tape as with
Rainscreens
please refer to board size table on page 8. traditional Dry Lining. Once the tape has been
Square edge boards can be easily fitted and bedded into place and the Tapered area filled
finished using Fermacell Jointstik and Fine and the Fermacell Filler is set the entire surface is
Installation Overview
5. FERMACELL SCREWS
The boards should be screwed to the studs or Nails should be galvanised, 45 mm long and a
frame using Fermacell screws (3.9 x 30 mm) at minimum of 2.2 mm gauge. Staples and nails
250 mm centres along the studs. Staples should should be fixed at 200 mm centres. Refer to
be 38 mm long, have a head width of 10mm the fixings tables for specific fixings information
and be a minimum of 1.4 mm gauge. dependant on Fermacell thickness and
application. Fixings should be 10 mm from the
edge of the board, and 50 mm from corners.
Wet Areas
For screw spacing and usage for wall and ceilings please refer to our Dry Lining Wall & Ceilings Guide.
Fermacell Boards are fixed at the following maximum screw centres:-
(1) Wall 250 mm
(2) Ceiling 200 mm
6 FERMACELL JOINTSTIK
Partitions
Jointstik is used for gluing square edge boards Because the adhesive expands on contact with
together. Each cartridge will cover 20 linear air, the bead should be applied to the edge of
Introduction
meters of joint using a 3 mm bead. This equates square edge boards and not the ‘V’ between
to approximately 8 boards. the tapers of Tapered edge boards.
Fermacell Jointstik adhesive is applied to the If the bead is applied incorrectly, excess Jointstik
edge of the board in a continuous 3 mm bead may be trapped between board and subframe
prior to fixing the next board. causing subsequent lipping.
Linings
7 FERMACELL JOINTSTIK
Once Jointstik is applied the next board is then Any greater than this may result in weaker
fitted to the subframe, spreading the adhesive joints. If Jointstik has been for a long period
across the face of the board edge and ensuring it may be hard to remove, a Surform or any
a tight fit of less than 1 mm. Allow the adhesive similar tool may be used to remove it. The joint
& Ceilings
Floorings
to harden fully before attempting to remove and screw heads should then be filled with
any excess (typically 24 hours). Once hardened, Fermacell Joint Filler. All joints above 2500 mm
the excess can be struck off with a decorator's partition height must be jointed using Jointstik
scraper. There is no requirement for noggings or reinforced with noggings. Horizontal joints
behind these joints. The final gap between are jointed in the same manner as vertical
boards with Jointstik should be less than 1 mm. Joints.
Detailed Overview
Fire Protection
8 FERMACELL JOINT FILLER
A hard filler used for jointing Tapered edge If using Tapered edge boards, jointing tape
boards, jointing the gaps between cut edges will be required. We recommend a paper tape
and for filling screw heads. As well as an rather than a self adhesive fibre tape as this
alternative to Jointstik when using square edge gives a stronger joint. When using Fermacell
boards. Joint Filler for Tapered edge boards, allow 1 kg
*For double layers systems the base layer should be per 4 meters of joint length, and 1 kg per 7–8
Timber Frames
square edged Fermacell. If Tapered edge Fermacell meters of joint length for jointing off cuts.
is used as a base layer then all joints must be filled
with Fermacell filler, prior to fitting the outer layer
of board.
Rainscreens
Edge boards and off cuts. Where square edge boards
or offcuts are installed prior to jointing, a 5 – 7 mm
gap is left between boards, which is then filled with
Installation Overview
Fermacell Joint Filler ensuring that the joint filler is
pushed fully through the gap. (Fermacell Jointstik
adhesive is not a gap filler). The filler can then be
rubbed down prior to final decoration. Ensure filled
joints are backed/supported.
Fix & Finish
10 FLExIBLE SEALANT
For use in sealing the gap between boards and The edges of the boards must be primed prior
other material surfaces such as walls, floors to application, and the sealant should be fire or
and ceilings. Typically, this should be where acoustic rated as required.
any building movement is expected on internal
corners or abutments. Typically a 3 – 5 mm gap
should be left.
Wet Areas
≥ 200 mm
Floorings
4 5
Fire Protection
vertically.
Diagram C
Isolation Strips
1 2 3
Typically strips 50 mm to 75 mm
wide and 10 mm thick, these
should be sized to suit the wall
thickness. These can be either
purchased as a roll or may be
offcuts from the insulation material
Timber Frames
edge boards 3 5
Tapered edge boards are fitted to Joint variation 1: Two factory Tapered edge
the subframe with the board edges boards with Fermacell Jointing Tape and
touching. The boards are jointed Fermacell Joint Filler
using Fermacell Joint Filler and is
applied to the joint, ensuring that
the central ‘V’ of the joint is fully
Fix & Finish
Partitions
Fixing Fermacell to Walls Length (mm) Spacing (mm) Use (no./m2) Length (mm) Spacing (mm) Use (no./m2)
Metal – single-layer
Introduction
10 mm – – – 30 250 26
12.5 mm – – – 30 250 20
15 mm – – – 30 250 20
18 mm – – – 40 250 20
Metal – 2 layered /
2nd. layer into the stud
Linings
2nd Layer: 10 mm or 12.5 mm – – – 40 250 20
1st Layer: 15 mm – – – 30 400 12
2nd Layer: 12.5 mm or 15 mm – – – 40 250 20
Wood – single layer
10 mm ≥30 200 32 30 250 26
12.5 mm ≥35 200 24 30 250 20
15 mm ≥44 200 24 40 250 20
Wood – 2 layered /
& Ceilings
Floorings
2nd. layer into the stud
1st Layer: 12.5 mm ≥35 400 12 30 400 12
2nd Layer: 10 mm or 12.5 mm ≥50 200 24 40 250 20
Detailed Overview
Fire Protection
Wall zone per m2 wall surface Length (mm) Spacing (mm) Use (no./m2) Length (mm) Spacing (mm) Use (no./m2)
Timber Frames
Fixing Fermacell to Ceilings Length (mm) Spacing (mm) Use (no./m2) Length (mm) Spacing (mm) Use (no./m2)
Metal – single-layer
10 mm – – – 30 200 22
12.5 mm – – – 30 200 19
15 mm – – – 30 200 16
Metal – double-layer /
2nd layer into the sub-structure
1st Layer: 10 mm – – – 30 300 16
2nd Layer: 10 mm – – – 40 200 22
Rainscreens
1st Layer: 12.5 mm – – – 30 300 14
2nd Layer: 12.5 mm – – – 40 200 19
1st Layer: 15 mm – – – 30 300 12
Installation Overview
Timber – double-layer /
2nd layer into the sub-structure
1st Layer: 10 mm ≥30 300 16 30 300 16
2nd Layer: 10 mm ≥44 150 30 40 200 22
1st Layer: 12.5 mm ≥35 300 14 30 300 14
2nd Layer: 12.5 mm ≥50 150 25 40 200 19
1st Layer: 15 mm ≥44 300 12 40 300 12
2nd Layer: 12.5 mm or 15 mm ≥60 150 22 40 200 16
Wet Areas
FINIShING
gives a fast and easy equivalent that this dry Apply straight from the tub using a trowel or
in 45 minutes, ready to accept a paint finish.
Introduction
dirt. Any damage or indentations must be filled removed. The FST will dry within 45 minutes and
Linings
with Fermacell Joint filler and allowed to dry. subsequent layers can be applied as required.
Before any decoration, the moisture content If necessary, smooth the surface with ‘fine 240
of the boards must be less than 1.3%. This grit’ sandpaper, prior to final decoration. For
moisture content will be achieved automatically larger projects or modular applications, FST
within 48 hours if the relative humidity of the is available in a sprayable format for use with
airless spray equipment. Spray nozzle sizes
& Ceilings
over 15°C and the boards are stored off the should be 431-435 (i.e. a 40° spray angle with
ground in well ventilated conditions. an opening size of 31-35).
Installation Overview
Fix & Finish
Wet Areas
CreaTING COrNerS
Partitions
There are a number of ways to construct an
Introduction
internal corner depending on the installers Leave a 3-5 mm gap the gap at the junction
preference. between the boards the gap is filled using a
flexible filler.
FerMaCell TO exISTING
SUBSTraTeS A paper jointing tape, if desired, can be bedded
Linings
Leave a 3 -5 mm gap between the Femacell and Joint Filler.
other building backgrounds, the gap can then
be filled with a flexible decorators’ filler and over Once the filling material and tape (if used)
coated with Fermacell Fine Surface Treatment had dried the corner is then over coated with
(FST) at the same time as finishing coat is Fermacell Fine Surface Treatment (FST) at the
& Ceilings
same time as the rest of the boards.
Floorings
applied to the boards.
exTerNal COrNerS
FerMaCell TO FerMaCell USING
FerMaCell JOINT FIller Fermacell boards are strong enough to
Detailed Overview
Fire Protection
withstand day to day impacts on external
Leave a 5-7 mm gap at the junction between corners with out the requirement of additional
the boards, the gap is filled using Fermacell corner protection.
Joint Filler
To create an external corner the boards should
A paper jointing tape, if desired, can be bedded be aligned flush and fixed to the stud using
over the filled gap using an additional coat of Fermacell screws or staples with timber studs
Timber Frames
Fermacell Joint Filler. and secured with Fermacell Jointstik.
Once the filling material and tape (if used) Once the Jointstik is dry it can then be struck
had dried the corner is then over coated with off and any deviation dressed with Fermacell
Fermacell Fine Surface Treatment (FST) at the Joint Filler. A final coat of Fermacell Fine Surface
same time as the rest of the boards. Treatment is then applied the corner at the same
time as the rest of the board.
Rainscreens
Alternatively the boards are fixed to the studs Installation Overview
Introduction 131
Partitions
New build a challenge for the developer.
Introduction
Factory built Fermacell has four options for exposure to
water and moisture.
Recreation
Linings
PERFORMANCE RATINGS In general domestic applications and where the
relative humidity does not exceed 80% or where
49 60 protection from water is provided by tiles, regular
dB dB
Fermacell Gypsum Fibreboards can be used in
& Ceilings
Floorings
partitions and linings.
30 120
mins mins
Detailed Overview
FERMACELL PERFORMANCE
Fire Protection
For shower and wet areas in commercial and
Impact – Severe duty, able to domestic applications, Fermacell Powerpanel H2O
withstand impact from people as board provides an impervious to water solution. H2O
well as objects (door handles etc). boards can also be used for semi exposed external
applications such as soffits.
Acoustics – Greater acoustic
Timber Frames
performance often with less layers
than plasterboard constructions FerMaCell POWerPaNel hD BOarDS
Component Details
providing slimmer partitions.
Fermacell Powerpanel HD Boards are for external
Loadbearing – Fermacell gives cladding on timber-framed construction providing
a category 1 racking strength. weatherproofing, structural rigidity, fire
Powerpanel HD and Fermacell also
protection and sound proofing.
provide structural solutions to Euro
Rainscreens
Code 5.
FerMaCell GYPSUM FIBreBOarDS Installation Overview
Speed of construction – Fermacell WITh FerMaCell WaTerPrOOFING
allows the partitions to be installed
before the building envelope SYSTeM
is complete. Due to the unique
finishing system (FST) the overall
The Fermacell Waterproofing system is for surface
installation of Fermacell is faster
Fix & Finish
Leisure Centre.
Introduction
Detailed Overview
Fire Protection
Timber Frames
Partitions
Introduction
Components & Accessories
Linings
& Ceilings
Floorings
Detailed Overview
Fire Protection
Timber Frames
FaCIlITIeS Brian Dukes, Site Agent for main contractors
Component Details
Galliford Try, commented: “We specified the use
The main entrance to the Centre leads directly to of Fermacell’s H2O board on this project. One
the main foyer space which contains a dramatic of its strengths is that it is ideally suited to the
climbing wall, reception and café with views environment.
directly into the pool area and up to the fitness
suite above. The reception area leads to a multi Internally Fermacell Boards (with glued joints)
Rainscreens
purpose room providing facilities for dance, were used by the sub contractor for Galliford
exercise classes, soft play and functions. There is Try, providing lightweight walls achieving all the Installation Overview
also a pool, wet health, sports hall and changing requirements for fire, acoustics and severe duty
facilities on this floor. rating using a single board rather than using
many different combination of boards with
A large changing village with facilities for group other systems. This enabled partition walls to
and accessible changing leads to a 25 m x 5-lane be constructed both rapidly and to the required
Fix & Finish
level deck Community Pool, a separate 13 m standard providing a very high quality, robust finish
x 7 m level deck Studio Pool, with movable floor throughout the first floor. A high standard of finish
for flexibility of use and the Wet Health Suite which is provided poolside with the H2O readymixed
includes two Spa Pools, a Steam Room and Sauna. surface finish.
Spectator access to the main pool is provided direct
from the café area.
Wet Areas
Standard Fermacell Boards have a high vapour special primers. This makes standard Fermacell
Introduction
resistively capability and can perform up to relative Boards a cost effective and simple solution for
humidity up to 80%. around bath areas that are tiled full height.
Making them versatile for domestic usage in Wet areas and painted areas – Standard Fermacell
kitchens and bathrooms, the boards themselves Boards can be waterproofed using the Fermacell
Components & Accessories
are ready to accept a tiled finish with no need for Waterproofing system with the following products:
Linings
PRIMER SEALER
The Fermacell Waterproofing application:
• impermeable to water
& Ceilings
timber studs.
Coverage
For watertight corner and
20 m2 walls
joint protection
22 m2 ceilings
Pack size
500 (35 mm)
500 (50 mm)
Rainscreens
Installation Overview
2000 mm
300 mm
Fix & Finish
For waterproofing
Fermcell boards in
splashback areas, and
for sealing internal corners
with Powerpanel H2O 150 mm
– Splashback Area
Partitions
resistance. They are used as a supporting, structural
and stiffening sheathing in external wall cassettes
Introduction
Fermacell Powerpanel H2O is a cement-bonded
to provide racking against wind loads, buckling and
light concrete construction board with a laminated
vertical loading.
structure, reinforced on both sides with an alkali-
resistance glass fibre mesh (5 mm x 5 mm), it is non
The mineral composition of Fermacell Powerpanel
combustible and conforms to construction material
Linings
combustible – in accordance with DIN 4102.
Powerpanel H2O is a water resistant board for wet
areas and domestic bathrooms as well as showers,
wet areas and kitchens in commercial, education RENDER FINISH TO POWERPANEL HD
and healthcare projects. Fermacell HD
& Ceilings
Joint Reinforcement
Floorings
Tape
The properties of Powerpanel H2O means it can also
be used in swimming pools, in this instance special Fermacell
HD Adhesive Fermacell HD
treatment of steel profiles is required. Building Board
Detailed Overview
Fire Protection
The Fermacell Waterproofing system can be
used to further enhance the performance of the
Powerpanel H2O system.
Timber Frames
to our flooring range enabling the complete
Component Details
waterproof construction of wet areas including
preformed drainage and shower tray outlets.
FerMaCell POWerPaNel
hD BOarDS
Rainscreens
Fermacell HD Boards are cement-bonded, glass
fibre–reinforced sandwich boards with an
Installation Overview
Fermacell HD
essential characteristics required in external
Reinforcing
cladding are combined in a single component. Mesh
External render is applied directly to the board. (embedded)
No composite thermal insulation substrate is Finishing coats
required. During construction the boards seal of Fermacell HD
the building envelope even without rendering, Light Render or a
proprietary render
and can be stored outside.
Wet Areas
Jointing technique
(1) Fermacell HD Joint Reinforcement Tape Fermacell HD
Introduction
Render system
(1) Fermacell HD Light Render for applying a full
Components & Accessories
(e.g. horizontal
timber boards)
Ventilated cavity
Vertical battening
Fermacell HD
Detailed Overview
Fire Protection
Building Board
Vapour barrier
Timber Frames
Fermacell Gypsum
Fibreboard
Component Details
≥ 100
Masonry facade/
outer leaf
Installation Overview
≥ 20 ≥ 30
Air cavity
Building Board
Vapour barrier
Fermacell Gypsum
Wet Areas
Fibreboard
CUTTING BOARDING
Partitions
Powerpanel H2O boards Install insulation (if
can be cut in a similar required) making sure
Introduction
way to regular Fermacell that there is a cavity
Boards either using a between the insulation
standard rail guided hand and one face of the
held circular saw with a Powerpanel H2O boards.
tungsten tipped blade or Cut the boards 10 mm
cut by lightly scoring with less than the room height
a Stanley knife. and install tight to the
Linings
FIxING JOINTING
& Ceilings
Floorings
using Fermacell H2O to the edge of the board
screws at ≤ 250 mm and position the next
centres or staple at board once the Jointstik
≤200 mm centres. has dried (approx 8
hours) remove the excess
with a scraping knife.
Detailed Overview
Fire Protection
FINISHING
Timber Frames
Where the Powerpanel
H2O boards are not being
tiled the whole surface can
Component Details
be finished with Fermacell
Powerpanel H2O. Surface
Finish which is available
ready mixed. The joints
can be further reinforced
with a self adhesive
fibre tape.
Prior to tiling in
Rainscreens
permanently wet areas
Powerpanel H2O boards
must be sealed with
Installation Overview
www.fermacell.com
FC-022-00016/k/06.13