METSEPM5350: Product Data Sheet
METSEPM5350: Product Data Sheet
Main
Range PowerLogic
Product name PowerLogic PM5350
Device short name PM5350
Product or component Power meter
type
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Power quality analysis Total demand distortion
Total harmonic distortion
Device application Power monitoring
Type of measurement Phase angle
Energy
Voltage
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
Current
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Frequency
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Active power
Power factor
Reactive power
Apparent power
Supply voltage 85...265 V AC (45...65 Hz)
100...300 V DC
Network frequency 50 Hz
60 Hz
[In] rated current 1A
5A
Type of network 1P + N
3P
3P + N
Power consumption in VA <= 9.6 VA
Display type Backlit LCD
Display resolution 6 lines
Sampling rate 32 samples/cycle
Measurement current 0...5 A
0...1 A
Analogue input type Current 0.05...9 A (impedance <= 0.3 Ohm)
Measurement voltage 20...690 V AC phase to phase
20...400 V AC phase to neutral
Frequency measurement range 45...70 Hz
Number of inputs 4 digital
Measurement accuracy 0.3 % current
0.3 % voltage
0.05 % frequency
0.005 % power factor
Accuracy class Class 0.5S (active energy according to IEC 62053-22)
Class 0.5 (power according to IEC 61557-12)
Class 0.5 (active energy according to IEC 61557-12)
Class 3 (reactive energy according to IEC 62053-23)
Class 2 (reactive energy according to IEC 61557-12)
Number of outputs 2 relay
Aug 7, 2018
1
Information displayed Tariff 4
Communication port protocol JBUS
Modbus RTU and ASCII : 9.6, 19.2 and 38.4 kbauds,
Communication port support RS485 terminal block
Data recording Alarms
Min/Max of instantaneous values
Connections - terminals Voltage circuit: 4 screw terminal block
Control circuit: 2 screw terminal block
Current transformer: 6 screw terminal block
Input/Output circuit: 6 screw terminal block
Relay output: 4 screw terminal block
Ethernet network: RJ45 connector
Mounting mode Flush-mounted
Type of installation Indoor installation
Standards IEC 61010-1
Product certifications CULus
CE
Width 96 mm
Depth 44 mm
Height 96 mm
Product weight 0.25 kg
Environment
Electromagnetic compatibility ● susceptibility to electromagnetic fields, conforming to IEC 61000-4-3
● electrical fast transient/burst immunity test, conforming to IEC 61000-4-4
● 1.2/50 µs shock waves immunity test, conforming to IEC 61000-4-5
● conducted RF disturbances, conforming to IEC 61000-4-6
● immunity to impulse waves, conforming to IEC 61000-4-12
● limits for harmonic current emissions, conforming to IEC 61000-3-2
● limitation of voltage changes, voltage fluctuations and flicker in low-voltage,
conforming to IEC 61000-3-3
● electrostatic discharge, conforming to IEC 61000-4-2
● conducted and radiated emissions class class A, conforming to EN 55011
Overvoltage category III
IP degree of protection IP30 (back) conforming to IEC 60529
IP51 (front face) conforming to IEC 60529
Relative humidity 0...95 % 50 °C
Pollution degree 2
Ambient air temperature for operation -40...85 °C
Ambient air temperature for storage -25...70 °C
Operating altitude 0...3000 m
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1104 - Schneider Electric declaration of conformi-
ty Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile
Available Product Environmental
Product end of life instructions Available
Contractual warranty
Warranty period 18 months