Initiating Devices
Conventional
Fixed-Temperature Heat Detector
Technical Manual
Note
i Do not install, operate, and maintain this product before fully reading this
manual.
1 Introduction
Telefire's TFH-280F is a fixed-temperature conventional heat detector.
The detection process is fully electronic and does not include moving parts.
The TFH-280F will trigger an alarm when the temperature reaches 65°C (149°F)
The detector contains an alarm LED viewable from 360°. This LED blinks during normal
operation and is latched on during an alarm.
2 Compatibility
2.1 Control Panels
The TFH-280F is compatible with the following control panels:
• All TSA-1000 models
• TSA-1000X
• TSA-200 and TSA-200X
• All GSA-1000 models
• GSA-2B
The TFH-280F is compatible with Telefire's ADR-3000 Analog Addressable Control
Panel when used with an ADR-812 or ADR-818 Input module.
2.2 Bases
The TFH-280F is compatible with Telefire's TFB-180 Standard Detector Base.
Warning
! Do not connect these detectors to control panels made by
manufacturers other than Telefire.
3 Installation
Planning of quantity and location of detectors shall be done according to the local codes
and regulations and in accordance to the planning consultant's requirements.
– Page 1 of 4 –
TFH-280F
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.01 June 2012
3.2 Installation
3.2.1 Control Panel Configuration (TSA-1000 Only)
Ensure that the input zone is configured as type d (standard initiating device zone).
Please refer to the TSA-1000 technical manual for a detailed description of programming
and configuration.
3.2.2 Location
The TFH-280F Heat Detector is recommended for use in locations where smoke
detectors are unsuitable, particularly in areas that are subject to excessive fumes, such
as boiler rooms or kitchens.
Observe NFPA 72 guidelines and local fire codes when installing the TFH-280F.
Use only Telefire's TFB-180 Standard Detector Base.
For remote signaling use only Telefire's TFL-1N Auxiliary Signaling Indicator for
Conventional Detectors.
UL UL Requirement
Heat detectors are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.
– Page 2 of 4 –
TFH-280F
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.01 June 2012
4 Maintenance
4.1 Periodic Testing
Fire alarm systems should be checked periodically. Please refer to NFPA and local fire
codes to determine service frequency.
Use the control panel’s Walk Test mode to perform automatic reset. Please refer to the
control panel’s manual for additional details on how to perform Walk Test.
4.1.1 Test Procedure – Locally
1. Apply a magnet to the side of the detector next to the LED for 3 – 5 seconds. This
activates an internal testing circuit that simulates alarm temperature in the detector,
tests the sensing mechanism and the detector's electronic circuit.
Warning
! Do not apply naked flame to the detector!
2. The detector's LED should latch on and the detector will alert the control panel.
3. Once the detector is in alarm mode, it keeps an alarm condition until reset by
disconnecting the detectors power for a few seconds. Press the Reset key at the
control panel's keyboard to reset the detector. Control panels that have a “walk
test” function can reset a tested detector automatically if set to operate in walk test
mode. Please refer to the appropriate control panel manual for instructions on how
to conduct a walk test.
– Page 3 of 4 –
TFH-280F
© 2010 – 2012 Telefire Fire & Gas Detectors Ltd Revision 1.01 June 2012
6 Specification
Diameter ....................................................................... 101 mm including base
Height (including base and LED)................................... 52 mm
Weight .......................................................................... 106 gr.
Operating Temperature Range ..................................... -10°C – +60°C (14°F – 140°F)
Relative Humidity Range .............................................. 10% – 93% non-condensing
Sensitivity ..................................................................... 65°C
Operating Voltage
(supplied by control panel via SLC) ........................ 12 – 28 Vdc
Maximum Current Consumption:
Quiescence mode .................................................. 120µA
Alarm mode (without Auxiliary Indicators) .............. 27mA
Alarm mode (3 Auxiliary Indicators) ....................... 35mA
Maximum Current to auxiliary indicators ....................... 50mA
Local Indication Local red LED (light-emitting diode) and an auxiliary indicator
output. Use only Telefire’s TFL-1N Auxiliary Indicator for
Conventional Detectors. Connect up to 5 auxiliary indicators to
each detector.
All values are nominal. Specifications are subject to change without prior notice
7 Certification
Telefire’s TFH-280F Conventional Fixed-Temperature Heat Detector has the following
approvals:
• EN 54-5 Approved
• IS 1220 Approved
• GOST Approved
• UL 521 Compliant
• CE Marked