Manual de Variador Bombas Ingles
Manual de Variador Bombas Ingles
To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
Receiving 1
Mechanical Installation 2
Electrical Installation 3
Start-Up Programming &
Operation 4
Troubleshooting 5
Periodic Inspection &
Maintenance 6
Peripheral Devices &
Options 7
Specifications A
Parameter List B
MANUAL NO. TOEP YAIP1U 01C Standards Compliance C
Copyright © 2012 YASKAWA AMERICA, INC.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise,
without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the
information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality
products, the information contained in this manual is subject to change without notice. Every precaution has
been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this
publication.
Quick Reference
Easily Set Parameters for Specific Applications
Preset parameter defaults are available for setting up applications. Refer to Application Selection on
page 92.
Perform Auto-Tuning
Automatic tuning sets motor parameters. Refer to Auto-Tuning on page 120.
Standards Compliance
Refer to European Standards on page 246 and Refer to UL and CSA Standards on page 254 <1> .
<1> CE marking applies to 200 V class and 400 V class models only.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 3
This Page Intentionally Blank
4 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
Table of Contents
QUICK REFERENCE ...................................................................................... 3
1. RECEIVING ................................................................................................... 21
1.1 Model Number and Nameplate Check ..................................................................... 22
Nameplate ............................................................................................................................. 22
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 5
Table of Contents
10 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
i
Preface & General Safety
This section provides safety messages pertinent to this product that, if not heeded, may result in fatality,
personal injury, or equipment damage. Yaskawa is not responsible for the consequences of ignoring
these instructions.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 11
i.1 Preface
i.1 Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and
application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no
responsibility for the way its products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all
controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment
designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and
instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to
the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and
specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its
products.
This manual is designed to ensure correct and suitable application of drives. Read this manual before attempting to install,
operate, maintain, or inspect a drive and keep it in a safe, convenient location for future reference. Be sure you understand all
precautions and safety information before attempting application.
Applicable Documentation
The following manuals are available for P1000 series drives:
P1000 Series AC Drive Quick Start Guide (TOEPYAIP1U01)
Read this guide first. This guide is packaged together with the product and contains basic information
required to install and wire the drive. It also gives an overview of fault diagnostics, maintenance, and
parameter settings. The purpose of this guide is to prepare the drive for a trial run with an application and
for basic operation. This manual is available for download on our documentation website,
www.yaskawa.com.
P1000 Series AC Drive Technical Manual (SIEPYAIP1U01)
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/
Modbus specifications. Use this manual to expand drive functionality and to take advantage of higher
performance features. This manual is available for download on our documentation website,
www.yaskawa.com.
12 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
i.2 General Safety
WARNING
Read and understand this manual before installing, operating or servicing this drive. The drive must be installed according
to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result
in serious or fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 13
i.2 General Safety
Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in
this manual.
Electrical Shock Hazard
Before servicing, disconnect all power to the equipment.
The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish
when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait for at least the time specified on the warning label,
once all indicators are OFF, measure for unsafe voltages to confirm the drive is safe prior to servicing.
Failure to comply will result in death or serious injury.
WARNING
Sudden Movement Hazard
System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the drive, motor and machine area before applying power. Secure covers, couplings, shaft keys and
machine loads before applying power to the drive.
Electrical Shock Hazard
Do not attempt to modify or alter the drive in any way not explained in this manual.
Failure to comply could result in death or serious injury.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and service must be performed only by authorized personnel familiar with installation,
adjustment and maintenance of AC drives.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Make sure the protective earthing conductor complies with technical standards and local safety regulations.
Because the leakage current exceeds 3.5 mA in models 4A0414 and larger, IEC/EN 61800-5-1 states that either the power
supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective
earthing conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result
in death or serious injury.
Always use appropriate equipment for Ground Fault Circuit Interrupters (GFCIs).
The drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual current
operated protective or monitoring device is used for protection in case of direct or indirect contact, always use a type B GFCI
according to IEC/EN 60755.
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Install adequate branch circuit protection according to applicable local codes and this Installation Manual. Failure
to comply could result in fire and damage to the drive or injury to personnel.
14 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
i.2 General Safety
WARNING
The device is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 240 Vac
maximum (200 V class) and 480 Vac maximum (400 V class), and 600 Vac maximum (600 V class) when protected by
branch circuit protection devices specified in this document.
Crush Hazard
Do not use this drive in lifting applications without installing external safety circuitry to prevent accidental dropping
of the load.
The drive does not possess built-in load drop protection for lifting applications.
Failure to comply could result in death or serious injury from falling loads.
Install electrical and/or mechanical safety circuit mechanisms independent of drive circuitry.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards. Failure to
comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test or megger test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment. Do not connect or operate any equipment with visible
damage or missing parts.
If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the
peripheral devices.
Check for short circuits or ground faults on the secondary side of fuses and GFCIs and check the wiring and the selection of
peripheral devices. Remove the cause of the problem and then turn the power supply off and on again. If the cause cannot
be identified, do not turn on the power supply or attempt to operate the equipment.
Do not restart the drive immediately operate the peripheral devices if a fuse is blown or a GFCI is tripped.
Check the wiring and the selection of peripheral devices to identify the cause. Contact your supplier before restarting the
drive or the peripheral devices if the cause cannot be identified.
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized. Do not sterilize the entire package after
the product is packed.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 15
i.2 General Safety
• when the drive is running from a power supply system with thyristor converters.
Note: A DC link choke is built in to drive models 2A0110 to 2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242.
Power Supply
Capacity (kVA)
600
Reactor
unnecessary
0
60 400
Drive Capacity (kVA)
Drive Capacity
For specialized motors, make sure that the motor rated current is less than the rated output current for the drive.
When running more than one motor in parallel from a single drive, the capacity of the drive should be larger than [total motor
rated current × 1.1].
Starting Torque
The overload rating for the drive determines the starting and accelerating characteristics of the motor. Expect lower torque
than when running from line power. To achieve a higher starting torque, use a larger drive or a drive and motor with larger
capacity.
Emergency Stop
During a drive fault condition, the output shuts off but the motor does not stop immediately. A mechanical brake may be
required when it is necessary to stop the motor faster than the ability of the Fast Stop function of the drive.
Options
NOTICE: The B1, B2, ⊖, ⊕1, ⊕2, and ⊕3 terminals are used to connect optional drive-specific compatible devices only. Connecting non-
Yaskawa-approved devices to these terminals may damage the drive.
Repetitive Starting/Stopping
Laundry machines, punching presses, and other applications with frequent starts and stops often approach 150% of their rated
output current values. Heat stress generated from repetitive high current will shorten the life span of the IGBTs.
Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. It is beneficial to
reduce the load, increase the acceleration and deceleration times, or switch to a larger drive to help keep peak current levels
under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during the initial test run, and
make adjustments accordingly.
Installation
Enclosure Panels
Keep the drive in a clean environment by installing the drive in an enclosure panel or selecting an installation area free of
airborne dust, lint, and oil mist. Be sure to leave the required space between drives to provide for cooling, and take proper
measures so the ambient temperature remains within allowable limits and keep flammable materials away from the drive.
Yaskawa offers protective designs for drives that must be used in areas subjected to oil mist and excessive vibration. Contact
Yaskawa or your Yaskawa agent for details.
Installation Direction
NOTICE: Install the drive upright as specified in the manual. Refer to the Mechanical Installation section for more information on installation.
Failure to comply may damage the drive due to improper cooling.
Settings
Upper Limits
NOTICE: The drive is capable of running the motor up to 400 Hz. Be sure to set the upper limit for the frequency of the drive to prevent the
possible danger of accidentally operating equipment at higher than rated speed. The default setting for the maximum output frequency is
60 Hz.
DC Injection Braking
NOTICE: Excessive current during DC Injection Braking and excessive duration of DC Injection Braking can cause motor overheat.
16 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
i.2 General Safety
Acceleration/Deceleration Times
Acceleration and deceleration times are affected by the amount of torque generated by the motor, the load torque, and the
moment of inertia. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for
as long as the Stall Prevention function is in operation. Install one of the available braking options or increase the capacity of
the drive for faster acceleration and deceleration.
General Handling
Wiring Check
NOTICE: Do not connect power supply lines to output terminals U/T1, V/T2, or W/T3. Failure to comply will destroy the drive. Be sure to
perform a final check of all sequence wiring and other connections before turning on the power and also check for short circuits on the
control terminals, which may damage the drive.
Selecting a Circuit Breaker or Circuit Interrupter
Yaskawa recommends installing a Ground Fault Circuit Interrupter (GFCI) to the power supply side. The GFCI should be
designed for use with AC drives (e.g., Type B according to IEC 60755).
Select a Molded Case Circuit Breaker (MCCB) or GFCI with a rated current 1.5 to 2 times higher than the drive rated input
current to avoid nuisance trips caused by harmonics in the drive input current.
Magnetic Contactor Installation
WARNING! Fire Hazard. Shut off the drive with a magnetic contactor (MC) when a fault occurs in any external equipment such as braking
resistors. Failure to comply may cause resistor overheating, fire, and injury to personnel.
NOTICE: To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power supply
off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.
Inspection and Maintenance
WARNING! Electrical Shock Hazard. Capacitors in the drive do not immediately discharge after shutting off the power. Wait for at least the
amount of time specified on the drive before touching any components after shutting off the power. Failure to comply may cause injury to
personnel from electrical shock.
WARNING! Burn Hazard. Because the heatsink can get very hot during operation, take proper precautions to prevent burns. When replacing
the cooling fan, shut off the power and wait at least 15 minutes to be sure that the heatsink has cooled down. Failure to comply may cause
burn injury to personnel.
Wiring
Yaskawa recommends using ring terminals on all drive models. Drive models 2A0069 to 2A0415, 4A0058 to 4A1200, and
5A0041 to 5A0242 require the use of use ring terminals for UL/cUL compliance. Use only the tools recommended by the
terminal manufacturer for crimping.
Transporting the Drive
NOTICE: Never steam clean the drive. During transport, keep the drive from coming into contact with salts, fluorine, bromine, phthalate
ester, and other such harmful chemicals.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 17
i.2 General Safety
3 6 20 60
Frequency (Hz)
Insulation Tolerance
NOTICE: Consider motor voltage tolerance levels and motor insulation in applications with an input voltage of over 440 V or particularly
long wiring distances.
High-Speed Operation
NOTICE: Problems may occur with the motor bearings and dynamic balance of the machine when operating a motor beyond its rated speed.
Contact the motor or machine manufacturer.
Torque Characteristics
Torque characteristics differ compared to operating the motor directly from line power. The user should have a full
understanding of the load torque characteristics for the application.
Vibration and Shock
The drive allows selection of high carrier PWM control and low carrier PWM. Selecting high carrier PWM can help reduce
motor oscillation.
Take particular caution when adding a variable speed drive to an application running a motor from line power at a constant
speed. If resonance occurs, install shock-absorbing rubber around the base of the motor and enable the Jump frequency selection
to prevent continuous operation in the resonant frequency range.
Audible Noise
The audible noise of the motor varies based on the carrier frequency setting. However, drive current derating may be required.
When using a high carrier frequency, audible noise from the motor is comparable to the motor noise generated when running
from line power.
Synchronous Motors
• Contact Yaskawa or a Yaskawa agent when planning to use a synchronous motor not endorsed by Yaskawa.
• Use a standard induction motor when running multiple synchronous motors simultaneously. A single drive does not have
this capability.
• A synchronous motor may rotate slightly in the opposite direction of the Run command at start depending on parameter
settings and rotor position.
• The amount of generated starting torque differs depending on the control mode and motor type. Set up the motor with the
drive after verifying the starting torque, allowable load characteristics, impact load tolerance, and speed control range.
Contact Yaskawa or a Yaskawa agent when planning to use a motor that does not fall within these specifications:
• To restart a coasting motor rotating over 200 Hz while in V/f Control, first use the Short Circuit Braking function to bring
the motor to a stop. Short Circuit Braking requires a special braking resistor. Contact Yaskawa or a Yaskawa agent for
details.
• To restart a coasting motor rotating below 200 Hz, use the Speed Search function if the motor cable is not too long. If the
motor cable is relatively long, stop the motor using Short Circuit Braking.
Specialized Motors
Multi-Pole Motor
The rated current of a multi-pole motor differs from that of a standard motor, so be sure to check the maximum current when
selecting a drive. Always stop the motor before switching between the number of motor poles. The motor will coast to stop if
a regenerative overvoltage (ov) fault occurs or if overcurrent (oC) protection is triggered.
18 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
i.2 General Safety
Submersible Motor
The rated current of a submersible motor is greater than that of a standard motor, so select the drive accordingly. Use a motor
cable large enough to avoid decreasing the maximum torque level from voltage drop caused by a long motor cable.
Explosion-Proof Motor
The motor and the drive must be tested together to be certified as explosion-proof. The drive is not designed for explosion-
proof areas.
When attaching an encoder to an explosion-proof motor, make sure the encoder is also explosion-proof. Use an insulating
signal converter to connect the encoder signal lines to the speed feedback option card.
Geared Motor
Make sure that the gear and the lubricant are rated for the desired speed range to avoid gear damage when operating at low
speeds or very high speeds. Consult with the manufacturer for applications that require operation outside the rated speed range
of the motor or gear box.
Single-Phase Motor
Variable speed drives are not designed to operate with single phase motors. Using capacitors to start the motor causes a high-
frequency current to flow to the capacitors and can damage the capacitors. A split-phase start or a repulsion start can burn out
the starter coils because the internal centrifugal switch is not activated. The drive is for use with three-phase motors only.
Motor with Brake
Take caution when using the drive to operate a motor with a built-in holding brake. If the brake is connected to the output side
of the drive, it may not release at start due to low voltage levels, so be sure to install a separate power supply for the motor
brake. Note that motors with built-in brakes tend to generate a fair amount of noise when running at low speeds.
Notes on Power Transmission Machinery
Installing an AC drive in machinery that was previously connected directly to the power supply will allow the machine to
operate at variable speeds. Continuous operation outside of the rated speeds can wear out lubrication material in gear boxes
and other power transmission parts. Make sure that lubrication is sufficient within the entire speed range to avoid machine
damage. Note that operation above the rated speed can increase the noise generated by the machine.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 19
i.2 General Safety
WARNING
Risk of electric shock.
●
Read manual before installing.
●
Wait 5 minutes for capacitor
discharge after disconnecting
power supply.
●
To conform to requirements,
make sure to ground the supply
neutral for 400V class.
●
After opening the manual switch
between the drive and motor,
please wait 5 minutes before
inspecting, performing
maintenance or wiring the drive.
Hot surfaces
●
Top and Side surfaces may
become hot. Do not touch.
Warning Label
Warranty Information
Restrictions
The drive is not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or
health.
Customers who intend to use the product described in this manual for devices or systems relating to transportation, health
care, space aviation, atomic power, electric power, or in underwater applications must first contact their Yaskawa
representatives or the nearest Yaskawa sales office.
WARNING! Injury to Personnel. This product has been manufactured under strict quality-control guidelines. However, if this product is to
be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility
where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.
20 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
1
Receiving
This chapter explains how to inspect the drive upon receipt, and gives an overview of the different
enclosure types and components.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 21
1.1 Model Number and Nameplate Check
Nameplate
200/400 V Class A
600 V Class A
H MODEL : CIMR-PU5A0003FAA REV : A
C/C : CIMR-PU5A0003FAA
G INPUT : AC3PH 500-600V 50/60Hz 3. 6A
IND.CONT.EQ.
F OUTPUT : AC3PH 0-600V 0-400Hz 2. 7A
7J48 B
MASS : 3.4 kg PRG : 8500 B
E O / N : 6W3050-2-100 VAJ123456
D S / N : J0073D207410100
22 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
1.1 Model Number and Nameplate Check
CIMR - P U 2 A 0021 F A A
Drive P1000 No. Customized Enclosure Design
Series Specifications No. Type <1> Revision
A Standard model IP00/Open Order
Region A
No. Type
Code
U USA IP20/NEMA
No. Voltage Class F
Type 1
2 3-phase, 200-240 Vac
4 3-phase, 380-480 Vac Environmental
No.
5 3-phase, 500-600 Vac Specification <2>
A Standard
K Gas-resistant
M Humidity- and
dust-resistant
N Oil-resistant
S Vibration-resistant
<1> Refer to Mechanical Installation on page 26 for differences regarding enclosure protection types and component
descriptions.
<2> Drives with these specifications do not guarantee complete protection for the environmental conditions indicated.
Three-Phase 200 V Class
Drive Model Max. Motor Capacity kW (HP) Rated Output Current A
2A0004 0.75 (0.75) 3.5
2A0006 1.1 (1) 6.0
2A0008 1.5 (2) 8.0
2A0010 2.2 (3) 9.6
2A0012 3.0 (3) 12
2A0018 3.7 (5) 17.5
Receiving
2A0021 5.5 (7.5) 21
2A0030 7.5 (10) 30
2A0040 11 (15) 40
2A0056 15 (20) 56
2A0069 18.5 (25) 69 1
2A0081 22 (30) 81
2A0110 30 (40) 110
2A0138 37 (50) 138
2A0169 45 (60) 169
2A0211 55 (75) 211
2A0250 75 (100) 250
2A0312 90 (125) 312
2A0360 110 (150) 360
2A0415 110 (175) 415
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 23
1.1 Model Number and Nameplate Check
24 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2
Mechanical Installation
This chapter explains how to properly mount and install the drive.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 25
2.1 Mechanical Installation
Installation Environment
Install the drive in an environment matching the specifications in Table 2.1 to help prolong the optimum performance life of
the drive.
Table 2.1 Installation Environment
Environment Conditions
Installation Area Indoors
-10 °C to +40 °C (IP20/NEMA 1, UL Type 1 enclosure)
-10 °C to +50 °C (IP00/Open Type enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
Ambient Temperature When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity 95% RH or less and free of condensation
Storage Temperature -20 to +60 °C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
Surrounding Area • combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude 1000 m or lower, up to 3000 m with derating
10 to 20 Hz at 9.8 m/s2 (32.15 ft/s2) <1>
Vibration 20 to 55 Hz at 5.9 m/s2 (19.36 ft/s2) (Models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0099) or
2.0 m/s2 (6.56 ft/s2) (Models 2A0250 to 2A0415, 4A0208 to 4A1200, and 5A0125 to 5A0242)
Orientation Install the drive vertically to maintain maximum cooling effects.
<1> Models 4A0930 and 4A1200 are rated at 5.9 m/s2 (19.36 ft/s2)
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to erroneous
operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply
could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before
drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
NOTICE: Install the drive upright as specified in the manual. Failure to comply may damage the drive due to improper cooling.
26 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2.1 Mechanical Installation
A C
D D
B B C
A
Note: IP20/NEMA 1, UL Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive
for installation.
Mechanical Installation
Line up the tops of the drives.
Side Clearance Top/Bottom Clearance
A C A D
B D
B
A A
A – 50 mm minimum C – 2 mm minimum
B – 30 mm minimum D – 120 mm minimum
Figure 2.3 Space Between Drives (Side-by-Side Mounting)
Note: Align the tops of the drives when installing drives of different heights in the same enclosure panel. Leave space between the tops and bottoms
of stacked drives for easier cooling fan replacement.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 27
2.1 Mechanical Installation
Remove the top protective covers of all drives as shown in Figure 2.4 when mounting IP20/NEMA 1, UL Type 1 enclosure
drives side-by-side. Refer to Top Protective Cover on page 54 to remove and reattach the top protective cover.
A B C D
28 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2.1 Mechanical Installation
Eye bolt
Mechanical Installation
2
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 29
2.1 Mechanical Installation
3. Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight.
4. Lower the drive when ready to install in the enclosure panel. Stop lowering the drive when it is near the floor then
begin lowering the drive again very slowly until the drive is placed correctly.
30 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2.1 Mechanical Installation
W1 4-d W1 4-d
t2
H4
H0
H1
H0
H
H
H1
H2
H3
H2
H3
t1
t1
D1 D1
W D Max.W2 W Max.W2 D
Figure 1 Figure 2
Mechanical Installation
140 300 147 122 260 248 6 40 1.5 38 5 3.4
2A0010F – – M5
(5.51) (11.81) (5.79) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (1.50) (0.20) (7.5)
140 300 147 122 260 248 6 40 1.5 38 5 3.4
2A0012F – – M5
(5.51) (11.81) (5.79) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (1.50) (0.20) (7.5)
140 300 164 122 260 248 6 40 1.5 55 5 3.8
2A0018F – – M5
1 (5.51) (11.81) (6.46) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (8.2)
<1>
140 300 164 122 260 248 6 40 1.5 55 5 3.8
2A0021F – – M5
(5.51) (11.81) (6.46) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (8.2)
140 300 167 122 260 248 6 40 1.5 55 5 4.2
2A0030F
(5.51) (11.81) (6.57) (4.80)
–
(10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20)
– M5
(9.3)
2
140 300 167 122 260 248 6 40 1.5 55 5 4.2
2A0040F – – M5
(5.51) (11.81) (6.57) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (9.3)
180 340 187 160 300 284 7.9 40 1.5 75 5 5.9
2A0056F – – M5
(7.09) (13.39) (7.36) (6.30) (11.81) (11.18) (0.31) (1.57) (0.06) (2.95) (0.20) (13.0)
220 400 197 192 350 335 7.9 50 1.5 78 5 9
2A0069F – – M6
(8.66) (15.75) (7.76) (7.56) (13.78) (13.19) (0.31) (1.97) (0.06) (3.07) (0.20) (20.1)
220 400 197 192 350 335 7.9 50 1.5 78 5 10
2A0081F – – M6
(8.66) (15.75) (7.76) (7.56) (13.78) (13.19) (0.31) (1.97) (0.06) (3.07) (0.20) (22.0)
254 534 258 195 7.9 400 385 7.7 134 1.5 100 2.2 2.286 23
2A0110F M6
(10.00) (21.02) (10.16) (7.68) (0.31) (15.75) (15.16) (0.30) (5.28) (0.06) (3.94) (0.09) (0.09) (50.7)
279 614 258 220 7.9 450 435 7.7 164 100 2.2 2.286 28
2A0138F – M6
2 (10.98) (24.17) (10.16) (8.66) (0.31) (17.72) (17.13) (0.30) (6.46) (3.94) (0.09) (0.09) (61.7)
<1>
329 730 283 260 7.9 550 535 7.7 180 110 2.2 2.286 41
2A0169F – M6
(12.95) (28.74) (11.14) (10.24) (0.31) (21.65) (21.06) (0.30) (7.09) (4.33) (0.09) (0.09) (90.4)
329 730 283 260 7.9 550 535 7.7 180 110 2.2 2.286 42
2A0211F – M6
(12.95) (28.74) (11.14) (10.24) (0.31) (21.65) (21.06) (0.30) (7.09) (4.33) (0.09) (0.09) (92.6)
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 31
2.1 Mechanical Installation
Dimensions mm (in)
Drive Model Figure
Wt. kg
W H D W1 W2 H0 H1 H2 H3 H4 D1 t1 t2 d (lb)
Dimensions below are the dimensions of IP00/Open Type models after customer installation of the appropriate IP20/NEMA 1, UL Type 1 Kit.
456 960 330 325 7.9 28 680 12 255 130 3.3 3.3 83
2A0250A – M10
(17.95) (37.80) (12.99) (12.80) (0.31) (27.76) (26.77) (0.49) (10.04) (5.12) (0.13) (0.13) (183.0)
456 960 330 325 7.9 28 680 12 255 130 3.3 3.30 88
2A0312A 2 – M10
(17.95) (37.80) (12.99) (12.80) (0.31) (27.76) (26.77) (0.49) (10.04) (5.12) (0.13) (0.13) (194.0)
194 1168 35 370 7.9 800 773 13 368 130 4.6 4.6 108
2A0360A – M12
(19.84) (45.98) (13.78) (14.57) (0.31) (31.50) (30.43) (0.51) (14.49) (5.12) (0.18) (0.18) (238.1)
<1> Removing the top protective cover from an IP20/NEMA 1, UL Type 1 enclosure drive voids NEMA 1, UL Type 1 protection while retaining IP20
conformity.
Table 2.3 Dimensions for IP20/NEMA 1, UL Type 1 Enclosure: 400 V Class
Dimensions mm (in) Wt. kg
Drive Model Figure
W H D W1 W2 H0 H1 H2 H3 H4 D1 t1 t2 d (lb)
140 300 147 122 260 248 6 40 1.5 38 5 3.4
4A0002F – – M5
(5.51) (11.81) (5.79) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (1.50) (0.20) (7.5)
140 300 147 122 260 248 6 40 1.5 38 5 3.4
4A0004F – – M5
(5.51) (11.81) (5.79) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (1.50) (0.20) (7.5)
140 300 147 122 260 248 6 40 1.5 38 5 3.4
4A0005F – – M5
(5.51) (11.81) (5.79) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (1.50) (0.20) (7.5)
140 300 164 122 260 248 6 40 1.5 55 5 3.6
4A0007F – – M5
(5.51) (11.81) (6.46) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (7.9)
140 300 164 122 260 248 6 40 1.5 55 5 3.8
4A0009F – – M5
(5.51) (11.81) (6.46) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (8.2)
1 140 300 164 122 260 248 6 40 1.5 55 5 3.8
4A0011F <1> – – M5
(5.51) (11.81) (6.46) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (8.2)
140 300 167 122 260 248 6 40 1.5 55 5 4.0
4A0018F – – M5
(5.51) (11.81) (6.57) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (9.0)
140 300 167 122 260 248 6 40 1.5 55 5 4.0
4A0023F – – M5
(5.51) (11.81) (6.57) (4.80) (10.24) (9.76) (0.24) (1.57) (0.06) (2.17) (0.20) (9.0)
180 340 167 160 300 284 7.9 40 1.5 55 5 5.8
4A0031F – – M5
(7.09) (13.39) (6.57) (6.30) (11.81) (11.18) (0.31) (1.57) (0.06) (2.17) (0.20) (12.6)
180 340 187 160 300 284 7.9 40 1.5 75 5 6.0
4A0038F – – M5
(7.09) (13.39) (7.36) (6.30) (11.81) (11.18) (0.31) (1.57) (0.06) (2.95) (0.20) (13.2)
220 400 197 195 35 335 7.9 50 1.5 78 5 8.8
4A0044F – – M6
(8.66) (15.75) (7.76) (7.68) (13.78) (13.19) (0.31) (1.97) (0.06) (3.07) (0.20) (19.2)
254 465 258 195 7.9 400 385 7.7 65 100 2.2 2.2 23
4A0058F – M6
(10.00) (18.31) (10.16) (7.68) (0.31) (15.75) (15.16) (0.30) (2.56) (3.94) (0.09) (0.09) (50.7)
279 515 258 220 7.9 450 435 7.7 65 100 2.2 2.2 27
4A0072F – M6
(10.98) (20.28) (10.16) (8.66) (0.31) (17.72) (17.13) (0.30) (2.56) (3.94) (0.09) (0.09) (59.5)
329 630 258 260 7.9 509 495 7.7 120 105 2.2 3.3 39
4A0088F – M6
2 (12.95) (24.80) (10.16) (10.24) (0.31) (20.08) (19.49) (0.30) (4.72) (4.13) (0.09) (0.13) (86.0)
<1>
329 630 258 260 7.9 509 495 7.7 120 105 2.2 3.3 39
4A0103F – M6
(12.95) (24.80) (10.16) (10.24) (0.31) (20.08) (19.49) (0.30) (4.72) (4.13) (0.09) (0.13) (86.0)
329 730 283 260 7.9 550 535 7.7 180 110 2.2 2.2 45
4A0139F – M6
(12.95) (28.74) (11.14) (10.24) (0.31) (21.65) (21.06) (0.30) (7.09) (4.33) (0.09) (0.09) (99.2)
329 730 283 260 7.9 550 535 7.7 180 110 2.2 2.2 46
4A0165F – M6
(12.95) (28.74) (11.14) (10.24) (0.31) (21.65) (21.06) (0.30) (7.09) (4.33) (0.09) (0.09) (101.4)
Dimensions below are the dimensions of IP00/Open Type models after customer installation of the appropriate IP20/NEMA 1, UL Type 1 Kit.
456 960 330 325 7.9 28 680 12 255 130 3.3 3.3 87
4A0208A – M10
(17.95) (37.80) (12.99) (12.80) (0.31) (27.76) (26.77) (0.49) (10.04) (5.12) (0.13) (0.13) (191.8)
194 1168 35 370 7.9 800 773 13 368 130 4.6 4.6 106
4A0250A – M12
(19.84) (45.98) (13.78) (14.57) (0.31) (31.50) (30.43) (0.51) (14.49) (5.12) (0.18) (0.18) (233.7)
2
194 1168 35 370 7.9 800 773 13 368 130 4.6 4.6 112
4A0296A – M12
(19.84) (45.98) (13.78) (14.57) (0.31) (31.50) (30.43) (0.51) (14.49) (5.12) (0.18) (0.18) (246.9)
194 1168 35 370 7.9 800 773 13 368 130 4.6 4.6 117
4A0362A – M12
(19.84) (45.98) (13.78) (14.57) (0.31) (31.50) (30.43) (0.51) (14.49) (5.12) (0.18) (0.18) (257.9)
<1> Removing the top protective cover from an IP20/NEMA 1, UL Type 1 enclosure drive voids NEMA 1, UL Type 1 protection while retaining IP20
conformity.
32 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2.1 Mechanical Installation
Mechanical Installation
456 960 330 325 7.9 28 680 12 255 130 3.3 3.3 87
5A0145A – M10
(17.95) (37.80) (12.99) (12.80) (0.31) (27.76) (26.77) (0.49) (10.04) (5.12) (0.13) (0.13) (191.8)
2
194 1168 35 370 7.9 800 773 13 368 130 4.6 4.6 106
5A0192A – M12
(19.84) (45.98) (13.78) (14.57) (0.31) (31.50) (30.43) (0.51) (14.49) (5.12) (0.18) (0.18) (233.7)
194 1168 35 370 7.9 800 773 13 368 130 4.6 4.6 117
5A0242A – M12
(19.84) (45.98) (13.78) (14.57) (0.31) (31.50) (30.43) (0.51) (14.49) (5.12) (0.18) (0.18) (257.9)
<1> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA 1, UL Type 1 enclosure drive voids NEMA 1, UL Type 1
protection while maintaining IP20 conformity.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 33
2.1 Mechanical Installation
Ød7
Ød5 Ød7
D2
D1
D1
D1
D2
D3
D3
D2
D3
D
D
W1 W1
Figure 1
Figure 2
Figure 3
W W W W Ød5
W1 W1 Ød5 W1 W1 W W
Ød5
W2 W2 W2 W2 W1 W1
Ød6
Ød6 Ød6
Ød7
D1
D1
D1
D2
D3
D2
D2
D3
D3
Ød7
D
D
D
Figure 6
Figure 4 Figure 5
W W W W
W2 Ød5
W W W1 W1
Ød5
W1 W4 W1 W1 Ød5 W4 W4
W3 W3 Ød6 Ød6
W2 W2 Ød6 W3
Ød7
D1
D1
D2
D2
D1
D3
D2
D3
D3
D4
D
D
D
W2 W2 Ød7
W3 W3 Ød7 Figure 9
Figure 8
Figure 7
34 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2.1 Mechanical Installation
Mechanical Installation
43 38 38 41 71 79 23 36
4A0005F – – – – –
(1.7) (1.5) (1.5) (1.6) (2.8) (3.1) (0.9) (1.4)
43 56 38 41 71 79 23 36
4A0007F 1 – – – – –
(1.7) (2.2) (1.5) (1.6) (2.8) (3.1) (0.9) (1.4)
43 56 38 41 71 79 23 36
4A0009F – – – – –
(1.7) (2.2) (1.5) (1.6) (2.8) (3.1) (0.9) (1.4)
43 56 38 41 71 79 23 36
4A0011F – – – – –
(1.7) (2.2) (1.5) (1.6) (2.8) (3.1) (0.9) (1.4)
4A0018F
43
(1.7)
56
(2.2)
38
(1.5)
– – –
41
(1.6)
71
(2.8)
79
(3.1)
–
23
(0.9)
36
(1.4)
– 2
25 76 56 48 84 53 36 23 43
4A0023F – – – –
(1.0) (3.0) (2.2) (1.9) (3.3) (2.1) (1.4) (0.9) (1.7)
25 76 56 48 84 53 36 23 43
4A0031F – – – –
(1.0) (3.0) (2.2) (1.9) (3.3) (2.1) (1.4) (0.9) (1.7)
2
28 79 64 51 86 56 36 23 43
4A0038F – – – –
(1.1) (3.1) (2.5) (2.0) (3.4) (2.2) (1.4) (0.9) (1.7)
28 79 64 51 86 56 36 23 43
4A0044F – – – –
(1.1) (3.1) (2.5) (2.0) (3.4) (2.2) (1.4) (0.9) (1.7)
86 99 38 23 99 43 25 61 28 51
4A0058F – – –
(3.4) (3.9) (1.5) (0.9) (3.9) (1.7) (1.0) (2.4) (1.1) (2.0)
3
89 99 41 23 99 43 25 61 28 51
4A0072F – – –
(3.5) (3.9) (1.6) (0.9) (3.9) (1.7) (1.0) (2.4) (1.1) (2.0)
84 104 23 99 66 25 51 61 28
4A0088F – – – –
(3.3) (4.1) (0.9) (3.9) (2.6) (1.0) (2.0) (2.4) (1.1)
6
84 104 23 99 66 25 51 61 28
4A0103F – – – –
(3.3) (4.1) (0.9) (3.9) (2.6) (1.0) (2.0) (2.4) (1.1)
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 35
2.1 Mechanical Installation
Note: Removing the top protective cover or bottom conduit bracket from an IP20/NEMA 1, UL Type 1 enclosure drive voids NEMA 1, UL Type
1 protection while maintaining IP20 conformity.
36 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2.1 Mechanical Installation
W1 4-d
t2
H1
H
H1
H
t1
H2
D1
D1 t1
H2
D Max W2 W Max W2 D
Max W2 W Max W2
Figure 1
Figure 2
W1 6-d
W3 W3 t2
W1
W3 W4 W3 8-d t2
H1
H
H1
H
t1
H2
D1 t1
H2
D D1
Max W2 W Max W2 Max W2 W Max W2 D
Mechanical Installation
Figure 3 Figure 4
2A0312A
<1>
450
(17.72)
705
(27.76)
330
(12.99)
325
(12.80)
10
(0.39)
680
(26.77)
12
(0.49)
130
(5.12)
3.3
(0.13)
3.3
(0.13)
M10
80
(176.4)
2
1
2A0360A 500 800 350 370 10 773 13 130 4.6 4.6 98
M12
<1> (19.69) (31.50) (13.78) (14.57) (0.39) (30.43) (0.51) (5.12) (0.18) (0.18) (216.1)
<1> Customers may convert these models to IP20/NEMA 1, UL Type 1 enclosures using an IP20/NEMA 1, UL Type 1 Kit.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 37
2.1 Mechanical Installation
4A0362A 500 800 350 370 10 773 13 130 4.6 4.6 107
– – M12
<1> (19.69) (31.50) (13.78) (14.57) (0.39) (30.43) (0.51) (5.12) (0.18) (0.18) (235.9)
500 950 370 370 7.9 923 13 135 4.6 4.6 125
4A0414A 2 – – M12
(19.69) (37.40) (14.57) (14.57) (0.31) (36.34) (0.51) (5.31) (0.18) (0.18) (275.6)
670 1140 370 440 6 220 1110 15 150 4.6 4.6 216
4A0515A – M12
(26.38) (44.88) (14.57) (17.32) (0.24) (8.66) (43.70) (0.59) (5.91) (0.18) (0.18) (476.2)
3
670 1140 370 440 6 220 1110 15 150 4.6 4.6 221
4A0675A – M12
(26.38) (44.88) (14.57) (17.32) (0.24) (8.66) (43.70) (0.59) (5.91) (0.18) (0.18) (487.2)
1250 1380 370 1110 6 330 440 1345 15 150 4.6 4.6 545
4A0930A 4 M12
(49.21) (54.33) (14.57) (43.70) (0.24) (13.00) (17.32) (52.95) (0.59) (5.91) (0.18) (0.18) (1201.5)
1250 1380 370 1110 6 330 440 1345 15 150 4.6 4.6 555
4A1200A 4 M12
(49.21) (54.33) (14.57) (43.70) (0.24) (13.00) (17.32) (52.95) (0.59) (5.91) (0.18) (0.18) (1223.6)
<1> Customers may convert these models to IP20/NEMA 1, UL Type 1 enclosures using an IP20/NEMA 1, UL Type 1 Kit.
Table 2.8 Dimensions for IP00/Open Type Enclosure: 600 V Class
Drive Dimensions mm (in) Wt. kg
Figure
Model W H D W1 W2 W3 W4 H1 H2 D1 t1 t2 d (lb)
5A0125A 450 705 330 325 10 680 12.4 130 3.3 3.3 79
– – M10
<1> (17.72) (27.76) (12.99) (12.80) (0.39) (26.77) (0.49) (5.12) (0.13) (0.13) (174.2)
5A0145A 450 705 330 325 10 680 12.4 130 3.3 3.3 79
– – M10
<1> (17.72) (27.76) (12.99) (12.80) (0.39) (26.77) (0.49) (5.12) (0.13) (0.13) (174.2)
1
5A0192A 500 800 350 370 10 773 13 130 4.6 4.6 107
– – M12
<1> (19.69) (31.50) (13.78) (14.57) (0.39) (30.43) (0.51) (5.12) (0.18) (0.18) (235.9)
5A0242A 500 800 350 370 10 773 13 130 4.6 4.6 107
– – M12
<1> (19.69) (31.50) (13.78) (14.57) (0.39) (30.43) (0.51) (5.12) (0.18) (0.18) (235.9)
<1> Customers may convert these models to IP20/NEMA 1, UL Type 1 enclosures using an IP20/NEMA 1, UL Type 1 Kit.
38 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
2.1 Mechanical Installation
2A0250A
2A0312A
100-054-503
2A0360A
4A0208A
4A0250A Refer to IP20/NEMA 1, UL Type 1 Enclosure
4A0296A 100-054-504 Drives on page 31 for drive dimensions with the
IP20/NEMA 1, UL Type 1 Kit installed.
4A0362A
5A0125A
100-054-503
5A0145A
5A0192A
100-054-504
5A0242A
Mechanical Installation
2
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 39
2.1 Mechanical Installation
40 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3
Electrical Installation
This chapter explains proper procedures for wiring the control circuit terminals, motor, and power
supply.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 41
3.1 Standard Connection Diagram
42 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.1 Standard Connection Diagram
<12>
Terminals -, +1, +2, B1, B2 are DC link choke <1>
for connection options. Never (option) FU
connect power supply lines to U X FV M
these terminals Jumper Braking resistor
(option) <2> FW Cooling fan
Main 2 1 - B1 B2
U
Three-Phase
Switch Fuse Main Circuit U/T1
V/T2 V
Power Supply R
200 to 600 V EMC R/L1
S S/L2 M
W
50/60 Hz
(Depending on T
model capacity)
Filter
T/L3 P1000 Drive W/T3
Electrical Installation
Resolution = 10 bit plus sign
Termination resistor
(120 Ω, 1/2 W)
DIP
R
Switch S2
R- <9>
MEMOBUS/Modbus comm.
RS-422/RS-485 S FM Multi-function analog output 1
shielded line twisted-pair shielded line control circuit terminal main circuit terminal
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 43
3.1 Standard Connection Diagram
<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an optional regenerative
converter or dynamic braking option. Leaving L8-55 enabled may cause a braking resistor fault (rF). Additionally, disable Stall
Prevention (L3-04 = 0) when using an optional regenerative converter, regenerative or braking units, or dynamic braking option.
Leaving If L3-04 enabled may prevent the drive from stopping within the specified deceleration time.
<3> Supplying power to the control circuit separately from the main circuit requires 24 V power supply (option).
<4> This figure illustrates an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Install
the wire link between terminals SC-SP for Sink mode, between SC-SN for Source mode, or leave the link out for external power
supply. Never short terminals SP and SN, as it will damage the drive.
<5> This voltage source supplies a maximum current of 150 mA.
<6> The maximum output current capacity for the +V terminal on the control circuit is 20 mA. Never short terminals +V and AC, as
it can cause erroneous operation or damage the drive.
<7> Set jumper S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<8> Set jumper S1 to select between a voltage or current input signal to terminal A1 and A3. The default setting is for voltage input.
<9> Set DIP switch S2 to the ON position to enable the termination resistor in the last drive in a MEMOBUS/Modbus network.
<10> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not
intended for use as a feedback-type signal.
<11> Use jumper S5 to select between voltage or current output signals at terminals AM and FM. Set parameters H4-07 and H4-08
accordingly.
<12> Self-cooling motors do not require the same wiring necessary for motors with cooling fans.
WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the multifunction input terminal parameters are
properly set. Improper sequencing of run/stop circuitry could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing
the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary
closure on terminal S1 may cause the drive to start.
WARNING! Sudden Movement Hazard. When using a 3-Wire sequence, set the drive to 3-Wire sequence prior to wiring the control terminals
and set parameter b1-17 to 0 so the drive will not accept a Run command at power up (default). If the drive is wired for a 3-Wire sequence
but set up for a 2-Wire sequence (default), and parameter b1-17 is set to 1 so the drive accepts a Run command at power up, the motor
will rotate in reverse direction at drive power up and may cause injury.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before executing the application preset
function. Executing the application preset function or setting A1-03 ≠ 0 will change the drive I/O terminal functions and may cause unexpected
equipment operation. Failure to comply may cause death or serious injury.
NOTICE: When using the automatic fault restart function with wiring designed to shut off the power supply upon drive fault, make sure the
drive does not trigger a fault output during fault restart (L5-02 = 0, default). Failure to comply will prevent the automatic fault restart function
from working properly.
44 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.2 Main Circuit Connection Diagram
+1
+2 Relay
Current
sensor
R/L1 U/T1
S/L2 +
V/T2
T/L3 W/T3
Control Operator
Gate board board
Electrical Installation
B1 B2
+1
Relay
DC link Current
choke sensor
R/L1 U/T1
S/L2 + V/T2
T/L3 W/T3
3
–
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 45
3.2 Main Circuit Connection Diagram
+1
Relay
DC link Current
choke sensor
R/L1 U/T1
+
S/L2 V/T2
T/L3 W/T3
+1
Relay
DC link Current
choke sensor
R/L1 U/T1
+
S/L2 V/T2
T/L3 W/T3
24 V
Gate board Control Operator
Power board
Supply
46 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.2 Main Circuit Connection Diagram
+1
Relay
DC link Current
choke sensor
R/L1
U/T1
S/L2 +
V/T2
T/L3
W/T3
R1/L11
S1/L21
T1/L31
–
24 V
Power Gate board Control Operator
Supply board
Note: Models 4A0930 and 4A1200 are compatible for operation with 12-pulse rectification. Refer to 12-Pulse Rectification on page 47 for
details.
12-Pulse Rectification
Application Notes
Models 4A0930 and 4A1200 are shipped from the factory with jumpers short-circuiting terminals R/L1-R1/L11, S/L2-S1/
L21, and T/L3-T1/L31.
Remove M5 screws and jumpers as shown in Figure 3.7 to operate with 12-pulse rectification.
Electrical Installation
Jumper
S1/L21
R 1/L11
T1/L31
R/L1 T/L3
S/L2
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 47
3.2 Main Circuit Connection Diagram
Connection Diagram
Braking Resistor Unit
(option)
Braking Unit
(option)
+ 3 −
+1
−
U1 U/T1
R/L1
V1 V/T2 Motor
S/L2
W1 W/T3
T/L3
W2 V2 U2
R1/L11
S1/L21
T1/L31
48 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.3 Terminal Cover
Figure 3.9 Removing the Terminal Cover on an IP20/NEMA 1, UL Type 1 Enclosure Drive
2. Push in on the tab located on the bottom of the terminal cover and gently pull forward to remove the terminal cover.
Figure 3.10 Removing the Terminal Cover on an IP20/NEMA 1, UL Type 1 Enclosure Drive
Electrical Installation
Reattaching the Terminal Cover
Power lines and signal wiring should pass through the opening provided. Refer to Wiring the Main Circuit Terminal on
page 66 and Wiring the Control Circuit Terminal on page 70 for details on wiring.
Reattach the terminal cover after completing the wiring to the drive and other devices.
<1>
Figure 3.11 Reattaching the Terminal Cover on an IP20/NEMA 1, UL Type 1 Enclosure Drive
<1> Connect the ground wiring first, then the main circuit wiring, and finally the control circuit wiring.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 49
3.3 Terminal Cover
Models 2A0110 to 2A0250, 4A0208 to 4A0675, and 5A0125 to 5A0242 (IP00/Open Type
Enclosure)
Removing the Terminal Cover
1. Loosen the screws on the terminal cover, then pull down on the cover.
Note: The terminal cover and the number of terminal cover screws differ depending on the drive model.
CAUTION! Do not completely remove the cover screws, just loosen them. If the cover screws are removed completely, the terminal
cover may fall off causing an injury.
Figure 3.12 Removing the Terminal Cover on an IP00/Open Type Enclosure Drive
Figure 3.13 Removing the Terminal Cover on an IP00/Open Type Enclosure Drive
<1>
Figure 3.14 Reattaching the Terminal Cover on an IP00/Open Type Enclosure Drive
<1> Connect the ground wiring first, then the main circuit wiring, and finally the control circuit wiring.
50 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.4 Digital Operator and Front Cover
Electrical Installation
Removing the Front Cover
Models 2A0004 to 2A0081, 4A0002 to 4A0044, and 5A0003 to 5A0032
After removing the terminal cover and the digital operator, loosen the screw that affixes the front cover (models
2A0056, 4A0038, 5A0022, and 5A0027 do not use a screw to affix the front cover) . Pinch in on the tabs found on each side
of the front cover, then pull forward to remove it from the drive.
3
Figure 3.17 Remove the Front Cover (2A0004 to 2A0081, 4A0002 to 4A0044, and 5A0003 to 5A0032)
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 51
3.4 Digital Operator and Front Cover
Hook Hook
Figure 3.18 Remove the Front Cover (2A0010 to 2A0415 and 4A0058 to 4A1200)
4. Unhook the left side of the front cover then swing the left side towards you as shown in Figure 3.19 until the cover
comes off.
Figure 3.19 Remove the Front Cover (2A0010 to 2A0415 and 4A0058 to 4A1200)
52 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.4 Digital Operator and Front Cover
Figure 3.20 Reattach the Front Cover (2A0110 to 2A0415 and 4A0058 to 4A1200)
2. After connecting the hooks to the drive, press firmly on the cover to lock it into place.
Electrical Installation
3
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 53
3.5 Top Protective Cover
Protective Cover
Mounting Holes
54 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.6 Main Circuit Wiring
Electrical Installation
⊕2 • DC link choke Not available
connection
⊕1
(⊕1, ⊕2)
(remove the For connecting:
shorting bar DC power supply • the drive to a DC power
between input • DC power supply input (⊕1, ⊖) supply –
⊖ ⊕1 and ⊕2) (⊕1, ⊖) • dynamic braking options
• DC power • Braking unit connection (⊕3, ⊖)
supply input • a DC link choke
(⊕1, ⊖) 3
⊕3 Not available
For 200 V class: 100 Ω or less
For 400 V class: 10 Ω or less Grounding terminal 65
For 600 V class: 10 Ω or less
Note: Use terminals B1 and ⊖ when installing a CDBR-type braking unit on drives with built-in braking transistors (Models 2A0004 to 2A0138,
4A0002 to 4A0072, and 5A0003 to 5A0052).
Wiring Fuses for Models 4A0930 and 4A1200
NOTICE: If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devices
to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakage
current in the upper controller power supply will trigger the fuse and shut off the power supply.
Select the appropriate fuse from Table 3.2.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 55
3.6 Main Circuit Wiring
56 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.6 Main Circuit Wiring
Drive Model Terminal Recomm. Gauge Wire Range Screw Tightening Torque
AWG, kcmil AWG, kcmil Size N·m (lb.in.)
R/L1, S/L2, T/L3 14 14 to 10
2A0004 U/T1, V/T2, W/T3 14 14 to 10
2A0006 1.2 to 1.5
⊖, ⊕1, ⊕2 – 14 to 10 M4
2A0008 (10.6 to 13.3)
2A0010 B1, B2 – 14 to 10
10 <1> 14 to 10
Electrical Installation
R/L1, S/L2, T/L3 12 14 to 10
U/T1, V/T2, W/T3 14 14 to 10
1.2 to 1.5
2A0012 ⊖, ⊕1, ⊕2 – 14 to 10 M4
(10.6 to 13.3)
B1, B2 – 14 to 10
10 <1> 14 to 10
R/L1, S/L2, T/L3 10 12 to 10
U/T1, V/T2, W/T3 10 14 to 10
2A0018 ⊖, ⊕1, ⊕2 – 14 to 10 M4
1.2 to 1.5
(10.6 to 13.3)
3
B1, B2 – 14 to 10
10 <1> 14 to 10
R/L1, S/L2, T/L3 10 12 to 10
U/T1, V/T2, W/T3 10 12 to 10
1.2 to 1.5
2A0021 ⊖, ⊕1, ⊕2 – 12 to 10 M4
(10.6 to 13.3)
B1, B2 – 14 to 10
10 <1> 12 to 10
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 57
3.6 Main Circuit Wiring
Drive Model Terminal Recomm. Gauge Wire Range Screw Tightening Torque
AWG, kcmil AWG, kcmil Size N·m (lb.in.)
R/L1, S/L2, T/L3 8 10 to 6
U/T1, V/T2, W/T3 8 10 to 6 2.1 to 2.3
M4
2A0030 ⊖, ⊕1, ⊕2 – 10 to 6 (18.6 to 20.4)
B1, B2 – 14 to 10
2.0 to 2.5
8 <2> 10 to 8 M5
(17.7 to 22.1)
R/L1, S/L2, T/L3 6 8 to 6
U/T1, V/T2, W/T3 8 8 to 6 2.1 to 2.3
M4
2A0040 ⊖, ⊕1, ⊕2 – 6 (18.6 to 20.4)
B1, B2 – 12 to 10
2.0 to 2.5
8 <2> 10 to 8 M5
(17.7 to 22.1)
R/L1, S/L2, T/L3 4 6 to 4
5.4 to 6.0
U/T1, V/T2, W/T3 4 6 to 4 M6
(47.8 to 53.1)
⊖, ⊕1, ⊕2 – 6 to 4
2A0056
2.7 to 3.0
B1, B2 – 10 to 6 M5
(23.9 to 26.6)
5.4 to 6.0
6 8 to 6 M6
(47.8 to 53.1)
R/L1, S/L2, T/L3 3 4 to 3
9.9 to 11.0
U/T1, V/T2, W/T3 3 4 to 3 M8
(87.6 to 97.4)
⊖, ⊕1, ⊕2 – 4 to 3
2A0069
2.7 to 3.0
B1, B2 – 8 to 6 M5
(23.9 to 26.6)
5.4 to 6.0
6 6 to 4 M6
(47.8 to 53.1)
R/L1, S/L2, T/L3 2 3 to 2
9.9 to 11.0
U/T1, V/T2, W/T3 2 3 to 2 M8
(87.6 to 97.4)
⊖, ⊕1, ⊕2 – 3 to 2
2A0081
2.7 to 3.0
B1, B2 – 6 M5
(23.9 to 26.6)
5.4 to 6.0
6 6 to 4 M6
(47.8 to 53.1)
R/L1, S/L2, T/L3 1/0 3 to 1/0
U/T1, V/T2, W/T3 1/0 3 to 1/0
9 to 11
2A0110 ⊖, ⊕1 – 2 to 1/0 M8
(79.7 to 97.4)
B1, B2 – 6 to 1/0
6 6 to 4
R/L1, S/L2, T/L3 2/0 1 to 2/0
U/T1, V/T2, W/T3 2/0 1 to 2/0 18 to 23
M10
2A0138 ⊖, ⊕1 – 1/0 to 3/0 (159 to 204)
B1, B2 – 4 to 2/0
9 to 11
4 4 M8
(79.7 to 97.4)
R/L1, S/L2, T/L3 4/0 2/0 to 4/0
U/T1, V/T2, W/T3 4/0 3/0 to 4/0
18 to 23
2A0169 ⊖, ⊕1 – 1 to 4/0 M10
(159 to 204)
⊕3 – 1/0 to 4/0
4 4 to 2
R/L1, S/L2, T/L3 1/0 × 2P 1/0 to 2/0
U/T1, V/T2, W/T3 1/0 × 2P 1/0 to 2/0
18 to 23
2A0211 ⊖, ⊕1 – 1 to 4/0 M10
(159 to 204)
⊕3 – 1/0 to 4/0
4 4 to 1/0
58 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.6 Main Circuit Wiring
Drive Model Terminal Recomm. Gauge Wire Range Screw Tightening Torque
AWG, kcmil AWG, kcmil Size N·m (lb.in.)
R/L1, S/L2, T/L3 3/0 × 2P 3/0 to 300
32 to 40
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300 M12
(283 to 354)
⊖, ⊕1 – 3/0 to 300
2A0250
18 to 23
⊕3 – 2 to 300 M10
(159 to 204)
32 to 40
3 3 to 300 M12
(283 to 354)
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 300
32 to 40
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300 M12
(283 to 354)
⊖, ⊕1 – 3/0 to 300
2A0312
18 to 23
⊕3 – 3/0 to 300 M10
(159 to 204)
32 to 40
2 2 to 300 M12
(283 to 354)
R/L1, S/L2, T/L3 250 × 2P 4/0 to 600
32 to 40
U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600 M12
(283 to 354)
⊖, ⊕1 – 250 to 600
2A0360
18 to 23
⊕3 – 3/0 to 600 M10
(159 to 204)
32 to 40
1 1 to 350 M12
(283 to 354)
R/L1, S/L2, T/L3 350 × 2P 250 to 600
32 to 40
U/T1, V/T2, W/T3 300 × 2P 300 to 600 M12
(283 to 354)
⊖, ⊕1 – 300 to 600
2A0415
18 to 23
⊕3 – 3/0 to 600 M10
(159 to 204)
32 to 40
1 1 to 350 M12
(283 to 354)
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2> Install a GFCI, or use 10 mm2 (AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.
Note: When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
Electrical Installation
Table 3.4 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
Drive Model Terminal Recomm. Gauge Wire Range Screw Tightening Torque
AWG, kcmil AWG, kcmil Size N·m (lb.in.)
R/L1, S/L2, T/L3 14 14 to 10
U/T1, V/T2, W/T3 14 14 to 10
4A0002 1.2 to 1.5
⊖, ⊕1, ⊕2 – 14 to 10 M4
4A0004 (10.6 to 13.3)
B1, B2 – 14 to 10
12 <1> 14 to 12 3
R/L1, S/L2, T/L3 14 14 to 10
U/T1, V/T2, W/T3 14 14 to 10
4A0005
1.2 to 1.5
4A0007 ⊖, ⊕1, ⊕2 – 14 to 10 M4
(10.6 to 13.3)
4A0009 B1, B2 – 14 to 10
10 <1> 14 to 10
R/L1, S/L2, T/L3 12 14 to 10
U/T1, V/T2, W/T3 14 14 to 10
1.2 to 1.5
4A0011 ⊖, ⊕1, ⊕2 – 14 to 10 M4
(10.6 to 13.3)
B1, B2 – 14 to 10
10 <1> 14 to 10
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 59
3.6 Main Circuit Wiring
Drive Model Terminal Recomm. Gauge Wire Range Screw Tightening Torque
AWG, kcmil AWG, kcmil Size N·m (lb.in.)
R/L1, S/L2, T/L3 10 12 to 6
U/T1, V/T2, W/T3 10 12 to 6 2.1 to 2.3
M4
4A0018 ⊖, ⊕1, ⊕2 – 12 to 6 (18.6 to 20.4)
B1, B2 – 12 to 10
2.0 to 2.5
10 <1> 14 to 10 M5
(17.7 to 22.1)
R/L1, S/L2, T/L3 10 10 to 6
U/T1, V/T2, W/T3 10 10 to 6 2.1 to 2.3
M4
4A0023 ⊖, ⊕1, ⊕2 – 12 to 6 (18.6 to 20.4)
B1, B2 – 12 to 10
2.0 to 2.5
10 <1> 12 to 10 M5
(17.7 to 22.1)
R/L1, S/L2, T/L3 8 8 to 6
3.6 to 4.0
U/T1, V/T2, W/T3 8 10 to 6
(31.8 to 35.4)
⊖, ⊕1, ⊕2 – 10 to 6 M5
4A0031
2.7 to 3.0
B1, B2 – 10 to 8
(23.9 to 26.6)
5.4 to 6.0
8 <2> 10 to 8 M6
(47.8 to 53.1)
R/L1, S/L2, T/L3 6 8 to 6
3.6 to 4.0
U/T1, V/T2, W/T3 8 8 to 6
(31.8 to 35.4)
⊖, ⊕1, ⊕2 – 6 M5
4A0038
2.7 to 3.0
B1, B2 – 10 to 8
(23.9 to 26.6)
5.4 to 6.0
6 10 to 6 M6
(47.8 to 53.1)
R/L1, S/L2, T/L3 6 6 to 4
5.4 to 6.0
U/T1, V/T2, W/T3 6 6 to 4 M6
(47.8 to 53.1)
⊖, ⊕1, ⊕2 – 6 to 4
4A0044
2.7 to 3.0
B1, B2 – 10 to 8 M5
(23.9 to 26.6)
5.4 to 6.0
6 8 to 6 M6
(47.8 to 53.1)
R/L1, S/L2, T/L3 4 6 to 4
U/T1, V/T2, W/T3 4 6 to 4
9 to 11
4A0058 ⊖, ⊕1 – 6 to 1 M8
(79.7 to 97.4)
B1, B2 – 8 to 4
6 8 to 6
R/L1, S/L2, T/L3 3 4 to 3
U/T1, V/T2, W/T3 3 4 to 3
9 to 11
4A0072 ⊖, ⊕1 – 4 to 1 M8
(79.7 to 97.4)
B1, B2 – 6 to 3
6 6
R/L1, S/L2, T/L3 2 3 to 1/0
U/T1, V/T2, W/T3 2 3 to 1/0
9 to 11
4A0088 ⊖, ⊕1 – 3 to 1/0 M8
(79.7 to 97.4)
⊕3 – 6 to 1/0
4 6 to 4
R/L1, S/L2, T/L3 1/0 2 to 1/0
U/T1, V/T2, W/T3 1 2 to 1/0
9 to 11
4A0103 ⊖, ⊕1 – 3 to 1/0 M8
(79.7 to 97.4)
⊕3 – 4 to 1/0
4 6 to 4
60 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.6 Main Circuit Wiring
Drive Model Terminal Recomm. Gauge Wire Range Screw Tightening Torque
AWG, kcmil AWG, kcmil Size N·m (lb.in.)
R/L1, S/L2, T/L3 3/0 1/0 to 4/0
U/T1, V/T2, W/T3 2/0 1/0 to 4/0
18 to 23
4A0139 ⊖, ⊕1 – 1/0 to 4/0 M10
(159 to 204)
⊕3 – 3 to 4/0
4 4
R/L1, S/L2, T/L3 4/0 3/0 to 4/0
U/T1, V/T2, W/T3 4/0 3/0 to 4/0
18 to 23
4A0165 ⊖, ⊕1 – 1 to 4/0 M10
(159 to 204)
⊕3 – 1/0 to 4/0
4 4 to 2
R/L1, S/L2, T/L3 300 2 to 300
U/T1, V/T2, W/T3 300 2 to 300
18 to 23
4A0208 ⊖, ⊕1 – 1 to 250 M10
(159 to 204)
⊕3 – 3 to 3/0
4 4 to 300
R/L1, S/L2, T/L3 400 1 to 600
U/T1, V/T2, W/T3 400 1/0 to 600
18 to 23
4A0250 ⊖, ⊕1 – 3/0 to 600 M10
(159 to 204)
⊕3 – 1 to 325
2 2 to 350
R/L1, S/L2, T/L3 500 2/0 to 600
32 to 40
U/T1, V/T2, W/T3 500 2/0 to 600 M12
(283 to 354)
⊖, ⊕1 – 3/0 to 600
4A0296
18 to 23
⊕3 – 1 to 325 M10
(159 to 204)
32 to 40
2 2 to 350 M12
(283 to 354)
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 600
32 to 40
U/T1, V/T2, W/T3 4/0 × 2P 3/0 to 600 M12
(283 to 354)
⊖, ⊕1 – 4/0 to 600
4A0362
18 to 23
⊕3 – 3/0 to 600 M10
(159 to 204)
Electrical Installation
32 to 40
1 1 to 350 M12
(283 to 354)
R/L1, S/L2, T/L3 300 × 2P 4/0 to 300
U/T1, V/T2, W/T3 300 × 2P 4/0 to 300
32 to 40
4A0414 ⊖, ⊕1 – 3/0 to 300 M12
(283 to 354)
⊕3 – 3/0 to 300
1 1 to 3/0
R/L1, S/L2, T/L3 3/0 × 4P 3/0 to 300 3
U/T1, V/T2, W/T3 4/0 × 4P 3/0 to 300
32 to 40
4A0515 ⊖, ⊕1 – 1/0 to 300 M12
(283 to 354)
⊕3 – 1/0 to 300
1/0 1/0 to 300
R/L1, S/L2, T/L3 300 × 4P 4/0 to 300
U/T1, V/T2, W/T3 300 × 4P 4/0 to 300
32 to 40
4A0675 ⊖, ⊕1 – 1/0 to 300 M12
(283 to 354)
⊕3 – 1/0 to 300
2/0 2/0 to 300
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 61
3.6 Main Circuit Wiring
Drive Model Terminal Recomm. Gauge Wire Range Screw Tightening Torque
AWG, kcmil AWG, kcmil Size N·m (lb.in.)
R/L1, S/L2, T/L3, R1/L11, S1/L21,
4/0 × 4P×2 3/0 to 300
T1/L31
U/T1, V/T2, W/T3 4/0 × 4P×2 3/0 to 300
32 to 40
4A0930 M12
⊖, ⊕1 – 4/0 to 300 (283 to 354)
⊕3 – 4/0 to 300
3/0 3/0 to 250
R/L1, S/L2, T/L3, R1/L11, S1/L21,
300 × 4P×2 4/0 to 300
T1/L31
U/T1, V/T2, W/T3 300 × 4P×2 4/0 to 300
32 to 40
4A1200 M12
⊖, ⊕1 – 250 to 300 (283 to 354)
⊕3 – 4/0 to 300
4/0 4/0 to 250
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2> Install a GFCI or use 10 mm 2 (AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.
Note: When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
62 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.6 Main Circuit Wiring
Electrical Installation
(6) (6)
25 6.0 to 25
R/L1, S/L2, T/L3
(4) (10 to 3)
16 6.0 to 25
U/T1, V/T2, W/T3
(6) (10 to 3)
16 to 35 9.0 to 11
5A0052 ⊖, ⊕1 – M8
(6 to 1) (79.7 to 97.4)
10 to 25
B1, B2 –
(8 to 3)
3
16 10 to 16
(6) (6)
25 6.0 to 95
R/L1, S/L2, T/L3
(4) (10 to 4/0)
25 6.0 to 95
U/T1, V/T2, W/T3
(4) (10 to 4/0)
25 to 95 18 to 23
5A0062 ⊖, ⊕1 – M10
(4 to 4/0) (159 to 204)
16 to 95
⊕3 –
(6 to 4/0)
25 25
(4) (4)
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 63
3.6 Main Circuit Wiring
Note: When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2 , refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
64 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.6 Main Circuit Wiring
Ground Wiring
Follow the precautions below when wiring the ground for one drive or a series of drives.
WARNING! Electrical Shock Hazard. Make sure the protective earthing conductor complies with technical standards and local safety
regulations. Because the leakage current exceeds 3.5 mA in models 4A0414 and larger, IEC/EN 61800-5-1 states that either the power
supply must be automatically disconnected in case of discontinuity of the protective earthing conductor or a protective earthing conductor
with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to comply may result in death or serious injury.
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and minimize
the length of the ground wire. Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could
result in death or serious injury.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (200 V class: ground to 100 Ω or less; 400 V class: ground
to 10 Ω or less; 600 V class: ground to 10 Ω or less). Improper equipment grounding could result in death or serious injury by contacting
Electrical Installation
ungrounded electrical equipment.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper
equipment grounding could result in drive or equipment malfunction due to electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could result in
abnormal operation of drive or equipment.
Refer to Figure 3.24 when using multiple drives. Do not loop the ground wire.
3
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 65
3.6 Main Circuit Wiring
B
_
R/L1 S/L2 T/L3 +1 +2 U/T1 V/T2 W/T3
66 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.7 Control Circuit Wiring
Input Terminals
Table 3.7 lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.
Table 3.7 Control Circuit Input Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
Multi-function input 1
S1
(Closed: Forward run, Open: Stop)
Multi-function input 2
S2
(Closed: Reverse run, Open: Stop)
S3 Multi-function input 3
(External fault, N.O.)
Multi-function input 4 • Photocoupler
S4
(Fault reset) • 24 Vdc, 8 mA
S5
Multi-function input 5 • Refer to Sinking/Sourcing Mode for Digital Inputs on page 213
(Multi-step speed reference 1) 72.
Multi-Function Multi-function input 6
Digital Inputs S6
(Multi-step speed reference 2)
S7 Multi-function input 7
(Jog reference)
S8 Multi-function input 8
(Baseblock command (N.O.))
SC Multi-function input common Multi-function input common
SP Digital input power supply +24 Vdc 24 Vdc power supply for digital inputs, 150 mA max 72
Digital input power supply 0 V NOTICE: Do not jumper or short terminals SP and SN. Failure
SN to comply will damage the drive. 72
24 V transducer power supply 0 V
Electrical Installation
• Input frequency range: 0 to 32 kHz
Multi-function pulse train input • Signal Duty Cycle: 30 to 70% 95
RP (Frequency reference) • High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc 220
• Input impedance: 3 kΩ
+V Power supply for analog inputs 10.5 Vdc (max allowable current 20 mA) 94
+24
24 V use Vdc transducer power supply for customer 150 mA maximum capacity –
3
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
Multi-function analog input 1 94
Analog Inputs / A1 (Frequency reference bias) • 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Pulse Train 112
• Voltage or current input must be selected by jumper S1 and H3-01.
Input
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ) 94
Multi-function analog input 2
A2 (Frequency reference bias) • 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω) 94
• Voltage or current input must be selected by jumper S1 and H3-09. 114
• -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
Multi-function analog input 3 • 4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
A3 (Frequency reference bias) 94
• Voltage or current input must be selected by jumper S1 and H3-05.
AC Frequency reference common 0V 94
E (G) Ground for shielded lines and option cards – –
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 67
3.7 Control Circuit Wiring
Output Terminals
Table 3.8 lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.
Table 3.8 Control Circuit Output Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting Page
MA N.O.
Fault Relay 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Output MB N.C. output 110
Minimum load: 5 Vdc, 10 mA
MC Fault output common
MD N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
ME N.C. Output
Minimum load: 5 Vdc, 10 mA
Multi-Function MF Common (Speed agree)
Digital Output M1 110
<1> Multi-function digital output (During run)
M2 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
M3 Minimum load: 5 Vdc, 10 mA
Multi-function digital output (Zero speed)
M4
FM Analog monitor output 1 (Output frequency)
Monitor -10 to +10 Vdc, or 0 to +10 Vdc 219
Output AM Analog monitor output 2 (Output current)
AC Monitor common 0V –
<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching
life is estimated at 200,000 times (assumes 1 A, resistive load).
Connect a suppression diode as shown in Figure 3.26 when driving a reactive load such as a relay coil. Ensure the diode rating
is greater than the circuit voltage.
B
C
A
D
68 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.7 Control Circuit Wiring
Terminal Configuration
The control circuit terminals are arranged as shown in Figure 3.27.
E(G) IG R+ R- S S-
M1 M2 M3 M4
+
MD ME MF
V+ AC A1 A2 A3 FM AM AC RP AC 24V
E(G) IG R+ R- S+ S-
M1 M2 M3 M4
V+ AC A1 A2 A3 FM AM AC RP AC 24V MD ME MF
MA MB MC TB5
S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP MA MB MC S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP
Electrical Installation
FM, AM, AC
R+, R-, S+, S-, IG
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 69
3.7 Control Circuit Wiring
8 mm
(0.31 in.)
L
d2
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3, ⊖, ⊕1, ⊕2) and
other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Separate wiring for digital output terminals MA, MB, MC, MD, ME, MF and M1 to M4 from wiring to other control circuit lines.
Improper wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result in
drive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,
Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment. Improper wiring practices could
result in drive or equipment malfunction due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment grounding could result in drive or
equipment malfunction or nuisance trips.
NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may result in erroneous operation, damage to the
terminal block, or cause a fire.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or
equipment malfunction due to electrical interference.
Wire the control circuit only after terminals have been properly grounded and main circuit wiring is complete. Refer to
Terminal Board Wiring Guide on page 71 for details. Prepare the ends of the control circuit wiring as shown in Figure
3.31. Refer to Wire Gauges on page 69.
Connect control wires as shown in Figure 3.29 and Figure 3.30.
70 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.7 Control Circuit Wiring
Preparing wire D
terminal ends
C
When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires (preparing
Electrical Installation
wire ends as shown in Figure 3.31) and connect the shield to the ground terminal of the drive.
E B
A C
NOTICE: The analog signal wiring between the drive and the operator station or peripheral equipment should not exceed 50 meters when
using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 71
3.8 Control I/O Connections
S7
S7
S8 S8
SC
SC
24 Vdc 24 Vdc
SP
External SP
24 Vdc ±10%
S7 S7
S8 S8
SC
SC
24 Vdc 24 Vdc
SP External SP
24 Vdc ±10%
72 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.8 Control I/O Connections
Load Impedance
MP
VMP
RL
AC
Load Impedance
Electrical Installation
MP
Sink Current
AC
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 73
3.8 Control I/O Connections
Jumper S1
A1 A2 A3
Figure 3.34 Terminal A2 Set to Current Input; A1 and A3 Set to Voltage Input
Terminal AM I I
FM AM FM AM
V V
Terminal FM I I
FM AM FM AM
74 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.9 Connect to a PC
3.9 Connect to a PC
This drive is equipped with a USB port (type-B).
The drive can connect to a USB port on a PC using a USB 2.0, AB-type cable (sold separately). After connecting the drive to
a PC, Yaskawa DriveWizard Industrial software can be used to monitor drive performance and manage parameter settings.
Contact Yaskawa for more information on DriveWizard Industrial.
USB Cable
(Type-AB)
(Type-B) (Type-A)
PC
Electrical Installation
3
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 75
3.10 Wiring Checklist
Set up overload protection circuits when running multiple motors from a single drive.
Power supply Drive MC1 OL1
M1
MC2 OL2
15 M2
MC1 - MCn ... magnetic contactor
OL 1 - OLn ... thermal relay
–
MCn OLn
Mn
Note: Close MC1 – MCn before operating the drive. MC1 – MCn cannot be switched off during run.
Install a magnetic contactor when using a dynamic braking option. Properly install the resistor and ensure that overload
16 protection shuts off the power supply using the magnetic contactor. –
17 Verify phase advancing capacitors, input noise filters, or GFCIs are NOT installed on the output side of the drive. –
Control Circuit Wiring
18 Use twisted-pair line for all drive control circuit wiring. 70
19 Ground the shields of shielded wiring to the GND terminal. 70
20 For 3-Wire sequence, set parameters for multi-function contact input terminals S1 – S8, and wire control circuits. –
21 Properly wire any option cards. 70
22 Check for any other wiring mistakes. Only use a multimeter to check wiring. –
Properly fasten drive control circuit terminal screws. Refer to Main Circuit Wire Gauges and Tightening Torque on
23 page 57. 57
76 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
3.10 Wiring Checklist
Electrical Installation
3
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 77
3.10 Wiring Checklist
78 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4
Start-Up Programming & Operation
This chapter explains the functions of the digital operator and how to program the drive for initial
operation.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 79
4.1 Using the Digital Operator
1
11
F1 F2
2 ESC
LO
RE
9
3 RESET ENTER 8
10 RUN STOP
4 5 6 7
5 Up Arrow Key Scrolls up to display the next item, selects parameter numbers, and increments setting
values.
6 Down Arrow Key Scrolls down to display the previous item, selects parameter numbers, and decrements
setting values.
7 STOP STOP Key <1> Stops drive operation.
• Enters parameter values and settings.
8 ENTER Key
• Selects a menu item to move between displays
Switches drive control and frequency setting between the operator (LOCAL) and an
9 LO/RE Selection Key <2> external source (REMOTE).
10 RUN Light Lit while the drive is operating the motor. Refer to page 82 for details.
11 LO/RE Light Lit while the operator is selected to run the drive (LOCAL mode). Refer to page 82 for
details.
12 ALM LED Light Refer to ALARM (ALM) LED Displays on page 82.
<1> The STOP key has highest priority. Pressing the STOP key will always cause the drive to stop the motor, even if a Run command is active at any
external Run command source. To disable the STOP key priority, set parameter o2-02 to 0.
<2> The LO/RE key can only switch between LOCAL and REMOTE when the drive is stopped. To disable the LO/RE key to prohibit switching between
LOCAL and REMOTE, set parameter o2-01 to 0.
80 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.1 Using the Digital Operator
LCD Display
1 2 3
4
5
9 8 7
Start-Up Programming
OP Displayed when the frequency reference is assigned to an Option Unit of the drive.
RP Displayed when the frequency reference is assigned to the Pulse Train Input of the drive.
RSEQ Displayed when the run command is supplied from a remote source.
& Operation
LO/RE LSEQ Displayed when the run command is supplied from the operator keypad.
6
Display <2> RREF Displayed when the run command is supplied from a remote source.
LREF Displayed when the run command is supplied from the operator keypad.
FWD/REV Pressing F2 switches between forward and reverse. 4
DATA Pressing F2 scrolls to the next display.
Function Key 2
7 (F2)
→ Pressing F2 scrolls the cursor to the right.
RESET Pressing F2 resets the existing drive fault error.
FWD Indicates forward motor operation.
8 FWD/REV
REV Indicates reverse motor operation.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 81
4.1 Using the Digital Operator
Examples
82 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.1 Using the Digital Operator
- MODE - PRG
Quick Setting Initial Display <5>
P1000
HELP FWD DATA XXXV, X.X/X.XkW
P1000 XX.XX/XX.XXA
YASKAWA <XXXXXXXXX>
<6>
- MODE - PRG
Programming
AUTO
Start-Up Programming
Figure 4.3 Digital Operator Menu and Screen Structure
& Operation
<1> RUN
will start the motor.
Pressing
<2> Drive cannot operate motor.
<3> Flashing characters are shown as 0 .
<4> “X” characters are used as examples in this manual. The LCD Operator will display the actual setting values.
<5> The Frequency Reference appears after the initial display that shows the product name.
4
<6> The information that appears on the display will vary depending on the drive.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 83
4.2 The Drive, Programming, and Clock Adjustment Modes
Clock Adjustment
The digital operator will display the Real Time Clock Adjustment Display in Figure 4.4 when the drive is powered up for the
first time. Refer to Manual Clock Adjustment Procedure by Setting o4-17 to 1 on page 85 for the Real-Time Clock setting
procedure.
Note: Setting the Real-Time Clock will clear a “TIM” alarm.
YYYY/MM/DD HH:MM A
20 1 0/01/01 00:00
Second per month
+ 0 sec B
FWD
A – Real Time Clock Setting Display B – Gain/Loss Adjustment Display
Figure 4.4 Real Time Clock Adjustment Display
Display Description
YYYY Set the year with the last two digits.
MM Set the month with two digits.
DD Set the day with two digits.
HH:MM Set the hours and minutes, with two digits for each.
Second per month Set the gain or loss in seconds per month.
84 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.2 The Drive, Programming, and Clock Adjustment Modes
ALM
Turn the power on. The Real Time Clock Adjustment Display will appear. Use the right arrow YYYY/MM/DD HH:MM
1 key to select the desired digit, then set the correct date and time using the up and down arrow 20 1 0/01/01 00:00
keys. Second per month
+ 0 sec
ALM
After entering the Real-Time Clock data, press the ENTER key to save the changes.
2 The display will indicate “Entry Accepted” and return to the initial display in step 3 and the alarm
LED will be OFF. Entry accepted
Start-Up Programming
The following actions are possible in the Clock Adjustment Mode:
• Set the current time
• Check the time set to the drive Real-Time Clock
& Operation
Table 4.5 illustrates how to set the Real-Time Clock manually.
Table 4.5 Manual Clock Adjustment Procedure by Setting o4-17 to 1
Procedure Display
ALM
4
The “Time Not Set” (TIM) display will appear if the Real-Time Clock data is not entered within - MODE - DRV
FWD RESET
ALM
- MODE - PRG
Use the up and down arrow keys to scroll through display menu until the screen shows Programming
2 “Programming”.
HOME FWD
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 85
4.2 The Drive, Programming, and Clock Adjustment Modes
Procedure Display
ALM
- PRMSET - PRG
3 Press the ENTER key to enter select the parameter setting mode. Initialization
A1-00 = 0
Select Language
ALM
- PRMSET - PRG
4 Use the up and down arrow keys to scroll through display menu until parameter o4-17 appears. Maintenance
o4-17 = 0
Set time
ALM
- PRMSET - PRG
5 Press the ENTER key until “0” flashes. Set time
o4-17= 0 *0*
--
“0”
HOME FWD DATA
ALM
- PRMSET - PRG
Set time
6 Press the up arrow key so that the display changes to “1”.
o4-17= 1 *0*
Set
“0”
HOME FWD DATA
ALM
Press the ENTER key and the time setting screen will appear. Use the right arrow key to select YYYY/MM/DD HH:MM
7 the desired digit, then set the correct date and time using the up and down arrow keys. 20 1 0/01/01 00:00
Second per month
+ 0 sec
ALM
After entering the correct time, press the ENTER key to save the changes.
8
The display will return to the display shown in step 5 and the alarm LED will be OFF. Entry accepted
Setting 0: — —
No Setting (Default)
Setting 1: Set
When o4-17 is set to 1, the digital operator will show the Clock Adjustment display. In Clock Adjustment Mode the user can
adjust the Real-Time Clock.
Setting 2: Reset
When o4-17 is set to 2, the Real-Time Clock data is cleared. A TIM fault will occur until o4-17 is set to 1 and the Real-Time
Clock is set.
86 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.2 The Drive, Programming, and Clock Adjustment Modes
Step Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
1. Turn on the power to the drive. The initial display appears. U1-02= 0.00Hz LSEQ
U1-03= 0.00A LREF
JOG FWD FWD/REV
- MODE - PRG
Programming
2. Press or until the Parameter Setting Mode screen appears.
HELP FWD DATA
-PRMSET- PRG
Initialization
A1-00= 0
3. Press to enter the parameter menu tree. Select Language
← FWD →
-PRMSET- PRG
Basic Setup
C1-01= 10.0 sec
4. Press or to select the C parameter group. Accel Time 1
← FWD →
-PRMSET- PRG -PRMSET- PRG
Accel/Decel Accel Time 1
C1-01= 10.0 sec C1-01= 10.0Sec
5. Press two times. Accel Time 1 (0.0~6000.0)
“10.0 sec”
← FWD → ← FWD →
-PRMSET- PRG
Decel Time 1
C1-02= 10.0Sec
6. Press or to select parameter C1-02. (0.0~6000.0)
“10.0 sec”
← FWD →
-PRMSET- PRG
Decel Time 1
C1-02= 0010.0Sec
7. Press to view the current setting value (10.0 s). The leftmost digit flashes. (0.0~6000.0)
“10.0 sec”
← FWD →
-PRMSET- PRG
Decel Time 1
C1-02=0010.0Sec
8. Press F1
, F2 , or until the desired number is selected. “1” flashes. (0.0~6000.0)
“10.0 sec”
← FWD →
-PRMSET- PRG
Decel Time 1
Start-Up Programming
C1-02=0020.0Sec
9. Press and enter 0020.0. (0.0~6000.0)
“10.0 sec”
← FWD →
& Operation
10. Press to confirm the change. Entry Accepted
-PRMSET- PRG
Decel Time 1 4
C1-02= 20.0Sec
11. The display automatically returns to the screen shown in Step 4. (0.0~6000.0)
“10.0 sec”
← FWD →
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
12. Press as many times as necessary to return to the initial display. U1-02= 0.00Hz LSEQ
U1-03= 0.00A LREF
JOG FWD FWD/REV
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 87
4.2 The Drive, Programming, and Clock Adjustment Modes
- MODE - D RV Rdy
FREF (OPR) U1-
01= 0.00Hz
U1-02= 0.00Hz LSEQ
U1-03= 0.00A LREF
JOG FW D FW D/REV
F1 F2
Press . The LO/RE light will light up. The drive is now in LOCAL. LO
2. ESC
RESET
RE
ENTER
RUN STOP
To set the drive for REMOTE operation, press the key again.
88 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.2 The Drive, Programming, and Clock Adjustment Modes
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 89
4.3 Start-Up Flowchart
START
Refer to
NO
Application
Selection Section
Set the basic parameters
b1-01/b1-02 for frequency reference selection and run command source selection
H1-,H2-,H3-,H4-,H6- for I/O terminal setting
d1- for using multi-speed references
C1- and C2- for accel/decel and S-curve time settings
L3-04 if using dynamic braking options
L8-55 = 0 if using a regen converter
YES
Is the motor cable
YES longer than 50 meters?
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Note: 1. Execute Stationary Auto-Tuning for Line-to-Line Resistance if the drive has been Auto-Tuned and then moved to a different location
where the motor cable length exceeds 50 m.
2. Perform Auto-Tuning again after installing an AC reactor or other such components to the output side of the drive.
90 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.4 Powering Up the Drive
Status Display
When the power supply to the drive is turned on, the digital operator lights will appear as follows:
Status Name Description
DIGITAL OPERATOR JVOP-180 ALARM
- MODE - DRV
EF3 Data displayed varies by the type of fault. Refer to Fault Displays, Causes, and Possible
Fault Ext Fault S3
Solutions on page 137 for more information. and are lit.
FWD RESET
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 91
4.5 Application Selection
92 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Start-Up Programming
Setting 5550: Terminal/Control Initialize
An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed
in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.
& Operation
Setting 8008: Pump
Application Preset for pump applications. Refer to Fan and Pump Application Presets on page 127 for a list of parameters
and default values for this Application Preset.
Setting 8009: Pump w/ PI 4
Application Preset for pump with PI applications. Refer to Fan and Pump Application Presets on page 127 for a list of
parameters and default values for this Application Preset.
Setting 8010: Fan
Application Preset for fan applications. Refer to Fan and Pump Application Presets on page 127 for a list of parameters and
default values for this Application Preset.
Setting 8011: Fan w/ PI
Application Preset for fan with PI applications. Refer to Fan and Pump Application Presets on page 127 for a list of
parameters and default values for this Application Preset.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 93
4.6 Basic Drive Setup Adjustments
Drive Drive
+V 10.5 V, 20 mA power supply +10 V +V 10.5 V, 20 mA power supply
0 to 10 V -10 to 10 V
k
2 A1 Analog Input 1 4k A1 Analog Input 1
Customer
+/- 10 V
A2 Analog Input 2 Supply A2 Analog Input 2
OR -10 V
A3 Analog Input 3 A3 Analog Input 3
Current Input
Input terminals, A1, A2, and A3 can accept a current input signal. Refer to Table 4.9 for an example to set terminal A2 for
current input.
Table 4.9 Analog Input Settings for Frequency Reference Using a Current Signal
Parameter Settings
Signal
Terminal Level Signal Level Function Notes
Selection Selection Gain Bias
4 to 20 mA H3-09 = 2 H3-10 = 0 Make sure to set jumper S1 on the
A2 H3-11 H3-12 terminal board to “I” for current
0 to 20 mA H3-09 = 3 (Frequency Bias) input.
94 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Jumper S1
V
A1/A2/A3
Voltage/Current I
Drive
Selection
A1 A2 A3
+V 10.5 V, 20 mA power supply
A1 Analog Input 1
0 or 4 to 20 mA
A2 Analog Input 2
A3 Analog Input 3
Start-Up Programming
Determines the Run command source 1 in the REMOTE mode.
No. Parameter Name Setting Range Default
& Operation
b1-02 Run Command Selection 1 0 to 3 1
Setting 0: Operator
This setting will illuminate the LO/RE light to indicate that the Run command source is assigned to the digital operator. Use
the digital operator RUN and STOP keys to start and stop operation.
4
Setting 1: Control Circuit Terminal
This setting requires entering the Run command via the digital input terminals using one of following sequences:
• 2-Wire sequence 1:
Setting A1-03 to 2220 initializes the drive and presets terminals S1 and S2 to FWD/Stop and REV/Stop. These are the default
settings of the drive.
• 2-Wire sequence 2:
Two inputs (Start/Stop-FWD/REV).
• 3-Wire sequence:
Setting A1-03 to 3330 initializes the drive and presets terminals S1, S2, and S5 to Start, Stop, and FWD/REV.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 95
4.6 Basic Drive Setup Adjustments
Output
frequency
Drive output is shut off
Motor speed
Note: After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do
not enter Run command until it has come to a complete stop. Use DC Injection at Start (Refer to b2: DC Injection Braking and Short
Circuit Braking on page 193) or Speed Search (Refer to b3: Speed Search on page 194) to restart the motor before it has completely
stopped.
96 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Run
command ON OFF
DC Injection Braking
Output with the current set in
frequency b2-02
Motor speed
Motor coasts
Minimum Baseblock
Time (L2-03)
DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is
removed. It can be calculated by:
(b2-04) x 10 x Output frequency
DC Injection brake time =
Maximum output frequency (E1-04)
b2-04×10
b2-04
Note: If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no
longer occurs.
Start-Up Programming
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t
after t has expired to start the drive.
& Operation
Run command ON OFF ON OFF ON
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 97
4.6 Basic Drive Setup Adjustments
Note: If b2-01 is set to a smaller value than E1-09 (Minimum Frequency), then DC Injection Braking will begin when the frequency falls to the
E1-09 value.
EZ Sleep/Wake-up Function
To enable EZ Sleep/Wake-up functionality on the drive, first set parameter b5-89 to 1. The default setting for b5-89 is 0, which
disables the EZ Sleep functionality and related parameters, except for parameter b5-91, EZ Sleep Minimum Speed.
Setting b5-89 to 1 disables the existing PID Sleep function (b5-15) and enables the EZ Sleep/Wake-up functionality.
EZ Sleep and Minimum Speed Units
Parameter b5-90, EZ Sleep Unit, determines the unit, range, and resolution of parameters b5-92 and b5-93. When set to Hz,
the range is 0.1 to 400.0 Hz. When set to RPM, the range is 0 to 24000 RPM. Changing b5-90 will NOT automatically re-
scale the values of b5-92 and b5-93.
Minimum Speed
98 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Parameter b5-91, EZ Minimum Speed, acts as a lower limit on the PID output. This value is internally limited to the higher
value between b5-34 or d2-02 and is active regardless of the b5-89 setting. When this limit is active, the PID integrator will
be held to avoid integral wind-up. Parameter b5-90 determines whether the value is input in Hz or RPM.
Sleep
When the output frequency (or speed) is at or below the EZ Sleep Level (b5-92) for the time set in EZ Sleep Time (b5-93),
the drive will sleep. The EZ Sleep Level is internally lower limited to the b5-92 setting.
Wake-up using Absolute Level (b5-95 = 0)
For Normal Acting PID, the PID Feedback must drop below the EZ Wake-up Level (b5-94) for the time set in EZ Wake-up
Time (b5-96) in order for the drive to wake-up.
For Reverse Acting PID, the PID Feedback must rise above the b5-94 level for the time set in b5-96 in order for the drive to
wake-up.
Wake-up using Setpoint Delta Level (b5-95 = 1)
For Normal Acting PID, the wake-up level is determined by the PID Setpoint minus the b5-94 level. The PID Feedback must
drop below the wake-up level for the time set in b5-96 in order for the drive to wake-up
For Reverse Acting PID, the wake-up level is determined by the PID Setpoint plus the b5-94 level. The PID Feedback must
rise above the wake-up level for the time set in b5-96 in order for the drive to wake-up.
Refer to Figure 4.14 and Figure 4.15 for detailed diagrams of EZ Sleep/Wake-up functions.
Refer to Table 4.10 for descriptions of EZ Sleep/Wake-up parameters.
Wake-up Wake-up Sleep Above Sleep Sleep Wake-up Wake-up Wake-up Wake-up
Level Timer Level Sleep Level Timer Level Level Level Timer
reached expired reached Level reached expired reached reached reached expired
Above Above
Wake-up Wake-up
Level Level
PID Set-point
PID Feedback
Wake-up Level <1>
b5 -96 b5 -93 b5 -93 b5-9 6 b5-9 6 b 5-96
Minimum Speed
(b 5-91) <2>
Output Frequency
Run Command
Sleeping Sleeping
Start-Up Programming
<2> EZ Sleep Level (b 5-92) is left at default (0.0 Hz), thus effectively making b 5-91 the Sleep Level
Figure 4.14 EZ Sleep/Wake-up with Normal Acting PID and b5-92 = 0.0 Hz
& Operation
4
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 99
4.6 Basic Drive Setup Adjustments
Above Above
Wake-up Wake-up
Level Level
EZ Sleep Level
(B5-92)
Minimum Speed
(B5-91)
Output Frequency
Run Command
Sleeping
Figure 4.15 EZ Sleep/Wake-up with Reverse Acting PID and b5-92 > b5-91
100 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
b5-93 The drive will go to sleep when the drive output frequency is at or below the level Default: 5.0 s
<1> EZ Sleep Time set to b5-92 for the time set in this parameter. Min.: 0.0
Max.: 1000.0
When b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback (H3-
= 20) drops below this level for the time set in b5-96.
For reverse-acting, the PID Feedback must be above this level for the time set in
b5-94 b5-96. Default: 0.00%
<1> <1> EZ Wake-up Level When b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID Feedback Min.: 0.00
(H3- = 20) drops below the PID Setpoint minus this level (for normal acting Max.: 600.00
PID) for the time set in b5-96.
For reverse-acting, Wake-up level is PID Setpoint plus this level. The PID Feedback
must be above the wake-up level for the time set in b5-96.
b5-95 Sets how the wake-up level is determined. Default: 0
<1> EZ Wake-up Mode 0: Absolute
Range: 0, 1
1: Setpoint Delta
b5-96 The drive will wake up when the PID Feedback drops below the b5-94, EZ Wake- Default: 1.0 s
<1> EZ Wake-up Time up Level for the time set in this parameter. Min.: 0.0
Max.: 1000.0
<1> Parameter is only effective when EZ Sleep is enabled by setting b5-89 to 1.
<2> Unit, range and resolution is determined by b5-90. Changing b5-90 will not automatically update the value of this parameter.
Start-Up Programming
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
Switching Acceleration Times by Digital Input
Accel/decel time 1 is active by default if no input is set. Activate accel/decel times 2, 3, and 4 by digital inputs
& Operation
(H1- = 7 and 1A) as explained in Table 4.11.
Table 4.11 Accel/Decel Time Selection by Digital Input
Accel/Decel Time Sel. 1 Accel/Decel Time Sel. 2 Active Times
H1- = 7 H1- = 1A Acceleration Deceleration 4
0 0 C1-01 C1-02
1 0 C1-03 C1-04
Figure 4.16 shows an operation example for changing accel/decel. times. The example below requires that the stopping method
be set for “Ramp to stop” (b1-03 = 0).
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 101
4.6 Basic Drive Setup Adjustments
Time
ON OFF
Accel/Decel Time Selection 1
(Terminals S1 to S8, H1- = “7”)
Settings:
C6-02 Carrier Frequency C6-02 Carrier Frequency C6-02 Carrier Frequency
1 2.0 kHz 5 12.5 kHz 9 Swing PWM 3
2 5.0 kHz 6 15.0 kHz A Swing PWM 4
3 8.0 kHz 7 Swing PWM 1
F User defined (C6-03 to C6-05)
4 10.0 kHz 8 Swing PWM 2
Note: Swing PWM uses a carrier frequency of 2.0 kHz as a base, then applies a special PWM pattern to reduce the audible noise.
102 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Start-Up Programming
Frequency Reference 6 (d1-06) ON OFF ON OFF OFF
Frequency Reference 7 (d1-07) OFF ON ON OFF OFF
& Operation
Frequency Reference 8 (d1-08) ON ON ON OFF OFF
Frequency Reference 9 (d1-09) OFF OFF OFF ON OFF
Frequency Reference 10 (d1-10) ON OFF OFF ON OFF
Frequency Reference 11 (d1-11) OFF ON OFF ON OFF
Frequency Reference 12 (d1-12) ON ON OFF ON OFF
Frequency Reference 13 (d1-13) OFF OFF ON ON OFF
4
Frequency Reference 14 (d1-14) ON OFF ON ON OFF
Frequency Reference 15 (d1-15) OFF ON ON ON OFF
Frequency Reference 16 (d1-16) ON ON ON ON OFF
Jog Frequency Reference (d1-17) <1> − − − − ON
<1> The Jog frequency overrides all other frequency references.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 103
4.6 Basic Drive Setup Adjustments
d1-16
Frequency d1-15
reference
d1-14
d1-13
d1-12
d1-07
d1-06
d1-05
d1-04
d1-03
(A3)
d1-02
(A2)
d1-01
(A1)
d1-17
Time
FWD (REV) Run/Stop
ON
104 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Start-Up Programming
E 180 Hz (with 60 Hz base)
F For general purpose applications. Torque remains
<1> 60 Hz Constant torque constant regardless of changes to speed.
& Operation
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 2A0004 to 2A0021, 4A0002 to 4A0011, and 5A0003 to 5A0009 4
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V drives.
Table 4.15 Constant Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
200 200 200 200
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
15 15 15 15
9 9 9 9
0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 50 60 0 1.5 3 60 72
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 105
4.6 Basic Drive Setup Adjustments
Voltage (V)
Voltage (V)
Voltage (V)
50 50
35 35
9 9
8 8
0 1.3 25 50 0 1.3 25 50 0 1.5 30 60 0 1.5 30 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
24 24
19 19
13 15
11 11
0 1.3 2.5 50 0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
15 15 15 16.1
9 9 9 8.1
0 1.5 3 60 90 0 1.5 3 60 120 0 1.5 3 60 180 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Predefined V/f Patterns for Models 2A0030 to 2A0211, 4A0018 to 4A0103, and 5A0011 to 5A0077
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V class drives.
Table 4.19 Rated Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
200 200 200 200
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
14 14 14 14
7 7 7 7
0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 50 60 0 1.5 3 60 72
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
50 50
35 35
7 7
6 6
0 1.3 25 50 0 1.3 25 50 0 1.5 30 60 0 1.5 30 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
106 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
23 23
18
18
11 13
9 9
0 1.3 2.5 50 0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
14 14 14 16.1
7 7 7 8.1
0 1.5 3 60 90 0 1.5 3 60 120 0 1.5 3 60 180 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Predefined V/f Patterns for Models 2A0250 to 2A0415, 4A0139 to 4A1200, and 5A0099 to 5A0242
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives. Multiply the
values by 2.875 for 600 V class drives.
Table 4.23 Rated Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
200 200 200 200
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
12 12 12 12
6 6 6 6
0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 50 60 0 1.5 3 60 72
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
Voltage (V)
Voltage (V)
Start-Up Programming
50 50
35 35
6 6
5 5
0 1.3 25 50 0 1.3 25 50 0 1.5 30 60 0 1.5 30 60
& Operation
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
4
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
20 20
15 15
9 11
7 7
0 1.3 2.5 50 0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 107
4.6 Basic Drive Setup Adjustments
Voltage (V)
Voltage (V)
Voltage (V)
12 12 12 13.8
6 6 6 6.9
0 1.5 3 60 90 0 1.5 3 60 120 0 1.5 3 60 180 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
E1-13
E1-08
E1-10
E1-09 E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
Note: 1. The following condition must be true when setting up the V/f pattern: E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
4. Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.
108 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
H1-01 Multi-Function Digital Input Terminal S1 Function Selection 1 to 9F 40 (F) <1> : Forward Run Command (2-Wire sequence)
H1-02 Multi-Function Digital Input Terminal S2 Function Selection 1 to 9F 41 (F) <1> : Reverse Run Command (2-Wire sequence)
H1-03 Multi-Function Digital Input Terminal S3 Function Selection 0 to 9F 24: External Fault
H1-04 Multi-Function Digital Input Terminal S4 Function Selection 0 to 9F 14: Fault Reset
H1-05 Multi-Function Digital Input Terminal S5 Function Selection 0 to 9F 3 (0) <1> : Multi-Step Speed Reference 1
H1-06 Multi-Function Digital Input Terminal S6 Function Selection 0 to 9F 4 (3) <1> : Multi-Step Speed Reference 2
H1-07 Multi-Function Digital Input Terminal S7 Function Selection 0 to 9F 6 (4) <1> : Jog Reference Selection
H1-08 Multi-Function Digital Input Terminal S8 Function Selection 0 to 9F 8: (6) <1> : External Baseblock Command
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Table 4.27 Multi-Function Digital Input Terminal Settings
Setting Function Page Setting Function Page
0 3-Wire Sequence 110 31 PID Integral Hold —
1 LOCAL/REMOTE Selection — 32 Multi-Step Speed Reference 4 —
2 External Reference 1/2 Selection — 34 PID Soft Starter Cancel —
3 Multi-Step Speed Reference 1 35 PID Input Level Selection —
4 Multi-Step Speed Reference 2 — 40 Forward Run Command (2-Wire sequence)
—
5 Multi-Step Speed Reference 3 41 Reverse Run Command (2-Wire sequence)
6 Jog reference Selection — 42 Run Command (2-Wire sequence 2)
—
7 Accel/Decel Time Selection 1 — 43 FWD/REV Command (2-Wire sequence 2)
8 Baseblock Command (N.O.) 47 Node Setup —
—
9 Baseblock Command (N.C.) 51 Disable Sequence Timers —
A Accel/Decel Ramp Hold — 52 Cancel Active Sequence Timer —
Start-Up Programming
B Drive Overheat Alarm (oH2) — 60 DC Injection Braking Command —
C Analog Terminal Input Selection — 61 External Speed Search Command 1 —
F Through Mode — 62 External Speed Search Command 2 —
& Operation
10 Up Command 63 Field Weakening —
—
11 Down Command 65 KEB Ride-Thru 1 (N.C.)
—
12 Forward Jog 66 KEB Ride-Thru 1 (N.O.)
—
13 Reverse Jog 67 Communications Test Mode —
14 Fault Reset — 68 High Slip Braking (HSB) —
4
15 Fast Stop (N.O.) — 6A Drive Enabled —
17 Fast Stop (N.C.) — 75 Up 2 Command
—
18 Timer Function Input — 76 Down 2 Command
19 PID Disable — 7A KEB Ride-Thru 2 (N.C.)
—
1A Accel/Decel Time Selection 2 — 7B KEB Ride-Thru 2 (N.O.)
1B Program Lockout — A8 Secondary PI Disable (N.O.) —
1E Reference Sample Hold — A9 Secondary PI Disable (N.C.) —
20 to 2F External Fault — AA Secondary PI Inverse Operation —
30 PID Integral Reset — AB Secondary PI Integral Reset —
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 109
4.6 Basic Drive Setup Adjustments
2 ms min.
Motor speed
Note: 1. The Run command must be closed for more than 2 ms.
2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the Run LED will flash to indicate
that protective functions are operating. If required by the application, set b1-17 to 1 to automatically issue the Run command upon drive
power up.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before applying
power to the drive. Failure to comply could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence
but set up for 2-Wire sequence (default). Make sure b1-17 is set to “0” (drive does not accept a Run command active at power up). When
initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.
110 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Start-Up Programming
Closed Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note: Detection works in forward and reverse.
& Operation
Frequency
reference
L4-02
Speed agree 1 OFF ON
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 111
4.6 Basic Drive Setup Adjustments
Status Description
Open Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.
Closed Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Frequency reference + L4-02
Frequency reference
L4-01 + L4-02
Frequency reference – L4-02
L4-01
–L4-01
Frequency reference + L4-02
–L4-01 – L4-02
Frequency reference
112 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
H3-01 = 0 H3-01 = 1
Frequency 100%
reference E1-04
-10 V -5 V
100 % 0V 5V 10 V
E1-04
-100%
E1-04
Figure 4.23 Frequency Reference Setting by Analog Input with Increased Gain
• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.
H3-01 = 0 H3-01 = 1
100 % 100%
Frequency H3-01 = 0
reference -10 V -6.0 V
2.0 V 10 V
-25% Analog Input
Voltage
0
2.0 V 10 V
Analog Input -100%
-25% Voltage E1-04
H3-01 = 1 -150%
Figure 4.24 Frequency Reference Setting by Analog Input with Negative Bias
Start-Up Programming
Setting 0: 0 to 10 Vdc
The input level is 0 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 0: 0 to 10 Vdc on page 112.
& Operation
Setting 1: 0 to 10 Vdc Bipolar
The input level is -10 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 1: 0 to 10 Vdc Bipolar on page
112.
Setting 2: 4 to 20 mA
4
Setting 3: 0 to 20 mA
H3-06: Terminal A3 Function Selection
Determines the function assigned to analog input terminal A3.
No. Name Setting Range Default
H3-06 Terminal A3 Function Selection 0 to 26 2
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 113
4.6 Basic Drive Setup Adjustments
114 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and
H4-08. Figure 4.25 illustrates how gain and bias settings work.
No. Name Setting Range Default
H4-02 Multi-Function Analog Output Terminal FM Gain -999.9 to 999.9% 100.0%
H4-03 Multi-Function Analog Output Terminal FM Bias -999.9 to 999.9% 0.0%
H4-05 Multi-Function Analog Output Terminal AM Gain -999.9 to 999.9% 50.0%
H4-06 Multi-Function Analog Output Terminal AM Bias -999.9 to 999.9% 0.0%
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Terminal FM
1. View the value set to H4-02 (Terminal FM Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-01 will be output from terminal FM.
2. Adjust H4-02 viewing the monitor connected to the terminal FM.
3. View the value set to H4-03 on the digital operator; terminal FM will output a voltage equal to 0% of the parameter
being set in H4-01.
4. Adjust H4-03 viewing the output signal on the terminal FM.
Terminal AM
1. View the value set to H4-05 (Terminal AM Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-04 will be output from terminal AM.
2. Adjust H4-05 viewing the monitor connected to the terminal AM.
3. View the value set to H4-06 on the digital operator; terminal AM will output a voltage equal to 0% of the parameter
being set in H4-04.
4. Adjust H4-06 viewing the output signal on the terminal AM.
H4-07, 08 = 0 H4-07, 08 = 1
15 V
Gain = 150%
Output Voltage
Bias = 0%
10 V
Gain = 100%
10 V Bias = 0%
Gain 150% 5V
Bias 0% Gain = 50%
Output Voltage Bias = 0%
-100%
Gain 100%
5V Bias 0% 100%
Monitor Value
-5 V
Gain 50%
Start-Up Programming
Bias 0%
0V -10 V
0% 100%
Monitor Value
-15 V
& Operation
Figure 4.25 Analog Output Gain and Bias Setting Example 1 and 2
Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
H4-07, 08 = 0 H4-07, 08 = 1
Gain = 100%
Bias = 30%
4
10V
Gain = 100%
10 V Output Voltage Bias = 0%
Bias 30% 3V
Output Voltage Gain 100% -100%
100%
Bias 0% Monitor Value
3V -4 V
Gain 100%
0V -10 V
0% Monitor Value 100%
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 115
4.6 Basic Drive Setup Adjustments
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
No. Name Setting Range Default
H4-07 Multi-Function Analog Output Terminal FM 0 to 2 0
Signal Level Selection
H4-08 Multi-Function Analog Output Terminal AM 0 to 2 0
Signal Level Selection
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
L3-01: Stall Prevention Selection during Acceleration
Stall Prevention during acceleration prevents tripping with overcurrent (oC), motor overload (oL1), or drive overload (oL2)
faults common when accelerating with heavy loads.
L3-01 determines the type of Stall prevention the drive should use during acceleration.
No. Name Setting Range Default
L3-01 Stall Prevention Selection during Acceleration 0 to 2 1
Setting 0: Disabled
No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to speed
fast enough, causing an overload fault.
Setting 1: Enabled
Enables Stall Prevention during acceleration.
Acceleration is reduced when the output current value exceeds 85% of the level set to parameter L3-02 for a longer than the
time set to L3-27. The acceleration stops when the current exceeds L3-02. Acceleration continues when the current falls below
L3-02 for longer than the time set to L3-27.
The Stall Prevention level is automatically reduced in the constant power range. Refer to L3-03: Stall Prevention Limit during
Acceleration on page 117.
Output current
L3-02
-15%
Time
Output frequency
116 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
L3-02
L3-03
Output frequency
E1-06
Base frequency
Start-Up Programming
<1> Setting 3 is not available in models 4A0930 or 4A1200.
Setting 0: Disabled
& Operation
The drive decelerates according to the set deceleration time. With high inertia loads or rapid deceleration, an overvoltage fault
may occur. If an overvoltage fault occurs, use dynamic braking options or switch to another L3-04 selection.
Setting 1: General-purpose Stall Prevention
The drive tries to decelerate within the set deceleration time. The drive pauses deceleration when the DC bus voltage exceeds
the Stall Prevention level and then continues deceleration when the DC bus voltage drops below that level. Stall Prevention 4
may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall Prevention depends on the input
voltage setting E1-01.
Drive Input Voltage Stall Prevention Level during Deceleration
200 V Class 377 Vdc
400 V Class 754 Vdc
600 V Class 1084 Vdc
Note: 1. Do not use this setting in combination with a Dynamic Braking Resistor or other dynamic braking options. If Stall Prevention during
deceleration is enabled, it will be triggered before the braking resistor option can operate.
2. This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider
using a dynamic braking option.
Figure 4.29 illustrates the function of Stall Prevention during deceleration.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 117
4.6 Basic Drive Setup Adjustments
Output Frequency
Deceleration characteristics
when Stall Prevention was
triggered during deceleration
Time
118 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.6 Basic Drive Setup Adjustments
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 119
4.7 Auto-Tuning
4.7 Auto-Tuning
Types of Auto-Tuning
The drive offers different types of Auto-Tuning for induction motors. Refer to the tables below to select the type of Auto-
Tuning that bests suits the application. Refer to Start-Up Flowchart on page 90 for directions on executing Auto-Tuning.
Auto-Tuning for Induction Motors
This feature automatically sets the V/f pattern and motor parameters E1- and E2- for an induction motor.
Table 4.29 Types of Auto-Tuning for Induction Motors
Type Setting Application Conditions and Benefits
• The drive is used in V/f Control and other Auto-Tuning selections are not possible.
• Perform when entering motor data manually while using motor cables longer than 50
Stationary Auto-Tuning for Line-to- m.
T1-01 = 2
Line Resistance • Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced with a
cable over 50 m long. Assumes Auto-Tuning has already been performed.
• Recommended for applications using Speed Estimation Speed Search or using the
Energy Saving function in V/f Control.
Rotational Auto-Tuning for V/f
Control
T1-01 = 3 • Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy for
certain functions like torque compensation, slip compensation, Energy Saving, and
Speed Search.
Table 4.30 lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.
The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor
manufacturer. Refer to Start-Up Flowchart on page 90 for details on the Auto-Tuning process.
Table 4.30 Auto-Tuning Input Data
Tuning Type (T1-01)
Input Value Input Parameter Unit 2 3
Rotational for V/f
Line-to-Line Resistance Control
Motor rated power T1-02 kW YES YES
Motor rated voltage T1-03 Vac – YES
Motor rated current T1-04 A YES YES
Motor rated frequency T1-05 Hz – YES
Number of motor poles T1-06 - – YES
Motor rated Speed T1-07 r/min – YES
Motor iron loss T1-11 W – YES
120 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.7 Auto-Tuning
- MODE - PRG
Auto-Tuning
2. Press or until the Auto-Tuning display appears. AUTO
Step Display/Result
Start-Up Programming
- A.TUNE - PRG Rdy
Mtr Rated Power
T1-02= 0.75kW
1. Press to access the motor output power parameter T1-02. (0.00 ~ 650.00)
“0.75kW”
& Operation
ESC FWD DATA
F1 F2
- A.TUNE - PRG Rdy
Mtr Rated Power 4
T1-02= 000.40kW
3. Press left , right , , , and to enter the motor power nameplate data in (0.00 ~ 650.00)
kW. “0.75kW”
FWD
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 121
4.7 Auto-Tuning
Step Display/Result
- A.TUNE - PRG Rdy
Mtr Rated Power
T1-02= 0.40kW
5. The display automatically returns to the display in Step 1. (0.00 ~ 650.00)
“0.75kW”
ESC FWD DATA
- A.TUNE - PRG
Rated Voltage
T1-03= 200.0VAC
Repeat Steps 1 through 5 to set the following parameters: (0.0 ~ 255.0)
“200.0VAC”
• T1-03, Motor Rated Voltage (Rotational Auto-Tuning for V/f Control only) ESC FWD DATA
Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or
serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the
motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply could result in improper
operation of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.
Enter the required information from the motor nameplate. Press to proceed to the Auto-Tuning start display.
Note: These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.
Step Display/Result
- A.TUNE - DRV Rdy
Auto-Tuning
0.00 Hz/ 0.00A
1. After entering the data listed on the motor nameplate, press to confirm. Tuning Ready ?
Press RUN key
ESC FWD
Press to activate Auto-Tuning. flashes. The drive begins by injecting current - A.TUNE - DRV Rdy
Tune Proceeding
into the motor for about 1 min, and then starts to rotate the motor.
X.XX Hz/ X.XXA
2. Note: The first digit on the display indicates which motor is undergoing <<<<<< >>> >>>
Auto-Tuning. The second digit indicates the type of Auto-Tuning being FWD
performed.
- MODE - DRV
End
3. Auto-Tuning finishes in approximately one to two minutes. Tune Successful
FWD RESET
122 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.8 No-Load Operation Test Run
Step Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz
1. Turn on the power to the drive. The initial display appears. U1-02= 0.00Hz LSEQ
U1-03= 0.00A LREF
JOG FWD FWD/REV
F1 F2
ESC LO
RE
2. Press to select LOCAL. The LO/RE light will turn on. RESET ENTER
RUN STOP
Off On
DIGITAL OPERATOR JVOP-180 ALARM
Start-Up Programming
F1 F2
ESC LO
RE
3. Press to give the drive a Run command. RUN will light and the motor will rotate RESET ENTER
& Operation
RUN RUN
Off On
Motor
4
4. Ensure the motor is rotating in the correct direction and that no faults or alarms occur.
Forward
If there is no error in step 4, press to increase the frequency reference. Increase the
5. frequency in increments of 10 Hz, verifying smooth operation at all speeds. For each – –
frequency, check the drive output current using monitor U1-03. The current should be well
below the motor rated current.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 123
4.8 No-Load Operation Test Run
Step Display/Result
F1 F2
ESC LO
RE
STOP
6. The drive should operate normally. Press to stop the motor. RUN flashes until the RESET ENTER
RUN RUN
Off On
124 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.9 Test Run with Load Connected
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 125
4.10 Test Run Checklist
Check the items that correspond to the control mode being used.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before energizing
the drive. Failure to comply could result in death or serious injury from moving equipment. When programmed for 3-Wire control, a momentary
closure on terminal S1 may cause the drive to start.
5 Select Stationary Auto-Tuning for Line-to-Line Resistance or Rotational Auto-Tuning for V/f Control if using Energy
Saving functions. 120
6 Decouple the motor for Rotational Auto-Tuning for V/f Control. 120
Enter the following data depending on Auto-Tuning method according to the information listed on the motor nameplate:
• Motor rated power to T1-02 (kW)
• Motor rated voltage to T1-03 (V)
7 • Motor rated current to T1-04 (A) –
• Motor base frequency to T1-05 (Hz)
• Number of motor poles to T1-06
• Motor base speed to T1-07 (r/min)
8 The should light after giving a Run command. –
9 To give Run command and frequency reference from the digital operator, press “LO/RE” key to set to LOCAL. 88
10 If the motor rotates in the opposite direction during test run, switch two of U/T1, V/T2, W/T3, or change b1-14. 91
11 Set motor rated current (E2-01) and motor protection (L1-01) values for motor thermal protection. –
12 Set the drive for REMOTE when control circuit terminals provide the Run command and frequency reference. 88
13 If the control circuit terminals should supply the frequency reference, select the correct voltage input signal level
(0 to +10 V or -10 to +10 V) or the correct current input signal level (4 to 20 mA or 0 to 20 mA). 94
14 Set the proper signal level to terminals A1, A2, A3 (0 to 20 mA, 4to 20 mA, 0 to +10 V or -10 to +10 V). 94
For A1, A2, and A3, when current input is used, switch the jumper on S1 from the V-side to I-side. Set the level for current
15 signal used with parameter H3-01 for terminal A1, H3-09 for terminal A2, H3-05 for terminal A3, (set “2” for 4 to 20 94
mA, or “3” for 0 to 20 mA). V = Voltage, I = Current analog input signal.
If an analog input supplies the frequency reference, make sure it produces the desired frequency reference. Make the
following adjustments if the drive does not operate as expected:
Gain adjustment: Set the maximum voltage/current signal and adjust the analog input gain (H3-03 for A1, H3-11 for A2,
16 H3-07 for A3) until the frequency reference value reaches the desired value. –
Bias adjustment: Set the minimum voltage/current signal and adjust the analog input bias (H3-04 for A1, H3-12 for A2,
H3-08 for A3) until the frequency reference value reaches the desired minimum value.
126 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.11 Fan and Pump Application Presets
Start-Up Programming
b5-46 PID Unit Selection 131
b5-90 EZ Sleep Unit 131
b5-91 EZ Minimum Speed 131
& Operation
b5-92 EZ Sleep Level 132
b5-94 EZ Wake-up Level 132
C1-01 Acceleration Time 1 101
C1-02 Deceleration Time 1 101
E2-01 Motor Rated Current 108 4
H3-09 Terminal A2 Signal Level Selection 114
L5-01 Number of Auto Restart Attempts 133
L5-04 Fault Reset Interval Time 133
o1-07 Second Line Monitor Selection 134
o1-08 Third Line Monitor Selection 134
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 127
4.11 Fan and Pump Application Presets
128 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.11 Fan and Pump Application Presets
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 129
4.12 Fan and Pump Application Preset Details
130 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.12 Fan and Pump Application Preset Details
b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID
feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No. Name Setting Range Default
b5-38 PID Setpoint User Display 1 to 60000 Determined by
b5-20
b5-39 PID Setpoint Display Digits 0 to 3 Determined by
b5-20
Setting 0: No Decimal Places
Setting 1: One Decimal Place
Setting 2: Two Decimal Places
Setting 3: Three Decimal Places
b5-46: PI Setpoint Monitor Unit Selection
Sets the digital operator display units in U5-01 and U5-04 when b5-20 is set to 3.
No. Name Setting Range Default
b5-46 PI Setpoint Monitor Unit Selection 0 to 15; 25 0
Setting 0: “WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Start-Up Programming
Setting 13: LPM (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)
Setting 15: “Hg (Inches of Mercury)
& Operation
Setting 25: No unit
b5-90: EZ Sleep Unit
Sets the unit, range, and resolution of parameters b5-91 and b5-92.
No. Name Setting Range Default
4
b5-90 EZ Sleep Unit 0, 1 0
Setting 0: Hz
Setting 1: RPM (number of motor poles must be entered)
b5-91: EZ Minimum Speed
Sets the PID minimum speed and integral lower limit.
The lower limit of the internal value is the higher of b5-34 and d2-02.
No. Name Setting Range Default
b5-91 EZ Minimum Speed 0.0 to 400.0 Hz <1> 0.0
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 131
4.12 Fan and Pump Application Preset Details
<1> Unit, range and resolution is determined by b5-90. Changing b5-90 will not automatically update the value of this parameter. Range is 0 to 24000
RPM when b5-90 is set to 1.
Internal frequency
reference
d2-01
Frequency Reference Upper Limit
Operating
range
132 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
4.12 Fan and Pump Application Preset Details
Start-Up Programming
L5-01: Number of Auto Restart Attempts
Sets the number of times that the drive may attempt to restart itself.
& Operation
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,
the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter
reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when: 4
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
No. Name Setting Range Default
L5-01 Number of Auto Restart Attempts 0 to 10 Times 0 Times
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 133
4.12 Fan and Pump Application Preset Details
134 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5
Troubleshooting
This chapter provides descriptions of the drive faults, alarms, errors, related displays, and guidance for
troubleshooting. This chapter can also serve as a reference guide for tuning the drive during a trial run.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 135
5.1 Drive Alarms, Faults, and Errors
136 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.2 Fault Detection
Troubleshooting
Faulty communications wiring or an existing
short circuit • Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or the
Communication data error occurred due to drive input power side.
noise • Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if 5
required.
• Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive
power supply input.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 137
5.2 Fault Detection
138 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.2 Fault Detection
Troubleshooting
Option Card External Fault
EF0
An external fault condition is present.
Cause Possible Solution
An external fault was received from the PLC • Remove the cause of the external fault.
and F6-03 is set to a value other than 3. • Remove the external fault input from the PLC.
Problem with the PLC program Check the PLC program and correct problems. 5
Digital Operator Display Fault Name
External Fault (input terminal S1)
EF1
External fault at multi-function input terminal S1.
External Fault (input terminal S2)
EF2
External fault at multi-function input terminal S2.
External Fault (input terminal S3)
EF3
External fault at multi-function input terminal S3.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 139
5.2 Fault Detection
Hardware problem If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
140 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.2 Fault Detection
Hardware problem If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
The output terminal is loose • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Main Circuit
Wire Gauges and Tightening Torque on page 57 for details.
The rated current of the motor being used is Check the drive selection and motor capacities.
Troubleshooting
less than 5% of the drive rated current
An output transistor is damaged If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
A single-phase motor is being used The drive cannot operate a single phase motor.
The output circuit is damaged If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 141
5.2 Fault Detection
142 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.2 Fault Detection
Troubleshooting
Same type of option card is currently connected
to oFb03 to oFb11
Option card error occurred at Option Port CN5-B
to oFb12 to oFb17
to oFC03 to oFC11
Option Card Error Occurred at Option Port CN5-C
to oFC12 to oFC17
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 143
5.2 Fault Detection
144 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.2 Fault Detection
The electrical thermal relay is operating at the • Check the current rating listed on the motor nameplate.
wrong level • Check the value set for the motor rated current (E2-01).
• Overexcitation increases the motor loss and the motor temperature. Excessive duration of
overexcitation may cause motor damage. Prevent excessive overexcitation operation or apply proper
Motor overheated by overexcitation operation cooling to the motor.
• Reduce the excitation deceleration gain (n3-13).
• Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
• Check values set to Speed Search related parameters.
Parameters related to Speed Search are set • Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively).
incorrectly
• After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.
Output current fluctuation due to power Check the power supply for phase loss.
supply loss
Troubleshooting
Overtorque Detection 2
oL4 The current has exceeded the value set for Torque Detection Level 2 (L6-05) for longer than the allowable
time (L6-06).
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 145
5.2 Fault Detection
Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.
ov • For 200 V class drives: approximately 410 V
• For 400 V class drives: approximately 820 V (740 V when E1-01 is less than 400)
• For 600 V class drives: approximately 1040 V
Cause Possible Solution
• Increase the deceleration time (C1-02 and C1-04).
Deceleration time is too short and regenerative • Install a dynamic braking resistor or a dynamic braking resistor unit.
energy is flowing from the motor into the drive • Set L3-04 to 1 to enable stall prevention during deceleration. Stall Prevention is enabled as the default
setting.
• Check if sudden drive acceleration triggers an overvoltage alarm.
• Increase the acceleration time.
Fast acceleration time causes the motor to • Use longer S-curve acceleration and deceleration times.
overshoot the speed reference
• Enable the Overvoltage Suppression function (L3-11 = 1).
• Lengthen the S-curve at acceleration end.
Excessive braking load The braking torque was too high, causing regenerative energy to charge the DC bus. Reduce the braking
torque, use a dynamic braking option, or lengthen decel time.
Install a DC link choke.
Surge voltage entering from the drive input
power Note: Voltage surge can result from a thyristor convertor and phase advancing capacitor using
the same input power supply.
Ground fault in the output circuit causes the • Check the motor wiring for ground faults.
DC bus capacitor to overcharge • Correct grounding shorts and reapply power.
• Check the settings for Speed Search-related parameters.
Improper parameters related to Speed Search • Enable Speed Search restart function (b3-19 greater than or equal to 1 to 10).
(including Speed Search after a momentary • Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03 respectively).
power loss and after a fault restart)
• Perform Stationary Auto-Tuning for line-to-line resistance and then set b3-14 to 1 to enable Speed
Estimation Speed Search.
• Check the voltage.
Drive input power voltage is too high
• Lower drive input power voltage within the limits listed in the specifications.
The braking transistor or braking resistor are • Check braking transistor and braking resistor wiring for errors.
wired incorrectly • Properly rewire the braking resistor device.
• Review the list of possible solutions provided for controlling noise.
Drive fails to operate properly due to noise
interference • Review the section on handling noise interference and check the control circuit lines, main circuit lines,
and ground wiring.
• Check the load inertia settings when using KEB, overvoltage suppression, or Stall Prevention during
Load inertia is set incorrectly deceleration.
• Adjust the load inertia ratio in L3-25 to better match the load.
• Adjust the parameters that control hunting.
Motor hunting occurs • Set the gain for Hunting Prevention (n1-02).
• Adjust the AFR time constant (n2-02 and n2-03).
146 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.2 Fault Detection
The braking operation duty cycle is too high Check the braking operation duty cycle. Braking resistor protection for ERF-type braking resistors
Troubleshooting
(L8-01 = 1) allows a braking duty cycle of maximum 3%.
The proper braking resistor has not been • Check the specifications and conditions for the braking resistor device.
installed • Select the optimal braking resistor.
Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more
frequently than its rating permits will trip the alarm even when the braking resistor surface is not very hot.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 147
5.2 Fault Detection
Thermistor Disconnect
<1> THo
The thermistor that detects motor temperature has become disconnected.
<1> Detected in models 4A0930 and 4A1200.
Motor Underload
UL6 UL6
The weight of the load has fallen below the underload curve defined in L6-14.
Cause Possible Solution
148 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.2 Fault Detection
The output current has fallen below the motor Adjust the value set to L6-14 so that output current remains above the motor underload curve during
underload curve defined in L6-14 for longer
than the time set to L6-03 normal operation.
Current Unbalance
<1> UnbC
Current flow has become unbalanced.
<1> Detected in models 4A0930 and 4A1200.
Troubleshooting
Power Loss Ride-Thru unit
• Cycle power to the drive. Check if the fault reoccurs.
Control power supply wiring is damaged • If the problem continues, replace the control board, the entire drive, or the control power supply. For
instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.
• Cycle power to the drive. Check if the fault reoccurs.
Internal circuitry is damaged • If the problem continues, replace either the control board or the entire drive. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
5
Digital Operator Display Fault Name
Undervoltage 3 (Soft-Charge Bypass Relay Fault)
Uv3
The soft-charge bypass relay failed.
Cause Possible Solution
• Cycle power to the drive and see if the fault reoccurs.
The relay or contactor on the soft-charge • Check monitor U4-06 for the performance life of the soft-charge bypass relay.
bypass relay is damaged • Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or a Yaskawa representative.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 149
5.2 Fault Detection
vToL VT Overload
Cause Possible Solution
The application may not be suited for the drive
The output current of the drive has been
elevated for a set length of time. • The application may not be suited for the drive
• The drive is undersized for the load
150 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.3 Alarm Detection
Baseblock
bb
Drive output interrupted as indicated by an external baseblock signal.
Troubleshooting
Option is damaged. If there are no problems with the wiring and the fault continues to occur, replace the option.
The option is not properly connected to the • The connector pins on the option are not properly lined up with the connector pins on the drive.
drive. • Reinstall the option.
• Check options available to minimize the effects of noise.
• Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring.
• Try to reduce noise on the controller side.
• Use surge absorbers on magnetic contactors or other equipment causing the disturbance.
5
A data error occurred due to noise.
• Use recommended cables or some other type of shielded line. Ground the shield to the controller side or
on the input power side.
• Separate the wiring for communication devices from the drive input power lines. Install an EMC noise
filter to the drive input power.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 151
5.3 Alarm Detection
Termination resistor setting is incorrect. Install a termination resistor at both ends of a communication line. Set the internal termination resistor switch
correctly on slave drives. Place DIP switch S2 to the ON position.
152 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.3 Alarm Detection
Troubleshooting
FbH The PID feedback input is higher than the level set to b5-36 for longer than the time set to b5-37, and b5-12
is set to 1 or 4.
Cause Possible Solutions
Parameter settings for b5-36 and b5-37 are Check parameters b5-36 and b5-37.
incorrect.
PID feedback wiring is faulty. Correct the wiring.
Feedback sensor has malfunctioned. Check the sensor and replace it if damaged. 5
Feedback input circuit is damaged. Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 153
5.3 Alarm Detection
Feedback input circuit is damaged. Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
Current Alarm
HCA
Drive current exceeded overcurrent warning level (150% of the rated current).
ILIM
Cur Lim Foldback Current Limit Foldback
<0x59>
Drive output speed is being limited due to the output current limit.
LT-2 The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note: The signal closes when the maintenance period ends if H2- = 2F. The signal will not close
if H2- = 10.
Cause Possible Solutions
The main circuit and control circuit
capacitors have reached 90% of their Replace the drive.
expected performance lives.
154 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.3 Alarm Detection
Motor Overheat
oH3 The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02,
H3-06 or H3-10 = E).
DC Bus Overvoltage
The DC bus voltage exceeded the trip point.
ov • For 200 V class drives: approximately 410 V
• For 400 V class drives: approximately 820 V (740 V when E1-01 is less than 400)
• For 600 V class drives: approximately 1040 V
Troubleshooting
Cause Possible Solutions
MEMOBUS/Modbus test has finished This verifies that the test was successful.
normally.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 155
5.3 Alarm Detection
1PH
1-Phase Foldback Output speed is being limited because of excessive DC bus voltage ripple.
<0x5A>
Cause Possible Solutions
An input phase has been lost or too much
load is being drawn by the motor in a Reduce the output load.
single-phase application.
156 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.4 Operator Programming Errors
Troubleshooting
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 157
5.5 Auto-Tuning Fault Detection
158 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.5 Auto-Tuning Fault Detection
Motor rated current and detected no-load • Check the motor rated current and no-load current.
current are inconsistent. • Correct the settings of parameters T1-04 and E2-03.
Troubleshooting
Er-05 No-Load Current Error
Cause Possible Solutions
Motor data entered during Auto-Tuning • Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
was incorrect. • Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the • Check and correct faulty motor wiring.
parameter setting range or the tuning
process took too long. • Perform Rotational Auto-Tuning.
5
• Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make
The load was too high during Rotational sure the load is lower than 30%.
Auto-tuning.
• If a mechanical brake is installed, make sure it is fully lifted during tuning.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 159
5.5 Auto-Tuning Fault Detection
160 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
5.6 Copy Function Related Displays
vFyE Parameter settings in the drive and those saved to the copy function are not the same
Troubleshooting
ways to restart the drive.
After the Fault Occurs Procedure
ALM
- MODE - DRV
oC
Overcurrent
Fix the cause of the fault, restart the drive, and Press on the digital operator when the error code
FWD RESET
RESET ENTER
RUN STOP
Drive
Close then open the fault signal digital input via Fault Reset Switch
S4 Fault Reset Digital Input
Resetting via Fault Reset Digital Input S4 terminal S4. S4 is set for “Fault Reset” as default
SC Digital Input Common
(H1-04 = 14).
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 161
5.6 Copy Function Related Displays
Note: If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear
a fault situation.
162 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
6
Periodic Inspection & Maintenance
This chapter describes the periodic inspection and maintenance of the drive to ensure that it receives
the proper care to maintain overall performance.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 163
6.1 Inspection
6.1 Inspection
Power electronics have limited life and may exhibit changes in characteristics or performance deterioration after years of use
under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and periodic
inspection on the drive.
Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and relays.
The electronics in the drive serve a critical role in maintaining proper motor control.
Follow the inspection lists provided in this chapter as a part of a regular maintenance program.
Note: The drive will require more frequent inspection if it is placed in harsh environments, such as:
• High ambient temperatures
• Frequent starting and stopping
• Fluctuations in the AC supply or load
• Excessive vibrations or shock loading
• Dust, metal dust, salt, sulfuric acid, chlorine atmospheres
• Poor storage conditions.
Perform the first equipment inspection one to two years after installation.
164 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
6.1 Inspection
• Inspect terminals for stripped, damaged, or loose • Tighten loose screws and replace damaged screws
or terminals.
General connections.
• If terminals are integral to a circuit board, then
• Make sure all terminals have been properly tightened.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 165
6.1 Inspection
166 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
6.2 Periodic Maintenance
Replacement Parts
Table 6.3 contains the estimated performance life of components that require replacement during the life of the drive. Only
use Yaskawa replacement parts for the appropriate drive model and revision.
Table 6.3 Estimated Performance Life
Component Estimated Performance Life
Cooling Fan, Circulation Fan 10 years
Electrolytic Capacitors 10 years <1>
<1> Electrolytic capacitors cannot be replaced on some lower capacity models. Complete drive replacement may be required for these models.
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for the purpose of replacing parts
to maintain performance. Some parts may require more frequent replacement due to poor environments or rigorous use.
Usage conditions for estimated performance life:
Ambient temperature: Yearly average of 40 °C (IP20/IP00 enclosure)
Yearly average of 30 °C (side-by-side mounting/NEMA 1, UL type 1 enclosure drive or external heatsink installation)
U4-06 Pre-charge Circuit Displays the number of times the drive is powered up as a percentage of the performance life of the inrush
circuit.
Maintenance
U4-07 IGBT Displays the percentage of the maintenance period reached by the IGBTs.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 167
6.2 Periodic Maintenance
168 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
6.3 Drive Replacement
2. Loosen the screws holding the terminal board in place. Remove the screw securing the bottom cover and remove the
bottom cover from the drive.
Note: IP00/Open Type enclosure drives do not have a bottom cover or conduit.
Figure 6.2 Unscrew the Terminal Board and Remove the Bottom Cover 6
3. Slide the terminal board as illustrated by the arrows to remove it from the drive along with the bottom cover.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 169
6.3 Drive Replacement
4. Disconnect all option cards and options, making sure they are intact before reusing.
5. Replace the drive and wire the main circuit.
2. Reconnect options for the new drive the same way the options were connected in the old drive. Connect option boards
to the same option ports in the new drive that were used in the old drive.
3. Replace the terminal cover.
4. After powering on the drive, all parameter settings are transferred from the terminal board to the drive memory. If an
oPE04 error occurs, load the parameter settings saved on the terminal board to the new drive by setting parameter
A1-03 to 5550. Reset the Maintenance Monitor function timers by setting parameters o4-01 through o4-12 to 0, and
parameter o4-13 to 1.
170 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
7
Peripheral Devices & Options
This chapter explains option installation procedures for the drive.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 171
7.1 Option Card Installation
Figure 7.1 shows an exploded view of the drive with the option and related components for reference.
K M A
C
NS MS
G TX RX
F
E
172 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
7.1 Option Card Installation
2. With the front covers and digital operator removed, apply the LED label (C) in the appropriate position on the drive
top front cover (A).
C
NS MS
TX RX
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 173
7.1 Option Card Installation
K M
L
2. Connect the ground wire (G) to the ground terminal (H) using one of the remaining provided screws (F). Connect the
other end of the ground wire (G) to the remaining ground terminal and installation hole on the option (M) using the
last remaining provided screw (F) and tighten both screws to 0.5 ~ 0.6 N m or (4.4 ~ 5.3 in lbs).
G
F
Note: There are two screw holes on the drive for use as ground terminals. When connecting three options, two ground wires will need
to share the same drive ground terminal.
Wiring the Option
1. Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to the
outside to provide adequate space for the wiring. In these cases, using diagonal cutting pliers, cut out the perforated
openings on the left side of the drive front cover. Sharp edges along the cut out should be smoothed down with a file
or sand paper to prevent any damage to the wires.
When installing option cards to models 2A0004 to 2A0040, 4A0002 to 4A0023, and 5A0003 to 5A0011, it may be
necessary to route the cables connected to the option through the top cover to the outside. Models 2A0056 to 2A0415,
4A0031 to 4A1200, and 5A0017 to 5A0242 have enough space to keep all wiring inside the unit.
2. Connect the communication cables to the option terminal block (TB1).
Note: Separate the communications cables from the main circuit cables and other wiring and power cables. Use properly grounded
shielded cables for the communication cables to prevent problems caused by electrical interference.
Replacing the Drive Covers and Digital Operator
1. Replace and secure the front covers of the drive (A, D) and replace the digital operator (B).
174 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
7.1 Option Card Installation
Note: Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure no cables
are pinched between the front covers and the drive when replacing the covers.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 175
7.1 Option Card Installation
176 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
Appendix: A
Specifications
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 177
A.1 Power Ratings
178 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
A.1 Power Ratings
Specifications
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 179
A.1 Power Ratings
180 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
A.1 Power Ratings
Specifications
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 181
A.1 Power Ratings
182 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
A.1 Power Ratings
ND Rating 207 248 300 346 410 465 657 922 1158
Input Current (A) <2>
HD Rating 170 207 248 300 346 410 584 830 1031
Rated Voltage
Input Rated Frequency Three-phase: 380 to 480 Vac 50/60 Hz/510 to 680 Vdc <3>
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
ND Rating 189 227 274 316 375 425 601 843 1059
Input Power (kVA)
HD Rating 155 189 227 274 316 375 534 759 943
ND Rating <5> 189 227 274 316 375 425 601 843 1059
Rated Output Capacity
(kVA) <4> 137 165 198 232 282 343 461 617 831
HD Rating <6> <6> <6> <6> <6> <5> <5> <5> <5>
ND Rating <5> 208 250 296 362 414 515 675 930 1200
Rated Output Current
(A) 180 216 260 304 370 450 605 810 1090
HD Rating <6> <6> <6> <6> <7> <5> <5> <5> <5>
Output ND Rating: 120% of rated output current for 60 s
Overload Tolerance HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency User-adjustable between 1 and 10 kHz User-adjustable between 1 and 5 kHz
0.95 ×
Maximum Output Voltage (V) Three-phase: 380 to 480 Vac (proportional to input voltage) [input voltage]
Maximum Output Frequency (Hz) 400 Hz (user-adjustable)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance.
<3> DC input is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
Specifications
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 183
A.1 Power Ratings
184 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
A.1 Power Ratings
Specifications
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 185
A.1 Power Ratings
ND Rating
Rated Output Current (A) <4> 125 145 192 242
186 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
A.2 Drive Specifications
Item Specification
Control Method V/f Control (V/f)
Frequency Control Range 0.01 to 400 Hz
Frequency Accuracy Digital input: within ±0.01% of the max output frequency (-10 to +40 °C)
(Temperature Fluctuation) Analog input: within ±0.1% of the max output frequency (25 °C ±10 °C)
Digital inputs: 0.01 Hz
Frequency Setting Resolution Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)
Resolution of analog inputs A1 and A3 is 10 bit + sign in current mode
Output Frequency Resolution 0.001 Hz
Main speed frequency reference: DC -10 to +10 V (20 kΩ), DC 0 to +10 V (20 kΩ),
Frequency Setting Signal 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)
Main speed reference: Pulse train input (max. 32 kHz)
Starting Torque <1> V/f: 150% at 3 Hz
Speed Control Range <1> V/f: 1:40
Accel/Decel Time 0.0 to 6000.0 s (2 selectable combinations of independent acceleration and deceleration settings)
Control
Character- Approx. 20% (approx. 125% when using braking resistor) <2>
istics • Short-time decel torque <3> : over 100% for 0.4/ 0.75 kW motors, over 50% for 1.5 kW motors, and
Braking Torque over 20% for 2.2 kW and above motors <4> (overexcitation braking/High Slip Braking: approx. 40%)
• Continuous regenerative torque: approx. 20% <4> (approx. 125% with dynamic braking resistor
option <2> : 10% ED, 10s)
Models 2A0004 to 2A0138, 4A0002 to 4A0072, and 5A0003 to 5A0052 have a built-in braking
Braking Transistor transistor.
V/f Characteristics User-selected programs and V/f preset patterns possible
Droop Control, Feed Forward Control, Momentary Power Loss Ride-Thru, Speed Search, Overtorque/
Undertorque Detection, Torque Limit, 17 Step Speed (max), Accel/decel Switch, S-curve Accel/decel,
3-wire Sequence, Auto-tuning (rotational, stationary tuning), Dwell, Cooling Fan on/off Switch, Slip
Compensation, Torque Compensation, Frequency Jump, Upper/lower Limits for Frequency Reference,
Main Control Functions DC Injection Braking at Start and Stop, Overexcitation Braking, High Slip Braking, PI Control (with
sleep function), Energy Saving Control, MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2
kbps), Fault Restart, Application Presets, Removable Terminal Block with Parameter Backup Function,
Online Tuning, KEB, Overexcitation Deceleration, Overvoltage Suppression, High Frequency
Injection, Dynamic Noise Control
Motor Protection Electronic thermal overload relay
Momentary Overcurrent Drive stops when output current exceeds 170% of rated output current
Protection
Overload Protection Drive stops when rated output current is 120% for 60 s <5>
Protection
Functions 200 V class: Stops when DC bus voltage exceeds approx. 410 V
Overvoltage Protection 400 V class: Stops when DC bus voltage exceeds approx. 820 V
600 V class: Stops when DC bus voltage exceeds approx. 1040 V
200 V class: Stops when DC bus voltage falls below approx. 190 V
Undervoltage Protection 400 V class: Stops when DC bus voltage falls below approx. 380 V
600 V class: Stops when DC bus voltage falls below approx. 475 V
Specifications
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 187
A.2 Drive Specifications
Item Specification
Momentary Power Loss Immediately stop after 15 ms or longer power loss <6> .
Ride-Thru Continuous operation during power loss than 2 s (standard) <7>
Heatsink Overheat Protection Thermistor
Protection Braking Resistor Overheat Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Functions Protection
Stall Prevention Stall Prevention is available during acceleration, deceleration, and during run.
Ground Protection Electronic circuit protection <8>
DC Bus Charge LED Remains lit until DC bus voltage falls below 50 V
Area of Use Indoors
Ambient Temperature -10 to +40 °C (IP20/NEMA Type 1 enclosure), -10 to +50 °C (IP00/Open Type enclosure)
Humidity 95 RH% or less (no condensation)
Environment Storage Temperature -20 to +60 °C (short-term temperature during transportation)
Altitude Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.
10 to 20 Hz: 9.8 m/s2 <9>
Vibration/Shock 20 to 55 Hz: 5.9 m/s2 (2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0099)
2.0 m/s2 (2A0250 to 2A0415, 4A0208 to 4A1200, and 5A0125 to 5A0242)
UL 508C (Power Conversion), UL/cUL listed, CSA 22.2 No. 14-05 (Industrial Control Equipment),
Safety Standard CE marked, RoHS compliant, EN 61800-5-1 (LVD), EN 61800-3 (EMC), IEC60529
Protection Design IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure <10>
<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors
and with changing motor temperature. Contact Yaskawa for consultation.
<2> Disable Stall Prevention during deceleration (L3-04 = 0) when using a regenerative converter, a regenerative unit, a braking resistor or the Braking
Resistor Unit. The default setting for the Stall Prevention function will interfere with the braking resistor.
<3> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed
down to zero in the shortest time.
<4> Actual specifications may vary depending on motor characteristics.
<5> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<6> May be shorter due to load conditions and motor speed.
<7> A separate Momentary Power Loss Ride-Thru Unit is required for models 2A0004 to 2A0056 and 4A0002 to 4A0031 if the application needs to
continue running for up to 2 seconds during a momentary power loss.
<8> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground
fault is present at the output.
<9> Models 4A0930 and 4A1200 are rated at 5.9 m/s2.
<10> Removing the top protective cover or bottom conduit bracket from an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while
maintaining IP20 conformity. This is applicable to models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242.
188 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
A.3 Drive Watt Loss Data
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 189
A.3 Drive Watt Loss Data
Normal Duty
Drive Model
Rated Amps (A) <1> Heatsink Loss (W) Interior Unit Loss (W) Total Loss (W)
4A0414 414 3443 1295 4738
4A0515 515 4850 1668 6518
4A0675 675 4861 2037 6898
4A0930 930 8476 2952 11428
4A1200 1200 8572 3612 12184
190 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
Appendix: B
Parameter List
This appendix contains a full listing of all parameters and settings available in the drive.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 191
B.1 A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
A1: Initialization
No.
(Addr. Name Description Values Page
Hex)
0: English
1: Japanese
A1-00 2: German
(100) 3: French Default: 0
Language Selection 4: Italian –
Range: 0 to 7
<1> 5: Spanish
6: Portuguese
7: Chinese
A1-01 0: View and set A1-01 and A1-04. U- parameters can also be viewed.
(101) 1: User Parameters (access to a set of parameters selected by the user, A2-01 Default: 2
Access Level Selection to A2-32) –
Range: 0 to 2
<2> 2: Advanced Access (access to view and set all parameters)
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization Default: 0
A1-03 5550: oPE04 error reset Range: 0 to 5550;
(103) Initialize Parameters 93
8008: Pump 8008 to 8011
8009: Pump w/ PI
8010: Fan
8011: Fan w/ PI
When the value set into A1-04 does not match the value set into A1-05, Default: 0000
A1-04
(104) Password parameters A1-01 through A1-03 and A2-01 through A2-33 cannot be Min.: 0000 –
changed. Max.: 9999
When the value set into A1-04 does not match the value set into A1-05, Default: 0000
A1-05
(105) Password Setting parameters A1-01 through A1-03 and A2-01 through A2-33 cannot be Min.: 0000 –
changed. Max.: 9999
0: General-purpose
8: Pump
A1-06 9: Pump w/PI Default: 0
(127) Application Preset 10: Fan –
Range: 0; 8 to 11
11: Fan w/PI
Note: This parameter is not settable. It is used as a monitor only.
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Initialization parameter A1-03.
192 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.2 b: Application
B.2 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID
control, the Dwell function, Energy Savings, and a variety of other application-related settings.
b2-01 DC Injection Braking StartSets the frequency at which DC Injection Braking starts when “Ramp to stop” Default: 0.5 Hz
(b1-03 = 0) is selected. Min.: 0.0 98
(189) Frequency
Parameter List
Max.: 10.0
Sets the DC Injection Braking current as a percentage of the drive rated current. Default: 50%
b2-02 DC Injection Braking
(18A) Current
Min.: 0 –
Max.: 100
Sets DC Injection Braking time at start. Disabled when set to 0.00 seconds. Default: 0.00 s
b2-03 DC Injection Braking Time
(18B) at Start
Min.: 0.00 –
Max.: 10.00
B
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 193
B.2 b: Application
No.
(Addr. Name Description Values Page
Hex)
Default: 0.50 s
b2-04 DC Injection Braking Time Sets DC Injection Braking time at stop.
(18C) at Stop
Min.: 0.00 –
Max.: 10.00
b3-10 Speed Search Detection Sets the gain which is applied to the speed detected by Speed Estimation Speed Default: 1.05
(19A) Compensation Gain Search before the motor is reaccelerated. Increase this setting if ov occurs Min.: 1.00 –
when performing Speed Search after a relatively long period of baseblock. Max.: 1.20
Default: 6.0
b3-12 Minimum Current Detection Sets the minimum current detection level during Speed Search.
(19C) Level during Speed Search
Min.: 2.0 –
Max.: 10.0
b3-14 Bi-Directional Speed Search 0: Disabled (uses the direction of the frequency reference) Default: 1
–
(19E) Selection 1: Enabled (drive detects which way the motor is rotating) Range: 0, 1
Sets the Speed Search restart current level as a percentage of the drive rated Default: 150%
b3-17 Speed Search Restart
(1F0) Current Level
current. Min.: 0 –
Max.: 200
Sets the time to detect Speed Search restart. Default: 0.10 s
b3-18 Speed Search Restart
(1F1) Detection Time
Min.: 0.00 –
Max.: 1.00
Sets the number of times the drive can attempt to restart when performing Default: 3
b3-19 Number of Speed Search
(1F2) Restarts
Speed Search. Min.: 0 –
Max.: 10
b3-24 Speed Search Method 0: Current Detection Default: 0
–
(1C0) Selection 1: Speed Estimation Range: 0, 1
b3-25 Sets the time the drive must wait between each Speed Search restart attempt. Default: 0.5 s
(1C8) Speed Search Wait Time Min.: 0.0 –
Max.: 30.0
194 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.2 b: Application
No.
(Addr Name Description Values Page
Hex.)
Selects a condition to activate Speed Search Selection at Start (b3-01) or
b3-27 External Speed Search Command 1 or 2 from the multi-function input. Default: 0
(1C9) Start Speed Search Select 0: Triggered when a Run command is issued (normal). –
Range: 0, 1
1: Triggered when an external baseblock is released.
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Available in drive software versions PRG: 8504 and later.
Max.: 25.00
0: Negative PID output triggers zero limit.
b5-11 PID Output Reverse 1: Rotation direction reverses with negative PID output. Default: 0
(1AF) Selection –
Note: When using setting 1, make sure reverse operation is permitted Range: 0, 1
by b1-04.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 195
B.2 b: Application
No.
(Addr. Name Description Values Page
Hex)
0: No fault. Digital output only.
1: Fault detection. Alarm output, drive continues operation.
2: Fault detection. Fault output, drive output is shut off.
3: No fault. Digital output only. No fault detection when PID control is Default: 0
b5-12 PID Feedback Loss
(1B0) Detection Selection
disabled. –
4: Fault detection. Alarm is triggered and drive continues to run. Fault Range: 0 to 5
detection even when PID is disabled.
5: Fault detection. Drive output shuts off. No fault detection when PID control
is disabled.
b5-13 PID Feedback Loss Sets the PID feedback loss detection level as a percentage of the maximum Default: 0%
(1B1) Detection Level
output frequency. Min.: 0 –
Max.: 100
Sets a delay time for PID feedback loss. Default: 1.0 s
b5-14 PID Feedback Loss
(1B2) Detection Time
Min.: 0.0 –
Max.: 25.5
Sets the frequency level that triggers the sleep function. Default: 0.0 Hz
b5-15 PID Sleep Function Start
(1B3) Level
Min.: 0.0 –
Max.: 400.0
Sets a delay time before the sleep function is triggered. Default: 0.0 s
b5-16
(1B4) PID Sleep Delay Time Min.: 0.0 –
Max.: 25.5
Sets the acceleration and deceleration time to PID setpoint. Default: 0.0 s
b5-17
(1B5) PID Accel/Decel Time Min.: 0.0 –
Max.: 6000.0
b5-18 0: Disabled Default: 0
(1DC) PID Setpoint Selection –
1: Enabled Range: 0, 1
b5-19 Sets the PID target value as a percentage of the maximum output frequency Default: 0.00%
(1DD) PID Setpoint Value when b5-18 is set to 1. Min.: 0.00 –
<1> Note: Values set above b5-38 will be internally limited to b5-38 Max.: 600.00
0: 0.01 Hz units
b5-20 1: 0.01% units (100% = max output frequency) Default: 1
(1E2) PID Setpoint Scaling 2: RPM (number of motor poles must entered) –
Range: 0 to 3
3: User-set (set scaling to b5-38 and b5-39, units based on b5-46 setting)
b5-34 Sets the minimum output possible from the PID controller as a percentage of Default: 0.00%
(19F) PID Output Lower Limit the maximum output frequency. Min.: -100.00 –
Max.: 100.00
b5-35 Limits the PID control input (deviation signal) as a percentage of the maximum Default: 1000.0%
(1A0) PID Input Limit output frequency. Acts as a bipolar limit. Min.: 0.0 –
Max.: 1000.0
Sets the PID feedback high detection level as a percentage of the maximum Default: 100%
b5-36 PID Feedback High
(1A1) Detection Level output frequency. Min.: 0 –
Max.: 100
Sets the PID feedback high level detection delay time. Default: 1.0 s
b5-37 PID Feedback High
(1A2) Detection Time
Min.: 0.0 –
Max.: 25.5
Scales the PID units to the maximum output frequency. Default: 10000
b5-38
(1FE) PID Setpoint User Display Min.: 1 –
Max.: 60000
0: No decimal places
b5-39 1: One decimal place Default: 2
(1FF) PID Setpoint Display Digits 2: Two decimal places –
Range: 0 to 3
3: Three decimal places
0: Display the frequency reference (U1-01) after PID compensation has been
b5-40 Frequency Reference added. Default: 0
(17F) Monitor Content during PID 1: Display the frequency reference (U1-01) before PID compensation has been –
Range: 0, 1
added.
196 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.2 b: Application
No.
(Addr. Name Description Values Page
Hex)
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second) Default: 0
b5-41
(160) PI Output 2 Unit Selection 8: Bar (Bar) –
9: Pa (Pascal) Range: 0 to 15; 25
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: “Hg (Inches of Mercury)
25: None
0: Linear - the monitor displays PID output
b5-42 1: Square root - the monitor displays square root PID output
(161) PI Output 2 Calculation 2: Quadratic - the monitor displays 1/(PID output) Default: 0
Mode –
3: Cubic - the monitor displays 1/(PID output) Range: 0 to 3
Note: Used for U5-14 and U5-15 only.
Sets the upper 4 digits of the maximum monitor value.
b5-43 Used with b5-44 to set maximum monitor value of U5-14 and U5-15 at Default: 0
(162) PI Output 2 Monitor Max
Upper 4 Digits maximum frequency. Min.: 0 –
Max.: 9999
Note: Used for U5-14 and U5-15 only.
Sets the lower 4 digits of the maximum monitor value.
b5-44 Used with b5-43 to set maximum monitor value of U5-14 and U5-15 at Default: 0
(163) PI Output 2 Monitor Max
Lower 4 Digits maximum frequency. Min.: 0 –
Max.: 99.99
Note: Used for U5-14 and U5-15 only.
b5-45 Sets the minimum display value at zero speed. Default: 0
(164) PI Output 2 Monitor This function is effective when b5-42 is set to 0 (Linear output mode).
Minimum
Min.: 0 –
Note: Used for U5-14 and U5-15 only. Max.: 999.9
Sets the display units for parameter b5-19, and monitors U5-01, U5-04 and
U5-99
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour) Default: 0
b5-46
(165) PID Units Selection 7: LPS (Liters per second) –
8: Bar (Bar) Range: 0 to 15; 25
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: “Hg (Inches of Mercury)
25: None
0: Zero limit when PID output is a negative value.
b5-47 Reverse Operation Selection Default: 1
(17D) 2 by PID Output 1: Reverse operation when PID output is a negative value –
(Zero limit if the reverse operation is prohibited by b1-04). Range: 0, 1
b5-89 Determines how the drive sleeps and wakes-up when using PID.
(B89) 0: Standard Default: 0
Sleep Method Selection –
1: EZ Sleep/Wake-up Range: 0, 1
Parameter List
b5-90 Sets the unit, range, and resolution of parameters b5-91 and b5-92. Default: 0
(B90) EZ Sleep Unit 0: Hz –
<1> Range: 0, 1
1: RPM (number of motor poles must be entered)
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 197
B.2 b: Application
No.
(Addr. Name Description Values Page
Hex)
Sets the PID minimum speed and integral lower limit. Default: 0.0 Hz
b5-91 The internal value is lower limited to the higher setting between b5-34 and Range: 0.0 to
(B91) EZ Minimum Speed d2-02. 400.0 Hz –
<1> or 0 to 24000 RPM
<2>
The drive will go to sleep when the drive output frequency (or speed) is at or Default: 0.0 Hz
b5-92 below this level for the time set in b5-93. Range: 0.0 to
(B92) EZ Sleep Level This parameter is internally lower limited to b5-91 (EZ Min Speed) + 1Hz. 400.0 Hz –
<1> or 0 to 24000 RPM
<2>
b5-93 The drive will go to sleep when the drive output frequency is at or below the Default: 5.0 s
(B93) EZ Sleep Time level set to b5-92 for the time set in this parameter. Min.: 0.0 –
<1> Max.: 1000.0
When b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback
(H3- = 20) drops below this level for the time set in b5-96.
b5-94 For reverse-acting, the PID Feedback must be above this level for the time set
(B94) in b5-96. Default: 0.00%
EZ Wake-up Level When b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID Min.: 0.00 –
<1>
Feedback (H3- = 20) drops below the PID Setpoint minus this level (for Max.: 600.00
normal acting PID) for the time set in b5-96.
For reverse-acting, Wake-up level is PID Setpoint plus this level. The PID
Feedback must be above the wake-up level for the time set in b5-96.
b5-95 Sets how the wake-up level is determined. Default: 0
(B95) EZ Wake-up Mode 0: Absolute –
<1> Range: 0, 1
1: Setpoint Delta
b5-96 The drive will wake up when the PID Feedback drops below the b5-94, EZ
(B96) Wake-up Level for the time set in this parameter. Default: 1.0 s
EZ Wake-up Time Min.: 0.0 –
<1>
Max.: 1000.0
<1> Unit and resolution are determined by b5-20, b5-39 and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
<2> Parameter is only effective when EZ Sleep is enabled by setting b5-89 to 1.
<3> Unit, range and resolution is determined by b5-90. Changing b5-90 will not automatically update the value of this parameter.
b6-01 Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain Default: 0.0 Hz
(1B6) Dwell Reference at Start that frequency at start. Min.: 0.0 –
Max.: 400.0
Default: 0.0 s
b6-02
(1B7) Dwell Time at Start Min.: 0.0 –
Max.: 10.0
b6-03 Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain Default: 0.0 Hz
(1B8) Dwell Reference at Stop that frequency at stop. Min.: 0.0 –
Max.: 400.0
Default: 0.0 s
b6-04
(1B9) Dwell Time at Stop Min.: 0.0 –
Max.: 10.0
198 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.2 b: Application
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 199
B.3 C: Tuning
B.3 C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, torque compensation, and carrier frequency
selections.
C1-09 Sets the time for the Fast Stop function. Default: 10.0 s
(208) Fast Stop Time Min.: 0.0 –
Max.: 6000.0 <1>
C1-10 Accel/Decel Time Setting 0: 0.01 s (0.00 to 600.00 s) Default: 1
(209) Units –
1: 0.1 s (0.0 to 6000.0 s) Range: 0, 1
Sets the frequency to switch between accel/decel time settings Default: 0.0 Hz
C1-11 Accel/Decel Time
(20A) Switching Frequency
Min.: 0.0 –
Max.: 400.0
<1> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
200 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.3 C: Tuning
C3-03 Sets an upper limit for the slip compensation function as a percentage of motor Default: 200%
(211) Slip Compensation Limit rated slip for motor 1 (E2-02). Min.: 0 –
Max.: 250
Slip Compensation 0: Disabled.
C3-04 Default: 0
(212)
Selection during 1: Enabled above 6 Hz. –
Regeneration Range: 0 to 2
2: Enabled whenever slip compensation is possible.
Max.: 99
<1> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 201
B.4 d: References
B.4 d: References
Reference parameters set the various frequency reference values during operation.
202 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.4 d: References
No.
(Addr. Name Description Values Page
Hex)
d1-17 Sets the Jog frequency reference. Setting units are determined by parameter Default: 6.00 Hz
(292) Jog Frequency Reference o1-03. Min.: 0.00 102
Max.: 400.00 <1>
<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 203
B.4 d: References
No.
(Addr. Name Description Values Page
Hex)
d4-05 0: Bias value is held if no input Up 2 or Down 2 is active.
Frequency Reference Bias 1: When the Up 2 reference and Down 2 reference are both on or both off, the Default: 0
(2AC) Operation Mode Selection –
(Up/Down 2) applied bias becomes 0. The specified accel/decel times are used for Range: 0, 1
acceleration or deceleration.
d4-06 Frequency Reference Bias The Up/Down 2 bias value is saved in d4-06 when the frequency reference is Default: 0.0%
(2AD) (Up/Down 2)
not input by the digital operator. Set as a percentage of the maximum output Min.: -99.9 –
frequency. Max.: 100.0
Limits how much the frequency reference is allowed to change while an input
d4-07 Analog Frequency terminal set for Up 2 or Down 2 is enabled. If the frequency reference changes Default: 0.01%
(2AE) Reference Fluctuation Limit for more than the set value, then the bias value is held and the drive accelerates Min.: 0.01 –
(Up/Down 2) or decelerates to the frequency reference. Set as a percentage of the maximum Max.: 100.0
output frequency.
d4-08 Sets the upper limit for the bias and the value that can be saved in d4-06. Set Default: 1.0%
(2AF) Frequency Reference Bias as a percentage of the maximum output frequency.
Upper Limit (Up/Down 2)
Min.: 0.0 –
Max.: 100.0
d4-09 Sets the lower limit for the bias and the value that can be saved in d4-06. Set Default: 0.0%
(2B0) Frequency Reference Bias as a percentage of the maximum output frequency. Min.: -99.9 –
Lower Limit (Up/Down 2)
Max.: 0.0
d4-10 Up/Down Frequency 0: The lower limit is determined by d2-02 or an analog input. Default: 0
(2B6) Reference Limit Selection 1: The lower limit is determined by d2-02. –
Range: 0, 1
204 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.5 E: Motor Parameters
E1-01 WARNING! Electrical Shock Hazard. Drive input voltage (not motor Default: 230 V <1>
(300) Input Voltage Setting voltage) must be set in E1-01 for the protective features of the drive to Min.: 155 104
function properly. Failure to do so may result in equipment damage Max.: 255 <1>
and/or death or personal injury.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 205
B.5 E: Motor Parameters
E2-02
Sets the motor rated slip. Automatically set during Auto-Tuning. Default: <1>
(30F) Motor Rated Slip Min.: 0.00 Hz –
Max.: 20.00 Hz
Sets the no-load current for the motor. Automatically set during Auto-Tuning. Default: <1>
E2-03
(310) Motor No-Load Current Min.: 0 A –
Max.: E2-01 <2>
Sets the number of motor poles. Automatically set during Auto-Tuning. Default: 4
E2-04
(311) Number of Motor Poles Min.: 2 –
Max.: 48
206 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.6 F: Communication Options
F4-01 Terminal V1 Monitor Sets the monitor signal for output from terminal V1. Set this parameter to the Default: 102
(391) Selection
last three digits of the desired U- monitor. Some U parameters are –
available only in certain control modes. Range: 000 to 999
F4-02 Sets the gain for voltage output via terminal V1. Default: 100.0%
(392) Terminal V1 Monitor Gain Min.: -999.9 –
Max.: 999.9
F4-03 Terminal V2 Monitor Sets the monitor signal for output from terminal V2. Set this parameter to the Default: 103
(393) Selection
last three digits of the desired U- monitor. Some U parameters are –
available only in certain control modes. Range: 000 to 999
F4-04 Sets the gain for voltage output via terminal V2. Default: 50.0%
(394) Terminal V2 Monitor Gain Min.: -999.9 –
Max.: 999.9
F4-05 Sets the amount of bias added to the voltage output via terminal V1. Default: 0.0%
(395) Terminal V1 Monitor Bias Min.: -999.9 –
Max.: 999.9
F4-06 Sets the amount of bias added to the voltage output via terminal V2. Default: 0.0%
(396) Terminal V2 Monitor Bias Min.: -999.9 –
Max.: 999.9
F4-07 0: 0 to 10 V Default: 0
(397) Terminal V1 Signal Level –
1: -10 to 10 V Range: 0, 1
F4-08 0: 0 to 10 V Default: 0
(398) Terminal V2 Signal Level –
1: -10 to 10 V Range: 0, 1
F6-07 Multi-Step Speed Enable/ 0: Multi-step reference disabled (same as F7) Default: 0
(3A8)
Disable Selection when 1: Multi-step reference enabled (same as V7) –
NefRef/ComRef is Selected Range: 0, 1
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 207
B.6 F: Communication Options
No.
(Addr. Name Description Values Page
Hex)
F6-08 0: Communication-related parameters (F6-/F7-) are not reset when
Reset Communication the drive is initialized using A1-03. Default: 0
(36A)
Parameters 1: Reset all communication-related parameters –
<2> Range: 0, 1
(F6-/F7-) when the drive is initialized using A1-03.
Sets the node address if a CC-Link option is installed. Default: 0
F6-10
(3B6) CC-Link Node Address Min.: 0 –
Max.: 64
0: 156 Kbps
1: 625 Kbps Default: 0
F6-11 CC-Link Communication 2: 2.5 Mbps –
(3B7) Speed 3: 5 Mbps Range: 0 to 4
4: 10 Mbps
F6-14 0: Disabled Default: 0
(3BB) bUS Error Auto Reset –
1: Enabled Range: 0, 1
Default: 21
F6-20 MECHATROLINK Station Sets the station address when the MECHATROLINK option has been
(36B) Address installed. Min.: 20 <4> —
Max.: 3F
F6-21 MECHATROLINK Frame 0: 32 byte Default: 0
(36C) —
Size 1: 17 byte Range: 0, 1
F6-22 MECHATROLINK Link 0: 10 Mbps Default: 0
(36D) —
Speed 1: 4 Mbps Range: 0, 1
Sets the MECHATROLINK-II monitor (E). Default: 0
F6-23 MECHATROLINK
(36E) Min.: 0 —
Monitor Selection (E) Max.: FFFF
Sets the MECHATROLINK-II monitor (F). Default: 0
F6-24 MECHATROLINK
(36F) Min.: 0 —
Monitor Selection (F) Max.: FFFF
0: Ramp to stop. Decelerate using the deceleration time in C1-02.
F6-25 Operation Selection at 1: Coast to stop Default: 1
(3C9) Watchdog Timer Error (E5) 2: Fast stop. Decelerate using the deceleration time in C1-09. —
Range: 0 to 3
3: Alarm only
Sets the number of option communication errors (bUS). Default: 2
F6-26 MECHATROLINK bUS
(3CA)
Min.: 2 —
Errors Detected
Max.: 10
Sets the node address. Default: 0
F6-30 PROFIBUS-DP Node
(3CB)
Min.: 0 –
Address Max.: 125
F6-31 PROFIBUS-DP Clear Mode 0: Resets drive operation with a Clear mode command. Default: 0
–
(3CC) Selection 1: Maintains the previous operation state when Clear mode command is given. Range: 0, 1
0: PPO Type
1: Conventional
F6-32 PROFIBUS-DP Data 2: PPO (w/bit 0) <1> Default: 0
(3CD) 3: PPO Type (Auto Enter) <1> –
Format Selection Range: 0 to 5
4: Conventional (Auto Enter) <1>
5: PPO (w/bit0, Auto Enter) <1>
Sets the node address. Default: 0
F6-35 CANopen Node ID
(3D0) Selection
Min.: 0 –
Max.: 126
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps Default: 6
F6-36 CANopen Communication 4: 125 kbps
(3D1) Speed –
5: 250 kbps Range: 0 to 8
6: 500 kbps
7: 800 kbps
8: 1 Mbps
F6-41
CompoNet Communication
(03D6)
Speed Reserved. – –
<1>
208 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.6 F: Communication Options
No.
(Addr. Name Description Values Page
Hex)
0: 125 kbps
1: 250 kbps Default: 4
F6-51 DeviceNet Communication 2: 500 kbps –
(3C2) Speed Range: 0 to 4
3: Adjustable from network
4: Detect automatically
Sets the format of the data set from the DeviceNet master to the drive. Default: 21
F6-52
(3C3) DeviceNet PCA Setting Min.: 0 –
Max.: 255
Sets the format of the data set from the drive to the DeviceNet master. Default: 71
F6-53
(3C4) DeviceNet PPA Setting Min.: 0 –
Max.: 255
0: Enabled
1: Disabled, no fault detection
F6-54 DeviceNet Idle Mode Fault 2: Vendor Specific <1> Default: 0
(3C5) Detection –
Range: 0 to 4
3: Forward <1>
4: Reverse <1>
Verifies the baud rate running on the network.
F6-55 DeviceNet Baud Rate 0: 125 kbps Default: 0
(3C6) Monitor 1: 250 kbps –
Range: 0 to 2
2: 500 kbps
Sets the scaling factor for the speed monitor in DeviceNet. Default: 0
F6-56
(3D7) DeviceNet Speed Scaling Min.: -15 –
Max.: 15
Sets the scaling factor for the output current monitor in DeviceNet. Default: 0
F6-57
(3D8) DeviceNet Current Scaling Min.: -15 –
Max.: 15
Sets the scaling factor for the torque monitor in DeviceNet. Default: 0
F6-58
(3D9) DeviceNet Torque Scaling Min.: -15 –
Max.: 15
Sets the scaling factor for the power monitor in DeviceNet. Default: 0
F6-59
(3DA) DeviceNet Power Scaling Min.: -15 –
Max.: 15
Sets the scaling factor for the voltage monitor in DeviceNet. Default: 0
F6-60
(3DB) DeviceNet Voltage Scaling Min.: -15 –
Max.: 15
Sets the scaling factor for the time monitor in DeviceNet. Default: 0
F6-61
(3DC) DeviceNet Time Scaling Min.: -15 –
Max.: 15
Sets the heartbeat interval for DeviceNet communications. Default: 0
F6-62 DeviceNet Heartbeat
(3DD) Interval
Min.: 0 –
Max.: 10
Saves and monitors settings 0 to 63 of F6-50 (DeviceNet MAC Address). Default: 63
F6-63 DeviceNet Network MAC
(3DE) ID
Min.: 0 –
Max.: 63
F6-64 to Reserved for Dynamic I/O Assembly Parameters.
F6-71
(3DF to Reserved – –
3C8)
F6-72
(081B) PowerLink Node Address Reserved. – –
<1>
F6-75 Selects the protocol for the SI-J3 option card. Default: 2
(0B20) P1-N2 Protocol Select 1: N2 –
<3> Range: 1, 2
2: P1
F6-76
0: Disabled Default: 1
(0B20) P1-N2 Comm Fault –
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 209
B.6 F: Communication Options
No.
(Addr. Name Description Values Page
Hex)
F6-79 Sets the baud rate for the P1 protocol. Default: 3
(0B24) Baud Rate Select 2: 4800 –
<3> Range: 2, 3
3: 9600
F7-01 Sets the most significant octet of network static IP address.
Default: 192
(3E5) IP Address 1 –
<5> Range: 0 to 255
F7-02 Sets the second most significant octet of network static IP address.
Default: 168
(3E6) IP Address 2 –
<5> Range: 0 to 255
F7-03 Sets the third most significant octet of network static IP address.
Default: 1
(3E7) IP Address 3 –
<5> Range: 0 to 255
F7-04 Sets the fourth most significant octet of network static IP address.
Default: 20
(3E8) IP Address 4 –
<5> Range: 0 to 255
F7-05 Sets the most significant octet of network static Subnet Mask. Default: 255
(3E9) Subnet Mask 1 –
Range: 0 to 255
F7-06 Sets the second most significant octet of network static Subnet Mask. Default: 255
(3EA) Subnet Mask 2 –
Range: 0 to 255
F7-07 Sets the third most significant octet of network static Subnet Mask. Default: 255
(3EB) Subnet Mask 3 –
Range: 0 to 255
F7-08 Sets the fourth most significant octet of network static Subnet Mask. Default: 0
(3EC) Subnet Mask 4 –
Range: 0 to 255
F7-09 Sets the most significant octet of network Gateway address. Default: 192
(3ED) Gateway Address 1 –
Range: 0 to 255
F7-10 Sets the second most significant octet of network Gateway address. Default: 168
(3EE) Gateway Address 2 –
Range: 0 to 255
F7-11 Sets the third most significant octet of network Gateway address. Default: 1
(3EF) Gateway Address 3 –
Range: 0 to 255
F7-12 Sets the fourth most significant octet of network Gateway address. Default: 1
(3E0) Gateway Address 4 –
Range: 0 to 255
Select the option address setting method
F7-13 Address Mode at Startup 0: Static <6> Default: 2
–
(3F1) 1: BOOTP Range: 0 to 2
2: DHCP
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half duplex forced (port 1)/Auto-negotiate duplex mode and
communication speed (port 2) <1>
F7-14 4: Half duplex forced (port 1)/Full duplex forced (port 2) <1> Default: 1
(3F2) Duplex Mode Selection 5: Auto-negotiate duplex mode and communication speed (port 1)/Half duplex –
Range: 0 to 8
forced (port 2) <1>
6: Auto-negotiate duplex mode and communication speed (port 1)/Full duplex
forced (port 2) <1>
7: Full duplex forced (port 1)/Half duplex forced (port 2) <1>
8: Full duplex forced (port 1)/Auto-negotiate duplex mode and communication
speed (port 2) <1>
Sets the communication speed
10: 10 Mbps
F7-15 Communication Speed Default: 10
(3F3) Selection
100: 100 Mbps –
101: 10 Mbps (port 1)/100 Mbps (port 2) <1> Range: 10 to 102
102: 100 Mbps (port 1)/10 Mbps (port 2) <1>
Sets the timeout value for communication loss detection in tenths of a second. Default: 0.0 s
F7-16 Communication Loss
(3F4) Timeout A value of 0 disables the connection timeout. Min.: 0.0 –
Example: An entered value of 100 represents 10.0 seconds. Max.: 30.0
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH Default: 0
F7-17 EtherNet/IP Speed Scaling
(3F5) Factor
Object. Min.: -15 –
Max.: 15
210 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.6 F: Communication Options
No.
(Addr. Name Description Values Page
Hex)
F7-18 EtherNet/IP Current Scaling Sets the scaling factor for the output current monitor in EtherNet/IP Class ID Default: 0
(3F6) Factor 2AH Object. Min.: -15 –
Max.: 15
F7-19 EtherNet/IP Torque Scaling Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH Default: 0
(3F7) Factor
Object. Min.: -15 –
Max.: 15
F7-20 EtherNet/IP Power Scaling Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH Default: 0
(3F8) Factor Object. Min.: -15 –
Max.: 15
F7-21 EtherNet/IP Voltage Scaling Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH Default: 0
(3F9) Factor
Object. Min.: -15 –
Max.: 15
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH Default: 0
F7-22
(3FA) EtherNet/IP Time Scaling Object. Min.: -15 –
Max.: 15
F7-23 to Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly 116
F7-32 Dynamic Output Assembly will be written to this corresponding MEMOBUS/Modbus address. A
(3FB to Parameters Default: 0 –
374) MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus register.
Parameters used in Input Assembly 166. Each parameter contains a
F7-33 to MEMOBUS/Modbus address. The value sent for Input Assembly 166 will be
F7-42 Dynamic Input Assembly read from this corresponding MEMOBUS/Modbus address. A MEMOBUS/
(375 to Parameters Modbus address value of 0 means that the value sent for Input Assembly 166 Default: 0 –
37E) is not defined by the user, therefore the option default register value will be
returned.
F7-60 Default: 0
Sets MEMOBUS/Modbus address for PZD1 Write (PPO Write).
(0780) PZD1 Write Values 0 to 2 enable the PZD1 Write as STW. Min.: 0 –
<1> Max.: FFFF
F7-61 Default: 0
Sets MEMOBUS/Modbus address for PZD2 Write (PPO Write).
(0781) PZD2 Write Values 0 to 2 enable the PZD2 Write as HSW. Min.: 0 –
<1> Max.: FFFF
F7-62 Default: 0
Sets MEMOBUS/Modbus address for PZD3 Write (PPO Write).
(0782) PZD3 Write Values 0 to 2 disable the PZD3 Write. Min.: 0 –
<1> Max.: FFFF
F7-63 Default: 0
Sets MEMOBUS/Modbus address for PZD4 Write (PPO Write).
(0783) PZD4 Write Values 0 to 2 disable the PZD4 Write. Min.: 0 –
<1> Max.: FFFF
F7-64 Default: 0
Sets MEMOBUS/Modbus address for PZD5 Write (PPO Write).
(0784) PZD5 Write Values 0 to 2 disable the PZD5 Write. Min.: 0 –
<1> Max.: FFFF
F7-65 Default: 0
Sets MEMOBUS/Modbus address for PZD6 Write (PPO Write).
(0785) PZD6 Write Values 0 to 2 disable the PZD6 Write. Min.: 0 –
<1> Max.: FFFF
F7-66 Default: 0
Sets MEMOBUS/Modbus address for PZD7 Write (PPO Write).
(0786) PZD7 Write Values 0 to 2 disable the PZD7 Write. Min.: 0 –
<1> Max.: FFFF
F7-67 Default: 0
Sets MEMOBUS/Modbus address for PZD8 Write (PPO Write).
(0787) PZD8 Write Values 0 to 2 disable the PZD8 Write. Min.: 0 –
<1> Max.: FFFF
F7-68 Default: 0
Sets MEMOBUS/Modbus address for PZD9 Write (PPO Write).
(0788) PZD9 Write Values 0 to 2 disable the PZD9 Write. Min.: 0 –
<1> Max.: FFFF
F7-69 Default: 0
Sets MEMOBUS/Modbus address for PZD10 Write (PPO Write).
(0789) PZD10 Write Values 0 to 2 disable the PZD10 Write. Min.: 0 –
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 211
B.6 F: Communication Options
No.
(Addr. Name Description Values Page
Hex)
F7-72 Default: 0
Sets MEMOBUS/Modbus address for PZD3 Read (PPO Read).
(078C) PZD3 Read Values 0 to 2 disable the PZD3 Read. Min.: 0 –
<1> Max.: FFFF
F7-73 Default: 0
Sets MEMOBUS/Modbus address for PZD4 Read (PPO Read).
(078D) PZD4 Read Values 0 to 2 disable the PZD4 Read. Min.: 0 –
<1> Max.: FFFF
F7-74 Default: 0
Sets MEMOBUS/Modbus address for PZD5 Read (PPO Read).
(078E) PZD5 Read Values 0 to 2 disable the PZD5 Read. Min.: 0 –
<1> Max.: FFFF
F7-75 Default: 0
Sets MEMOBUS/Modbus address for PZD6 Read (PPO Read).
(078F) PZD6 Read Values 0 to 2 disable the PZD6 Read. Min.: 0 –
<1> Max.: FFFF
F7-76 Default: 0
Sets MEMOBUS/Modbus address for PZD7 Read (PPO Read).
(0790) PZD7 Read Values 0 to 2 disable the PZD7 Read. Min.: 0 –
<1> Max.: FFFF
F7-77 Default: 0
Sets MEMOBUS/Modbus address for PZD8 Read (PPO Read).
(0791) PZD8 Read Values 0 to 2 disable the PZD8 Read. Min.: 0 –
<1> Max.: FFFF
F7-78 Default: 0
Sets MEMOBUS/Modbus address for PZD9 Read (PPO Read).
(0792) PZD9 Read Values 0 to 2 disable the PZD9 Read. Min.: 0 –
<1> Max.: FFFF
F7-79 Default: 0
Sets MEMOBUS/Modbus address for PZD10 Read (PPO Read).
(0793) PZD10 Read Values 0 to 2 disable the PZD10 Read. Min.: 0 –
<1> Max.: FFFF
<1> Available in drive software versions PRG: 8503 and later.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Available in drive software versions PRG: 8502 and later.
<4> Values shown are for the MECHATROLINK-II option (SI-T3). Values for MECHATROLINK-III option (SI-ET3) are: Min: 03, Max.: EF
<5> Cycle power for setting changes to take effect.
<6> If F7-13 is set to 0, all IP addresses (F7-01 to F7-04) must be unique.
212 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.7 H Parameters: Multi-Function Terminals
H1-01 Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 40 (F) <1>
Terminal S1 Function Refer to pages 213 to 215 for descriptions of setting values. Min.: 1 109
(438) Selection Note: Set unused terminals to F. Max.: 9F
Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 41 (F) <1>
H1-02 Terminal S2 Function Refer to pages 213 to 215 for descriptions of setting values.
(439) Min.: 1 109
Selection Note: Set unused terminals to F. Max.: 9F
Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 24
H1-03 Terminal S3 Function Refer to pages 213 to 215 for descriptions of setting values. Min.: 0
(400) 109
Selection Note: Set unused terminals to F. Max.: 9F
Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 14
H1-04 Terminal S4 Function Refer to pages 213 to 215 for descriptions of setting values.
(401) Min.: 0 109
Selection Note: Set unused terminals to F. Max.: 9F
Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 3 (0) <1>
H1-05 Terminal S5 Function Refer to pages 213 to 215 for descriptions of setting values.
(402) Min.: 0 109
Selection Note: Set unused terminals to F. Max.: 9F
H1-06 Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 4 (3) <1>
Terminal S6 Function Refer to pages 213 to 215 for descriptions of setting values. Min.: 0 109
(403) Selection Note: Set unused terminals to F. Max.: 9F
H1-07 Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 6 (4) <1>
Terminal S7 Function Refer to pages 213 to 215 for descriptions of setting values. Min.: 0 109
(404) Selection Note: Set unused terminals to F. Max.: 9F
Multi-Function Digital Input Assigns a function to the multi-function digital inputs. Default: 8 (6) <1>
H1-08 Terminal S8 Function Refer to pages 213 to 215 for descriptions of setting values.
(405) Min.: 0 109
Selection Note: Set unused terminals to F. Max.: 9F
<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).
6 Jog reference selection Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference –
sources.
7 Accel/decel time selection 1 Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set –
in C1-03, C1-04).
8 Baseblock command (N.O.) Closed: No drive output –
B
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 213
B.7 H Parameters: Multi-Function Terminals
B Drive overheat alarm (oH2) Closed: An external device has triggered an oH2 alarm. Sets Drive Overheat Pre-alarm Multi- –
Function Digital Output 20h.
214 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.7 H Parameters: Multi-Function Terminals
62 External Speed Search Closed: Activates Current Detection Speed Search from the frequency reference. –
command 2
63 Field weakening Closed: The drive performs Field Weakening control as set for d6-01 and d6-02. –
65 KEB Ride-Thru 1 (N.C.) Open: KEB Ride-Thru 1 enabled. –
66 KEB Ride-Thru 1 (N.O.) Closed: KEB Ride-Thru 1 enabled. –
67 Communications test mode Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the test –
completes successfully.
68 High Slip Braking (HSB) Closed: Activates High Slip Braking to stop the drive during a Run command. –
Open: Drive disabled. If this input is opened during run, the drive will stop as specified by
6A Drive enable b1-03. –
Closed: Ready for operation.
75 Up 2 command Used to control the bias added to the frequency reference by the Up/Down 2 function. The –
Up 2 and Down 2 commands must always be used in conjunction with one another.
76 Down 2 command Used to control the bias added to the frequency reference by the Up/Down 2 function. The –
Up 2 and Down 2 commands must always be used in conjunction with one another.
7A KEB Ride-Thru 2 (N.C.) Open: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB –
Ride-Thru 2.
7B KEB Ride-Thru 2 (N.O.) Closed: KEB Ride-Thru 2 enabled. Drive disregards L2-29 and performs Single Drive KEB –
Ride-Thru 2.
A8 Secondary PI Disable (N.O.) Closed: Disables the secondary PI controller. Output behavior depends on the setting of –
S3-12.
A9 Secondary PI Disable (N.C.) Closed: Enables the secondary PI controller. Output behavior depends on the setting of S3-12 –
when open.
AA Secondary PI Inverse Operation Closed: Changes the sign of the secondary PI controller input (reverse acting PI control). –
AB Secondary PI Integral Reset Closed: Resets the secondary PI controller integral value. –
AC Secondary PI Integral Hold Closed: Locks the value of the secondary PI controller integral value. –
Closed: Uses the secondary PI controller Proportional and Integral adjustments (S3-06 and
Parameter List
S3-07) instead of the primary PI controller Proportional and Integral adjustments (b5-02 and
AD Select Secondary PI Parameters b5-03). Only valid when S3-01 = 0 (secondary PI controller disabled). –
Note: This multi-function input has no effect on the secondary PI controller. It is only
used for the primary PI controller (b5-).
AF Emergency Override Forward Run Closed: Run the drive forward using the speed set in S6-02. –
B0 Emergency Override Reverse Run Closed: Run the drive in reverse using the speed set in S6-02. –
<1> Available in drive software versions PRG: 8502 and earlier.
B
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 215
B.7 H Parameters: Multi-Function Terminals
1 Zero speed Open: Output frequency is above the minimum output frequency set in E1-09. –
Closed: Output frequency is below the minimum output frequency set in E1-09.
2 Speed agree 1 Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02). 111
3 User-set speed agree 1 Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to
L4-02). 111
4 Frequency detection 1 Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined –
by L4-02.
5 Frequency detection 2 Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined –
by L4-02.
6 Drive ready Closed: Power up is complete and the drive is ready to accept a Run command. –
7 DC bus undervoltage Closed: DC bus voltage is below the Uv trip level set in L2-05. –
8 During baseblock (N.O.) Closed: Drive has entered the baseblock state (no output voltage). –
9 Frequency reference source Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15). –
Closed: Digital operator supplies the frequency reference.
A Run command source Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16). –
Closed: Digital operator supplies the Run command.
B Torque detection 1 (N.O.) Closed: An overtorque or undertorque situation has been detected. –
Closed: Analog frequency reference has been lost.
C Frequency reference loss Frequency reference loss is detected when the frequency reference drops below 10% of the –
reference within 400 ms.
D Braking resistor fault Closed: Braking resistor or transistor is overheated or faulted out. –
E Fault Closed: Fault occurred. –
F Through mode Set this value when using the terminal in the pass-through mode. –
10 Minor fault Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span. –
11 Fault reset command active Closed: A command has been entered to clear a fault via the input terminals or from the serial –
network.
12 Timer output Closed: Timer output. –
13 Speed agree 2 Closed: When drive output frequency equals the frequency reference ±L4-04. –
14 User-set speed agree 2 Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04. –
15 Frequency detection 3 Closed: When the drive output frequency is less than or equal to the value in L4-03 ±L4-04. –
16 Frequency detection 4 Closed: When the output frequency is greater than or equal to the value in L4-03 ±L4-04. –
17 Torque detection 1 (N.C.) Open: Overtorque or undertorque has been detected.
–
18 Torque detection 2 (N.O.) Closed: Overtorque or undertorque has been detected.
19 Torque detection 2 (N.C.) Open: Overtorque or undertorque has been detected. –
1A During reverse Closed: Drive is running in the reverse direction. –
1B During baseblock (N.C.) Open: Drive has entered the baseblock state (no output voltage). –
216 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.7 H Parameters: Multi-Function Terminals
2F Maintenance period Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require –
maintenance.
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
37 During frequency output Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being –
performed).
38 Drive enabled Closed: Multi-function input set for “Drive enable” is closed (H1- = 6A) –
39 Watt hour pulse output Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count. –
Open: REMOTE
3C LOCAL/REMOTE status –
Closed: LOCAL
3D During speed search Closed: Speed Search is being executed. –
3E PID feedback low Closed: PID feedback level is too low. –
3F PID feedback high Closed: The PID feedback level is too high. –
4A During KEB Ride-Thru Closed: KEB Ride-Thru is being performed. –
4C During fast stop Closed: A Fast Stop command has been entered from the operator or input terminals. –
Closed: An oH pre-alarm is present after 10 output frequency reduction cycles have passed (L8-03
4D oH Pre-alarm time limit –
= 4).
4E Braking transistor fault (rr) Closed: The built-in dynamic braking transistor failed. –
4F Braking resistor overheat (oH) Closed: The dynamic braking resistor has overheated. –
50 Waiting to Run Closed: b1-11 Timer is active. –
51 Sequence timer 1 Closed: Sequence timer 1 is active. –
52 Sequence timer 2 Closed: Sequence timer 2 is active. –
53 Sequence timer 3 Closed: Sequence timer 3 is active. –
54 Sequence timer 4 Closed: Sequence timer 4 is active. –
58 Underload detection Closed: Underload is detected. –
60 Internal cooling fan alarm Closed: Internal cooling fan alarm –
71 Secondary PI Feedback Low Closed: PI2 feedback level is too low. –
72 Secondary PI Feedback High Closed: The PI2 feedback level is too high. –
89 Closed: Drive output speed is being limited due to the output current limit or due the single-phase
<1> Output I Lim foldback regulator. –
Function 0 to 89 with inverse Inverts the output switching of the multi-function output functions.
100 to 189 output –
Set the last two digits of 1 to reverse the output signal of that specific function.
<1> Available in drive software versions PRG: 8503 and later.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 217
B.7 H Parameters: Multi-Function Terminals
No.
(Addr. Name Description Values Page
Hex)
H3-03 Sets the level of the input value selected in H3-02 when 10 V is input at Default: 100.0%
(411) Terminal A1 Gain Setting terminal A1. Min.: -999.9 112
Max.: 999.9
H3-04 Sets the level of the input value selected in H3-02 when 0 V is input at terminal Default: 0.0%
(412) Terminal A1 Bias Setting A1. Min.: -999.9 112
Max.: 999.9
0: 0 to 10 V
1: -10 to 10 V
H3-05 Terminal A3 Signal Level 2: 4 to 20 mA Default: 0
(413) Selection 3: 0 to 20 mA Range: 0 to 3 113
Note: Use Jumper S1 to set input terminal A3 for a current or voltage
input signal.
H3-06 Terminal A3 Function Sets the function of terminal A3. Default: 2
(414) Selection 113
Range: 0 to 26
H3-07 Sets the level of the input value selected in H3-06 when 10 V is input at Default: 100.0%
(415) Terminal A3 Gain Setting terminal A3. Min.: -999.9 113
Max.: 999.9
H3-08 Sets the level of the input value selected in H3-06 when 0 V is input at terminal Default: 0.0%
(416) Terminal A3 Bias Setting A3. Min.: -999.9 113
Max.: 999.9
0: 0 to 10 V
1: -10 to 10 V
H3-09 Terminal A2 Signal Level 2: 4 to 20 mA Default: 2
(417) Selection 3: 0 to 20 mA Range: 0 to 3 114
Note: Use Jumper S1 to set input terminal A2 for a current or voltage
input signal.
H3-10 Terminal A2 Function Sets the function of terminal A2. Default: 0
(418) Selection 114
Range: 0 to 26
H3-11 Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input Default: 100.0%
(419) Terminal A2 Gain Setting at terminal A2. Min.: -999.9 114
Max.: 999.9
H3-12 Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is Default: 0.0%
(41A) Terminal A2 Bias Setting input at terminal A2. Min.: -999.9 114
Max.: 999.9
H3-13 Analog Input Filter Time Sets a primary delay filter time constant for terminals A1, A2, and A3. Used Default: 0.03 s
(41B) Constant for noise filtering. Min.: 0.00 –
Max.: 2.00
Determines which analog input terminals will be enabled when a digital input
programmed for “Analog input enable” (H1- = C) is activated.
1: Terminal A1 only
H3-14 Analog Input Terminal 2: Terminal A2 only Default: 7
(41C) Enable Selection 3: Terminals A1 and A2 only –
4: Terminal A3 only Range: 1 to 7
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
H3-16
(2F0) Terminal A1 Offset Min.: -500 –
Max.: 500
Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0
H3-17
(2F1) Terminal A2 Offset Min.: -500 –
Max.: 500
Adds an offset when the analog signal to terminal A3 is at 0 V. Default: 0
H3-18
(2F2) Terminal A3 Offset Min.: -500 –
Max.: 500
218 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.7 H Parameters: Multi-Function Terminals
Multi-Function Analog Selects the data to be output through multi-function analog output terminal
H4-01 FM. Default: 102
(41D) Output Terminal FM 114
Monitor Selection Set the desired monitor parameter to the digits available in U-. Range: 000 to 999
For example, enter “103” for U1-03.
H4-02 Sets the signal level at terminal FM that is equal to 100% of the selected Default: 100.0%
(41E) Multi-Function Analog monitor value. Min.: -999.9
Output Terminal FM Gain 114
Max.: 999.9
H4-03 Sets the signal level at terminal FM that is equal to 0% of the selected monitor Default: 0.0%
(41F) Multi-Function Analog value. Min.: -999.9
Output Terminal FM Bias 114
Max.: 999.9
Multi-Function Analog Selects the data to be output through multi-function analog output terminal
H4-04 AM. Default: 103
(420) Output Terminal AM 114
Monitor Selection Set the desired monitor parameter to the digits available in U-. Range: 000 to 999
For example, enter “103” for U1-03.
H4-05 Sets the signal level at terminal AM that is equal to 100% of the selected Default: 50.0%
(421) Multi-Function Analog monitor value. Min.: -999.9
Output Terminal AM Gain 114
Max.: 999.9
Parameter List
H4-06 Sets the signal level at terminal AM that is equal to 0% of the selected monitor Default: 0.0%
(422) Multi-Function Analog value. Min.: -999.9
Output Terminal AM Bias 114
Max.: 999.9
Multi-Function Analog 0: 0 to 10 V
H4-07 Default: 0
(423) Output Terminal FM Signal 1: -10 to 10 V 116
Level Selection 2: 4 to 20mA Range: 0 to 2
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 219
B.7 H Parameters: Multi-Function Terminals
No.
(Addr. Name Description Values Page
Hex)
Multi-Function Analog 0: 0 to 10 V
H4-08 Default: 0
(424) Output Terminal AM Signal 1: -10 to 10 V 116
Level Selection 2: 4 to 20 mA Range: 0 to 2
H5-11 Communications ENTER 0: Drive requires an Enter command before accepting any changes to Default: 0
(43C) Function Selection
parameter settings. –
Range: 0, 1
1: Parameter changes are activated immediately without the Enter command.
H5-12 Run Command Method 0: FWD/Stop, REV/Stop Default: 0
(43D) Selection –
1: Run/Stop, FWD/REV Range: 0, 1
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
220 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.7 H Parameters: Multi-Function Terminals
No.
(Addr. Name Description Values Page
Hex)
H6-03 Sets the level of the value selected in H6-01 when a frequency with the value Default: 100.0%
(42E) Pulse Train Input Gain set in H6-02 is input. Min.: 0.0 –
Max.: 1000.0
H6-04 Sets the level of the value selected in H6-01 when 0 Hz is input. Default: 0.0%
(42F) Pulse Train Input Bias Min.: -100.0 –
Max.: 100.0
H6-05 Sets the pulse train input filter time constant. Default: 0.10 s
(430) Pulse Train Input Filter Time Min.: 0.00 –
Max.: 2.00
H6-08 Pulse Train Input Minimum Sets the minimum frequency for the pulse train input to be detected. Enabled Default: 0.5 Hz
(43F) Frequency
when H6-01 = 0, 1, or 2. Min.: 0.1 –
Max.: 1000.0
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 221
B.8 L: Protection Function
0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
L1-01 Motor Overload Protection 3: Vector motor with a speed range of 1:100 Default: 1
(480) Selection 6: General purpose motor (50 Hz) –
Range: 0 to 6
The drive may not be able to provide protection when using multiple motors,
even if overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal
relays to each motor.
Sets the motor thermal overload protection (oL1) time. Default: 1.0 min
L1-02 Motor Overload Protection
(481) Time
Min.: 0.1 –
Max.: 5.0
Sets operation when the motor temperature analog input (H3-02, H3-10, or
Motor Overheat Alarm H3-06 = E) exceeds the oH3 alarm level.
L1-03 Operation Selection 0: Ramp to stop Default: 3
(482) (PTC input) 1: Coast to stop –
Range: 0 to 3
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only (“oH3” will flash)
Motor Overheat Fault Sets stopping method when the motor temperature analog input (H3-02,
H3-10, or H3-06 = E) exceeds the oH4 fault level. Default: 1
L1-04 Operation Selection
(483) (PTC input) 0: Ramp to stop –
1: Coast to stop Range: 0 to 2
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
Adjusts the filter for the motor temperature analog input (H3-02, H3-10, or Default: 0.20 s
L1-05 Motor Temperature Input
(484) Filter Time (PTC input) H3-06 = E). Min.: 0.00 –
Max.: 10.00
0: Disabled
L1-13 Continuous Electrothermal Default: 1
(46D) Operation Selection
1: Enabled –
Range: 0 to 2
2: Enabled (RTC)
222 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.8 L: Protection Function
No.
(Addr. Name Description Values Page
Hex)
Sets the DC bus undervoltage trip level. Default: 190 Vdc
L2-05 Undervoltage Detection <2> <3>
(489) Level (Uv1) –
Min.: 150 Vdc
Max.: 210 Vdc <3>
Sets the time required to decelerate from the speed when KEB was activated Default: 0.00 s
L2-06
(48A) KEB Deceleration Time to zero speed. Min.: 0.00 –
Max.: 6000.0 <4>
Sets the time to accelerate to the frequency reference when momentary power Default: 0.00 s
L2-07
(48B) KEB Acceleration Time loss is over. If set to 0.0, the active acceleration time is used. Min.: 0.00 –
Max.: 6000.0 <4>
Sets the percentage of output frequency reduction at the beginning of Default: 100%
L2-08 Frequency Gain at KEB
(48C) Start deceleration when the KEB Ride-Thru function is started. Min.: 0 –
Reduction = (slip frequency before KEB) × L2-08 × 2 Max.: 300
Sets the time to perform KEB Ride-Thru. Default: 50 ms
L2-10 KEB Detection Time
(48E) (Minimum KEB Time)
Min.: 0 –
Max.: 2000
Sets the desired value of the DC bus voltage during KEB Ride-Thru. Default: <2>
L2-11 DC Bus Voltage Setpoint [E1-01] × 1.22
(461) during KEB Min.: 150 Vdc –
Max.: 400 Vdc <5>
0: Single Drive KEB Ride-Thru 1
L2-29 1: Single Drive KEB Ride-Thru 2 Default: 0
(475) KEB Method Selection 2: System KEB Ride-Thru 1 –
Range: 0 to 3
3: System KEB Ride-Thru 2
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but
set the value below 1040 Vdc (overvoltage protection level).
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 223
B.8 L: Protection Function
No.
(Addr. Name Description Values Page
Hex)
0: Disabled. Drive runs at a set frequency. A heavy load may cause speed loss.
1: Decel time 1. Uses the deceleration time set to C1-02 while Stall Prevention Default: 1
L3-05 Stall Prevention Selection is performed.
(493) during Run 118
2: Decel time 2. Uses the deceleration time set to C1-04 while Stall Prevention Range: 0 to 2
is performed.
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current. Default: <1>
L3-06 Stall Prevention Level Min.: 30%
(494) during Run 118
Max.: 150% <1>
Enables or disables the ov suppression function, which allows the drive to
L3-11 Overvoltage Suppression change the output frequency as the load changes to prevent an ov fault. Default: 0
(4C7) Function Selection 0: Disabled –
Range: 0, 1
1: Enabled
Sets the desired value for the DC bus voltage during overvoltage suppression Default: 375 Vdc
L3-17 Target DC Bus Voltage for and Stall Prevention during deceleration. <2> <3>
(462)
Overvoltage Suppression –
and Stall Prevention Min.: 150
Max.: 400 <3>
Default: 1.00
L3-20 DC Bus Voltage Adjustment Sets the proportional gain for KEB Ride-Thru, Stall Prevention, and
(465) Gain overvoltage suppression. Min.: 0.00 –
Max.: 5.00
Sets the proportional gain used to calculate the deceleration rate during KEB Default: 1.00
L3-21 Accel/Decel Rate
(466) Calculation Gain
Ride-Thru, ov suppression function, and Stall Prevention during deceleration Min.: 0.10 –
(L3-04 = 2). Max.: 10.00
Automatic Reduction 0: Sets the Stall Prevention level set in L3-04 that is used throughout the entire
L3-23 frequency range. Default: 0
(4FD)
Selection for Stall 1: Automatic Stall Prevention level reduction in the constant output range. The Range: 0, 1 –
Prevention during Run lower limit value is 40% of L3-06.
Sets the time needed to accelerate the uncoupled motor at rated torque from Default: <4> <5>
L3-24 Motor Acceleration Time for stop to the maximum frequency.
(46E) Inertia Calculations Min: 0.001 s –
Max: 10.000 s
Sets the ratio between the motor and machine inertia. Default: 1.0
L3-25
(46F) Load Inertia Ratio Min.: 1.0 –
Max.: 1000.0
When DC bus capacitors have been added externally, be sure to add those Default: 0 μF
L3-26 Additional DC Bus
(455) Capacitors values to the internal capacitor table for proper DC bus calculations. Min: 0 –
Max: 65000
Sets the time the current must exceed the Stall Prevention level to activate Default: 50 ms
L3-27 Stall Prevention Detection Stall Prevention.
(456) Time
Min.: 0 –
Max.: 5000
<1> Upper limit is dependent on parameter L8-38, Frequency Reduction Selection.
<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but
set the value below 1040 Vdc (overvoltage protection level).
<4> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
<5> Default setting is dependent on parameter o2-04, Drive Model Selection.
224 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.8 L: Protection Function
No.
(Addr. Name Description Values Page
Hex)
Default: 2.0
L4-04 Speed Agreement Detection L4-04 sets the hysteresis or allowable margin for speed detection.
(49C) Width (+/-)
Min.: 0.0 –
Max.: 20.0
L4-05 Frequency Reference Loss 0: Stop. Drive stops when the frequency reference is lost. Default: 0
–
(49D) Detection Selection 1: Run. Drive runs at a reduced speed when the frequency reference is lost. Range: 0, 1
L4-06 Frequency Reference at Sets the percentage of the frequency reference that the drive should run with Default: 80.0%
(4C2) Reference Loss when the frequency reference is lost. Min.: 0.0 –
Max.: 100.0
L4-07 Speed Agreement Detection 0: No detection during baseblock. Default: 0
(470) Selection 1: Detection always enabled. –
Range: 0, 1
L5-01 Number of Auto Restart Sets the number of times the drive may attempt to restart after the following Default: 0
(49E) Attempts faults occur: GF, LF, oC, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1. Min.: 0 –
Max.: 10
L5-02 Auto Restart Fault Output 0: Fault output not active. Default: 0
(49F) Operation Selection –
1: Fault output active during restart attempt. Range: 0, 1
Sets the amount of time to wait between performing fault restarts. Default: 10.0 s
L5-04
(46C) Fault Reset Interval Time Min.: 0.5 –
Max.: 600.0
0: Continuously attempt to restart while incrementing restart counter only at
L5-05 Fault Reset Operation a successful restart (same as F7 and G7). Default: 0
(467) Selection 1: Attempt to restart with the interval time set in L5-04 and increment the –
Range: 0, 1
restart counter with each attempt (same as V7).
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 225
B.8 L: Protection Function
No.
(Addr. Name Description Values Page
Hex)
0: Disabled
1: oL4 detection only active during speed agree, operation continues after
detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4
Torque Detection fault Default: 0
L6-04
(4A4) Selection 2 4: oL4 detection always active during run, output shuts down on an oL4 fault –
5: UL4 detection only active during speed agree, operation continues after Range: 0 to 8
detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4
fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
Torque Detection Sets the overtorque and undertorque detection level. Default: 150%
L6-05
(4A5)
Level 2 Min.: 0 –
Max.: 300
Torque Detection Sets the time an overtorque or undertorque condition must exist to trigger Default: 0.1 s
L6-06
(4A6) Time 2 torque detection 2. Min.: 0.0 –
Max.: 10.0
L6-13 Sets the motor underload
Motor Underload Protection 0: Base frequency enable protection (UL6) based on motor load. Default: 0
(62E) Selection –
Range: 0, 1
1: Max frequency enable
L6-14 Motor Underload Protection Sets the UL6 detection level at minimum frequency by percentage of drive Default: 15%
(62F) Level at Minimum rated current. Min.: 0 –
Frequency Max.: 300
226 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.8 L: Protection Function
No.
(Addr. Name Description Values Page
Hex)
L8-19 Frequency Reduction Rate Specifies the frequency reference reduction gain at overheat pre-alarm when Default: 0.8
(4BF) during Overheat Pre-Alarm L8-03 = 4.
Min.: 0.1 –
Max.: 0.9
Determines drive response when a fault occurs with the internal cooling fan.
0: Ramp to stop
Main Contactor and Cooling 1: Coast to stop Default: 1
L8-32
(4E2) Fan Power Supply Failure 2: Fast stop (Decelerate to stop using the deceleration time set to C1-09) –
Selection Range: 0 to 4
3: Alarm only (“FAn” will flash)
4: Continue operation at reduced speed as set to L8-19.
0: IP00/Open-Chassis enclosure
L8-35 Installation Method 1: Side-by-Side mounting Default: <2> <3> –
(4EC) Selection 2: IP20/NEMA Type 1 enclosure Range: 0 to 3
3: External heatsink installation
0: Disabled
L8-38 Carrier Frequency Default: 2
(4EF) Reduction
1: Enabled below 6 Hz –
Range: 0 to 2
2: Enabled for the entire speed range
L8-40 Carrier Frequency Sets the time that the drive continues running with reduced carrier frequency Default: 0.5 s
(4F1) Reduction Off Delay Time after the carrier reduction condition is gone. Setting 0.00 s disables the carrier Min.: 0.00 –
frequency reduction time. Max.: 2.00
0: Disabled
L8-41 High Current Alarm Default: 0
(4F2) Selection 1: Enabled. An alarm is triggered at output currents above 150% of drive rated –
current. Range: 0, 1
L8-55 Internal Braking Transistor 0: Disabled. Disable when using a regen converter or optional braking unit. Default: 1 –
(45F) Protection 1: Protection enabled. Range: 0, 1
Default: 1.0 s
L8-93 LSo Detection Time at Low Sets the amount of time until baseblock is executed after detecting pull-out at Min.: 0.0
(73C) Speed low speed. –
Max.: 10.0
Default: 3%
L8-94 LSo Detection Level at Low Determines the detection level of pull-out at low speed.
(73D) Speed
Min.: 0 –
Max.: 10
Default: 10 times
L8-95 Average LSo Frequency at Sets the average number of times pull-out can occur at low speed.
(73D) Low Speed
Min.: 1 –
Max.: 50
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is determined by the drive model:
Setting 2: Model code CIMR-P2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242
Setting 0: Model code CIMR-P2A0250 to 2A0415 and 4A0208 to 4A0675
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 227
B.9 n: Special Adjustment
n3-04 High-Slip Braking Overload Sets the time required for an HSB overload fault (oL7) to occur when the drive Default: 40 s
(58B) Time
output frequency does not change during an HSB stop. This parameter does Min.: 30 –
not typically require adjustment. Max.: 1200
Sets the gain applied to the V/f pattern during Overexcitation Deceleration Default: 1.10
n3-13 Overexcitation Deceleration (L3-04 = 4).
(531) Gain
Min.: 1.00 –
Max.: 1.40
High Frequency Injection 0: Disabled
n3-14 Default: 0
(532)
during Overexcitation 1: Enabled –
Deceleration Range: 0, 1
Sets output current level at which the drive will start reducing the Default: 100%
n3-21 High-Slip Suppression
(579) Current Level overexcitation gain in order to prevent a too high motor slip during Min.: 0 –
Overexcitation Deceleration. Set as a percentage of the drive rated current. Max.: 150
0: Enabled in both directions
n3-23 Overexcitation Operation Default: 0
(57B) Selection 1: Enabled only when rotating forward –
2: Enabled only when in reverse Range: 0 to 2
228 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.10 o: Operator-Related Settings
Selects the monitors displayed on the second and third lines of the digital
o1-06 User Monitor Selection operator display. Default: 0
(517) Mode 0: 3 Monitor Sequential (displays the next two sequential monitors) –
Range: 0, 1
1: 3 Monitor Selectable (set by o1-07 and o1-08)
Selects the monitor that is shown in the second line.
o1-07 Second Line Monitor Enter the last three digits of the monitor parameter number to be displayed: Default: 102
(518) Selection U-. For example, set "403" to display monitor parameter U4-03. –
Range: 101 to 799
Note: Parameter is effective only when o1-06 is set to 1.
Selects the monitor that is shown in the third line.
o1-08 Third Line Monitor Enter the last three digits of the monitor parameter number to be displayed: Default: 103
(519) Selection U-. For example, set "403" to display monitor parameter U4-03. –
Range: 101 to 799
Note: Parameter is effective only when o1-06 is set to 1.
Sets unit display for the frequency reference parameters and frequency related
monitors when o1-03 = 3.
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour) Default: 25
o1-09 Frequency Reference 7: LPS (Liters per second)
(51C) Display Units 8: Bar (Bar) Range: 0 to 15; 24, –
9: Pa (Pascal) 25
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: “Hg (inches of mercury)
24: Custom units (determined by o1-13 to o1-15)
25: None
o1-10 User-Set Display Units These settings define the display values when o1-03 is set to 3. Default: <1>
Parameter List
(520) Maximum Value o1-10 sets the display value that is equal to the maximum output frequency. Range: 1 to 60000 –
o1-11 sets the position of the decimal position.
o1-11 User-Set Display Units Default: <1>
(521) Decimal Display –
Range: 0 to 3
o1-13 Frequency Reference and Sets the first character of the customer-specified unit display when o1-03 is Default: 41
(3105)
Frequency Related Monitor set to 3 and o1-09 is set to 24.
Range: 30 to 7A –
Custom Units 1
B
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 229
B.10 o: Operator-Related Settings
No.
(Addr. Name Description Values Page
Hex)
o1-14 Frequency Reference and Sets the second character of the customer-specified unit display when o1-03 Default: 41
(3106) Frequency Related Monitor is set to 3 and o1-09 is set to 24. Range: 30 to 7A –
Custom Units 2
o1-15 Frequency Reference and Sets the third character of the customer-specified unit display when o1-03 is Default: 41
(3107)
Frequency Related Monitor set to 3 and o1-09 is set to 24.
Range: 30 to 7A –
Custom Units 3
<1> Default setting is dependent on parameter o1-03, Digital Operator Display Selection.
<2> Available in drive software versions PRG: 8503 and later.
o2-04 Enter the drive model. Setting required only if installing a new control board. Default:
(508) Drive Model Selection Determined by –
drive capacity
0: ENTER key must be pressed to enter a frequency reference.
o2-05 Frequency Reference Default: 0
(509) Setting Method Selection 1: ENTER key is not required. The frequency reference can be adjusted using –
the up and down arrow keys only. Range: 0, 1
o2-06 Operation Selection when 0: The drive continues operating if the digital operator is disconnected. Default: 1
(50A)
Digital Operator is 1: An oPr fault is triggered and the motor coasts to stop. –
Disconnected Range: 0, 1
o2-07 Motor Direction at Power This parameter requires assigning drive operation to the digital operator. Default: 0
(527) Up when Using Operator 0: Forward –
Range: 0, 1
1: Reverse
When running during a power loss, the Run command is issued via the digital
o2-20 operator and the Run state is saved to the EEPROM.
(81E) Operator RUN Save at When power is restored, the Run command is automatically applied if the Default: 0
Power Loss LOCAL/REMOTE or FREF conditions have not changed in the drive. –
Range: 0, 1
0: Disabled
1: Enabled
230 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.10 o: Operator-Related Settings
o4-12 0: U4-10 and U4-11 monitor data is not reset when the drive is initialized Default: 0
(512)
(A1-03).
kWh Monitor Initialization –
Range: 0, 1
1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).
0: Number of Run commands counter is not reset when the drive is initialized
o4-13 Number of Run Commands (A1-03). Default: 0
(528) Counter Initialization 1: Number of Run commands counter is reset when the drive is initialized –
Range: 0, 1
(A1-03).
Sets the current date and time for the Real-Time Clock.
o4-17 0: - - Default: 0
(3100) Set/Reset Real-Time Clock 1: Set 86
Range: 0 to 2
2: Reset
o4-20 Sets the time display format. Default: 0
(81F) Time Display Format 0: 12-hour –
Range: 0, 1
1: 24-hour
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 231
B.11 S: Special Application
232 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.11 S: Special Application
No.
(Addr. Name Description Values Page
Hex)
Sets the start time for timer 2. The value must be set less than or equal to S2-07. Default: 00:00
S2-06 Sequence Timer 2 Start
(320B) Time
Min.: 00:00 –
Max.: 24:00 <1>
Sets the stop time for timer 2. The value must be set greater than or equal to Default: 00:00
S2-07
(320C) Sequence Timer 2 Stop Time S2-06. Min.: 00:00 –
Max.: 24:00 <1>
Sets the days for which sequence timer 2 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
S2-08 Sequence Timer 2 Day 4: Monday Default: 0
(320D) Selection 5: Tuesday –
Range: 0 to 10
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the action that occurs when sequence timer 2 is active.
S2-09 0: Digital output only Default: 0
(320E) Sequence Timer 2 Selection 1: Run –
Range: 0 to 2
2: Run - PI disable
Selects the frequency reference source used for running the drive when
sequence timer 2 is active (only applicable when S2-09 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
S2-10 Sequence Timer 2 Reference 2: Operator (d1-03) Default: 0
(320F) Source 3: Operator (d1-04) –
Range: 0 to 7
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
Default: 00:00
Sets the start time for timer 3. The value must be set less than or equal to S2-12.
S2-11 Sequence Timer 3 Start
(3210) Time
Min.: 00:00 –
Max.: 24:00 <1>
Sets the stop time for timer 3. The value must be set greater than or equal to Default: 00:00
S2-12
(3211) Sequence Timer 3 Stop Time S2-11. Min.: 00:00 –
Max.: 24:00 <1>
Sets the days for which sequence timer 3 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
S2-13 Sequence Timer 3 Day 4: Monday Default: 0
(3212) Selection 5: Tuesday –
Range: 0 to 10
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the action that occurs when sequence timer 3 is active.
S2-14 0: Digital output only Default: 0
(3213) Sequence Timer 3 Selection 1: Run –
Range: 0 to 2
2: Run - PI disable
Selects the frequency reference source used for running the drive when
sequence timer 3 is active (only applicable when S2-14 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
S2-15 Sequence Timer 3 Reference 2: Operator (d1-03) Default: 0
–
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 233
B.11 S: Special Application
No.
(Addr. Name Description Values Page
Hex)
Sets the stop time for timer 4. The value must be set greater than or equal to Default: 00:00
S2-17
(3216) Sequence Timer 4 Stop Time S2-16. Min.: 00:00 –
Max.: 24:00 <1>
Sets the days for which sequence timer 4 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
S2-18 Sequence Timer 4 Day 4: Monday Default: 0
(3217) Selection 5: Tuesday –
Range: 0 to 10
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the action that occurs when sequence timer 4 is active.
S2-19 0: Digital output only Default: 0
(3218) Sequence Timer 4 Selection 1: Run –
Range: 0 to 2
2: Run - PI disable
Selects the frequency reference source used for running the drive when
sequence timer 4 is active (only applicable when S2-19 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
S2-20 Sequence Timer 4 Reference 2: Operator (d1-03) Default: 0
(3219) Source 3: Operator (d1-04) –
Range: 0 to 7
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
<1> Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer.
234 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.11 S: Special Application
No.
(Addr. Name Description Values Page
Hex)
Sets the units for the secondary PI control function.
0: Inch of water (WC)
1: Pounds per square inch (PSI)
2: Gallons per minute (GPM)
3: Degrees Fahrenheit (F)
4: Cubic feet per minute (CFM)
5: Cubic meters per hour (CMH)
S3-04 6: Liters per hour (LPH)
(321D) Secondary PI Unit Default: 15
Selection
7: Liters per second (LPS) –
8: Bar (Bar) Range: 0 to 15
9: Pascals (Pa)
10: Degrees Celsius (C)
11: Meters (Mtr) (Ft: Feet)
12: Liters per minute (LPM)
13: Cubic meters per minute (CMM)
14: No unit
15: Percentage (%)
S3-05 Sets the secondary PI controller target value. Default: 0.00 <1>
(321E) Secondary PI Setpoint Value Min.: 0.00 –
Max.: 600.00 <2>
S3-06 Sets the proportional gain of the secondary PI controller. A setting of 0.00 Default: 1.00
(321F) Secondary PI Proportional disables P control.
Gain Setting
Min.: 0.00 –
Max.: 25.00
S3-07 Sets the integral time for the secondary PI controller. A setting of 0.0 s disables Default: 1.0 s
(3220) Secondary PI Integral Time integral control.
Setting
Min.: 0.0 –
Max.: 360.0
S3-08 Sets the maximum output possible from the integrator. Default: 100.0%
(3221) Secondary PI Integral Limit
Setting
Min.: 0.0 –
Max.: 100.0
S3-09 Sets the maximum output possible from the secondary PI controller. Default: 100.0%
(3222) Secondary PI Output Upper
Limit
Min.: 0.0 –
Max.: 100.0
S3-10 Sets the minimum output possible from the secondary PI controller. Default: 0.00%
(3223) Secondary PI Output Lower
Limit
Min.: -100.00 –
Max.: 100.00
S3-11 Sets the secondary PI controller output direction.
(3224) Secondary PI Output Level 0: Normal Output (direct acting) Default: 0
Selection –
1: Reverse Output (reverse acting) Range: 0, 1
Max.: 25.5
S3-17 Selects when secondary PI controller low and high feedback detection are
(322A) Secondary PI Feedback active. Default: 0
Detection Selection 0: Secondary PI enabled –
Range: 0, 1
1: Always
<1> Unit is determined by S3-04.
<2> Upper limit is S3-02, decimal placeholder is determined by S3-03. B
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 235
B.11 S: Special Application
236 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.12 T: Motor Tuning
Parameter List
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 237
B.13 U: Monitors
B.13 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
U1-07
(46) DC Bus Voltage Displays the DC bus voltage. 10 V: 400 V <3> 1 Vdc
U1-08 Output Power Displays the output power (this value is calculated internally). 10 V: Drive capacity <4>
(47) (motor capacity) kW
Displays the input terminal status.
U1 - 10= 00000000
1 Digital input 1
(terminal S1 enabled)
1 Digital input 2
(terminal S2 enabled)
1 Digital input 3
(terminal S3 enabled)
U1-10 1 Digital input 4 No signal output
(49) Input Terminal Status available –
(terminal S4 enabled)
1 Digital input 5
(terminal S5 enabled)
1 Digital input 6
(terminal S6 enabled)
1 Digital input 7
(terminal S7 enabled)
1 Digital input 8
(terminal S8 enabled)
U1-11 1 Digital
Multi-Function
Output No signal output
(4A) Output Terminal Status (terminal M1-M2) available –
1 Multi-Function
Digital Output
(terminal M3-M4)
0 Not Used
1 (terminal
Fault Relay
MA-MC closed
MA-MC open)
238 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.13 U: Monitors
4: Thursday
5: Friday
6: Saturday
<1> The number of decimal places in the parameter value depends on the drive model and the ND selection. This value has two decimal places (0.01
A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current. B
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 239
B.13 U: Monitors
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is higher than 11 kW.
U2-15 Soft Starter Speed Displays the speed reference for the soft starter at the previous fault. No signal output
(7E0) Reference at Previous available 0.01 Hz
Fault
U2-20 Heatsink Temperature at Displays the temperature of the heatsink when the most recent fault No signal output 1 °C
(8E) Previous Fault occurred. available
U2-27 Motor Temperature at Displays the temperature of the motor when the most recent fault occurred. No signal output 1 °C
(7FA) Previous Fault (NTC) available
U2-30 Date Year at Previous Displays the year when the most recent fault occurred. No signal output –
(3008) Fault available
U2-31 Date Month and Day at Displays the date and day when the most recent fault occurred. No signal output –
(3009) Previous Fault available
U2-32 Time Hours and Minutes at Displays the time when the most recent fault occurred. No signal output –
(300A) Previous Fault available
<1> The number of decimal places in the parameter value depends on the drive model and the ND selection. This value has two decimal places (0.01
A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
240 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.13 U: Monitors
U3-21 Date Year at Most Recent Displays the year when the most recent fault occurred. No signal output –
(300B) Fault available
U3-22 Date Month and Day at Displays the date and day when the most recent faults occurred. No signal output –
(300C) Most Recent Fault available
U3-23 Time Hours and Minutes Displays the time when the most recent fault occurred. No signal output –
(300D) at Most Recent Fault available
U3-24 Date Year at 2nd Most Displays the year when the second most recent fault occurred. No signal output –
(300E) Recent Fault available
U3-25 Date Month and Day at Displays the date and day when the second most recent fault occurred. No signal output –
(300F) 2nd Most Recent Fault available
U3-26 Time Hours and Minutes Displays the time when the second most recent fault occurred. No signal output –
(3010) at 2nd Most Recent Fault available
U3-27 Date Year at 3rd Most Displays the year when the most third recent fault occurred. No signal output –
(3011) Recent Fault available
U3-28 Date Month and Day at 3rd Displays the date and day when the third most recent fault occurred. No signal output –
(3012) Most Recent Fault available
U3-29 Time Hours and Minutes Displays the time when the third most recent fault occurred. No signal output –
(3013) at 3rd Most Recent Fault available
U3-30 Date Year at 4th Most Displays the year when the fourth most recent fault occurred. No signal output –
(3014) Recent Fault available
U3-31 Date Month and Day at 4th Displays the date and day when the fourth most recent fault occurred. No signal output –
(3015) Most Recent Fault available
U3-32 Time Hours and Minutes Displays the time when the fourth most recent fault occurred. No signal output –
(3016 at 4th Most Recent Fault available
U3-33 Date Year at 5th Most Displays the year when the fifth most recent fault occurred. No signal output –
(3017) Recent Fault available
U3-34 Date Month and Day at 5th Displays the date and day when the fifth most recent fault occurred. No signal output –
(3018) Most Recent Fault available
U3-35 Time Hours and Minutes Displays the time when the fifth most recent fault occurred. No signal output –
(3019) at 5th Most Recent Fault available
U3-36 Date Year at 6th Most Displays the year when the sixth most recent fault occurred. No signal output –
(301A) Recent Fault available
U3-37 Date Month and Day a 6th Displays the date and day when the sixth most recent fault occurred. No signal output –
(301B) Most Recent Fault available
Parameter List
U3-38 Time Hours and Minutes Displays the time when the most sixth recent fault occurred. No signal output –
(301C) at 6th Most Recent Fault available
U3-39 Date Year at 7th Most Displays the year when the most seventh recent fault occurred. No signal output –
(301D) Recent Fault available
U3-40 Date Month and Day at 7th Displays the date and day when the seventh most recent fault occurred. No signal output –
(301E) Most Recent Fault available
B
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 241
B.13 U: Monitors
Displays the cumulative operation time of the drive. The value for the
U4-01 Cumulative Operation cumulative operation time counter can be reset in parameter o4-01. Use No signal output
parameter o4-02 to determine if the operation time should start as soon as 1h
(4C) Time the power is switched on or only while the Run command is present. The available
maximum number displayed is 99999, after which the value is reset to 0.
U4-02 Number of Run Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to No signal output 1 Time
(75) Commands 0 and start counting again after reaching 65535. available
U4-03 Cooling Fan Operation Displays the cumulative operation time of the cooling fan. The default value No signal output
(67) Time for the fan operation time is reset in parameter o4-03. This value will reset available 1h
to 0 and start counting again after reaching 99999.
U4-04 Displays main cooling fan usage time as a percentage of its expected No signal output
(7E) Cooling Fan Maintenance performance life. Parameter o4-03 can be used to reset this monitor. available 1%
Replace the fan when this monitor reaches 90%.
U4-05 Displays main circuit capacitor usage time as a percentage of their expected No signal output
(7C) Capacitor Maintenance performance life. Parameter o4-05 can be used to reset this monitor. available 1%
Replace the capacitor when this monitor reaches 90%.
Displays the soft charge bypass relay maintenance time as a percentage of
U4-06 Soft Charge Bypass Relay its estimated performance life. Parameter o4-07 can be used to reset this No signal output
(7D6) Maintenance monitor. available 1%
Replace the soft charge bypass relay when this monitor reaches 90%.
U4-07 Displays IGBT usage time as a percentage of the expected performance No signal output
(7D7) IGBT Maintenance life. Parameter o4-09 can be used to reset this monitor. available 1%
Replace the IGBT when this monitor reaches 90%.
U4-08 Heatsink Temperature Displays the heatsink temperature. 10 V: 100 °C 1 °C
(68)
U4-09 LED Check Lights all segments of the LED to verify that the display is working No signal output –
(5E) properly. available
U4-10 kWh, Lower 4 Digits Monitors the drive output power. The value is shown as a 9-digit number No signal output 1 kWh
(5C) displayed across two monitor parameters, U4-10 and U4-11. available
Example:
U4-11 12345678.9 kWh is displayed as: No signal output
(5D) kWh, Upper 5 Digits U4-10: 678.9 kWh available 1 MWh
U4-11: 12345 MWh
242 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
B.13 U: Monitors
U4-14 Peak Hold Output Displays the output frequency when the current value shown in U4-13 No signal output 0.01 Hz
(7D0) Frequency occurred. available
U4-16 Motor Overload Estimate Shows the value of the motor overload detection accumulator. 100% is 10 V: 100% 0.1%
(7D8) (oL1) equal to the oL1 detection level.
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Digital operator
U4-18 Frequency Reference No signal output
(7DA) Source Selection 1-01 = Analog (terminal A1) available –
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
5-01 = Pulse input
U4-19 Frequency Reference from Displays the frequency reference provided by MEMOBUS/Modbus No signal output
(7DB) MEMOBUS/Modbus (decimal). available 0.01%
Comm.
U4-20 Option Frequency Displays the frequency reference input by an option card (decimal). No signal output –
(7DC) Reference available
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
nn: Run command limit status data
U4-21 Run Command Source 00: No limit status. No signal output
(7DD) Selection 01: Run command was left on when stopped in the PRG mode available –
02: Run command was left on when switching from LOCAL to REMOTE
operation
03: Waiting for soft charge bypass contactor after power up (Uv or Uv1
flashes after 10 s)
04: Waiting for “Run command prohibited” time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during baseblock
09: Waiting for Enter command
U4-22 MEMOBUS/Modbus Displays the drive control data set by MEMOBUS/Modbus No signal output
(7DE)
Communications communications register no. 0001H as a four-digit hexadecimal number.
available –
Reference
U4-23 Communication Option Displays drive control data set by an option card as a four-digit hexadecimal No signal output –
(7DF) Card Reference number. available
Displays the motor temperature (NTC).
U4-32
(7FB) Motor Temperature (NTC) U4-32 will display “20 °C” when a multi-function analog input is not set 200 °C 1 °C
for motor thermistor input (H1- = 17H).
U4-37 oH Alarm Location Displays the module where the oH alarm occurred as a binary number. No signal output –
(1044) Monitor available
U4-38 FAn Alarm Location Displays the module where the FAn alarm occurred as a binary number. No signal output –
(1045) Monitor available
Parameter List
U4-39 voF Alarm Location Displays the module where the voF alarm occurred as a binary number. No signal output –
(1046) Monitor available
<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 243
B.13 U: Monitors
U5-02 PID Input Displays the amount of PID input (deviation between PID setpoint and 10 V: 100% 0.01%
(63) feedback).
U5-03 PID Output Displays PID control output. 10 V: 100% 0.01%
(64)
U5-04 Displays the PID setpoint. 0.01%
(65) PID Setpoint 10 V: 100% <1>
U5-05 Displays the 2nd PID feedback value if differential feedback is used (H3-
PID Differential Feedback 10 V: 100% 0.01%
(7D2) = 16).
U5-06 Displays the difference of both feedback values if differential feedback is
(7D3) PID Adjusted Feedback used (U5-01 - U5-05). If differential feedback is not used, then U5-01 and 10 V: 100% 0.01%
U5-06 will be the same.
Displays the custom PI output. 1
U5-14 No signal output
(86B) PI Output 2 Upper 4 Digits U5-14 shows the upper 4 digits while U5-15 shows the lower 4 digits. available <2>
Monitors are scaled by b5-43 and b5-44
Displays the custom PI output. 0.01
U5-15 No signal output
(86C) PI Output 2 Lower 4 Digits U5-14 shows the upper 4 digits while U5-15 shows the lower 4 digits. available <2>
Monitors are scaled by b5-43 and b5-44.
U5-17 PI2 Setpoint Displays the secondary PI setpoint. Dependent upon S3-02 <3>
(86E)
U5-18 PI2 Feedback Displays the secondary PI feedback value. Dependent upon S3-02 <3>
(86F)
U5-19 PI2 Input Displays the secondary PI input (deviation between PI target and feedback). Dependent upon S3-02 <3>
(870)
U5-20 PI2 Output Displays the secondary PI control output. Dependent upon S3-02 <3>
(871)
U5-30 Time Hr Min HHMM Displays the current time (Hours and Minutes). No signal output 1
(3000) available
U5-31 Date Year Displays the current year. No signal output 1
(3001) available
U5-32 Date Mo Day MMDD Displays the current date (Month and Day). No signal output 1
(3002) available
Displays the current date of the week.
0: Sunday
1: Monday
U5-33 2: Tuesday No signal output
(3003) Date Week 000W 3: Wednesday available 1
4: Thursday
5: Friday
6: Saturday
U5-99 No signal output 0.01%
(1599) PID Setpoint Command Displays the PID Setpoint commanded by the source. available <1>
<1> Unit, range and resolution is determined by b5-20, b5-38, b5-39, and b5-46
<2> Unit is determined by b5-41
<3> Unit is determined by S3-04.
244 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
Appendix: C
Standards Compliance
This appendix explains the guidelines and criteria for maintaining CE and UL standards.
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 245
C.1 European Standards
The CE mark indicates compliance with European safety and environmental regulations. It is required for engaging in business
and commerce in Europe.
European standards include the Machinery Directive for machine manufacturers, the Low Voltage Directive for electronics
manufacturers, and the EMC guidelines for controlling noise.
This drive displays the CE mark based on the EMC guidelines and the Low Voltage Directive.
• Low Voltage Directive: 2014/35/EU
• EMC Guidelines: 2014/30/EU
Devices used in combination with this drive must also be CE certified and display the CE mark. When using drives displaying
the CE mark in combination with other devices, it is ultimately the responsibility of the user to ensure compliance with CE
standards. After setting up the device, verify that conditions meet European standards.
Note: 600 V class drives (models 5) are not compliant with European Standards.
246 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.1 European Standards
Fuse Type
Drive Model Manufacturer: Bussmann
Model Fuse Ampere Rating (A)
2A0138 FWH-350A 350
2A0169 FWH-400A 400
2A0211 FWH-400A 400
2A0250 FWH-600A 600
2A0312 FWH-700A 700
2A0360 FWH-800A 800
2A0415 FWH-1000A 1000
Three-Phase 400 V Class
4A0002 FWH-40B 40
4A0004 FWH-50B 50
4A0005 FWH-70B 70
4A0007 FWH-70B 70
4A0009 FWH-90B 90
4A0011 FWH-90B 90
4A0018 FWH-80B 80
4A0023 FWH-100B 100
4A0031 FWH-125B 125
4A0038 FWH-200B 200
4A0044 FWH-250A 250
4A0058 FWH-250A 250
4A0072 FWH-250A 250
4A0088 FWH-250A 250
4A0103 FWH-250A 250
4A0139 FWH-350A 350
4A0165 FWH-400A 400
4A0208 FWH-500A 500
4A0250 FWH-600A 600
4A0296 FWH-700A 700
4A0362 FWH-800A 800
4A0414 FWH-800A 800
4A0515 FWH-1000A 1000
4A0675 FWH-1200A 1200
4A0930 FWH-1200A 1200
4A1200 FWH-1600A 1600
Three-Phase 600 V Class
5A0003 <1> FWP-50B 50
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 247
C.1 European Standards
Fuse Type
Drive Model Manufacturer: Bussmann
Model Fuse Ampere Rating (A)
5A0062 <1> FWP-250A 250
<1> 600 V class drives are not compliant with European Standards.
A D C
U/T1 U
V/T2 V
M
W/T3 W
E
A – Drive D – Metal conduit
B – 10 m max cable length between E – Ground wire should be as short as
drive and motor possible.
C – Motor
Figure C.2 Installation Method
5. Make sure the protective earthing conductor complies with technical standards and local safety regulations.
248 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.1 European Standards
WARNING! Electrical Shock Hazard. Because the leakage current exceeds 3.5 mA in models 4A0414 to 4A1200, IEC/EN
61800-5-1 states that either the power supply must be automatically disconnected in case of discontinuity of the protective earthing
conductor, or a protective earthing conductor with a cross-section of at least 10 mm2 (Cu) or 16 mm2 (Al) must be used. Failure to
comply may result in death or serious injury.
C B
A – Braided shield cable C – Cable clamp (conductive)
B – Metal panel
Figure C.3 Ground Area
Standards Compliance
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 249
C.1 European Standards
D
B C
K
E
I F
H
G
250 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.1 European Standards
EMC Filters
Install the drive with the EMC filters listed in Table C.2 to comply with the EN61800-3 requirements.
Table C.2 EN61800-3 Filters
Filter Data (Manufacturer: Schaffner)
Drive Model Dimensions
Type Rated Current (A) Weight (lb) Y x X (in) Figure
[W x D x H] (in)
Three-Phase 200 V Class
2A0004
2A0006 FS5972-10-07 10 2.6 5.6 × 1.8 × 13.0 4.5 × 12.3
2A0008
2A0010
FS5972-18-07 18 2.9 5.6 × 1.8 × 13.0 4.5 × 12.3
2A0012
1
2A0018
2A0021 FS5972-35-07 35 4.6 8.1 × 2.0 × 14.0 6.9 × 13.2
2A0030
2A0040
FS5972-60-07 60 8.8 9.3 × 2.6 × 16.1 8.1 × 15.4
2A0056
2A0069
FS5972-100-35 100 7.5 3.5 × 5.9 × 13.0 2.6 × 10.0
2A0081
2A0110
FS5972-170-40 170 13.2 4.7 × 6.7 × 17.8 4.0 × 14.4 2
2A0138
2A0169
FS5972-250-37 250 25.8 5.1 × 9.5 × 24.0 3.5 × 19.6
2A0211
2A0250
FS5972-410-99 410 23.1 10.2 × 4.5 × 15.2 9.3 × 4.7
2A0312
3
2A0360
FS5972-600-99 600 24.3 10.2 × 5.3 × 15.2 9.3 × 4.7
2A0415
Three-Phase 400 V Class
4A0002
4A0004
FS5972-10-07 10 2.7 5.6 × 1.8 × 13.0 4.5 × 12.3
4A0005
4A0007
4A0009
FS5972-18-07 18 2.9 5.6 × 1.8 × 13.0 4.5 × 12.3
4A0011
1
4A0018
4A0023 FS5972-35-07 35 4.6 8.1 × 2.0 × 14.0 6.9 × 13.2
4A0031
4A0038
4A0044 FS5972-60-07 60 8.8 9.3 × 2.6 × 16.1 8.0 × 15.4
4A0058
4A0072
FS5972-100-35 100 16.5 3.5 × 5.9 × 13.0 2.6 × 10.0
4A0088
4A0103
2
4A0139 FS5972-170-35 170 10.4 4.7 × 6.7 × 17.8 4.0 × 14.4
4A0165
4A0208 FS5972-250-37 250 25.8 5.1 × 9.5 × 24.0 3.5 × 19.6
4A0250
Standards Compliance
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 251
C.1 European Standards
H
X
X
Figure 1
Figure 2
W
Y
X
H
X
Figure 3
252 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.1 European Standards
DC Link Chokes
Drive Model
Model Rating
400 V Three-Phase Units
4A0002 3.2 A
UZDA-B 28 mH
4A0004
Note: DC link chokes are not required for other models to comply with EMC.
Standards Compliance
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 253
C.2 UL and CSA Standards
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described
below must be met to maintain compliance when using this drive in combination with other equipment:
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed
closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0110 to
2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended by the terminal manufacturer for
crimping. Refer to Closed-Loop Crimp Terminal Size on page 254 for closed-loop crimp terminal recommendations.
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2A0110 to 2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended
by the terminal manufacturer for crimping. Yaskawa recommends crimp terminals made by JST and Tokyo DIP (or equivalent)
for the insulation cap. Table C.4 matches the wire gauges and terminal screw sizes with Yaskawa-recommended crimp
terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge
and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.
Table C.4 Closed-Loop Crimp Terminal Size
Wire Gauge (AWG, kcmil) Crimp Tool Insulation
Screw Terminal
Drive Model Cap Model Code <1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 Size Model Machine No. Die Jaw No.
Number
200 V Class
2A0004 14 R2-4 TP-003 100-054-028
2A0006
2A0008 12 M4 YA-4 AD-900
R5.5-4 TP-005 100-054-029
2A0010 10
14 14 R2-4 TP-003 100-054-028
2A0012 12 12 M4 YA-4 AD-900
R5.5-4 TP-005 100-054-029
10
– 14 R2-4 TP-003 100-054-028
2A0018 12 M4 YA-4 AD-900
R5.5-4 TP-005 100-054-029
10
12
2A0021 M4 R5.5-4 YA-4 AD-900 TP-005 100-054-029
10
10 R5.5-4 AD-900 TP-005 100-054-029
2A0030 8 M4 8-4 YA-4 AD-901 TP-008 100-054-031
6 14-NK4 AD-902 TP-014 100-054-033
254 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.2 UL and CSA Standards
TD-321,
1/0 × 2P R60-10 TD-311 TP-060 100-051-266
M10 YF-1
2A0211 YET-300-1 TD-323,
2/0 × 2P 70-10 TD-312 TP-080 100-054-036
TD-323,
3/0 × 2P 80-L12 TD-312 TP-080 100-051-558
TD-324,
4/0 × 2P 100-L12 TD-312 TP-100 100-051-560
YF-1
2A0250 M12 YET-300-1
– 250 × 2P 150-L12 TP-150 100-051-562
TD-325,
250 – TD-313
R150-12 TP-150 100-051-273
300
TD-323,
3/0 × 2P 3/0 × 2P 80-L12 TD-312 TP-080 100-051-558
YF-1 TD-324,
2A0312 4/0 × 2P 4/0 × 2P M12 100-L12 TD-312 TP-100 100-051-560
YET-300-1
250 × 2P TD-325,
150-L12 TD-313 TP-150 100-051-562
300 × 2P
TD-324,
4/0 × 2P 4/0 × 2P 100-L12 TD-312 TP-100 100-051-560
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 255
C.2 UL and CSA Standards
400 V Class
4A0002 14 R2-4 TP-003 100-054-028
4A0004
4A0005 12 M4 YA-4 AD-900
4A0007 R5.5-4 TP-005 100-054-029
10
4A0009
14 14 R2-4 TP-003 100-054-028
4A0011 12 12 M4 YA-4 AD-900
R5.5-4 TP-005 100-054-029
10
12
R5.5-4 AD-900 TP-005 100-054-029
10
4A0018 M4 YA-4
8 8-4 AD-901 TP-008 100-054-031
6 14-NK4 AD-902 TP-014 100-054-033
10 R5.5-4 AD-900 TP-005 100-054-029
4A0023 8 M4 8-4 YA-4 AD-901 TP-008 100-054-031
6 14-NK4 AD-902 TP-014 100-054-033
– 10 R5.5-5 AD-900 TP-005 100-054-030
4A0031 8 M5 R8-5 YA-4 AD-901 TP-008 100-054-032
6 R14-5 AD-902 TP-014 100-054-034
8 8 R8-5 AD-901 TP-008 100-054-032
4A0038 M5 YA-4
6 6 R14-5 AD-902 TP-014 100-054-034
6 R14-6 AD-952 TP-014 100-051-261
4A0044 M6 YA-5
4 R22-6 AD-953 TP-022 100-051-262
6 R14-8 AD-952 TP-014 100-054-035
4A0058 M8 YA-5
4 R22-8 AD-953 TP-022 100-051-263
4 R22-8 AD-953 TP-022 100-051-263
4A0072 M8 YA-5
3 R38-8 AD-954 TP-038 100-051-264
3
2 R38-8 AD-954 TP-038 100-051-264
4A0088 M8 YA-5
1
1/0 R60-8 AD-955 TP-060 100-051-265
2
R38-8 AD-954 TP-038 100-051-264
4A0103 1 1 M8 YA-5
1/0 1/0 R60-8 AD-955 TP-060 100-051-265
TD-321,
1/0 R60-10 TD-311 TP-060 100-051-266
TD-323,
3/0 80-10 TD-312 TP-080 100-051-267
M10 YF-1
4A0165 YET-300-1 TD-324,
4/0 R100-10 TD-312 TP-100 100-051-269
2 × 2P TD-224,
38-L10 TD-212 TP-038 100-051-556
1 × 2P
TD-227,
3/0 × 2P 80-L10 TD-214 TP-080 100-051-557
YF-1
4A0208 M10 YET-150-1 TD-228,
4/0 R100-10 TD-214 TP-100 100-051-269
250 TD-229,
R150-10 TD-215 TP-150 100-051-272
300
256 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.2 UL and CSA Standards
TD-224,
1 × 2P – 38-L10 TD-212 TP-038 100-051-556
TD-227,
3/0 × 2P 80-L10 TD-214 TP-080 100-051-557
YF-1
YET-150-1 TD-228,
4/0 × 2P 100-L10 TD-214 TP-100 100-051-559
TD-324,
4/0 × 2P 100-L12 TD-312 TP-100 100-051-560
250 × 2P TD-325,
150-L12 TD-313 TP-150 100-051-562
300 × 2P YF-1
4A0296 M12 YET-300-1
– 350 × 2P 180-L12 100-066-688
TD-327,
350 – 180-12 TD-314 TP-200 100-066-689
400 R200-12 100-051-275
500 TD-328,
325-12 TD-315 TP-325 100-051-277
600
TD-323,
3/0 × 2P 80-L12 TD-312 TP-080 100-051-558
TD-324,
4/0 × 2P 100-L12 TD-312 TP-100 100-051-560
250 × 2P TD-325,
150-L12 YF-1 TD-313 TP-150 100-051-562
4A0362 300 × 2P M12 YET-300-1
350 × 2P 180-L12 TD-327, 100-066-688
TD-314 TP-200
400 × 2P 200-L12 100-051-564
500 TD-328,
325-12 TD-315 TP-325 100-051-277
600
TD-324,
4/0 × 2P 100-L12 TD-312 TP-100 100-051-560
M12 YF-1
4A0414 250 × 2P YET-300-1 TD-325,
150-L12 TD-313 TP-150 100-051-562
300 × 2P
TD-323,
3/0 × 4P 3/0 × 4P 80-L12 TD-312 TP-080 100-051-558
YF-1 TD-324,
4A0515 4/0 × 4P 4/0 × 4P M12 100-L12 TD-312 TP-100 100-051-560
YET-300-1
250 × 4P TD-325,
150-L12 TD-313 TP-150 100-051-562
300 × 2P
TD-324,
4/0 × 4P 100-L12 TD-312 TP-100 100-051-560
YF-1
4A0675 M12 YET-300-1
250 × 4P TD-325,
150-L12 TD-313 TP-150 100-051-562
300 × 4P
Standards Compliance
TD-323,
3/0 × 8P 80-L12 TD-312 TP-080 100-051-558
YF-1 TD-324,
4A0930 4/0 × 8P M12 100-L12 TD-312 TP-100 100-051-560
YET-300-1
250 × 8P TD-325,
150-L12 TD-313 TP-150 100-051-562
300 × 8P
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 257
C.2 UL and CSA Standards
TD-324,
4/0 × 8P 100-L12 TD-312 TP-100 100-051-560
M12 YF-1
4A1200 250 × 8P YET-300-1 TD-325,
150-L12 TD-313 TP-150 100-051-562
300 × 8P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Input Fuse Installation
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in Table C.5.
Table C.5 Factory Recommended AC Drive Branch Circuit Protection (Normal Duty)
258 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.2 UL and CSA Standards
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 259
C.2 UL and CSA Standards
Analog inputs / outputs +V, A1, A2, A3, AC, AM, FM Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
260 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.2 UL and CSA Standards
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection
(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable motor overload protection (L1-01 ≠ 0) when connecting the drive to a single motor, unless another motor overload
preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts off the output
of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated while the drive
is powered up.
L1-02: Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is running
a hot motor at 60 Hz and at 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the
set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
Operation time (minutes)
10
7
3 Cold start
(characteristics when an
overload occurs at a
1 complete stop)
Hot start
0.4 (characteristics when an
overload occurs during
continuous operation at 100%)
0.1
Motor current (%)
0 100 150 200 E2-01 = 100% motor current
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 261
C.2 UL and CSA Standards
262 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
C.2 UL and CSA Standards
E
D
A – Drive (outside panel) D – Installation screws
B – Drive (inside panel) E – Capacitor cover
C – Opening to capacitors
Figure C.9 Capacitor Cover
C
E
Standards Compliance
C
YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide 263
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
264 YASKAWA ELECTRIC TOEP YAIP1U 01C YASKAWA AC Drive - P1000 Quick Start Guide
YASKAWA AC Drive P1000
Industrial Fan and Pump Drive
Quick Start Guide
In the event that the end user of this product is to be the military and said product is to be
employed in any weapons systems or the manufacture thereof, the export will fall under the
relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations.