0% found this document useful (0 votes)
394 views1 page

Calculation For Class-Ps CT - 1500kva (DG) : Used CT Rating, Primary in Amp 2000 Used CT Rating, SEC. IN AMP 1

This document provides calculations for selecting a class-PS current transformer (CT) to monitor a 1500 kVA diesel generator set. It details the generator's capacity, voltage, full load current, and fault current levels. It also lists the distance between the generator and panel, wire resistance, CT resistance, knee point voltage, and magnetizing current to select a 2000:1 CT that can accurately measure the generator's current.

Uploaded by

supermannon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
394 views1 page

Calculation For Class-Ps CT - 1500kva (DG) : Used CT Rating, Primary in Amp 2000 Used CT Rating, SEC. IN AMP 1

This document provides calculations for selecting a class-PS current transformer (CT) to monitor a 1500 kVA diesel generator set. It details the generator's capacity, voltage, full load current, and fault current levels. It also lists the distance between the generator and panel, wire resistance, CT resistance, knee point voltage, and magnetizing current to select a 2000:1 CT that can accurately measure the generator's current.

Uploaded by

supermannon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CALCULATION FOR Class-PS CT - 1500KVA (DG)

Capacity of DG set, KVA = 1500


Voltage, KV = 0.44
Full Load Current = 1968.3
Sub Transient Reactane of DG Set, % = 14.7
Used CT Rating, PRIMARY IN AMP = 2000
Used CT Rating, SEC. IN AMP = 1
Fault current at CT Primary Side, AMP = 13389.78
Fault Current at CT Secondary Side Isc IN AMP = 6.69
Approximate Distance between DG to Panel, IN MTR. = 20
Appr. resistance of control wire (2.5SQ MM) IN Ω/KM = 7.41
Total load/wire resistance RL IN Ω = 0.2964
Resistance of CT Rct IN OHM = 5
Knee Point Voltage Vk IN VOLT = 2XIsc(Rct+RL)
= 70.92
= 70
MAGNETISING CURRENT, Ie (Imag) IN Ma <= 30mA at Vk/4
CT RATIO IN AMP = 2000/1A