BS5308 Part 1 Type 2
BS5308 Part 1 Type 2
BS5308 Part 1 Type 2
Application
7
These cables are designed to connect electrical instrument circuits and provide communication services in and around process
plants (e.g. petrochemical industry etc.). Suitable for direct buried applications.
8
9 Specifications
• In accordance with BS 5308 Part 1. • Mild galvanised steel wires to BS EN10257-1.
10 • Conductors: Solid (Class 1), stranded (Class 2) or • Outer Sheath: PVC outer sheath Type TM.1 to BS EN
flexible (Class 5) copper conductors to BS EN 60228. 50363-4-1. In addition, outer sheath displays following
• Insulation: Polythene insulation Type 03 to BS6234. characteristics:
11 Minimum oxygen index: 30%.
• Pair Identification: See colour code chart 1 page 4:22.
Maximum HCL Emission @ 800°C: 15%.
• 100mm maximum pair lay length (minimum 10 twists
12 • Flame retardant to BS EN 60332-3-24 & IEC60332-3-24
per metre).
Category C (NMV1.5).
• Binder Tape: p.e.t.p. tape 50% overlap.
• Voltage Rating: 300/500V.
13 • Collective Screen: tinned copper drain wire(s) under
• Temperature Rating: 65°C maximum conductor
and in contact with aluminium/p.e.t.p. laminated tape
operating temperature.
14 applied metallic side down.
• Polythene bedding Type 2C or 03 to BS6234.
15
16
17
18
19
18
19
ELECTRICAL CHARACTERISTICS
3
MAXIMUM MUTUAL CAPACITANCE VALUES
Conductor Size
4
0.5mm2 pF/m 0.75mm2 pF/m 1.0mm2 pF/m 1.5mm2 pF/m 2.5mm2 pF/m
Cables without Screens 75 75 75 85 85
5
Cables with Collective Screen Only 75 75 75 85 85
except 1 pair, 2 pair and 1 triple)
One Pair, One Triple and Two Pair 115 115 115 120 120
6
Collectively Screened and all Cables
with individually Screened Pairs
7
MAXIMUM D.C. CONDUCTOR RESISTANCE @ 20°C
Conductor Size Conductor Stranding Resistance @ 20ºC 8
Maximum
mm2 #/mm Ω/km 9
0.5 1/0.8 36.8 pF/m = pico Farads per metre
0.5 16/0.2 39.7 Ω/km = ohms per km
10
0.75 24/0.2 26.5 µH/Ω = micro Henrys per ohm
1.0 1/1.13 18.4
1.5 7/0.53 12.3 11
2.5 7/0.67 7.56