ADR 805en111 PDF
ADR 805en111 PDF
ADR 805en111 PDF
Analog Addressable
Accessories
Technical Manual
Note
i The terms “Trouble” as used in NFPA 72 guideline and UL 864 standard and
“Fault” as used in EN 54 standards are used interchangeably throughout this
manual.
Note
i Do not install, operate, and maintain this Product before fully reading this
manual.
1 Introduction
The ADR-805 switch input module interfaces between the ADR-3000 and a non-
powered initiating device such as a presostat, alarm switch, valve switch, sprinkler flow
switch, extinguishing gas flow switch, flooding switch, or a supervisory switch.
The module is powered by the SLC and does not require 24 Vdc input.
The module's input is supervised for short, open, alarm, and normal status. The end-of-
line device is a 100 KΩ resistor. Configuration jumpers allow the selection of operation
mode to be without short supervision (i.e., a short is considered as an alarm or
activation) or with short supervision (i.e., a 3.9KΩ resistance is considered an alarm or
activation, while a short is considered as a trouble condition).
The module is intended to be installed close to the switch it supervises (in the same
room or up to 10m) without short supervision; and up to 100m with short supervision.
The End of Line device is a 100KΩ resistor.
The ADR-805 occupies a single address. The address is stored in the module’s non-
volatile memory and can be programmed or verified by using the PROG-4000 Analog
Addressable Detector and Accessory Programmer. Please refer to the PROG-4000
Technical Manual for further information.
The ADR-805 includes an onboard indicating LED that flashes when addressed by the
control panel and latches on upon alarm.
The ADR-805 module is supervised by the control panel and communicates with it via
the SLC.
– Page 1 of 5 –
ADR-805
© 1999 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.11 January 2012
2 Compatibility
Rev C of the ADR-805 is compatible with previous revision when all jumpers are open
(off).
The ADR-805 is compatible with Telefire's TFT-2800 Flooding Switch.
It is compatible with devices that were approved by Telefire and the relevant authorities.
3 Installation
3.1 Pre-Installation Planning
3.1.1 Capacity Planning
Ensure that the control panel has a free address for the ADR-805.
3.1.2 Cabling Planning – Wire Characteristics' Effect on System
Performance
The following table shows the effect of wiring characteristics on system performance:
Wire Size Cross Section (mm2) Maximum SLC branch length for wire size
18 AWG 0.8 mm2 950 m
16 AWG 1.3 mm2 1,520 m
14 AWG 2.1 mm2 2,420 m
2
12 AWG 3.3 mm 3,830 m
Note
i Notify the operator or the security personnel that the system will be temporary
disconnected before adding devices to the control panel.
– Page 2 of 5 –
ADR-805
© 1999 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.11 January 2012
configured for short supervision, or no more than 10m, same-room installation without
short supervision.
Note
i When the ADR-805 is configured without supervision for shorts (JP2 open),
the IDC line is limited to the same room or no farther than 10m.
3.2 Installation
Connect the initiating device to the ADR-805 using a 12 – 18 AWG (cross section of
0.8mm2 to 3.3mm2).
3.2.1 ADR-805 Configuration
Mode JP1 JP2 JP3 Work Mode
1 Flow switch, NO, without short supervision1
2 • Flow switch, NC, without short supervision1
3 • Flow switch, NO, with short supervision2
4 • • Flow switch, NC, with short supervision2
5 • Flooding switch without short supervision1
6 • • Flooding switch without short supervision1
7 • • Flooding switch with short supervision2
8 • • • Flooding switch with short supervision2
Open
Jumpered •
Note
i When the ADR-805 is configured without supervision for shorts (JP2 open),
the IDC line is limited to the same room or no farther than 10m.
1
When the module is configured for no supervision for shorts (jumper JP2 is open), the input line
(IDC) is limited to the same room or no more than 10m. A short is considered as an alarm or
activation.
2
When the module is configured for supervision for shorts (jumper JP2 is jumpered), the input
line (IDC) is limited to no more than 100m. A short is considered as a fault (trouble), and a
resistance of 200Ω is considered as an alarm or activation.
– Page 3 of 5 –
ADR-805
© 1999 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.11 January 2012
3.2.3 Location
The ADR-805 should be installed in a closed location. Avoid exposure to outdoor
environment to prevent high humidity or dust or air pollution.
Mount the ADR-805 in an AIB-800 box on a solid wall at a height that will have
comfortable access to connecting the cables and where it is possible to supervise and
clearly see the LED indicators. Ensure that cable length limitations are met.
3.2.4 Connecting input (IDC) and SLC lines
Note
i Measure the wiring to ensure there are no shorts before connecting the wiring
to the ADR-805.
Connecting or adding modules to the control panel shall be done when all
power to the control power (AC and batteries) is disconnected.
Connect the input device and SLC cable.
3.3 Post-Installation
Test the module to ensure that it operates properly and verify that it is included in the
appropriate matrices as specified by the planning consultant.
3.4 Documentation
Mark the module’s addresses on a label that is easily visible. Indicate its purpose (for
example, “second-floor sprinkler flow switch").
4 Troubleshooting
The ADR-805 includes a red LED that flashes upon being addressed by the control
panel. This LED turns on when the ADR-805 is in alarm.
An alpha-numeric message on the ADR-3000's LCD screen and annunciators will be
indicated with a detailed description of the event.
5 Specification
Module PCB dimensions (W / H)................................... 70 / 70 mm
AIB-800 dimensions (W / H / D) .................................... 167 / 125 / 33 mm
Weight .......................................................................... 21 gr.
Operating Temperature range....................................... -10°C – +60°C (14°F – 140°F)
Operating Voltage (supplied by control panel)............... 21 V modulated
Maximum Current Consumption.................................... 200 µA (quiescence mode)
2.0 mA (Alarm)
Local Indication Local red LED (light-emitting diode) flashes upon being addressed
by the control panel and turns solid on upon alarm.
All values are nominal. Specifications are subject to change without prior notice
– Page 4 of 5 –
ADR-805
© 1999 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.11 January 2012
6 Certification
Telefire’s ADR-805 Analog Addressable Switch Interface Module has the following
approvals:
• EN 54-17 Approved
• IS 1220 Approved
• GOST Approved
• UL 864 Edition 9 Compliant
• CE Marked
– Page 5 of 5 –