RM-4005

Analog Addressable
Control Panels

Remote Panel and Annunciator

Technical Manual

TELEFIRE FIRE & GAS DETECTORS LTD


PO Box 7036
Petach Tikva 49250
Israel
Tel: 972 3 970 0400 RM-
RM-4005En
4005En122
En122.pdf
122.pdf
Fax: 972 3 921 1816
eMail: [email protected] Revision 1.22
Web: www.telefire.co.il March 2013
Note
i The terms “Trouble” as used in NFPA 72 guideline and UL standards and
“Fault” as used in EN 54 standards are used interchangeably throughout this
manual.

Note
i Do not install, operate, and maintain this product before fully reading this
manual.

© 1999 – 2013 Telefire Fire & Gas Detectors Ltd.


RM-4005
© 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013

1 Introduction
The RM-4005 Remote Panel and Annunciator enables control and supervision of the
ADR-3000 fire alarm control panel from remote locations and key positions such as
security officer, premises manager, or maintenance office.
The RM-4005 remote panel consists of an LCD display, keyboard, internal buzzer, and
features such as alarm output, trouble output, and an interface relay that reduces the
need for additional input/output interface modules.
The remote panels are connected to the main control panel via a twisted wire pair
(RS-485). As many as 16 remote panels can be connected to the control panel using
the same cable. Each remote panel should be configured with a unique address in the
range of 1 to 16. The communication and input/output circuits are fully supervised.
In large systems incorporating several control panels connected via a peer-to-peer
network as many as 16 remote panels can be connected to each of the control panels.
The RM-4005 operates with a 24Vdc power source that can be supplied from one of the
following options:
• 24Vdc supplied from the main control panel ADR-3000(connector TB11)
• 24Vdc supplied from a remote power supply such as Telefire's TPS-34A Analog
Addressable External Power Supply.

2 Keyboard and Display


The RM-4005 is equipped with an illuminated alphanumeric LCD display. Four rows of
40 characters each can display descriptions of all analog devices.
The RM-4005 contains the following indicating LEDs:

Figure 1 RM-4005 Keyboard


OK (green)
ALARM (red)
TROUBLE (yellow)
A flashing red LED means that the Alarm or Trouble events were silenced.
Any occurring event is clearly displayed on the LCD screen and relevant LEDs.
The RM-4005 keyboard includes a numeric pad and the following keys:

• (SILENCE) – Press this key silence the alarm bells or the trouble buzzer. In
order to activate this feature, an access code is required. This code will enable only
authorized personnel to silence the alarm.

– Page 1 of 5 –
RM-4005
© 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013

• RECALL MEMORY – Press this key to scan all the system’s events, when more
than one event occurring simultaneously.
• ARROWS – The 4 arrows enable navigating between the menus displayed on the
screen.
• NUMERICAL KEYBOARD – Enables to enter codes, numbers and the selection of
menus.

3 Programming the RM-4005


Both the ADR-3000 control panel and the RM-4005 need to be configured as part of the
installation process.

3.1 Configuring the ADR-3000 Control Panel


1. Press the asterisk (*) key on the ADR-3000’s keyboard to get to the menu.
2. From the main menu press 1 to select SYSTEM PROGRAM.
3. At the request enter the system's password.
4. Press 3 to select SYSTEM CONFIG.
5. Press the RIGHT ARROW key three times so that the REMOTE CONTROL field is
highlighted.
6. Press the UP arrow key to select the remote control’s address (1 – 16).
7. Press the ON key to add the appropriate RM-4005.
Repeat steps 6 and 7 for each additional remote panel in use.
8. Exit the system‘s programming mode by pressing QUIT three times.

3.2 Configuring the Remote Panel RM-4005


1. Enter the main menu screen by pressing the asterisk (*) key on the RM-4005’s
keyboard.
2. Select SYSTEM CONFIG.
3. Enter the password. The system will display a sub-menu.
4. Select address program by pressing 1 on the keyboard. The current address will be
displayed.
5. Enter the new address (1 – 16). Use unique addresses for each remote panel
connected to the same ADR-3000.
6. Exit program mode.

4 RM-4005 Output Programming


Output programming sets the alarm and trouble output circuits' characteristic and
operating conditions.
1. Select SYSTEM CONFIG.
2. Select OUTPUT PROGRAM by pressing 4 on the keyboard.
3. The Alarm output is marked AL and the Trouble output is marked TR.
4. Each can be configured as SILENCED or NOT SILENCED during silencing of the
system. Select the desired mode by using the navigating arrows.
5. The relay marked RL contains both normally open and normally closed dry contacts.
It can be programmed as an Alarm relay or Trouble relay and can be configured as
either silenced or not silenced.

– Page 2 of 5 –
RM-4005
© 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013

The alarm and trouble outputs are supervised and operate on level-activating mode
delivering 24Vdc during alarm or trouble condition.

5 Operating Instructions
5.1 Recall Memory
Whenever more than one event occurs simultaneously in the ADR-3000 system and the
first event is displayed on the screen, it is possible to scroll in order to display the
previous events by using the recall memory push button.

5.2 Lamp Test


Enter the main menu by pressing the asterisk (*) key and select LAMP TEST by
pressing 1 on the keyboard.
All the LEDs will light and the internal buzzer will sound for a few seconds.

5.3 Language Selection


The RM-4005 Remote Panel can operate in either of two languages: English and
Hebrew.
The "change language" feature in the main menu is disabled. You can change
languages via the ADR-3000's "System config" utility under "RM language". Please
refer to the ADR-3000 Technical Manual for further details.

5.4 System State


Selecting SYSTEM STATE in the main menu enables to monitor the system's status and
to display alarm and trouble details.

5.5 Reset
Whenever alarm event occur its possible make a Reset from RM-4005.
1. Press asterisk key ( * ) and select key 5 "Reset"
2. Enter a password
3. Press key 6 for quit from menu

6 Fuses
The following fuses are being used in the RM-4005 Remote Panel:
Fuse Rating Function
F1 0.5A Protects the 24 Vdc outputs
F2 0.1A Protects the LCD display’s illuminating circuit

Note
i In addition to fuse protection both the alarm output (AL) and trouble output
(TR) are protected electronically against short circuit and over-current.

– Page 3 of 5 –
RM-4005
© 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013

7 The RM-4005 Terminals

Figure 2 Connecting the RM-4005


TB11 Entry for 24Vdc from an auxiliary source.
TB10 Output of the 24Vdc for additional devices like: remote panels or different
input/output interface cards.
TB1 Alarm output, trouble output and relay connections.
RS485 Communication terminals (RS-485). Make sure you connect the wires with
proper polarity.

8 Operating Modes
8.1 Alarm Mode
During an alarm the alarm red LED will latch On and the following information will be
displayed:
The event’s number, time of occurrence, description (up to 40 characters, IDC type, and
total event count (if there is more than one event).

8.2 Trouble Mode


This mode is similar to the alarm, except that the yellow trouble LED will latch On.
When in trouble mode the yellow LED will flash and the following information will be
displayed:
The event’s number, time of occurrence, description (up to 40 characters), type of
device, and total event count (if there is more than one event).

8.3 Silencing – Alarm and Trouble


In order to silence the systems sounders from the RM-4005 Remote Panel, press the
key marked with the sounder symbol. The system will request a password. After
entering the password and pressing the ENTER key, the sounders of the entire system
will be silenced and the red flashing LED will light up.

– Page 4 of 5 –
RM-4005
© 1999 – 2013 Telefire Fire & Gas Detectors Ltd Revision 1.22 March 2013

9 Specification
Dimensions (W / H / D) ................................................. 280 / 195 / 50 mm
Weight .......................................................................... 1,535 gr.
Operating Temperature Range ..................................... -10°C – +60°C (14°F – 140°F)
Relative Humidity Range .............................................. 10% – 93% non-condensing
Operating Voltage ......................................................... 24Vdc
Current Consumption
Quiescence mode, LCD not illuminated ................. 40 mA
Alarm, excluding external sounder current ............. 70 mA
Maximum Alarm output current ..................................... 500 mA
Maximum Trouble output current .................................. 500 mA
All values are nominal. Specifications are subject to change without prior notice

10 Certification
Telefire’s RM-4005 Analog Addressable Conventional Remote Panel and Annunciator
has the following approvals:
• SI 1220 Approved
• EN-54 Approved
• UL 864 Compliant

– Page 5 of 5 –